LS Busduct - 0602 PDF
LS Busduct - 0602 PDF
13 1:33 PM 2
1. INTRODUCTION
51
45
1. INTRODUCTION
1.1
GENERAL SPECIFICATIONS
1.2
1.3
CATALOGING
Bus Bar
Service Conditions
Ambient temperature : -15C~40C
Relative Humidity : 95% or below
Installation Attitude : Maximum 1000M above sea level
Standards
KSC 8450: Bus ways
JISC 8364: BUS DUCT
IEC 60439-1&2: Bus ways
BSEN 60439: Bus ways
Insulation
Multi-Layer polyester films of class B(130C) shall be
applied into thickness 0.5mm on conductor.
BMC forms which is polyester reinforced by glass fiber
shall be applied as a spacer between conductors of joint
part or conductor and duct.
FR-Insulation
Multi-Layer of Fire Resistant Insulator(1200C) shall be
applied on conductor.
Compact Size
LSC Bus Duct requires less space than wire and
conduit.
Easy to Install
LSC Bus Duct incorporates the one joint bolt type. For
connection work, bolt fastening forces were unified into
the torque of 1200kg.cm.
5. Completion of joint.
SAFETY POINT: Nut (1) shall be neither taken off, nor dropped. when neck (2) is broken, twisting force remains.
1.3 Cataloging
LSC BUS DUCT CODING
Table 6
VOLTAGE SHAPE
CURRENTS
FIRE
RANGE STRUCTURE RANGE
RESISTANCE
BRANCH
LIMITS
GROUNDING
LSC
BUS DUCT
TYPE
GENERAL
IG TYPE
PE EARTH
IP TYPE
HALF EARTH
IH TYPE
FULL EARTH
IF TYPE
GENERAL
8G TYPE
PE EARTH
8P TYPE
HALF EARTH
8H TYPE
FULL EARTH
8F TYPE
GENERAL
FG TYPE
PE EARTH
FP TYPE
HALF EARTH
FH TYPE
FULL EARTH
FF TYPE
GENERAL
YG TYPE
PE EARTH
YP TYPE
HALF EARTH
YH TYPE
FULL EARTH
YF TYPE
I-SERIES
TO 400A
WITHOUT
POWER
SHUTDOWN
GENERAL
TYPE
COMPACT
TYPE
8-SERIES
TO 800A
WITHOUT
POWER
SHUTDOWN
BELOW
600V
600A~6000A
F-SERIES
TO 400A
WITHOUT
POWER
SHUTDOWN
LSC
BUS DUCT
SYSTEM
FIRE
RESISTANCE
TYPE
Y-SERIES
TO 800A
WITHOUT
POWER
SHUTDOWN
200A~400A
M-SERIES
100A~200A
B-SERIES
AIR
INSULATED BELOW 100A
TYPE
Mini
PE EARTH
Baby
Lighting
L-SERIES
GENERAL
TYPE
I P Grade
(41.54.65)
IG41
IG54
IG65
IP41
IP54
IP65
IH41
IH54
IH65
IF41
IF54
IF65
8G41
8G54
8G65
8P41
8P54
8P65
8H41
8H54
8H65
8F41
8F54
8F65
FG41
FG54
FG65
FP41
FP54
FP65
FH41
FH54
FH65
FF41
FF54
FF65
YG41
YG54
YG65
YP41
YP54
YP65
YH41
YH54
YH65
YF41
YF54
YF65
MP41
MP54
MP65
BP41
BP54
BP65
LP41
LP54
LP65
AP41
A-SERIES
PE EARTH
Low
Voltage
AP54
AP65
600A~4000A
HP41
OVER
600V
H-SERIES
PE EARTH
High
Voltage
HP54
HP65
SPRING VERTICAL
HANGER
ND
DE
GE
AN
L
F
L
ICA
RT W
BO
L
E
VE
2F
EXPANSION JOINT
RIG
ID
V
HA
NG ERT
ICA
ER
L
L
TA
ON
RIZ
HO
E
E
T
SE
WI
AT R
FL NGE
HA
D
GE
AN
FL D
EN
PLUG IN HOLE
1F
PLUG IN UNIT
RE
DU
CE
R
HO
R
EL IZON
BO
TA
W
L
ME
D
HA IUM
NG
ER
VE
TE
RT
L
TA
ON
RIZ
T
HO F-SE
OF
D
GE
AN OX
FL
DB
EN
ICA
RIGID VERTICAL
HANGER
BASE CHANNEL
FEED IN BOX
SE
WI
GE
ED GER
N
A
H
TR END FLANGED
END BOX
Transformer
Y
RA
ET
BL
CA
B1
EA
HG
TC
SW
FL
EN ANDE
DB D
OX
L
ICA
RT
VE BOW
EL
or
tdo
Ou
r
oo
Ind
HO
RI
EL ZON
BO
T
W AL
3.3KV 3P 3W 1200A(Cu-Fe)
High Voltage
Bus Duct
AL
NT
IZO T
R
E
HO F-S
OF
TR END FLANGED
Transformer
E
WIS
GE R
ED ANGE
H
Feed in Box
Cable
R
H.V GEA
H
ITC
SW
ED
EN
G
AN
FL
PLUG IN HOLE
R
L.V GEA
H
ITC
SW
PLUG IN BOX
END CLOSER
Copper or Aluminum
R.Head Bolt
High Tension
Joint Bolt
Disk Spring(C)
Stopper(D)
Joint Cover
Insulation Spacer(B)
Contact Surface(A)
Housing
Connection
Joint Cover
Square Nut
Description
10 11
OPTION 1
OPTION 2
Table 10
OPTION 3
OPTION 4
Code : IG TYPE
Code : IP TYPE
Code : IH TYPE
Code : IF TYPE
2.1.2 8-Series
8-Series(Plug-in 800A Bus Duct) has same all characteristics as I-Series. However 8-Series is
specially designed for larger branch plug-in Amperes. The maximum branch of this 8-series is by
plug-in upto 800A and by Tap off over 800A. So, this type is very useful for factory.
8-Series have double branch capacity. Max Plug in Ampere is 800A
Plu
g-in
Mo
ld
RSTN
RST
Mo
ld C
ove
r
Ca
ble
D-PLUG IN TYPE
Fig. 11.1
RSTN
RST
Plu
g-in
Co
ver
Ca
ble
S-PLUG IN TYPE
Fig. 11.2
Description
OPTION 1
OPTION 2
Table 11
OPTION 3
OPTION 4
Code : 8G TYPE
Code : 8P TYPE
Code : 8H TYPE
Code : 8F TYPE
Insulation Spacer
Silver Plated Joint
Description
12 13
OPTION 1
OPTION 2
Table 12
OPTION 3
OPTION 4
Code : FG TYPE
Code : FP TYPE
Code : FH TYPE
Code : FF TYPE
Description
OPTION 1
OPTION 2
OPTION 3
Table 13
OPTION 4
Code : YG TYPE
Code : YP TYPE
Code : YH TYPE
Code : YF TYPE
G-TYPE
P-TYPE
W
P.E BUS(CU)
3t x 25w
Fig. 14.1
Fig. 14.2
H-TYPE
F-TYPE
A
N C B A PE
1/2PE =A =B=C= N
Fig. 14.3
For dimensions and weights information, Please contact us.
C B A PEN
PE =A =B=C
N C B A PE
PE =A =B=C =N
Fig. 14.4
Full Earth
100%E
C B A PEN
1/2PE =A=B=C
14 15
Half Earth
50%E
2.2.2 IP DEGREE
LSC Bus Duct provides optimum performance in the most demanding applications. Through
superior design and applied materials technology, it assures uptime and reliability, even in
severe-duty weather environments.
Fig. 15.1
H+27
27
W(IP54)
Fig. 15.2
H +100
H+86
H+50
W+ 86
36
36
W+50
Fig. 15.3
Construction options
Table 15
IP41/IP42
Indoor
IP54/IP55
Spray-proof/Splash-proof
IP65/IP66
Feeder
Outdoor
Construction Type
600
800
1,000
1,200
1,500
1,600
2,000
2,500
3,000
3,500
4,000
4,500
5,000
6,000
6
6
6
10
10
10
10
10
10
10
10
10
10
10
Dimensions(mm)
W
B
3W
4W
55
100
125
75
100
125
100
100
125
100
110
140
125
110
140
150
110
140
175
110
140
230
110
140
150x2 110
140
175x2 110
140
200x2 110
140
230x2 110
140
175x3 110
140
200x3 110
140
Table 16.1
Weight
(kg/m)
H
115
135
160
160
185
210
235
290
385
435
485
545
635
710
3W
11
13
15
19
22
25
28
35
46
52
58
73
83
93
Fig. 16
Rating
in
Amps
600
800
1,000
1,200
1,500
1,600
2,000
2,500
3,000
3,500
4,000
4,500
5,000
6,000
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Dimensions(mm)
W
B
3W
4W
55
100
125
55
100
125
75
100
125
100
100
125
125
100
125
150
100
125
175
100
125
125x2 100
125
150x2 100
125
175x2 100
125
200x2 100
125
150x3 100
125
175x3 100
125
200x3 100
125
Flg.
4W
13
15
18
23
27
31
34
43
56
64
72
88
100
112
a.d
a.d
a.d
a.d
a.d
a.d
a.d
a.d
b.e
b.e
b.e
b.e
c.f
c.f
Table 16.2
Weight
(kg/m)
H
115
115
135
160
185
210
235
335
385
435
485
560
635
710
3W
18
18
21
27
32
37
42
58
70
80
93
109
125
141
Flg.
4W
22
22
27
33
40
47
53
73
88
101
119
136
157
178
a.d
a.d
a.d
a.d
a.d
a.d
a.d
b.e
b.e
b.e
b.e
c.f
c.f
c.f
Dimensions : Millimeters
Table 16.3
W-Dimensions
PHASE
3W
4W
Width
180
230
NOTE: Conductor size are same. Additional duct & Plug-in BMC structure will be treated over one for G-type. so weight will be added that much. For more information
contact us.
16 17
600
800
1,000
1,200
1,500
1,600
2,000
2,500
3,000
3,500
4,000
4,500
5,000
6,000
6
6
6
10
10
10
10
10
10
10
10
10
10
10
Dimensions(mm)
W
B
3W
4W
55
110
140
75
110
140
100
110
140
100
125
170
125
125
170
150
125
170
175
125
170
230
125
170
150x2 125
170
175x2 125
170
200x2 125
170
230x2 125
170
175x3 125
170
200x3 125
170
Table 17.1
Weight
(kg/m)
H
115
135
160
160
185
210
235
290
385
435
485
545
635
710
3W
14
17
18
22
25
28
31
38
49
55
61
76
86
96
Fig. 17
Rating
in
Amps
600
800
1,000
1,200
1,500
1,600
2,000
2,500
3,000
3,500
4,000
4,500
5,000
6,000
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Dimensions(mm)
W
B
3W
4W
55
110
140
55
110
140
75
110
140
100
110
140
125
110
140
150
110
140
175
110
140
125x2 110
140
150x2 110
140
175x2 110
140
200x2 110
140
150x3 110
140
175x3 110
140
200x3 110
140
Flg.
4W
16
18
21
26
30
34
37
46
59
67
75
91
103
115
a.d
a.d
a.d
a.d
a.d
a.d
a.d
a.d
b.e
b.e
b.e
b.e
c.f
c.f
Table 17.2
Weight
(kg/m)
H
115
115
135
160
185
210
235
335
385
435
485
560
635
710
3W
21
21
24
30
35
40
45
61
73
83
96
112
128
144
Flg.
4W
25
25
30
36
43
50
56
76
91
104
122
139
160
181
a.d
a.d
a.d
a.d
a.d
a.d
a.d
b.e
b.e
b.e
b.e
c.f
c.f
c.f
Dimensions : Millimeters
Table 17.3
W-Dimensions
PHASE
3W
4W
Width
180
230
NOTE: Conductor size are same. Additional duct & Plug-in BMC structure will be treated over one for G-type. so weight will be added that much. For more information
contact us.
Fig-a
Fig-b
600
800
1,000
1,200
1,500
1,600
2,000
2,500
3,000
3,500
4,000
4,500
5,000
6,000
6
6
6
10
10
10
10
10
10
10
10
10
10
10
Table 18.1
H
115
135
160
160
185
210
235
290
385
435
485
545
635
710
Weight
(kg/m)
Flg.
5W
16
17
21
26
31
35
38
47
61
69
78
88
106
119
a.
a.
a.
a.
a.
a.
a.
a.
b.
b.
b.
b.
c.
c.
Rating
in
Amps
Dimensions(mm)
W
B
5W
55
140
75
140
100
140
100
170
125
170
150
170
175
170
230
170
150x2
170
175x2
170
200x2
170
230x2
170
175x3
170
200x3
170
Fig-c
Fig. 18
Rating
in
Amps
600
800
1,000
1,200
1,500
1,600
2,000
2,500
3,000
3,500
4,000
4,500
5,000
6,000
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Dimensions(mm)
W
B
5W
55
140
55
140
75
140
100
140
125
140
150
140
175
140
125x2
140
150x2
140
175x2
140
200x2
140
150x3
140
175x3
140
200x3
140
Table 18.2
H
115
115
135
160
185
210
235
335
385
435
485
560
635
710
Weight
(kg/m)
Flg.
5W
26
26
31
38
45
53
59
81
97
111
130
147
170
192
a.
a.
a.
a.
a.
a.
a.
b.
b.
b.
b.
c.
c.
c.
Dimensions : Millimeters
Table 18.3
W-Dimensions
PHASE
5W
Width
230
NOTE: Conductor size are same. Additional duct & Plug-in BMC structure will be treated over one for G-type. so weight will be added that much. For more information
contact us.
18 19
Rating
in
Amps
600
800
1,000
1,200
1,500
1,600
2,000
2,500
3,000
3,500
4,000
4,500
5,000
6,000
6
6
6
10
10
10
10
10
10
10
10
10
10
10
Dimensions(mm)
W
B
5W
55
180
75
180
100
180
100
180
125
180
150
180
175
180
230
180
150x2
180
175x2
180
200x2
180
230x2
180
175x3
180
200x3
180
Table 19.1
H
115
135
160
160
185
210
235
290
385
435
485
545
635
710
Weight
(kg/m)
Flg.
5W
17
19
23
29
34
39
42
53
68
77
86
98
118
132
a.
a.
a.
a.
a.
a.
a.
a.
b.
b.
b.
b.
c.
c.
Fig-a
Fig-b
Fig-c
Fig. 19
Rating
in
Amps
600
800
1,000
1,200
1,500
1,600
2,000
2,500
3,000
3,500
4,000
4,500
5,000
6,000
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Dimensions(mm)
W
B
5W
55
180
55
180
75
180
100
180
125
180
150
180
175
180
125x2
180
150x2
180
175x2
180
200x2
180
150x3
180
175x3
180
200x3
180
Table 19.2
H
115
115
135
160
185
210
235
335
385
435
485
560
635
710
Weight
(kg/m)
Flg.
5W
28
28
35
42
50
59
66
90
108
123
144
164
189
214
a.
a.
a.
a.
a.
a.
a.
b.
b.
b.
b.
c.
c.
c.
Dimensions : Millimeters
Table 19.3
W-Dimensions
PHASE
5W
Width
230
NOTE: Conductor size are same. Additional duct & Plug-in BMC structure will be treated over one for G-type. so weight will be added that much. For more information
contact us.
200
105
105
200
105
B
3.2t
200
3.2t
3.2t
Flange
Flange
Flange
W
200
200
W
Fig. 20.2
200
25
25
Fig. 20.3
25
Fig. 20.4
11
11 A
Fig. 20.5
BAR WIDTH 55mm
11
14
A A
Fig. 20.6
Fig. 20.7
40
80
20
22
40
80
20
22
40
80
20
20
40
80
20
20
20
20
40
80
BUS BAR HOLE PATTERN (1 STACK, 2 STACKS, 3 STACKS ARE SAME, ALL HOLES ARE RECTANGULAR)
14
A A
Fig. 20.8
A A A
Fig. 20.9
Table 20.1
20 21
600
800
1,000
1,200
1,500
1,600
2,000
2,500
3,000
3,500
4,000
4,500
5,000
6,000
t
6
6
6
10
10
10
10
10
10
10
10
10
10
10
Dimensions(mm)
tI
W
A
3 or 6
55
3 or 6
75
40
3 or 6
100
50
5 or 10
100
50
5 or 10
125
40
5 or 10
150
50
5 or 10
175
60
5 or 10
230
60
5 or 10 150x2
50
5 or 10 175x2
60
5 or 10 200x2
70
5 or 10 230x2
60
5 or 10 175x3
60
5 or 10 200x3
70
B
100
100
100
100
100
100
100
100
130
130
130
130
130
130
Flg.
20.22 0 .5
20.22 0 .6
20.22 0 .6
20.22 0 .6
20.22 0 .7
20.22 0 .7
20.22 0 .8
20.22 0 .9
20.32 0 .9
20.32 0 .7
20.32 0 .8
20.32 0 .9
20.42 0 .8
20.42 0 .8
Table 20.2
Rating
in Amps(A)
COPPER
ALUMINUM
Rating
in Amps(A)
600
800
1,000
1,200
1,500
1,600
2,000
2,500
3,000
3,500
4,000
4,500
5,000
6,000
t
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Dimensions(mm)
tI
W
A
3 or 6
55
3 or 6
55
3 or 6
75
40
3 or 6
100
50
3 or 6
125
40
3 or 6
150
50
3 or 6
175
60
3 or 6 125x2
40
3 or 6 150x2
50
3 or 6 175x2
60
3 or 6 200x2
70
3 or 6 150x3
50
3 or 6 175x3
60
3 or 6 200x3
70
B
100
100
100
100
100
100
100
130
130
130
130
130
130
130
Flg.
20.22 0 .5
20.22 0 .5
20.22 0 .6
20.22 0 .6
20.22 0 .7
20.22 0 .7
20.22 0 .8
20.32 0 .7
20.32 0 .7
20.32 0 .8
20.32 0 .8
20.42 0 .7
20.42 0 .8
20.42 0 .8
Min
Min
.:3
.:3
00
00
Min
.:3
00
200
20 40
70 80
L=270
B
B
D
C
C
C
Fig. 21.1
Fig. 21.2
Fig. 21.3
Fig. 21.4
70
Fig-17.3 GEN.BOX
Fig. 21.5
Fig. 21.6
L=270
L=270
70
105
200
Flexible
conductor
105
200
Elastic Band
Fig. 21.7
Fig. 21.8
Table 21
COPPER
ALUMINUM
Rating
in Amps(A)
600~1200
1500~2000
2500
3000
3500~4000
4500
5000
6000
600~1200
1500~2000
2500
3000
3500~4000
4500
5000
6000
No. OF
STACKS
1
1
1
2
2
2
3
3
1
1
2
2
2
3
3
3
A
310
385
440
535
635
695
785
860
310
385
485
535
635
710
785
860
B
260
335
390
243x2
293x2
323x2
245x3
270x3
260
335
218x2
243x2
293x2
220x3
245x3
270x3
3 W (mm)
C
450
450
450
510
510
510
510
510
450
450
510
510
510
510
510
510
D
200x2
200x2
200x2
230x2
230x2
230x2
230x2
230x2
200x2
200x2
230x2
230x2
230x2
230x2
230x2
230x2
Note: refer to page 20 for flanged end and busbar hole pattern
L
270
270
270
270
270
270
270
270
270
270
270
270
270
270
270
270
A
310
385
440
535
635
695
785
860
310
385
485
535
635
710
785
860
Dimensions(mm)
4 W (mm)
B
C
D
260
550
250x2
335
550
250x2
390
550
250x2
243x2
640
295x2
293x2
640
295x2
323x2
640
295x2
245x3
640
295x2
270x3
640
295x2
260
550
250x2
335
550
250x2
218x2
640
295x2
243x2
640
295x2
293x2
640
295x2
220x3
640
295x2
245x3
640
295x2
270x3
640
295x2
L
270
270
270
270
270
270
270
270
270
270
270
270
270
270
270
270
A
310
385
440
535
635
695
785
860
310
385
485
535
635
710
785
860
B
260
335
390
243x2
293x2
323x2
245x3
270x3
260
335
218x2
243x2
293x2
220x3
245x3
270x3
5 W (mm)
C
D
650
300x2
650
300x2
650
300x2
770
360x2
770
360x2
770
360x2
770
360x2
770
360x2
650
300x2
650
300x2
770
360x2
770
360x2
770
360x2
770
360x2
770
360x2
770
360x2
L
270
270
270
270
270
270
270
270
270
270
270
270
270
270
270
270
D
D
OPENING
CUTOUT
C
Fig. 22.1
Fig. 22.2
Fig. 22.3
Table 22
COPPER
ALUMINUM
Rating
in Amps
(A)
22 23
600
800
1000
1200
1500
1600
2000
2500
3000
3500
4000
4500
5000
6000
600
800
1000
1200
1500
1600
2000
2500
3000
3500
4000
4500
5000
6000
Dimensions(mm)
A
3-W
240
240
240
240
240
240
240
240
300
300
300
300
300
300
240
240
240
240
240
240
240
240
300
300
300
300
300
300
4-W
340
340
340
340
340
340
340
340
430
430
430
430
430
430
340
340
340
340
340
340
340
430
430
430
430
430
430
430
B
115
135
160
160
185
210
235
290
385
435
485
545
635
710
115
115
135
160
185
210
235
335
385
435
485
560
635
710
3-W
135
135
135
135
135
135
135
135
165
165
165
165
165
165
135
135
135
135
135
135
135
165
165
165
165
165
165
165
C
4-W
185
185
185
185
185
185
185
185
230
230
230
230
230
230
185
185
185
185
185
185
185
230
230
230
230
230
230
230
5-W
235
235
235
235
235
235
235
235
295
295
295
295
295
295
235
235
235
235
235
235
235
295
295
295
295
295
295
295
D
145
165
190
190
215
240
265
320
208
233
258
288
222
247
145
145
165
190
215
240
265
183
208
238
258
197
222
247
Fig.
22.1
22.1
22.1
22.1
22.1
22.1
22.1
22.1
22.2
22.2
22.2
22.2
22.3
22.3
22.1
22.1
22.1
22.1
22.1
22.1
22.1
22.2
22.2
22.2
22.2
22.3
22.3
22.3
Forward
LSC Bus Duct has complete ranges which fit to all the
lay-out conditions. The other special parts than 90 angle
are also available.
Designation methods related to turning are specified in
Fig.x on the basis of source side and load side. Off set
and combination elbow will be applied only when
standard elbow is not applied.
Upward
Source Side
Load Side
Downward
Rearward
Fig. 23.1
Elbow-Fittings
Dimensions : mm
Upward
AMP. Rating(A)
Forward
Standard
Downward
Max.
Horizontal. Elbows(Edgewise)
Min.
Fig. 23.2
Rearward
Vertical. Elbows(Flatwise)
Fig. 23.3
600~2500
3000~4000
4500~6000
600~2500
3000~4000
4500~6000
600~2500
3000~4000
4500~6000
Table 23.1
Hor. Elbow
X
Y
500
500
500
500
500
500
1000
1000
1000
1000
1000
1000
300
300
300
300
300
300
Ver. Elbow
X
Y
500
500
600
600
700
700
2000
2000
2000
2000
2000
2000
400
400
500
500
600
600
Tee-Fittings
Dimensions : mm
AMP. Rating(A)
Standard
Horizontal. Tee(Edgewise)
Fig. 23.4
Max.
Vertical. Tee(Flatwise)
Fig. 23.5
Min.
600~2500
3000~4000
4500(AL)
4500~6000
600~2500
3000~4000
4500(AL)
4500~6000
600~2500
3000~4000
4500(AL)
4500~6000
Table 23.2
Hor. Tee
X
Y
Z
500 500 500
600 600 600
600 600 600
Ver. Tee
X
Y
Z
500 500 500
600 600 600
700 700 700
700 700 700
1000 1000 1000
1000 1000 1000
1000 1000 1000
1000 1000 1000
400 400 400
500 500 500
600 600 600
600 600 600
Offset
Fittings
Dimensions : mm
AMP. Rating(A)
Foreward
Standard
Downward
Max.
Horizontal. Offset
Vertical. Offset
Fig. 24.1
Fig. 24.2
Min.
600~2500
3000~4000
4500~6000
600~2500
3000~4000
4500~6000
600~2500
3000~4000
4500~6000
Table 24.1
Hor. Offset
Ver. Offset
X
Y
Z
X
Y
Z
500 500 500 500 500 500
500 500 500 600 600 600
500 500 500 700 700 700
1000 500 1000 1000 1000 1000
1000 500 1000 1000 1000 1000
1000 500 1000 1000 1000 1000
300 250 300 400 500 400
300 250 300 400 500 400
300 250 300 600 500 600
Combination Elbow
Fittings
Upward
Rearward
Combination Elbow
(For-ward+Up-ward)
Combination Elbow
(Down-ward+Rear-ward)
Fig. 24.3
Fig. 24.4
Reducer
This Fitting is used to economical engineering system. Another ratings are produced per costomers request.
Dimensions : mm
AMP. Rating(A)
Fig. 24.5
Primary
1000
1500
2000
2500
3000
4000
Secondary
600~800
800~1200
1200~1600
1500~2000
2000~2500
3000~2500
Table 24.2
AMP. Rating(A)
X
Standard : 1000
Min : 700
Max : 2000
Expansion
This Fitting is designed to absorb 25mm longitudinal expansion. In straight run it is recommended to install this section
every 40 meters.
Dimensions : mm
POLE
3
4
Fig. 24.6
24 25
AMP. Rating(A)
600~2000
2500~6000
600~2000
2500~6000
Table 24.3
AMP. Rating(A)
X
280
300
340
370
1500
Feed-in box
Feed-in box is a part used for connection to cable by diverging at the end of Bus Duct.
Min
.:3
00
Min
.:3
00
Min
.:3
00
L
L
B
B
B
A
A
A
Fig. 25.1
Fig. 25.2
Fig. 25.3
Table 25
COPPER
ALUMINUM
AMPERE
RATINGS
(A)
600
800
1000~1200
1500
1600
2000
2500
3000
3500
4000
4500
5000
6000
600~800
1000
1200
1500
1600
2000
2500~3000
3500
4000
4500
5000
6000
No. OF
STACKS
1
1
1
1
1
1
1
2
2
2
2
3
3
1
1
1
1
1
1
2
2
2
3
3
3
A
350
350
350
350
350
350
350
450
450
450
450
500
500
350
350
350
350
350
350
450
450
450
500
500
500
3 W(mm)
B
200
220
250
300
320
350
400
500
550
600
650
700
800
200
220
250
300
320
350
500
550
600
650
700
800
L
400
400
400
400
400
400
400
450
450
450
500
500
500
400
400
400
400
400
400
450
450
450
500
500
500
A
450
450
450
450
450
450
450
550
550
550
600
600
600
450
450
450
450
450
450
550
550
550
600
600
600
Dimensions(mm)
4 W(mm)
B
200
220
250
300
320
350
400
500
550
600
650
700
800
200
220
250
300
320
350
500
550
600
650
700
800
L
400
400
400
400
400
400
400
450
450
450
500
500
500
400
400
400
400
400
400
450
450
450
500
500
500
A
500
500
500
500
500
500
500
600
600
600
650
650
650
500
500
500
500
500
500
600
600
600
650
650
650
5 W(mm)
B
200
220
250
300
320
350
400
500
550
600
650
700
800
200
220
250
300
320
350
500
550
600
650
700
800
L
400
400
400
400
400
400
400
450
450
450
500
500
500
400
400
400
400
400
400
450
450
450
500
500
500
Min
.:3
00
Min
.:3
00
Min
.:3
00
B
B
Fig. 26.1
Fig. 26.2
Fig. 26.3
Table 26
COPPER
ALUMINUM
AMPERE
RATINGS
(A)
26 27
600
800
1000~1200
1500
1600
2000
2500
3000
3500
4000
4500
5000
6000
600~800
1000
1200
1500
1600
2000
2500~3000
3500
4000
4500
5000
6000
No. OF
STACKS
1
1
1
1
1
1
1
2
2
2
2
3
3
1
1
1
1
1
1
2
2
2
2
3
3
A
350
350
350
350
350
350
350
450
450
450
450
500
500
350
350
350
350
350
350
450
450
450
500
500
500
3 W(mm)
B
200
220
250
300
320
350
400
500
550
600
650
700
800
200
220
250
300
320
350
500
550
600
650
700
800
L
400
400
400
400
400
400
400
450
450
450
500
500
500
400
400
400
400
400
400
450
450
450
500
500
500
A
450
450
450
450
450
450
450
550
550
550
600
600
600
450
450
450
450
450
450
550
550
550
600
600
600
Dimensions(mm)
4 W(mm)
B
L
200
400
220
400
250
400
300
400
320
400
350
400
400
400
500
450
550
450
600
450
650
500
700
500
800
500
200
400
220
400
250
400
300
400
320
400
350
400
500
450
550
450
600
450
650
500
700
500
800
500
A
500
500
500
500
500
500
600
600
600
600
650
650
650
500
500
500
500
500
500
600
600
600
650
650
650
5 W(mm)
B
200
220
250
300
320
350
400
500
550
600
650
700
800
200
220
250
300
320
350
500
550
600
650
700
800
L
400
400
400
400
400
400
400
450
450
450
500
500
500
400
400
400
400
400
400
450
450
450
500
500
500
End closer
End closer is a part used for finishing BUS DUCT line, and the connection is unnecessary. To extend the line, simply
remove this part and install it in addition.
205
Fig. 27.1
FRONT
OR
REAR
FRONT
OR
REAR
FRONT
OR
REAR
FRONT
OR
REAR
Fig. 27.2
Fig. 27.3
Table 27
MIN. STUB DIMENSIONS(mm)
AMPERE
RATINGS
(A)
600~2000
2500~3500
4000~4500
5000~6000
FIG. 17.1
SINGLE RUN
X
Y
300
300
350
350
400
400
500
500
X
300
350
400
500
FIG. 17.2
DOUBLE RUN
Y
300
350
400
500
Z
400
500
550
550
SINGLE RUN
X
Y
250
330
300
350
350
400
400
500
X
250
300
350
400
DOUBLE RUN
Y
300
350
400
500
Z
400
500
550
550
100
300
W+100
W+100
W+10
H+320
100
25
25
H+15
H+120
H+15
H+100
H+215
W46
H+200
25
FOR OUTDOOR
Fig. 28.1
Fig. 28.2
W+200
130
418HOLE
200MM
Wall
FOR INDOOR
H+60
H+120
H+160
H
200MM
H+160
UP Flange Size
(=Base channel size)
CUTOUT
88.5HOLES
85
W+200
100
86TAPS
Floor Openings
1. Front type
The F-dimension of Floor opening(cutouts) shall be
larger on much as 30mm than external dimensions of
BUS DUCT in case Front type of hanger. The Sdimension of Floor opening(cutouts) shall be min W+60
S
W + 70
H
30
28 29
H + 60
2. Side type
The S-dimensions of Floor opening(cutouts) shall be
larger on much as 35mm than external dimensions of
BUS DUCT in case side type of hanger. The Fdimension of Floor opening(cutouts) shall be min H+60
30
35
35
Wall, ceiling
Wall, ceiling
250mm
BEAM
200mm
500mm
50mm
wall
wall
200mm
Joint point
200mm
Fig. 29.1
VERTICAL MOUNTING
P2
EDGEWSE FORMATION
Joint point
P3
Joint point
P1
P2
200
FLATWISE FORMATION
Joint point
Joint point
100
100
Bus Duct
200
P4
Joint point
P3
P4
100
200
Vertical hanger
Fig. 29.2
Table 29
P1
P2
P3
P4
3-W AND
3-W
3-W AND
4-W
4-W AND
4-W
110
150
190
270
135
175
215
275
130
180
230
270
20
40
Plug-in or
Tap-off box
or Expansion
Plug-in or
Tap-off box
or Expansion
Fig. 29.3
160
35 60
60 35
Water Bank
(Out of Supply)
100
290
100x50x5t
160
16
30
16
85
A type
B type
Bracket
35
65
65 35
100
200
70
30
16
16
30
P
A type
B type
Application of A or B Type
(Average floor height : 3.5~4.5M)
Aluminum
Conductor
3W 600A 3W 1,600A
4W 600A 4W 1,200A
Copper
Conductor
3W 600A 3W 1,000A
4W 600 4W 800A
Aluminum
Conductor
3W 2,000A 3W 3,000A
4W 1,500A 4W 2,500A
Copper
Conductor
3W 1,200A 3W 2,500A
4W 1,000 4W 2,500A
P(mm)
A Type
1,000
85
(1 Rod)
1,200
85
1,500
85
1,600
85
B Type
2,000
110
(2 Rods)
2,500
140
3,000
160
30 31
Table 30.2
Hanger
Clamp
Hanger Rod
(Out of supply)
12
Hanger Red
20
W
Hanger Clamp
45
15
20
45
Hanger
M10
40
300
350
10
40
P
L
Hanger
Hanger Clamp
Dimensions (mm)
Rating in Amps
(A)
600~1,200
350
300
1,500~2,500
500
450
3,000~3,500
650
600
4,000~4,500
750
700
5,000~6,500
850
800
Floor Open
W
25
A
Min.70
B
Min.100
300
B+ H
600
B
Min. 100
A
Min.70
25
A
Min. 70
25
B+ H
P1 = 2H+2A+2B
L1 = P1+50
650
W
25
300
300
900
950
A
Min. 70
B
Min.100
B+H
P1 = 2H+2A+2B
L1 = P1+50
Hanger
*PS3 = 6 HOLES
*PS1 = 2 HOLES
NOTE:
1. PS-Feeder has plug-in hole both side.
2. The position can be changed for maintenance or convenience
3. Max. 6 Holes per 3000mm
*PS2 = 4 HOLES
Fig. 32.1
Bre
ake
rB
Std
Min.: 300
.: 1 0(m
00 m)
0(m
m)
Std
Min.: 300
.: 1 0(m
00 m)
0(m
m)
80
ox
14
Ta
00
po
ff B
ox
80
Ta
pO
ff
Ta
pO
ff
Ta
pO
ff
Fig. 32.2
NOTE: 1. 2 tap-off per 3000mm are recommended. 2. Max branch Ampere is 1200A
32 33
Plug-in Cover
Plug-in Hole
Contact Surface
Plug-in Unit
MCCB
MCCB, in which a circuit breaker and trip device are
assembled in a mold case, can manually open and close
the electric circuit.
MCCB can automatically cut off elecctric power in case
of overload and short cicuit.
MCCB has a variety of rated current frame from small
to large capacities(30AF~1200AF).
MCCB has four(4) type of breaking capacities
economical type(ABE), standard type(ABS), high
interrupting type(ABH) and current limiting type(ABL).
this feater allows easy application of design with an
appropriate breaking capacity.
Applied standards KSC-8321, IEC-60947.
Table 34
MCCB RATINGS
MODEL
ABS
ABH
ABL
FRAME (AF)
POLES
50
100
225
400
600
800
1000
1200
50
100
225
400
50
100
225
400
600
800
1000
1200
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
34 35
FUSE
FUSE, in which a circuit breaker is assembled by fuse
link, holder carrier and base, can manually or
electrically open and close the electric circuit.
Fuse has outstanding features in breaking capacity,
discrimination and stability compare to MCCB.
FDS, fuse type switch built in plug in or tap off bow in
various type, capacities and manufactuter.
Applied standards IEC 269.
Hinge type
Hinge type
External operation
External operation
Hinge type
Hinge type
Internal operation
External operation
Separation type
Separation type
External operation
External outlet
Internal operation
Branch unit must match with the bus dcut and rating
There are many type of bus dcut in LSC, so the bus dcut unit is determined by not only breaking device but also the
bus dcut type that is inserted.
Table 36
CURRENTS
FIRE
BUS DUCT
RANGE RESIST ANCE
Terminal Block
GENERAL
TYPE
S PLUG IN
TYPE
600~1200A
30~800A
D PLUG IN
TYPE
8-SERIES
Gasket
Insulation Supporter
Plug-in Contactor
30~400A
S PLUG IN
TYPE
600~1200A
30~800A
D PLUG IN
TYPE
F-SERIES
FIRE
RESISTANCE
TYPE
Y-SERIES
BRANCH TYPE
30~400A
I-SERIES
Plug-in Unit
Insulation Cover
BRANCH
AMP
Flexible joint
Terminal Block
Plug-in Unit
Plug-in Unit
Coble
Insulation Cover
Plug-in Contactor
Gasket
Insulation Supporter
When the type of bus duct and branch unit is not matched,
the branch unit is not inserted in bus duct so besides the type
of breaking device, below Bus Duct type must be checked.
Bus duct type: ____________
(ex: I-series, F-series......)
36 37
Tap off
Branch unit can be made various size and also cable can be pulled out any direction(rear, side, top) the below are LSC
standards.
Note: The box size will be changed according to the side or top pulling
direction. Table-37 show below pulling box size.
Table 37
MODEL
FRAME
ABS
ABH, ABL
ABS
ABH, ABL
ABS
ABH, ABL
ABS
ABH, ABL
ABS
ABH, ABL
ABS
ABH, ABL
ABS
ABH, ABL
ABS
ABH, ABL
ABS
ABH, ABL
50, 60
100
REMARK
3W
4W
370
220
220
200
200
400
220
220
200
400
750
240
280
200
50, 60
100
400
280
280
200
200
500
280
280
200
400
750
340
400
200
600
800
800
340
400
200
600
800
800
340
400
230
I, F-SERIES
1000
1200
1000
340
400
230
SAME
SIZE
I, FSERIES
8, YSERIES
Flexible conductor
Flexible conductor is made of braided copper wire, and the connection section is silver-plated for excellent contacting
property. This is mainly used for expansion joint of BUS DUCT or the connection of BUS DUCT with transformer or
panel.
Fig. 38.1
Fig. 38.2
Fig. 38.3
Table 38
AMPS
600
800
800
1000
1000
1200
1500
1600
2000
2500
2500
3000
3000
3500
4000
4500
5000
6000
38 39
75
100
100
125
150
175
230
2x140
2x175
2x200
3x175
3x200
A (mm)
FOR CU, BUS BAR
55
55
75
100
125
150
175
2x125
2x150
2x175
2x200
3x150
3x175
3x200
B (mm)
Fig
40
40
50
40
50
40
50
60
60
40
50
50
60
70
50
60
70
37.1
37.1
37.2
37.2
37.2
37.2
37.3
37.3
37.3
37.3
37.3
37.3
37.3
37.3
37.3
37.3
37.3
37.3
ALUMINUM
RATED LOAD
AMPS(A)
600
800
1000
1200
1500
1600
2000
2500
3000
3500
4000
4500
5000
6000
BAR SIZES
(mm)
(1) 6x55
(1) 6x75
(1) 6x100
(1) 10x100
(1) 10x125
(1) 10x150
(1) 10x175
(1) 10x230
(2) 10x150
(2) 10x175
(2) 10x200
(2) 10x230
(3) 10x175
(3) 10x200
350Hz
Rac
11.32
8.37
6.37
3.96
3.26
2.78
2.43
1.93
1.39
1.22
1.09
0.96
0.81
0.73
X
2.95
2.02
1.59
2.05
1.70
1.45
1.27
0.99
0.75
0.65
0.58
0.51
0.45
0.39
360Hz
Z
11.61
8.61
6.57
4.46
3.68
3.14
2.74
2.17
1.58
1.38
1.23
1.09
0.93
0.83
Rac
11.36
8.45
6.43
4.05
3.34
2.85
2.50
1.98
1.43
1.25
1.12
0.99
0.83
0.75
X
3.10
2.43
1.91
2.45
2.04
1.74
1.52
1.18
0.90
0.79
0.69
0.61
0.54
0.48
Rdc
Z
11.78
8.79
6.71
4.73
3.91
3.34
2.93
2.30
1.69
1.48
1.32
1.16
0.99
0.89
11.13
8.17
6.12
3.67
2.94
2.45
2.10
1.60
1.22
1.05
0.92
0.80
0.70
0.62
COPPER
RATED LOAD
AMPS(A)
600
800
1000
1200
1500
1600
2000
2500
3000
3500
4000
4500
5000
6000
BAR SIZES
(mm)
(1) 6x55
(1) 6x55
(1) 6x75
(1) 6x100
(1) 6x125
(1) 6x150
(1) 6x175
(2) 6x125
(2) 6x150
(2) 6x175
(2) 6x200
(2) 6x230
(3) 6x175
(3) 6x200
350Hz
Rac
7.10
7.10
5.29
4.06
3.34
2.85
2.49
1.83
1.42
1.25
1.11
0.95
0.83
0.74
X
2.59
2.59
2.02
1.59
1.31
1.11
0.96
0.68
0.57
0.49
0.43
0.39
0.34
0.30
360Hz
Z
7.56
7.56
5.56
4.36
3.59
3.06
2.67
1.95
1.53
1.34
1.19
1.03
0.90
0.80
Rac
7.17
7.17
5.35
4.15
3.42
2.92
2.56
1.89
1.46
1.28
1.14
0.97
0.85
0.76
X
3.10
3.10
2.43
1.91
1.57
1.33
1.16
0.82
0.68
0.59
0.52
0.47
0.40
0.33
Rdc
Z
7.81
7.81
5.88
4.57
3.76
3.21
2.81
2.06
1.61
1.41
1.25
1.08
0.94
0.83
6.87
6.87
5.04
3.78
3.02
2.52
2.16
1.51
1.26
1.08
0.94
0.84
0.72
0.63
Voltage drop
For 3-phase alternating current, the values of voltage drop per 100 meter are as follows.
ALUMINUM
600
800
1000
1200
1500
1600
2000
2500
3000
3500
4000
4500
5000
6000
BAR SIZES
(mm)
(1) 6x55
(1) 6x75
(1) 6x100
(1) 10x100
(1) 10x125
(1) 10x150
(1) 10x175
(1) 10x230
(2) 10x150
(2) 10x175
(2) 10x200
(2) 10x230
(3) 10x175
(3) 10x200
VOLTAGE DROP-360Hz
POWER FACTOR
POWER FACTOR
1.00
.95
.90
.85
.80
.75
1.00
.95
.90
.85
.80
.75
11.76
11.60
11.03
8.24
8.46
7.71
8.43
8.34
7.22
7.38
7.52
7.51
7.02
7.59
12.01
11.90
11.34
9.15
9.41
8.57
9.38
9.26
8.08
8.24
8.39
8.37
7.89
8.47
11.76
11.76
11.12
9.26
9.54
8.69
9.50
9.37
8.20
8.37
8.51
8.48
8.02
8.59
11.41
11.34
10.82
9.24
9.52
8.67
9.47
9.34
8.20
8.36
8.50
8.46
8.02
8.58
11.02
10.97
10.47
9.14
9.42
8.58
9.37
9.24
8.12
8.28
8.42
8.38
7.96
8.50
10.60
10.56
10.09
8.99
9.26
8.44
9.22
9.08
8
8.15
8.29
8.24
7.85
8.37
11.80
11.70
11.13
8.42
8.67
7.91
8.66
8.59
7.41
7.58
7.73
7.73
7.22
7.79
12.22
12.17
11.61
9.59
9.89
9.02
9.87
9.76
8.51
8.68
8.85
8.83
8.32
8.96
12.03
12.00
11.46
9.80
10.11
9.22
10.08
9.97
8.72
8.89
9.05
9.03
8.53
9.19
11.73
11.72
11.20
9.84
10.16
9.26
10.13
10.00
8.73
8.95
9.10
9.07
8.60
9.25
11.38
11.38
10.89
9.79
10.12
9.22
10.08
9.95
8.75
8.91
9.07
9.03
8.58
9.23
10.99
11.00
10.53
9.69
10.01
9.12
9.97
9.83
8.66
8.83
8.98
8.93
8.51
9.15
COPPER
RATED LOAD
AMPS(A)
600
800
1000
1200
1500
1600
2000
2500
3000
3500
4000
4500
5000
6000
BAR SIZES
(mm)
(1) 6x55
(1) 6x55
(1) 6x75
(1) 6x100
(1) 6x125
(1) 6x150
(1) 6x175
(2) 6x125
(2) 6x150
(2) 6x175
(2) 6x200
(3) 6x150
(3) 6x175
(3) 6x200
40 41
VOLTAGE DROP-360Hz
POWER FACTOR
POWER FACTOR
1.00
.95
.90
.85
.80
.75
1.00
.95
.90
.85
.80
.75
6.88
9.84
9.17
8.44
8.67
7.89
8.62
7.94
7.39
7.55
7.69
7.39
7.19
7.69
7.37
10.47
9.80
9.05
9.30
8.45
9.23
8.47
7.95
8.10
8.24
7.97
7.74
8.28
7.36
10.42
9.78
9.04
9.28
8.44
9.22
8.44
7.94
8.09
8.23
7.98
7.74
8.28
7.26
10.25
9.64
8.92
9.16
8.32
9.09
8.31
7.84
7.99
8.12
7.89
7.64
8.18
7.11
10.02
9.43
8.47
8.97
8.15
8.90
8.13
7.69
7.83
7.95
7.74
7.50
8.02
6.93
9.75
9.19
8.52
8.75
7.95
8.67
7.92
7.50
7.64
7.75
7.56
7.32
7.83
6.94
9.93
9.27
8.63
8.87
8.08
8.85
8.18
7.58
7.75
7.90
7.58
7.38
7.90
7.60
10.78
10.12
9.43
9.70
8.83
9.66
8.88
8.31
8.48
8.63
8.34
8.10
8.57
7.65
10.81
10.18
9.49
9.76
8.89
9.71
8.91
8.31
8.54
8.68
8.41
8.16
8.60
7.60
10.71
10.09
9.42
9.69
8.82
9.63
8.82
9.31
8.47
8.62
8.36
8.11
8.52
7.49
10.52
9.94
9.28
9.55
8.68
9.48
8.67
8.20
8.35
8.49
8.25
8.00
8.38
7.34
10.29
9.73
9.09
9.35
8.51
9.29
8.48
8.04
8.18
8.31
8.10
7.85
8.19
Short-circuit characteristics
Short-current(KA) Symmetrical.m.s
The short-circuit characteristics shown below are based on KS C 8450 and JIS C 8364.
When required, can be designed and supplied a bus duct having a larger capacity, for example, a reinforced type
shown below.
Reinforced type
Standard type
Table 41
RATED CURRENT(A)
KS/JIS SPEC(KA)
MAKERS STANDARD(KA)
REINFORCED TYPE(KA)
600
22
40
75
800
22
40
75
1000
22
50
100
1200
42
50
100
1500
42
50
100
1600
60
60
100
2000
60
60
100
2500
60
75
125
3000
60
75
150
3500
60
100
200
4000
60
125
200
4500
90
125
200
5000
90
175
200
6000
90
175
200
Joint point
Fig. 42.1
Time(hr)
Fig. 42.2
Table 42
SPOT
Description
42 43
busbar joint
busbar joint
busbar joint
busbar joint
housing
housing
housing
housing
room temperature
2.6 MAINTENANCE
Regular maintenance is required to maintain the best performance for the expected span of life
through prevention of any unexpected accidents in BUS DUCT line.
CHECKING PERIOD
After energizing, check once between a half year and a year. At this time, especially, verify that jointing bolt tightened,
and if loosened, tighten it normally. After that, perform regular checking once per year.
Table 43
SECTION
ITEM
Connection
section
Diverging
section
Machinery
combining
section
ACTION TO TAKE
UP JOINT COVER
JOINT COVER
STOPPER
CONTACT SURTACE
INS SPACER
SERAL NO.
CAPTIVE HARDWARE
HIGH TENSON JOINT BOLT
BELLEVLLE WASHER
HOUSNG CONNECTION
JONT COVER
SOUARE NUT
FIN
AL
CO
VE
R
WA
TE
RP
RO
OF
CO
VE
R
SE
T
M6 BOLT
x25
L (2
+4
EA
)
JO
INT
IND COV
OO
ER
R
WA
TE
RP
RO
OF
DU
CT
JO
OU INT 01
TD
OO COV
ER
R
BU
SD
UC
T
M6
SO
P
(2 + MUT
4E
A)
BU
SD
UC
T
LB
RA
CK
ET
MU
T
HE M10 . W.5
X
M1 NU SUS . S.W
T
0
JO
INT
O
B
M6 UTDO 2 CO
VE
NU
OR
R
T
SW
WS
M6
x25
LH
EX
BO
LT
Please confirm the following information in the case of order or a technologic inquiry
Purpose
Quotation (
Confirming (
Application
System design (
Producing instruction (
Completion data (
Project details
Delivery details
Project Name
Drawing
Contractor/Buyer
Materials
Consignee/Distributor
Installation
Installation company
Powering
BUS DUCT SPECIFICATION AND SCOPE
Type
Insulation (
), Fire resistance (
Conductor
Cu (
Plating method
Silver plate (
Grounding method
Standard (
Duct quality
SPCC (
), SGP(
Color
5Y7/1 (
), 7.5BG6/1.5 (
Wiring
3P3W (
), 3P4W (
Flange type
Standard (
Supplying scope
Flexible (
), Al (
), PI 800 (
), Mini (
), Baby (
Ampere
Voltage
), Silver coating (
), PE (
), Tin coating (
/Size :
), SUS (
), Others (
), Non standard (
), End (
), AL (
), 1P2W (
)
Amp
), CU (
), 1P3W (
), Bare conductor (
), (
)P(
), Box (
), Hanger (
IP material
SGP(
), SUS (
IP grade
IP41(
), IP54(
), SPC (
), IP65 (
)
)
)
), Others (
Edgewise (
), Flatwise (
Front (
Installation site
Indoor (
Line constitution
PNL(M/T) + PNL(
), Oil TR+PNL(
Up (
), Up/Dwon (
), Side (
), Medium (
), Outdoor (
), Down (
), Mixed (
), Mixed (
), Riser (
), Support (
)
), Fire barrier (Economic type, Quality type)
mm )
Valance measurement
Y(
), N (
mm)
ABS (
), ABH (
Magnetic number
3P (
Switch ampere
Voltage (
), 4P (
), ABL (
), 2P (
V), 22KA (
), ABE (
)
), 42KA (
), FDS (
), MCCB (
Door operation
Standard (
), 85KA (
), 100KA (
)
), Bolting (
), Others (
), Handle (
), Lever (
:Y(
), N (
:Y(
), N (
:Y(
), N (
4. Utility
:Y(
), N (
44 45
3.2
46 47
3000mm
Housing
(Steel)
Conductor
(Cu)
Ampere
Ratings(A)
Conductor Size
(mm)
Ground bar
(mm)
WxH
(mm)
Resistance
(/m)
Resistance
(/m)
Appr.weight
(kg/m)
300
3x35
400
3x60
3x15
164x75
2.19xE4
1.28xE4
27
3x20
164x100
1.28xE4
0.96xE4
37
P.E
(Cu)
Insulator
(BMC)
Fig. 47.1
STANDARD CONSTRUCTION
Feed-in Box
Center Feed-in
Plug-in Box
TEE
End closure
Hanger
Elbow
Fig. 47.2
TOP
3 3W
3 4W
INTERNAL
NEUTRAL
1
INTERNAL
GROND BUS
2
3
W(140)
59
H(55)
GROUND BAR
BUS BAR
P.1 HOLE
INSULATOR
Fig. 48.3
Ampare Ratings(A)
Conductor Size(mm)
Ground bar(mm)
W x H(mm)
Lenght(m)
Approx.weigts(kg/m)
100
3x15
3x10
140x55
1~3
6~7
48 49
STANDARD CONSTRUCTION
15
Elbow
TEE
50
End closure
Hanger
Plug-in Box
Fig. 49.1
U
PL
PL
EN
DC
LO
R
SU
L
AB
E
EF
UG
-IN
BO
G-
IN
BA
U
YB
SD
UC
HO
RIZ
ON
TA
L
EL
BO
W
X
PL
ED
UG
-IN
BO
T
OR E
PP
SU TYP
LL
WA
ER
NG
G
H A ;OM
O
CE
Fig. 49.2
B-Series
1. Applicable standard :
2. Rated voltage : 100~600V
3. Rated current : 300~400A
4. Wiring system : ( ) Phase, ( )Wire
5. Current Rating of plug-in box :
6. Conductor material : Copper
7. Place of installation : Indoor, Outdoor,
Indoor+Outdoor
8. Color : 7.5BG 6/1.5 5Y7/1 N7.5 etc
9. Drawing of basic layout
10. Single line diagram
11. Something Important
1. Applicable standard :
2. Rated voltage : 100~600V
3. Rated current : 100A~200A
4. Wiring system : ( ) Phase, ( )Wire
5. Current Rating of plug-in box :
6. Conductor material : Copper
7. Place of installation : Indoor, Outdoor,
Indoor+Outdoor
8. Color : 7.5BG 6/1.5 5Y7/1 N7.5 etc
9. Drawing of basic layout
10. Single line diagram
11. Something Important
MEMO
50 51
4.2
3 WIRE
4 WIRE
Fig. 52.1
Fig. 52.2
COPPER
AC
Ampere
Rating
52 53
600
800
1000
1200
1500
1600
2000
2500
3000
3500
4000
Table 52
3 - W PE
4 - W PE
W Width
(mm)
H Height
(mm)
App. Weight
(mm)
W Width
(mm)
H Height
(mm)
App. Weight
(mm)
400
400
400
400
400
400
400
500
500
700
700
250
260
275
350
350
350
400
350
375
400
400
51
57
58
64
69
74
90
109
123
138
178
400
400
400
400
400
400
400
500
500
700
700
250
260
275
350
350
350
400
350
375
400
400
55
58
61
69
76
83
103
127
145
164
218
Feeder
Vertical Elbow
Horizontal Offset
Horizontal Elbow
Vertical Offset
Horizontal Tee
Wall Flange
Fig. 54.1
STRUCTURAL SUPPORTS
HV. BUS DUCT
Hanger
Hanger Bar
Clamp
C-CHANEL
W + 200
SW
BD
R
EA
HG
TTC
SW
SW
BD
Fig. 54.3
54 55
H
400
400
A-Series
1. Applicable standard :
2. Rated voltage : 3.3KV 6.6KV 7.2KV 11.5KV
13.8KV 15KV 22.9KV 24KV 35KV
3. Rated current : 400A~4000A
4. Wiring system : (
) Phase, (
)Wire
5. Short-Circuit Capacity : 1.6KV 4KV 8KV 12.5KV
16KV 20KV 25KV
31.5KV 40KV 50KV etc
6. Conductor material : Copper
7. Place of installation : Indoor, Outdoor,
Indoor+Outdoor
8. Color : 7.5BG 6/1.5 5Y7/1 N7.5 etc
9. Drawing of basic layout
10. Single line diagram
11. Something Important
1. Applicable standard :
2. Rated voltage : 100~600V
3. Rated current : 600~4000A
4. Wiring system : (
) Phase, (
)Wire
5. Conductor material : Copper
6. Place of installation : Indoor, Outdoor,
Indoor+Outdoor
7. Color : 7.5BG 6/1.5 5Y7/1 N7.5 etc
8. Drawing of basic layout
9. Single line diagram
10. Something Important
MEMO
www.lscable.com
555 Hogye-dong Dongan-gu Anyang-si, Gyeonggi-do, 431-831, Korea
BUS DUCT TEAM : Tel (031)428-4270~4280 Fax (031)428-4281
INTERNET : http://www.lscable.com E-MAIL : busduct@lscable.com
LSC-BD-2006-02