You are on page 1of 36

NUS/ECE

EE2011

Transmission Lines Smith Chart &


Impedance Matching
1 Smith Chart
Smith chart is a graphical plot of the normalized
resistance and reactance functions in the complex
reflection-coefficient plane. It is a graph showing both
the normalized impedance and the reflection coefficient.
Smith chart is convenient for transmission line and circuit
calculations. It is also a useful tool in impedance
matching circuit design.
Hon Tat Hui

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

Recall that:

EE2011

Z (A ) Z 0
(A ) =
Z (A ) + Z 0
1 + (A )
Z (A ) = Z 0
1 (A )

Now normalize the impedance Z() by Z0.


Z (A )
z=
Z0
Hon Tat Hui

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

In terms of the normalized impedance z (drop the


dependence), we can write:
z 1
=
= re + jim
z +1
1 + (1 + re ) + jim
z = r + jx =
=
1 (1 re ) jim

From the last equation, we have


r=

Hon Tat Hui

1 re 2 im 2
2

(1 re ) + im

x=

2im 2
(1 re ) 2 + im 2

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

The last two equations of r and x define two families of


circles in the complex plane of reflection coefficient .
im

im

r = 0 (short)

r =1
0

0.5

re

0.5

re

r=

(open)

The Smith char is the superposition of these two families


of circles together in the complex plane of reflection
coefficient .
Hon Tat Hui

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

The Smith Chart


Hon Tat Hui

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

A point in the Smith chart gives the values of the


normalized impedance z and the complex reflection
coefficient at the same point on a transmission line.
zim

zre

or z

S
Hon Tat Hui

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

When the angle of is zero, is real and =||.


Then,
1+ 1+
=
=S
1 1
But when the angle of is zero,
1+
=z=r
1
Thus, the value of S is same as r when the angle of is
zero and can be read out directly from the Smith chart by
noting the r value (S = r).

Since all points on the dotted black circle have the same
||, they must also have the same S. This circle is
known as the constant VSWR circle.
Hon Tat Hui

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

For example,
All points on this circle
have a S = r =3

r=3

Hon Tat Hui

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Example 1
Plot the following impedances on to the Smith chart.

3 = 1 28

Hon Tat Hui

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Solutions
Z1
Z3

Z5
Z6
Z8
Z7
Z4

Hon Tat Hui

Z2

10

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

1.1 Smith chart and transmission lines


L

towards generator

z = -d
=d

()
Z()

z=0
=0

Recall that on a transmission line:

(A ) = = L e j 2 kA

= L
Hon Tat Hui

11

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Hence, can be obtained from L by moving


clockwise along a constant circle on the Smith chart
with a radius |L| through an angle -2k which is
equivalent to / wavelengths measured towards the
generator on the periphery of the Smith chart.
l

l=/
=-2k

This circle is also


known as the constant
VSWR circle. All the
points on this circle has
the same S and same ||.
Hon Tat Hui

12

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

1.2 Reading on Smith chart


Several scales around
the outside of the Smith
chart are used to
determine the distance
along the line. Some
Smith charts have a
number of scales at the
bottom of the chart for
measuring the reflection
coefficient magnitude
and others.

Hon Tat Hui

13

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Two scales on the periphery (in wavelengths):


-Wavelengths towards generator (WTG scale),
clockwise sense
-Wavelengths towards load (WTL scale),
anticlock sense
Note also that a complete turn around the Smith
chart corresponds to a total length of /2. Because:

(A 2 ) = (A 1 )e j 2 k (A A )
When A 2 A 1 = 0.5 , the phase turned
from (A 1 ) to (A 2 ) is :
2
2k (A 2 A 1 ) = 2
0.5 = 2 = 360

Hon Tat Hui

14

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Impedance admittance
z y = 1/z
Any point reflected through
the centre point converts an
impedance to an admittance
and vice versa.

z=1.8+j2

Top Half: inductive reactance, XL = L


or
capacitive susceptance , BC = C
Bottom Half: capacitive reactance , XC = 1/C
or
inductive susceptance , BL = 1/L
Hon Tat Hui

15

y=0.25-j0.28
= 1/(1.8+j2)

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Example 2
Use Smith chart to find the input impedance Zin looking at
the input of a transmission line.
0.3

Zin

(a) Actual circuit


(b) Normalized circuit
Hon Tat Hui

16

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Example 2 (contd):

L = 0.745
= 0.7e

Hon Tat Hui

17

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Example 2 (contd):

in

in = L e j 2 kz '
j

= 0.7e e
4

j 2

0.3

= 0.7e j 0.95
1 + in
zin =
= 0.1775-j 0.0762 (at point c)
1 in
Zin = zin Z 0 = 8.8765 j 3.8118
See animation Transmission Line Impedance Calculation
Hon Tat Hui

18

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Voltage Maxima and Minima in Smith Chart


Voltage maxima occur when the angle of the
relfection coefficient (()) = -2n (n = 0, 1,
2, ). This corresponds to the right-most
point in the Smith chart. Voltage minima occur
when the angle of the relfection coefficient
(()) = -2(n+1) (n = 0, 1, 2, ). This
corresponds to the left-most point in the Smith
chart. See an example shown on next page.

Hon Tat Hui

19

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

V (A )

zL
AM

Am

A=0

m
=0
Hon Tat Hui

20

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

2 Impedance Matching
Meaning of impedance matching
Impedance matching is to eliminate the reflected voltage
or current on a transmission line.
Reasons for impedance matching:
1. Maximize power transfer to the load
2. The input impedance remains constant at the value Z0.
Therefore, the input impedance is independent of the
length of transmission line.
3. VSWR = 1. Therefore there are no voltage peaks on
the transmission line.
Two matching techniques:
1. Quarter-wave transformer
2. Single-stub matching network
Hon Tat Hui

21

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

2.1 Quarter-wave transformer


For a transmission line of length d=/4, characteristic
impedance = Zs, and terminated in an impedance RL,
RL + jZ s tan ( 2 ) Z s2
Zi = Z ( A = 4) = Z s
=
Z s + jRL tan ( 2 ) RL

Zi

When Zs is real, we can change Zs to achieve a desired


Zi.
Hon Tat Hui

22

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Example 3

A signal generator has an internal impedance of 50 . It needs to feed


equal power through a lossless 50 transmission line to two separate
resistive loads of 64 and 25 at a frequency of 10 MHz. Quarter-wave
transformers are used to match the loads to the 50 line, as shown below.
(a) Determine the required characteristic impedances and the physical
lengths of the quarter-wavelength lines assuming the phase velocities of
the waves traveling on the them is 0.5c. (b) Find the standing-wave ratios
on the matching line sections.

Hon Tat Hui

23

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Solutions
(a) As the two quarter-wave transformers are connected in parallel to
the 50- line, if equal powers are required to the two loads, the input
impedances of the two branches looking at the junction from the 50-
line must be equal to 100 so that when they add together in parallel,
the total impedance is 50 .
R0

Rin1=100

R0

100

100

50

Rin2=100
Hon Tat Hui

24

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Solutions (contd):

Z in1 = Rin1 = 100

Therefore,

Z in 2 = Rin 2 = 100
The characteristic impedances R01 and R02 can be found by:
R'01 = Rin1 RL1 = 100 64 = 80
R'02 = Rin 2 RL 2 = 100 25 = 50

up =

0 0 r

c
r = 4
2

0
30 m
= wavelength along the transformers =
=
= 15 m
2
r
Physical length of the transformers = /4 = 3.75 m
Hon Tat Hui

25

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Solutions (contd):

Hon Tat Hui

26

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

2.2 Single-stub matching network


What is a stub?
A stub is a short section of transmission line (shorted or open at
one end) whose input impedance can be changed by varying its
length.

load to be
matched
B-B = matching point
d = matching position
= length of the matching stud
yB = normalized admittance of line at B-B
ys = normalized admittance of the stub
yL = normalized admittance of the load
Hon Tat Hui

27

parallel stub
(short-circuited)

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

When a transmission line is matched at the matching point,


yi = y B + y s = 1 or Yi = YB + Ys = Y0
B

Matched

R0

jx
R0

-jx

After matched, there is no


reflection on the line to the
left of B-B. But there are
reflections on the line to the
right of B-B and on the stub.
Hon Tat Hui

28

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Use of admittance
For parallel stub matching, the stub is connected in parallel
with the transmission line. Hence it will be more
convenient to use admittance rather than impedance. In
Smith chart, when a impedance z is known, the
corresponding admittance, y = 1/z, can be obtained by a
reflection through the centre of the Smith chart. The
admittance y is represented on the same Smith chart but its
position is different from that of z. When every impedance
point on the Smith chart is reflected in this way, we
transform the impedance Smith chart to an admittance
Smith chart in which every point now represents a
normalized admittance.
For parallel-stub matching, we
work in the admittance Smith chart.
Hon Tat Hui

29

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Reminder
On plotting into the Smith chart, all values have to be
normalized by the characteristic impedance Z0 (or the
characteristic admittance Y0 = 1/ Z0) first. Normalized
values are usually represented by small letters while unnormalized values by CAPITAL LETTERS. For example:

Hon Tat Hui

Normalized quantity
zL= ZL / Z0
yL = YL / Y0

Un-normalized quantity
ZL
YL

zin = Zin / Z0

Zin

yin = YL / Y0

Yin
30

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Method to determine d and


Choose d such that:
Z 0 + jZ L tan (kd )
1
yB =
=
= 1 + jbB
z (A = d ) Z L + jZ 0 tan (kd )

Choose such that:


1
ys =
= j cot (kA ) = jbB
j tan (kA )

So that:
yi = y B + y s = 1
Hon Tat Hui

31

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Steps in single-stub matching (using normalized z and y):


1. Convert the load impedance zL to an equivalent
admittance yL = 1/zL.
2. Use a line of length d and a characteristic impedance Z0
(characteristic admittance Y0 = 1/Z0) to transform yL to
yB = 1 + jbB at B-B.
3. Connect a parallel stub of length and characteristic
impedance Z0 at B-B with an input admittance
ys=-jbB=-jcot(2/).
4. Then, the total admittance at B-B is:

yi = y B + ys = 1 + jbB jbB = 1 matched


Hon Tat Hui

32

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

The detailed matching steps in the Smith chart will be


explained by using the example shown below.
Example 4
A 50 lossless transmission line is connected to a load
impedance ZL=35-j47.5. Find the position d and length l of
a short-circuit stub required to match the load at a frequency
of 200 MHz. Assume that the transmission line is a coaxial
line filled with a dielectric material for which r = 9.
Solutions

Hon Tat Hui

33

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

Hon Tat Hui

EE2011

34

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

Reasons for Choosing a Shorter-Line Solution


Sometimes, out of the two basic sets of solutions, (d1, l1) and (d2 , l2), it is
advantageous to choose a shorter combination of d and l. There are at least two
reasons for this:
1. Shorter lines can always reduce the inevitable loss along the lines, though this is
small.
2. Shorter lines result in a smaller Q-factor for the resonant circuit consisting of the
stub and the transmission line to the right of the matching point. A smaller Qfactor produces a wider matching bandwidth, i.e., the matching condition being
less sensitive to frequency change.

Drawings on Smith chart shown on next page


Hon Tat Hui

35

Transmission Lines Smith Chart & Impedance Matching

NUS/ECE

EE2011

d1

yL

j1.2

P2 '

P4 "

P2

P3

P3 '
g =1

1+j1.2
Psc

zL

1-j1.2
P1 P4
P3 "

-j1.2
Hon Tat Hui

d2

P4 '

1
See animation
Parallel Stub
Matching Short

Solutions on Smith chart for Example 4


Transmission Lines Smith Chart & Impedance Matching
36

You might also like