Professional Documents
Culture Documents
Bravo Inverter Datasheet
Bravo Inverter Datasheet
Inverter
(-48Vdc + 230Vac) /
230Vac
Features and Benefits
Dual input sources (AC & DC)
Compact and lightweight solution
High efficiency
Full scalability and expandability
Hot swappable
Pure sine wave on AC output
Transfer time reduced to naught
No single point of failure
Total modularity as no external
static-switch required
DC Power for
Business-Critical Continuity
Description
Inverter systems are normally used for AC backup requirements in a
telecom / datacom site or anywhere a highly reliable AC power back up
source is needed.
BRAVO is a compact and scalable inverter providing a pure sine wave AC
supply. In conjunction with a DC Power system, it provides an excellent
AC backup solution. The TSI (Twin Sine Inverter) uses the latest inverter
technology, providing superior energy efficiency in a compact size.
The inverter is designed to work from 230Vac and 48Vdc sources through
AC/AC and DC/AC conversions. Unlike traditional inverters, the TSI features
an AC to AC conversion that assures double filtering function. This results in
an efficiency of 96% without any compromise in quality and stability of the
output wave form. This off line operation mode is called Enhanced Power
Conversion (EPC).
The EPC mode, which is the filtering of current and voltage, is similar to a
rectifier combined with an inverter (online mode) but gives a significantly
better efficiency. Compared to a UPS operating in offline mode (no current
conversions) the efficiency is the same, but the rejection of grid disturbances
is much higher.
The online mode is usually only used during a mains outage when inverters
are fed by batteries. Therefore, the TSI inverters will almost constantly
provide an efficiency of 96%. It will always be the most reliable AC backup
solution!
The TSI inverters also have an in-built static switch function. Because no external
static switch is needed, the inverter system becomes smaller, more reliable and
easily expandable. As many as 32 inverter modules can be used in parallel.
AC in
AC
AC in
AC out
AC
DC in
AC
AC out
DC in
DC
AC
DC
EN 61000-4
EN 55022 (Class B)
IEC 60950
Forced
Doubled
240,000 hrs
Enhanced power conversion 96%
On line 91%
DC/AC 4300Vdc
Compliant
3 disconnection levels on AC out and DC in
Power ports
4 disconnection levels on AC in port
Dielectric Strength
True Redundant Systems
RoHS
Connection
Compliant
I/O terminal block protected against inversion
of polarity
Self adaptive to wide operating conditions and
comprehensive table of troubleshooting codes
Trouble-free Operation
AC Output Power
Nominal Output Power
Output Power (resistive load)
Short Time Overload Capacity
Permanent Overload Capacity
Admissible Load Power Factor
Internal Temperature Mgmt.
2500 VA
2000 W
150% 5 second
110%
Full (power rating from 0 inductive to 0 capacitive)
Switch off
DC Input Specifications
Nominal Voltage (DC)
Voltage Range (DC)
Current (at 40Vdc)
Maximum Input Current
Recommended Protection
Voltage Ripple
Input Voltage Boundaries
48 V
40 - 60 V
56A (224A per shelf)
84A (336A per shelf for 5 seconds)
63A circuit breaker per inverter
2mV
User selectable
AC Input Specifications
Nominal Voltage (AC)
Voltage Range (AC)
Current (at 185Vac)
Conformity Range
Power Factor
Frequency Range (selectable)
Synchronization Range
AC Output Specifications
Nominal Voltage (AC)*
Voltage Range (AC)
Voltage Accuracy
Frequency
Frequency Accuracy
Total Harmonic Distortion (resistive load)
Load Impact Recovery Time
Turn On Delay
Nominal Current
Crest Factor at Nominal Power
(with short circuit mgmt. and protection)
Short Circuit Clear up Capacity**
230 V
200 - 240 V
2%
50 - 60 Hz
0.03 %
<1.5 %
0.4 ms
20 s
10.9 A (protected against reverse current)
3.5
10 x In for 20msec
0s
0s
Environment
Altitude Above Sea
Ambient Temperature
Storage Temperature
Relative Humidity
<1500m
-20 to 50 C
-40 to 70 C
95% , non-condensing
Synoptic LED
Dry contacts on shelf
Use optional devices
102 x 435mm x 2U
5 Kg
Coated steel
230 V
185 - 265 V
56A per shelf
Adjustable
>99%
50 - 60 Hz
47 - 53 Hz, 57 - 63 Hz
AC Power
Connectivity
Embedded Power
Precision Cooling
Racks & Integrated Cabinets
DC Power
Outside Plant
Services
Embedded Computing
Surge Protection
Business-Critical Continuity, Emerson Network Power
and the Emerson Network Power logo are trademarks
and service marks of Emerson Electric Co.
2010 Emerson Electric Co.
Emerson Network Power reserves the right to alter without notice the specification, design or conditions of supply of any product or service.