Basics of

Current and Voltage Transformers


Power Transmission and Distribution

Author

Page 241

2007-08

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

Equivalent current transformer circuit

I1

jX1 R1

I 2 = I1

N1
N2

jX2
Im

P1
N1

N2 U

R2

I2
S1

Zm

Zb

P2

Ideal CT

S2

X1 = Primary leakage reactance


R1 = Primary winding resistance
X2 = Secondary leakage reactance
Z0 = Magnetizing impedance
R2 = Secondary winding resistance
Zb = SecondaryAuthor
load
Note:

Page 242

2007-08

Power Transmission and Distribution

Normally the leakage fluxes X1 and X2 can be neglected

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

Current transformer, simplified equivalent circuit

jX2

1 : N2

i2

i1

i'1 =

N2
1

R2

i1

LW

L2<< LW

im

ZB

R2

i2
Power Transmission and Distribution

RB

Author

Page 243

2007-08

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

Current transformer:
Phase displacement () and current ratio error ()

I1 .
I1

N1
N2

N1
I2
N2
I2

Power Transmission and Distribution

Zb
Author

Im

Page 244

2007-08

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

CT classes to IEC 60044-1: 5P or 10P


Pi = I sec .2 R CT

Specification:

300/1 A

5P10, 30 VA

Ratio In -Prim / In -Sek.


5% accuracyat I= n x In
Actual accuracy limit factor
in operation is higher as the CT
ALF ' = ALF
is normally underburdened :
Operating ALF: ALF

RCT 5 Ohm

Rated burden
(nominal power) PNB
Accuracy
limit factor ALF

Pi + PNB
Pi + PBB

Dimension criterium:
I
ALF ' SC max KTF
Power Transmission
I n and Distribution

KTF (over-dimensioning factor) considers the single sided CT over-magnetising due to the d.c.
Author
component in short circuit current ISC.
KTF values required in practice depend on relay type and design.
Recommendations are provided by manufacturers (see Application Guides)
Page 245

2007-08

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

Definition of the CT knee-point voltage

U2
10 %
IEC 60044-1 Class PX

UKN

formerly

50 %

British Standard BS3938:


Class X
Power Transmission and Distribution

Author

Im

Page 246

2007-08

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

Current transformer, Standard for steady-state performance

IEC 60044-1 specifies the following classes:

Accuracy class

Current error
at nominal
current (In)

5P

1%

10P

5%

Angle error
at rated current
In
60 minutes

Total error at n x In
(rated accuracy limit)

5%
10 %
Power Transmission and Distribution

Author

Page 247

2007-08

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

Current transformers, Standard for transient performance

IEC 60044-6 specifies four classes:


Class

Error at rated current


Ratio error

TPX
(closed iron core)

TPY
with anti-remanence
air gap

TPZ
linear core

TPS

2007-08

Remanence

Angle error

0,5 %

30 min

10%

1,0 %

30 min

10%

1,0 %

180 18 min

10%

Author

no limit
< 10 %
Power Transmission and Distribution

(a.c. current only)

Special version for


high impedance protection
Author
(Knee point voltage, internal secondary resistance)

closed iron core

Page 248

Maximum error at
rated accuracy limit

negligible

No limit

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

Current transformer saturation

Steady-state saturation with AC current

Power Transmission and Distribution

Author
Transient saturation with offset current

Page 249

2007-08

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

Transient CT saturation due to DC component

ISC

Short circuit current

DC flux non-saturated

AC
flux
Power
Transmission and Distribution

Author

Im
Page 250

Magnetising current

2007-08

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

Course of CT-flux during off-set short-circuit current


P primary current

B
TN TS TN
= 1+
(e
e TS )
TN TS
B

d.c. component

TS
N TS TN

T
BMax
= 1+ TS
B~
TS

t
TN

total flux

t B Max =

BMax

transient
d.c. flux

B~

TS =

a.c. flux
Author

B~

Page 251

2007-08

Author

TN TS
TS
ln
TS TN TN

LW Power Transmission
1
and Distribution
=
Ri + RB tan

For 50 Hz:

TS =

10900

[min ]

[ms]

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

CT transient over-dimensioning factor KTF


KTF
6
0

TN
KTF = 1+ TS
TS

TS
TS TN

(KTF 1+TN)
5000

5
0

Closed iron core

1000

4
0

TS [ms]
500

3
0

250

2
0

100

Linear core

1
0

Power Transmission and Distribution

TN = network time constant


(short-circuit time constant)
Author

50

Page 252

2007-08

100

150

200

Author

TN [ms]

TS = CT secondary time constant

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

CT with closed iron core,


Over-dimensioning factor KTF for specified time to saturation (tM)
15
14

tM

tM

Ktd

50 ms
40 ms

10

30 ms
20 ms

10 ms

Page 253

20

2007-08

40

60

80
Tp

Author

Power Transmission and Distribution

tM :

KTF = 1+ TN = 1+

Author

K' TF

tM

= 1 + TN 1 - e T N

XN
RN

100 [ ms]
Copyright Siemens AG 2007. All rights reserved.
PTD SE PTI

CT over-dimensioning factor KTF (tM,TN)


in the case of short time to saturation (tM)

KTF

tM

(tM,TN)

(el. degree) 160

10 ms

3.5

140

120

8 ms

2.5

tM

100

10 ms
8 ms
6 ms
Power Transmission and Distribution
4 ms
2 ms

80
6 ms

1.5
1

60
40

4 ms

0.5
0

180

2 ms

Page 254

20

40

60

80

2007-08 T

Author

100

in ms

20

Author

20

40

60

80

100

Copyright Siemens AG 2007. All rights reserved.


TPTD
msPTI
N inSE

Current transformer
magnetising and de-magnetising

B
t

BMax

B = BR + (BMax. BR ) e
BR

BMax

t
TS

BR
Power Transmission and Distribution

m
Author

Page 255

2007-08

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

Current transformer
Course of flux in the case of non-successful auto-reclosure

Bmax

tF1 = duration of 1st fault

t
tF1

tDT

tF2

tDT dead time


Power Transmission and Distribution

tF2 =duration of 2nd fault

tF1
tDT+tF2
tF2
tF1
tF2

Author

N TS
Bmax TN TS TN
T

= 1+
e TS e TS + 1+
(e
(e TN e TS

TN TS
TN TS
B~

Page 256

2007-08

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

Current transformer
magnetising curve and point of remanence

II

III

up to 80%

< 10%
negligible

H = im w
Power Transmission and Distribution

I: closed iron core (TPX)


II: core with anti-remanence air-gaps (TPY)
Author

Page 257

2007-08

Author

III: Linearised core (TPZ)

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

Current transformers TPX und TPY


Course of the flux with non-successful auto-reclosure

BR

BR

closed iron core (TPX)


Power Transmission and Distribution
core
with antiremanence air-gaps (TPY)

Author

tDT

tF1

Page 258

2007-08

tF2

Author

t
Copyright Siemens AG 2007. All rights reserved.
PTD SE PTI

Standards of voltage transformers


VT classes to IEC 60044-2
Class
designation

Permissible error at 0.05 UN and 1.0 UN


Voltage error FU

Angle error

3P

3.0 %

120 minutes

5P

6.0 %

240 minutes

All 3P and 5P protection CTs must


additionally comply with one of the
below VT metering classes!

VT classes for measurement IEC 60044-2


Class
designation

Page 259

Permissible voltage error in %


at 1.0 UN

0.1
0.2

0.1
0.2

0.5

0.5

1
3

1
3

2007-08

Permissible angle error in minutes


at 1.0UN

Power Transmission and Distribution

Author

Author

10
20
30
Not determined

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

Capacitive voltage transformer,


Equivalent circuit
400 kV
C1 = 5 nF

C2 = 95 nF

RF

20 kV

LF

CE = C 1 + C 2
C1

U*1 = UP
C1 + C2

Page 260

2007-08

100 V

CF

LO
RE

T
Author

Author

ZB

Power Transmission and Distribution

RF
RT

LT

LF

CF

U*2

R'B
L'B

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

Transient performance of CVTs,


Recommendations acc. to IEC 60044-5

Ratio
Measured voltage transients after fault at
voltage maximum and zero-crossing
(Example)

Time
Ts
in ms

UP(t) Primary voltage

2 Us

100%

Classes

3PT1
6PT1

3PT2
6PT2

3PT3
6PT3

10

---

25

20

10

10

40

10

60

10

0.6

10

0.2

90
Legend:

Us (t)

Power Transmission and Distribution

Recommendations to IEC 60044-5

US(t) Secondary voltage

Author

Page 261

2007-08

(1)

Fault inception

(2)

Aperiodic damping of US(t)

(3)

Periodic damping of US(t)

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

CT dimensioning

K OD = KTF

Pi + PBN
RCT + RBN
ALF' = ALF
= ALF
Pi + PB
RCT + RB

Actual connected burden : PB= RB I2N2

P + PB
RCT + RB
= ALF'
ALF = ALF' i
Pi + PBN
RCT + RBN
with

I
ALF ' K OD K
IN

Theory:

K OD K TF K Re m
K Re m =

1
% Remanence
1
100

Page 262

2007-08

rated CT burden:
PBN
internal burden of the CT: Pi=Ri I2N2

RB=Rl+RR= burden resistance


Rl= resistance of connecting cables
RR= burden resistance of the relay
No saturation
for the total
short-circuit duration:
No saturation for
the specified time tM:

Practice:Author

K' TF =

BMax
XN
= 1 + TN = 1 +
RN
B ~

Power
tM
Transmission andtMDistribution

T
N TS

(e TN e TS
K ' 'TF = 1 +
TN TS

Remanence only considered in extra high voltage systems (EHV)


KTF-values acc. to relay manufacturers guides

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

Practical CT requirements
Transient over-dimensioning factors KTF (AR not considered)
Distance
7SA6 and 7SA522
Overcurrent
7SJ56

Close-in fault:

KTF 5

Fault atbalance point:

KTF 2 ( 1 if TN < 30ms)

ALF I>>setting/ IN, at least 20


Internal fault

External fault

Transformer Differential
7UT6

KTF 0.75
(Saturation free
time 4 ms)

KTF 1.2
(Saturation free
time 5 ms)

Line differential
7SD61

KTF 0.5
(Saturation free
time 3 ms)

KTF 1.2
Power Transmission and Distribution
(Saturation free
time 5 ms)

Bus differential
7SS52

Page 263

Author
KTF 0.5
(Saturation free
time 3 ms)

2007-08

Author

KTF 0.5
(Saturation free
time 3 ms)
Copyright Siemens AG 2007. All rights reserved.
PTD SE PTI

CT dimensioning for
Example differential protection (1)
1. Calculation of fault currents
110 kV, 3 GVA

F1

110/20 kV
40 MVA
uT=12%

F2

OH-line:
l = 8 km,
zL= 0,4 /km

F3

F4

Net
300/1A
IT

7UT61

Transf. :

IL

7SD61

IL

Impedances related to 20 kV:

Impedances related to 110 kV:

Net :

200/1A

200/1A

1200/1A

U N 2 kV 2
110 2

ZN =
=
= 4.03
SSC ' ' [MVA ] 3000
U N 2 kV 2
Author
uT [% ] 110 2 12 %

ZT =

= 36.3
PN -T [MVA ] 100
40 100

Net :

Transf. :

U N 2 kV 2
Power Transmission
20 2
and Distribution
ZN =
=
= 0.13
SSC ' ' [MVA ] 3000
U N 2 kV 2

uT [% ] 20 2 12 %
ZT=

= 1.2
PN -T [MVA ] 100
40 100

Line : Z L = l[km ] z L ' [/km ] = 8 0,4 = 3,2


Page 264

2007-08

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

CT dimensioning for
Example differential protection (2)
1.1 U N / 3 1.1 110kV/ 3
=
= 17.3 kA
ZN
4.03

F1

I F1 =

F2

1.1 U N / 3 1,1 110kV/ 3


I F2 =
=
= 1.73 kA
Z N + ZT
4.03 + 36.3

F3
F4

I F3 =
I F4 =

1.1 U N / 3 1.1 20kV/ 3


=
= 9.55 kA
Z N + ZT
0.13 + 1.2

1.1 U N / 3
1,1 20kV/ 3
=
= 2.8 kA
Z N + Z T + Z L 0.13 + 1.2 + 3.2

Dimensioning of the 110 kV CTs for the transformer differential protection:


Manufacturer recommends for relay 7UT61:
The saturation free time of 3 ms
corresponds to KTF 0,75
See diagram, page 59

Power Transmission and Distribution

Criterion 1) therefore reads:

I
17300
ALF' K TF F1 = 0,75
= 43
IN
300

1) Saturation free time 4ms for internal faults


2) Over-dimensioning factor KTF 1,2
for through flowing currents (external faults)

For criterion 2) we get:


Author

I
1730
ALF' K TF F2 = 1,2
=7
IN
300

The 110 kV CTs must be dimensioned according to criterion 1).


Page 265

2007-08

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

CT dimensioning for
Example differential protection (3)
We try to use a CT type: 300/1, 10 VA, 5P?, internal burden 2 VA.

Pi + Poperation
2 + 2.5
ALF
ALF ' =
43 = 16.1
Pi + Prated
2 + 10

(Connected burden estimated to about 2.5 VA)

Chosen, with a security margin : 300 /1 A, 5P20, 10 VA, R2 2 Ohm (Pi 2VA)
Specification of the CTs at the 20 kV side of the transformer:
It is good relaying practice to choose the same dimensioning as for the CTs on the 110 kV side:
1200/1, 10 VA, 5P20, R2 2 Ohm (Pi 2VA)
Dimensioning of the 20 kV CTs for line protection:
1) Saturation free time 3ms for internal faults
2) Over-dimensioning factor KTF 1.2
for through flowing currents
(external
faults)
Power
Transmission
and Distribution

For relay 7SD61, it is required:


The saturation free time of 3 ms corresponds
to KTF 0.5
See diagram, page 59
Criterion 1) therefore reads:
I
9550
ALF' K TF F3 = 0.5
= 24
IN
200

Page 266

2007-08

Author

For criterion 2) we get:

I
2800
ALF' KTF F4 = 1.2
= 16.8
IN
200
Author

The 20 kV line CTs


must be dimensioned
according to criterion 1).

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI

CT dimensioning for
Example differential protection (4)
For the 20 kV line we have considered the CT type: 200/5 A, 5 VA, 5P?, internal burden ca. 1 VA

Pi + Poperation
1+1
ALF ' =
24 = 8
ALF
1+ 5
Pi + Prated

(Connected burden about 1 VA)

Specification of line CTs:


We choose the next higher standard accuracy limit factor ALF=10 :
Herewith, we can specify: CT Type TPX, 200/5 A, 5 VA, 5P10, R2 0.04 Ohm ( Pi 1 VA)
Power Transmission and Distribution

Author

Page 267

2007-08

Author

Copyright Siemens AG 2007. All rights reserved.


PTD SE PTI