AMORPHOUS DISTRIBUTION TRANSFORMERS


Products range
Voltage: up to 36kV
Capacity: 5kVA~5000kVA

Contents
Certicates

Certicate of Quality awarded by GE

R&D milestones of Tatung Amorphous Distribution Transformers

Introduction of Amorphous Alloy Magnetic Material

Manufacturing process comparison of Amorphous ribbon and


CRGO

Feature comparisons of Amorphous ribbon and CRGO

Characteristic comparison between AMDT and CRGO


transformers

Characteristics of Standard Series-below 600V

11

Characteristics of Standard Series-12kV&12/24kV

11

Standard Seriesbelow 600V (Dimension ,oil quantity, total


weight)
Standard Series-General type (Dimension, Oil quantity, Total
weight)
Standard Series-Duct type (Dimension, Oil quantity, Total
weight)
Standard Series-General type (Dimension, Oil quantity, Total
weight)
Standard Series-Duct type (Dimension, Oil quantity, Total
weight)
Accessories of Oil Immersed Amorphous Distribution
Transformer
Specication of oil-immersed Amorphous Distribution
Transformer

12

Specication sheet of oil-immersed Amorphous transformer

22

L.V Bushing Terminal

23

Dimension of Ducts and Foundation Bolts

24

13
14
15
16
17
18

Certicates

Certicate of Quality awarded by GE

ISO-9001 Certicate

ISO-14001 Certicate

CNS mark Certicate by


BSMI Economic Ministry

The Second CED Innovative Design


and Technology Award

The Seventh CED Golden


Quality Award for Excellent
Products

Patent of a Corrugated
Tank TR with Force
Air-cooled

Certicate of Second
Category Environmental
Friendly Products

The Sixteenth Taiwan


Excellence Award

Certicate of SC
Withstand Test by CTQC

An Amorphous Transformer manufacturing company approved by Taiwan Power Co.


(Certificate Number 8509-244Y)

CED Certificate (Serial Number PN3002)

The original text statement is as follows:


This is relative to Tatung Company, a Licensee of General Electric Co. of Amorphous
transformer manufacturing technology.
Based on the relationship GE and Tatung have had over the past 4 years since Tatung
licensee GE's Technology, GE has complete confidence that Tatung's Amorphous
transformer quality is comparable to GE's using GE's manufacturing technology installed
with GE's assistance.

R&D milestones of Tatung Amorphous Distribution Transformer


1990 Tatung co. signed technical collaboration agreement with the world's largest AMDT
manufacturer GE. U.S.A. introducing AMDT design and manufacturing technology.
1991 Dispatched Tatung engineers to GE's HICKORY plant to study AMDT design.
1992 Dispatched production and equipment engineers to BTL plant and HICKORY plant to
study AMT manufacturing technology. Tatung completed installation and testing of AMT
production line.
1993 Tatung is the rst company to design and successfully produce 10kVA, 25kVA,
50kVA,100kVA transformers for the domestic market. The various characteristics of these
units are according to specications of TPC pole type transformers. This upgraded the
high technology industry and set up a new milestone for the domestic heavy electrical
appliance industry.
1994 Developed and produced single-phase 167kVA pole type AMDT according to TPC
specications.
1995 Developed and produced pad mounted type single-phase 100kVA AMDT according to
TPC specications.
1996 Developed and produced energy saving, high efciency single-phase 100kVA AMDT.
Dispatched engineers to GE Shreveport factory to study the design of 3 phase AMDT.
1997 Sold 300 units of pole type 25kVA, 50kVA AMDT to TPC. dispatched technological
engineer to GE for a 3 months long term study of manufacturing technology and plant
maintenance. Two design engineers were stationed at GE's Shreveport plant for six months
to undergo the latest design training.
1998 Secured orders for 3 phase 2000kVA, 1500kVA, 1000kVA, 500kVA and 300kVA from the
customers such as L.J. Electron etc. Among them 2000kVA won the seventh excellent

1999
2000
2001
2002

2003

2006

2008

electrical product award of Taiwan electrical and electronic development association


(CED) followed by Golden quality award. Succeeded in producing and making 3 phase
3000/3750kVA large capacity Amorphous transformer.
ISO 9001 and ISO 14001 certied.
Produced 500 units of pole type 100kVA Amorphous transformers for TPC.
Technological collaboration with Honeywell, USA for Amorphous core stacking skills.
Succeeded in developing 2000kVA Amorphous core cast resin dry type transformer.
Exported 1500kVA and 2000kVA AMDT to T.E.M. Malaysia.
Produced 115 units of pole type 100kVA Amorphous transformers for TPC.
Participated Yokohama IEEE/PES T&D 2002 Asia Pacic Exhibition in Japan.
1000kVA Amorphous transformer was tested and passed at transformer research institute in
Shenyang, China.
According to the TPC material code Y066 (91-11) , 100kVA and 167kVA pad
mounted type single phase Amorphous transformers were developed and passed the
TPC certication. (Certicate number : D9207-0036Y ).
Succeeded in producing 3-phase 5000kVA Amorphous transformer. Secured orders from
domestic customers and foreign customers such as Nissin Electric of Japan.
Developed and completed 1500kVA environmental friendly, energy-saving vegetable oil
Amorphous transformer, received orders for 1000kVA, 1500kVA from Taiwan DuPont Co.
Environmental friendly, energy-conserving vegetable oil Amorphous transformer won
2008 Taiwan excellence Award.

Introduction of Amorphous Alloy Magnetic Material


Manufacturing Process of Amorphous Metal Ribbon

A
F

C
D

1. Amorphous alloy
A melting alloy that has proper composition of metallic elements is extremely rapid quenched
at the rate of 106 per second, it is too fast to let the disordered atomic-scale structure become
crystalline in its solid state, as a result, amorphous alloy is to be formed. Its atom structure is nonordered and similar to the glass, therefore the amorphous alloy is also called glass metal. The
features of metallic elements and disordered non-crystalline structure make the amorphous alloy
own unique and superior properties.

2. Atom model

A: Raw materials are melted down in


induction furnace.
B: Melt is transferred to the feeder section.
C: Control of casting head.
D: Thin lm of melt is ejected onto the
rapid quenching wheel.
E: Jet is quenched at 106 per second to
form an amorphous strip.
F: Strip width & thickness are measured in
line and fed back for process control.
G: Strip is guided to the thread-up unit for
take-up.
H: Strip take-up.

Appearance of Amorphous alloy and


CRGO Silicon steel
Amorphous core transformer not only
can reduce the power loss of the
power system but also can reduce
the power development costs and
fuel costs, potentially reducing CO2
emissions, reducing air pollution, acid
rain and greenhouse effects.
Appearance of Amorphous alloy ribbon

Crystalline silicon steel

Non- crystalline Amorphous alloy

3. Performance of Amorphous alloy


The amorphous alloy posses excellent soft magnetic properties such as high saturation
magnetic, low coercivity and high permeability,
Non-crystalline has a high resistivity than crystalline, therefore, the eddy current loss that
generated when amorphous alloy is in the AC magnetisc field can be obviously reduced.
The very low core loss will be found when amorphous alloy is adopted for the core.
Good temperature stability.

Appearance of CRGO Silicon steel

Manufacturing process comparison of


Amorphous ribbon and CRGO

Feature comparisons of Amorphous


ribbon and CRGO

Amorphous ribbon

Comparison of magnetization curves

Raw Material

Melting(1100C)

Casting (25C)

CRGO
Raw Material

Melting (1500C)

Continuous casting

Re-heating

Hot rolling

Annealing
Acid washing
(De-rusting)
Cold rolling

The technology of planar ow casting


process is adopted for producing the
patented amorphous alloy ribbon which
is now belong to and manufactured by
Hitachi Metal a Japanese company.
Refer to the left manufacturing process
comparison, the amorphous ribbon is
extremely simple, its production process
does not consume large amount of
energy, therefore, we can say it is a
typical environmental friendly material.
On the contrary, the manufacturing
process of CRGO silicon steel is more
complicated, large energy is consumed
during the process, it is a high energyconsuming product.

Item

Amorphous
Ribbon

CRGO

Annealing
(De-carbonizing)

Heating
times

One

Six

Cold rolling

Energy
consumption

Less

More

Annealing
(Re-crystallizing)

Tesla

Silicon steel

1
0
1

Amorphous alloy

2
Oersteds

Characteristic comparison

Material code and Composition

Sweeping treatment

Re-coating

Packing (25C)

Packing (25C)

Iron loss W13/60 (25 )


Saturated magnetic ux
density (25 )
Curie temperature
Saturated magnetostriction

Amorphous

CRGO

2605SA1(1)

30G140(2)

Fe78B13Si9

Fe97Si3

0.17w/kg
1.56T
415
2710-6

0.86w/kg
2.03T
745
2.410-6

Density
Lamination factor
Physical
Crystallization temperature
characteristics Tension strength
Hardness
Coefcient of resistance

7.18g/cm3
>75%
550
>150kgf/mm2
860
130cm

7.65g/cm3
>94%
>150kgf/mm2
180
45cm

Dim

Width
Thickness

~213mm
0.02~0.03mm

~950mm
0.23~0.3mm

Others

Annealing

340 ~360
in the DC
750 ~850
magnetic field

Magnetic
characteristic

Coating
Annealing
(Flattening)

Refer to the left gure for the


magnetization curves of amorphous
alloy ribbon and CRGO silicon steel.
The close areas surrounded by the
curves represent energy loss when
an alternate magnetic eld passes
through the magnetic materials.
It is obvious that the two areas of
amorphous and CRGO are quite
different, 70% ~ 80% difference
is found according to actual
measurement, i.e. the no load loss of
transformer can be reduced about
70% ~ 80% when CRGO silicon steel
is replaced with amorphous alloy
ribbon.

Characteristic
ratio
(1) / (2)

20%
77%

4 times

10%

50%

Characteristic comparison between AMDT and CRGO transformers


Item

Comparison

Amorphous transformer
Number of heating times

Loss comparison

No- load loss

TPC series
single phase
transformers

3-phase
distribution
transformers

TPC series single phase transformer


3

Number of heating times

Benet assessment
6

Compared to CRGO, producing of amorphous alloy can save 1


liter of petrol per kg.

Energy consumption of producing raw materials


Energy consumption

CRGO transformer

Excitation current

Less

Energy consumption

Capacity

Core loss

Percentage

25kVA

25W

38%

50kVA

40W

36%

100kVA

75W

44%

No-Load loss of Amorphous transformer is 15%~20%

High

Capacity

Core loss

Base

In an era when power project development is difcult , ultra low


load loss of AMDT could be a good choice to save the energy.
25kVA
65W
100%
If CRGO distribution transformers are to be replaced with AMDT
by TPC, 5.5 billion KWH of electricity (About the capacity of
50kVA
110W
100%
90,000kW of Shihmen hydroelectric power plant can be saved
annually. The running costs of machinery and equipment,
maintenance charges and electricity transmission related
100kVA
170W
100%
costs (land, electricity towers, transmission and distribution and
switching etc.) can be saved. Therefore, the AMDT can be
No-Load loss of CRGO transformer is assumed to be 100% considered as non-fuel generators.

Capacity

Specied
value

Measured
value

Capacity

Specied
value

Measured
value

25kVA

0.75%

0.3331%

25kVA

0.75%

0.3189%

50kVA

0.68%

0.2146%

50kVA

0.68%

0.3139%

100kVA

0.64%

0.1304%

100kVA

0.64%

0.1973%

3-phase Distribution transformers

1.0%

2.5% 5.0%
According to IEEE C57.12 or IEC60076

TPC series single phase transformer

50dB

50dB

Meet TPC industry research specications 205(1998-05)

50 63dB
Comply with IEEE C57.12 or IEC60076 requirement

50 63dB
Comply with IEEE C57.12 or IEC60076 requirement

The noise level of AMDT is slightly lower than the CRGO


transformer

Noise
3-phase Distribution transformers

Operating temperature

Insulation degradation

Life-span of the transformer

30 years assessed by GE, U.S.A.

Normal life-span of 20 years is assessed

Anti Harmonic voltage

Extremely excellent magnetic properties of Amorphous


core will not be affected by the invading harmonic
voltage

Silicon steel core by the invasion of the harmonic voltage


will generate higher iron loss and noise

10

Environmental benets

Return of investment benets

Amorphous core excitation current are much lower than the


silicon steel transformer

AMDT:
Cores temperature:15
Coil temperature: 35
CRGO transformer :
Cores temperature: 35
Coil temperature: 65
( Super high overload capacity of AMDT because it operates in
low temperature )

Meet TPC industry research specications 205(1998-05)

Slow

1. Amorphous alloy material consumes low energy.


2. Amorphous core us annealed at 360 and consumes
less energy.

1. Extra investment will be returned in 3 5 years.


2. The AMDT will continuously save the electricity and its
running cost after investment is returne.

Fast

1. Silicon steel production consumes higher energy.


2. Silicon steel core is annealed at 800 and consumes
higher energy.

The cost of CRGO transformer as a base data

The core loss of AMDT is very low, less heat is generated,


the operation temperature is low, therefore, the insulation
degradation is slow, and this will longer the operating life span of
the transformer.
Compared to CRGO, the excellent magnetic characteristics of
Amorphous alloy material makes the losses generated by high
frequencies just about 1/10, harmonic effects arising from the
Iron losses can also be reduced drastically.
1. Low consumption of energy in material process and low
losses of AMDT can save a lot of energy, therefore, less gases
such as SO2, CO2 and NOX are emitted from power plant,
environmental pollution can be substantially reduced.
2. When the life-span of Amorphous transformer ends, the
Amorphous alloy can be recycled, no environmental pollution
is created.
3. Energy saving is a main goal of ISO 14000.
Compared the total owning cost of AMDT with CRGO
transformers, the extra cost of Amorphous transformer paid by
the owner can be returned within 3-5 years.

10

Standard Seriesbelow 600V (Dimension ,oil quantity, total weight)

Voltage
Efciency Impedance
Regulation
(%)
(%)
(%)

193

95.90

2.90

10

3.5

25

348

96.40

2.60

20

3.5

45

594

96.90

2.20

25

3.5

50

700

97.08

2.10

30

3.5

55

800

97.20

2.00

37.5

3.5

65

1000

97.24

2.00

50

3.5

75

1286

97.35

1.90

75

3.5

90

1872

97.45

1.90

100

3.0

105

2406

97.55

1.80

150

3.0

120

3490

97.65

3.0-4.0

1.70

200

3.0

170

4430

97.75

3.0-4.0

1.70

300

3.0

235

6045

97.95

3.0-4.0

1.60

H2

H3

X0

X1

X2

X3

530

13

11

13

2
4

Amorphous TR.

11

Amorphous TR.

10

150~300kVA

5~100kVA

Positions of accessories are marked in numbers, refer to the table "Accessories of oil immersed Amorphous
Distribution Transformer" on P17.

Characteristics of Standard Series-12kV&12/24kV


Voltage
Efciency Impedance
Regulation
(%)
(%)
(%)

A
(mm)

B
(mm)

C
(mm)

X
(mm)

Y
(mm)

Net
Weight
(kg)

Oil
(L)

650

450

550

140

30

1.7

10

700

480

550

180

40

3.0-4.0

1.6

20

800

520

600

260

55

98.52

3.0-4.0

1.5

30

880

580

650

380

80

7050

98.55

3.0-4.0

1.5

50

950

580

800

520

105

350

8300

98.58

3.5-4.5

1.5

75

980

600

850

600

145

3.0

420

9700

98.67

4.0-5.0

1.4

100

850

650

900

800

170

1000

2.5

530

12850

98.68

4.0-5.0

1.4

150

900

1250

1150

650

750

1050

300

1250

2.5

600

16050

98.69

4.5-5.5

1.4

200

900

1300

1180

650

750

1250

320

1500

2.5

650

18050

98.77

5.0-6.0

1.3

2000

2.0

870

23900

98.78

5.0-6.0

1.3

300

980

1450

1300

650

750

1550

400

2500

2.0

1150

25850

98.93

5.0-6.0

1.2

3000

2.0

1250

28800

99.01

5.0-6.0

1.2

Capacity
(kVA)

No Load
Current (%)

No Load
Loss (W)

Load Loss
(W)

150

3.0

120

2550

98.25

3.0-4.0

1.7

200

3.0

170

3300

98.29

3.0-4.0

300

3.0

235

4600

98.41

400

3.0

290

5700

500

3.0

320

600

3.0

750

11

H1

20

3.5

12

X0 X1 X2 X3

15

Load Loss
(W)

H1

No Load
Loss (W)

H2

No Load
Current (%)

H3

Capacity
(kVA)

Characteristics of Standard Series-below 600V

Cap.
(kVA)

Primary Secondary
Voltage Voltage
(V)
(V)

Below
600

Below
600

12
10

Standard Series-General type (Dimension, Oil quantity, Total weight


15

15

12

Standard Series-Duct type (Dimension, Oil quantity, Total weight)


15

12

15

12

13

12

14

8
A

Amorphous TR.

400
500
600

13

12/24kV

Primary Secondary
Cap.
A
Voltage Voltage
(kVA)
(mm)
(kV)
(V)

12kV

B
(mm)

C
(mm)

X
(mm)

Y
(mm)

Net
Weight
(kg)

Oil
(L)

12

930

1350

1330

650

750

1150

280

12/24

950

1350

1430

650

750

1120

330

12

930

1450

1400

650

750

1550

350

12/24

950

1500

1500

650

750

1650

380

12

1000

1450

1400

650

900

1700

460

1030

1450

1500

650

900

1850

500

12

1120

1550

1450

650

1000

2100

520

12/24

1150

1550

1550

650

1000

2300

580

12

1150

1620

1520

650

950

2450

650

12/24

1180

1650

1620

650

1000

2600

680

12

1240

1770

1465

650

1050

2850

710

12/24

1250

1800

1545

650

1050

2900

740

12/24

Positions of accessories are marked in numbers, refer to the table "Accessories of oil immersed Amorphous
Distribution Transformer" on P17.

300

10

12kV

200

1
Amorphous TR.

150

10

7
6

10

9
2

10

11

C
C

11

11

Amorphous TR.

16

11

16

Amorphous TR.
3

H1

H1

H1

8
A

X0 X1 X2 X3

X0 X1 X2 X3

H2

H1

X0 X1 X2 X3

H3

H2

H2

H2

13

H3

H3

H3

13

14

X0 X1 X2 X3

13

380/220

12/24kV

Positions of accessories are marked in numbers, refer to the table "Accessories of oil immersed Amorphous
Distribution Transformer" on P17.

Primary Secondary
Cap.
A
Voltage Voltage
(kVA)
(mm)
(kV)
(V)
150
200
300
400
500
600

B
(mm)

C
(mm)

X
(mm)

Y
(mm)

Net
Weight
(kg)

Oil
(L)

12

1050

1350

1520

650

750

1210

280

12/24

1100

1350

1690

650

750

1290

330

12

1050

1450

1590

650

750

1610

350

12/24

1100

1500

1760

650

750

1740

380

12

1200

1450

1590

650

900

1770

460

1200

1450

1760

650

900

1940

500

12

1300

1550

1640

650

1000

2180

520

12/24

1300

1550

1810

650

1000

2400

580

12

1300

1620

1710

650

950

2530

650

12/24

1300

1650

1880

650

1000

2700

680

12

1440

1770

1650

650

1050

2950

710

12/24

1450

1800

1790

650

1050

3000

740

12/24

380/220

14

Standard Series-General type (Dimension, Oil quantity, Total weight)


15

15

12

Standard Series-Duct type (Dimension, Oil quantity, Total weight)

12

15

15

12

13

12

14

2
10

Amorphous TR.

12kV

1000
1250
1500

2000
2500
3000

15

X
Y

12kV

B
(mm)

C
(mm)

X
(mm)

Y
(mm)

Net
Weight
(kg)

Oil
(L)

1270

2080

1465

800

1200

3550

910

12/24

1280

2110

1545

800

1200

3600

940

12

1340

2270

1665

800

1250

4450

1250

12/24

1350

2330

1745

800

1250

4550

1320

12

1440

2140

1665

950

1350

5000

1240

12/24

1450

2180

1750

950

1350

5100

1290

1460

2520

1665

950

1350

6100

1640

12/24

1470

2530

1750

950

1350

6200

1670

12

1610

2590

1765

950

1500

7350

1920

12/24

1620

2620

1850

950

1500

7450

1970

12

1800

2830

1915

950

1650

9450

2670

12/24

1810

2860

2000

950

1650

9550

2740

12

1830

2900

1965

950

1750

10650

2810

12/24

1840

2900

2050

950

1750

10750

2840

380/220

12

12

Positions of accessories are marked in numbers, refer to the table "Accessories of oil immersed Amorphous
Distribution Transformer" on P17.

750

12/24kV

Primary Secondary
Cap.
A
Voltage Voltage
(kVA)
(mm)
(kV)
(V)

10

10

10

11

7
6

11

16

Amorphous TR.

11

11

16

Amorphous TR.

X0 X1 X2 X3

X0 X1 X2 X3

X0 X1 X2 X3

H1
A
4

Amorphous TR.

H2

H3

H1

H1

H1

9
9

H2

H2

H2

13

H3

H3

H3

13

X0 X1 X2 X3

13
14

12/24kV

Positions of accessories are marked in numbers, refer to the table "Accessories of oil immersed Amorphous
Distribution Transformer" on P17.

Primary Secondary
Cap.
A
Voltage Voltage
(kVA)
(mm)
(kV)
(V)
750
1000
1250
1500
2000
2500
3000

B
(mm)

C
(mm)

X
(mm)

Y
(mm)

Net
Weight
(kg)

Oil
(L)

12

1470

2080

1650

800

1200

3700

910

12/24

1480

2110

1790

800

1200

3750

940

12

1540

2270

1850

800

1250

4600

1250

12/24

1550

2330

1990

800

1250

4700

1320

12

1640

2140

1850

950

1350

5150

1240

12/24

1650

2180

1990

950

1350

5250

1290

1660

2520

1850

950

1350

6250

1640

12/24

1670

2530

1990

950

1350

6350

1670

12

1810

2590

1950

950

1500

7500

1920

12/24

1820

2620

2090

950

1500

7600

1970

12

2000

2830

2100

950

1650

9600

2670

12/24

2010

2860

2240

950

1650

9700

2740

12

2030

2900

2150

950

1750

10850

2810

12/24

2040

2900

2290

950

1750

10950

2840

12

380/220

16

Accessories of Oil Immersed Amorphous Distribution Transformer


No.

Cap.(kVA)
Accessories

1. Application
5~100

150~600

750~3000

Name plate

Trade mark

Primary bushing

Secondary bushing

Base

Drain valve

7
8
9

Grounding terminal
Oil level gauge &
Thermometer
Oil level gauge &
Thermometer
Pressure relief device

10

Radiator

11

Lifting lug

12

Hand hole

13
14

No voltage tap
changer
Dual voltage tap
changer

15

Filter valve

16

Duct

1. When transformers with tap changers and the primary voltage is 3.3KV , standard
accessories shall be the same as in the above table.
2. Standard accessories are marked as "O" in the table. When there are special requests
from customers for optional accessories, additional charges shall be added.
3. Oil level gauge without contact.

17

Specication of oil-immersed Amorphous Distribution Transformer


This specication is applied to oil-immersed
Amorphous Distribution Transformers. The
core materials are made of amorphous
alloy.

2. Standards

The transformers covered by this specication


will be designed, manufactured and tested
in accordance with applicable requirement
of the following standards:
Institute of Electrical and Electronics
Engineers
(IEEE C57.12)
International Electro Technical Commission
(IEC 60076)

3. Operating Condition

Normal operating condition:


3.1. Max. Ambient temp : 40
3.2. Average temp.: below 35 (in any 24
hours)
3.3. Altitude: Below 1000m

4. Type

Two windings, oil immersed

5. Rating

5-1 Phase
5-2 Frequency
5-3 Capacity
5-4 Rated voltage
5-5 Primary Tap voltage

6. Polarity or phase sequence

6-1 Single phase transformer with negative


polarity
6-2 Connection of 3-phase transformer:
Whenconnection for primary, Y
connection for secondary, primary
voltage leads 30 degrees, vector group
symbol is Dy1.
Whenconnection for primary,
connection for secondary, phase
sequences of voltage are the same,
vector group symbol is Dd0.
When Y connection for primary,
connection for secondary, primary
Voltage leads 30 degrees, vector group
symbol is Yd1.
When Y connection for primary,
connection for secondary, phase
sequences of voltage are the same
vector group symbol is Yyn0.
(When primary connection is Y, the
neutral point is not led out)

7. Core material and its structure

7-1 The Amorphous alloy ribbon supplied


by Hitahi, Japan is adopted for the
core.The surface of the cores are
coated with special resin and the
cores are supported and clamped by
well designed structures for reducing
exciting current and noise level caused
by superior performances

7-2 The clamps shall be designed and


constructed solidly. It shall be strong
enough to withstand the vibrations
during transportation, installation and
normal operation

8. Windings

8-1 The windings shall be well designed to


provide the protection against impulse
voltage (Surge-proof).Windings and
leads are well supported and xed for
withstanding the electromechancial
strength caused by the short circuits
at load side .The sufcient oil ducts
arrangement is made for the excellent
oil circulation inside and between the
windings, so that a low temperature
gradient between conductors and oil
is assured, and local overheating shall
not occur. Drying treatment under
vacuum with moderate temperature
is performed while the windings
are tightly clamped to ensure the
exact size of windings. C.C.A. is dried
under vacuum, and a vacuum oil
impregnated process will be executed
immediately after nishing tanking
process to ensure the quality of
transformer

8-2 High temperature resistant enameled


at or round copper wires are adopted
for high voltage windings for attaining
the lowest losses and excellent
dielectric performance between
layers.
8-3 Primary windings are multilayer
winding designs. The invading surge
voltage will become uniform linear
distribution, therefore, The winding has
good withstanding impulse voltage
capability.

18

8-4 Tap lead positions of primary windings


should be designed to be led out at
middle segment of windings. It can
avoid high potential areas of winding
ends and guarantee the dielectric
strength of lead wires.
8-5 High conductivity foil conductor is
adopted for secondary winding,
unbalanced ampere-turn will not occur
between windings. It can also have
minimum short-circuit electromechanical
force, the best thermal conductivity
without occuring hotspot.
8-6 In order to obtain the best withstanding
voltage insulation capacity with the
best anti-short-circuit electromechanical
force strength and short-term overload
capacity, resin coated insulating paper
(temperature rise 65 ) shall be placed
between coil layers.
8-7 Current density of the coil shall be set up
to fully comply with the requirements of
the short-circuit test to avoid overheating
caused by external short circuit.

9. Tank and Accessories

9-1 The tank shall have the capacity to


withstand a pressure of 25% greater
than the maximum operating pressure
without permanent deformation. The
cover is provided with a hand-hole and
tted to the tank by bolts. All weld seams
and connecting joints shall be oil tight
thus there is no oil leaks. Inside the tank
shall be outtted with guide pins that will
prevent the displacement of CCA during
transportation and operation.There is an
ample space between CCA and tank
bottom for residue accumulation.
9-2 The base for the tank shall has enough
mechanical strength for the movement
of the transformer in forward, backward
and sidewise directions.
9-3 Gasket retainers shall be installed on all
contact surfaces of gaskets for prevent
gaskets slipping.

9-4 The transformer shall be equipped with


enough radiators for air nature capacity.
The radiator shall be designed and
manufactured with carefully chosen
material to withstand possible corrosion.

19

9-5 According to transformers capacity and


actual requirements, the manufacturer
shall provide suitable accessories such as
thermometers and oil gauges. Types of
these accessories shall be in accordance
with the recommendations of IEEE C57.12
or IEC 60076. If customer has additional
requirements, shall negotiate with the
supplier.

10. Cooling devices

10-1 Air nature and air forced cooling devices


for a dual capacities of transformer
shall be installed according to the
customer specifications with control
equipment, cooling fans, motors,
radiator and piping.The cooling fans
shall be driven by an unit motor and
controlled by a temperature relay for
start and stop automatically. Automatic
and manual operating control switches
shall be installed in terminal box xed on
transformer tank.

10-2 All the control and signal contacts of


cooling device shall be connected
to the terminal board inside the
connection box.
10-3 A standard motor rated with 3-phase
220V 60Hz for cooling fans are provided
by Tatung, its control power source
is single phase 220V 60Hz should be
prepared by the customer. If customer
specifications are different from the
above ratings, changes can be made
after an agreement by both parties.

11. No Voltage Tap Changer (NVTC)

An external manually operated NVTC is


provided and connected to the primary
windings for selecting the tap position to
t the system voltage. Manually operated
NVTC is tted with a single external handle
which can be used to select the taps for
all 3 phases simultaneously. The handle is
very convenient and easy to operate for
a technician. A tap position indicator is
provided to indicate the corresponding
voltage shown in the nameplate.

12. Characteristics of bushing

The bushings are made of porcelain


material or the material of the same
characteristics and in accordance with
the following regulations
12-1 Dielectric strength: Dielectric strength

of bushing and minimum creepage


distance required is as shown in
Table A.

transformer.

16. Transformer Testing

12-2 Insulation distance: Insulation distance


between phase to ground and
between phases, refer to table B.

13. Nameplate

Indications on nameplate comply with


IEEE C57.12 or IEC 60076. The transformer
shall have a stainless steel nameplate
written in English showing following data

Type of transformer
Number of phases
Connection diagram
Rated capacity(kVA)
Serial number
Rated frequency(Hz)
Total weightkg
Rated voltage(V)
Quantity of oilL
Tap voltages
Temperature rise
Date of manufacturing
Basic impulse insulation levelBIL
Name of manufacturer
Percentage impedance75
Phase sequence diagram

14. Surface Paint Processing

Tank shall be processed by going through


rust protection and abrasive blasting
processing. Inner layer is coated with
oil resistant white paint, and outside
is coated with weather resistant, antirust paint. The outermost layer of color is
emerald green (Taiwan Paint Association
1-06 color samples) or according to
customer specications.

15. Insulating Oil

Normal quantity of insulating oil complies


with ASTMD 3487 or IEC 60296 shall be
filled to the tank and delivered with

16-1 Ratio test


Apply rated frequency and voltage
to any windings and determine the
tap voltage ratio by voltmeter or
T.T.R. The tolerance is within 0.5%.

16-2 Polarity test


Testing of polarity is according to
chapter 6, with standard transformer
comparative method or any other
method.
16-3 Induced voltage test
For single phase double bushing and
3 phase transformer induce voltage
test, apply 2 times the rated voltage
of test voltage to any winding. Test
time is as follows
Test time(sec)=120

rated frequency
applied frequency

16-4 No load (Iron) loss test and Load (copper)


loss test
Open circuit test and short circuit test are
done in normal ambient temperature.
The results of measurement for No
load current, No load loss , Load loss,
Impedance voltage, voltage regulation
and efficiency are converted into
75 , It shall conform to the values of
characteristic table.
16-5 Dielectric Test
Except for single phase transformer
with single bushing, 60Hz AC test
shall be executed, for other types
of transformers, the AC test shall be
applied according to table C without
failure.

Table A
AC test voltage r.m.s. (kV)
Maximum
system
Water injection for
voltage Drying for 1 Minute
10 Sec
r.m.s.
Below
Over
Below
Over
(kV)
500kVA
500kVA
500kVA
500kVA
1.2
10
10
6
6
3.6
21
27
20
24
7.2
27
35
24
30
12.5
35
50
30
45
24.0
70
60

Impulse test voltage Minimum creepage


1.250 Sec
distance
(kV) Peak voltage
(mm)
Below
Over
500kVA
500kVA
30
45
60
75
75
95
95
110
150

Below
Over
500kVA
500kVA
90
125
150
180
250
280
430

20

16-6 Temperature Rise


16.6.1 The average winding temperature
rise shall not exceed 65 by
resistance measurement method.
16.6.2 The temperature rise of the
insulating oil shall not exceed
60 when it is measured near
the top of tank.
16-7 Noise
The transformer shall be designed
and manufactured to reduce the
noise and vibrations. For standard

values, refer to table D.


16-8 Factory Test
The transformer shall be tested at the
manufacturing shop as follows prior
to be delivered.
Resistance measurement
Ratio test
Polarity test or phase
sequence test
No load (Iron) loss test
Load ( copper) loss test

No load current test


Impedance test
Induced voltage test
Applied voltage test

Specication sheet of oil-immersed Amorphous transformer


No.

Maximum system
voltage
r.m.s. (kV)

Grounding part

1.2
3.6
7.2
12.5
24.0

50(25)
90(65)
115(90)
150(130)
205(205)

Between phases
Active parts

Top n of bushing

50(25)
100(65)
130(100)
165(140)
230(230)

25(25)
50(40)
65(50)
90(75)
150(150)

No.

a.Altitude: Below 1000m

Color

c.Ambient temp: Below 40

30

BIL test

60Hz 50Hz

31

Standard

32

3.3kV 11.4kV
11.4/22.8kV

Moisture
proong

33

Over load

220V 380/220V

34

Noise

35

Temperature
rise

36

Paint

Air nature

37

Accessories

- -Y

Name plate
Oil level
gauge &
Thermometer

Frequency

Capacity
Primary
voltage
Secondary
voltage

Item

29

b.Relative Humidity: Below 85%

Minimum insulation distance (mm)

Specication

Conditions of
use

Table B

Item

kVA

Location

outdoor indoor

Type

Standard type
Duct type

Insulation type Oil-immersed

10

Type of
cooling
Connection

NoteThe value of parentheses are applied to rated capacity below 500kVA.

11

Phase Symbol

Dd0 Dyn1

Table C

12

Winding

Two windings
Single winding

13

Polarity

Subtractive

14

Core material
Oil
preservation
system

Low loss Amorphous alloy

Grounding
terminal
Filter valve

Open type
Air sealed type

Hand hole

Insulation Level
Rated
voltage (V)

A.C. test
voltage
(KV)

1200
3300
6600
11400
22800

10
19
26
34
50

Impulse voltage full


wave test
1.250 Sec,(KV)
Peak voltage
500KVA
Over
under
500KVA
30
45
60
75
75
95
95
110
150

Chop wave test


Peak voltage (KV)
500kVA
under
36
69
88
110

Over
500KVA
54
88
110
130
175

Minimum chop wave


time ( Sec)
500kVA
Over
under
500KVA
1.0
1.5
1.5
1.6
1.6
1.8
1.8
2.0
3.0

Table D
Capacity
(kVA)
150, 200
250
300
400
500
600
750

21

Noise (dB)
(reference value)
52
54
56
57
58
59
60

Capacity
(kVA)
1000
1250
1500
2000
2500
3000
-

Noise (dB)
(reference value)
62
63
63
64
65
65
-

15

no voltage tap changer


tap changing board
Comply with IEEE C57.12 or IEC
60076 standard
kW

16

Tap changer

17

Tap voltage

18

No load loss

19

Load loss

kW

20

Total loss

kW

21

Efciency

22

27

Impedance
No load
current
Ratio of
voltage
regulation
Insulation
resistance
Duration of
short circuit
Tank

28

Oil

23
24
25
26

Radiator

Pressure relief
device
Pressure relief
valve
Lifting lug

Base

g
h

Specication
Munsell 2.5G 4/10

Comply with IEEE C57.12 or


IEC 60076 standard
Comply with IEEE C57.12 or
IEC 60076 standard
High quality moisture proof
oil resistant gasket
Comply with ANSI C57.91
standard
dB(A)
Winding temperature rise:
Below 65
Oil temperature rise:
Below 60
Refer to the Following
Remarks
Refer to specications

Panel Corrugated

Automatic involution
type

Remarks

1.Paint process: De-rusting + pickling +


phosphate processing + organic zinc-rich+
middle coat+ antirust paint+ nish coat. The
%
primer is a synthetic resin based primer, in order
to scratch check, the color of the layers of paint
%
should be different.

750M 2000M
By ANSI C57 standard

2.After receiving the order, the approved


drawing shall be submitted to the customer. Test
report shall be submitted when delivering the
transformer.

By IEEE C57.12 or IEC 60076 standard


By ASTMD 3487 or IEC 60296 standard

22

L.V Bushing Terminal

Dimension of Ducts and Foundation Bolts


Dimension of ducts

40

1100

15

540

40

590

620

40

15

40
400

450

1150

40

Thickness 20
Fig. 4

15

15

Fig. 3

40

740

40

Thickness 18

Fig. 2

1180
15

790

40
480

35

25
Thickness 12

15
15

145
30 45 45 25

20
40
85

30

20
Thickness 12
Fig. 1

820

100
25 50 25

15

6-14 Holes

50

4-14 Holes

40
85

4-14 Holes

25

2-14 Holes

75
40

45
110

50

100

24-12 Holes

16-12 Holes

Single Phase Transformer


220/440

220

440

150

Fig1

Fig1

Fig1

Fig1

200

Fig2

Fig1

Fig2

Fig1

250

Fig2

Fig1

Fig2

Fig1

300

Fig2

Fig1

Fig2

Fig1

400

Fig3

Fig2

Fig3

Fig2

500

Fig3

Fig2

Fig3

Fig2

40
85

110/220

20

2-14 Holes

Standard dimension below 24kV (mm)

Foundation bolts

25

Volt

Thickness 11
Fig. 5

Unitmm

N.P.

kVA

Standard dimension below 12kV (mm)

43

Three Phase Transformer


Volt

-Y

220 240 190Y/110 208Y/120 220Y/127 380Y/220 440Y/254 460Y/266 480Y/277

150

Fig5 Fig5

Fig5

Fig1

Fig5

Fig5

Fig5

Fig5

Fig5

200

Fig1 Fig1

Fig1

Fig1

Fig1

Fig1

Fig1

Fig1

Fig1

250

Fig1 Fig1

Fig1

Fig1

Fig1

Fig1

Fig1

Fig1

Fig1

300

Fig1 Fig1

Fig2

Fig1

Fig1

Fig1

Fig1

Fig1

Fig1

400

Fig2 Fig1

Fig2

Fig2

Fig2

Fig1

Fig1

Fig1

Fig1

500

Fig2 Fig1

Fig2

Fig2

Fig2

Fig1

Fig1

Fig1

Fig1

600

Fig2 Fig1

Fig3

Fig3

Fig2

Fig2

Fig1

Fig1

Fig1

750

Fig3 Fig2

Fig3

Fig3

Fig3

Fig2

Fig2

Fig2

Fig2

1000

Fig4 Fig2

Fig4

Fig4

Fig3

Fig2

Fig2

Fig2

Fig2

23

XY dimension (mm) Please refer to the values in the gures.

16

63
200

250

kVA

220

Connection

Please mark out in the order form of the


transformer if foundation bolts are needed.

24

Industrial Appliance Business Unit Export Division


102 Minsheng Rd., Neihai Village, Tayuan, Taoyuan County, Taiwan, 33759, R.O.C.
TEL : +886-3-3863123 #1304
FAX : +886-3-3863123 #1380
E-mail Address : chienge@heap.tatung.com.tw
Head ofce
No. 22, Sec. 3, ChungShan N. Rd., Taipei City, Taiwan, 10435, R.O.C.
TEL: +886-2-25925252#3633
FAX: +886-2-25984425
Website: www.tatung.com

2013.08