241-267 - CT and VT Basics - Quazvin PDF
241-267 - CT and VT Basics - Quazvin PDF
Author
Page 241
2007-08
Author
I1
jX1 R1
I 2 = I1
N1
N2
jX2
Im
P1
N1
N2 U
R2
I2
S1
Zm
Zb
P2
Ideal CT
S2
Page 242
2007-08
Author
jX2
1 : N2
i2
i1
i'1 =
N2
1
R2
i1
LW
L2<< LW
im
ZB
R2
i2
Power Transmission and Distribution
RB
Author
Page 243
2007-08
Author
Current transformer:
Phase displacement () and current ratio error ()
I1 .
I1
N1
N2
N1
I2
N2
I2
Zb
Author
Im
Page 244
2007-08
Author
Specification:
300/1 A
5P10, 30 VA
RCT 5 Ohm
Rated burden
(nominal power) PNB
Accuracy
limit factor ALF
Pi + PNB
Pi + PBB
Dimension criterium:
I
ALF ' SC max KTF
Power Transmission
I n and Distribution
KTF (over-dimensioning factor) considers the single sided CT over-magnetising due to the d.c.
Author
component in short circuit current ISC.
KTF values required in practice depend on relay type and design.
Recommendations are provided by manufacturers (see Application Guides)
Page 245
2007-08
Author
U2
10 %
IEC 60044-1 Class PX
UKN
formerly
50 %
Author
Im
Page 246
2007-08
Author
Accuracy class
Current error
at nominal
current (In)
5P
1%
10P
5%
Angle error
at rated current
In
60 minutes
Total error at n x In
(rated accuracy limit)
5%
10 %
Power Transmission and Distribution
Author
Page 247
2007-08
Author
TPX
(closed iron core)
TPY
with anti-remanence
air gap
TPZ
linear core
TPS
2007-08
Remanence
Angle error
0,5 %
30 min
10%
1,0 %
30 min
10%
1,0 %
180 18 min
10%
Author
no limit
< 10 %
Power Transmission and Distribution
Page 248
Maximum error at
rated accuracy limit
negligible
No limit
Author
Transient saturation with offset current
Page 249
2007-08
Author
ISC
DC flux non-saturated
AC
flux
Power
Transmission and Distribution
Author
Im
Page 250
Magnetising current
2007-08
Author
B
TN TS TN
= 1+
(e
e TS )
TN TS
B
d.c. component
TS
N TS TN
T
BMax
= 1+ TS
B~
TS
t
TN
total flux
t B Max =
BMax
transient
d.c. flux
B~
TS =
a.c. flux
Author
B~
Page 251
2007-08
Author
TN TS
TS
ln
TS TN TN
LW Power Transmission
1
and Distribution
=
Ri + RB tan
For 50 Hz:
TS =
10900
[min ]
[ms]
TN
KTF = 1+ TS
TS
TS
TS TN
(KTF 1+TN)
5000
5
0
1000
4
0
TS [ms]
500
3
0
250
2
0
100
Linear core
1
0
50
Page 252
2007-08
100
150
200
Author
TN [ms]
tM
tM
Ktd
50 ms
40 ms
10
30 ms
20 ms
10 ms
Page 253
20
2007-08
40
60
80
Tp
Author
tM :
KTF = 1+ TN = 1+
Author
K' TF
tM
= 1 + TN 1 - e T N
XN
RN
100 [ ms]
Copyright Siemens AG 2007. All rights reserved.
PTD SE PTI
KTF
tM
(tM,TN)
10 ms
3.5
140
120
8 ms
2.5
tM
100
10 ms
8 ms
6 ms
Power Transmission and Distribution
4 ms
2 ms
80
6 ms
1.5
1
60
40
4 ms
0.5
0
180
2 ms
Page 254
20
40
60
80
2007-08 T
Author
100
in ms
20
Author
20
40
60
80
100
Current transformer
magnetising and de-magnetising
B
t
BMax
B = BR + (BMax. BR ) e
BR
BMax
t
TS
BR
Power Transmission and Distribution
m
Author
Page 255
2007-08
Author
Current transformer
Course of flux in the case of non-successful auto-reclosure
Bmax
t
tF1
tDT
tF2
tF1
tDT+tF2
tF2
tF1
tF2
Author
N TS
Bmax TN TS TN
T
= 1+
e TS e TS + 1+
(e
(e TN e TS
TN TS
TN TS
B~
Page 256
2007-08
Author
Current transformer
magnetising curve and point of remanence
II
III
up to 80%
< 10%
negligible
H = im w
Power Transmission and Distribution
Page 257
2007-08
Author
BR
BR
Author
tDT
tF1
Page 258
2007-08
tF2
Author
t
Copyright Siemens AG 2007. All rights reserved.
PTD SE PTI
Angle error
3P
3.0 %
120 minutes
5P
6.0 %
240 minutes
Page 259
0.1
0.2
0.1
0.2
0.5
0.5
1
3
1
3
2007-08
Author
Author
10
20
30
Not determined
C2 = 95 nF
RF
20 kV
LF
CE = C 1 + C 2
C1
U*1 = UP
C1 + C2
Page 260
2007-08
100 V
CF
LO
RE
T
Author
Author
ZB
RF
RT
LT
LF
CF
U*2
R'B
L'B
Ratio
Measured voltage transients after fault at
voltage maximum and zero-crossing
(Example)
Time
Ts
in ms
2 Us
100%
Classes
3PT1
6PT1
3PT2
6PT2
3PT3
6PT3
10
---
25
20
10
10
40
10
60
10
0.6
10
0.2
90
Legend:
Us (t)
Author
Page 261
2007-08
(1)
Fault inception
(2)
(3)
Author
CT dimensioning
K OD = KTF
Pi + PBN
RCT + RBN
ALF' = ALF
= ALF
Pi + PB
RCT + RB
P + PB
RCT + RB
= ALF'
ALF = ALF' i
Pi + PBN
RCT + RBN
with
I
ALF ' K OD K
IN
Theory:
K OD K TF K Re m
K Re m =
1
% Remanence
1
100
Page 262
2007-08
rated CT burden:
PBN
internal burden of the CT: Pi=Ri I2N2
Practice:Author
K' TF =
BMax
XN
= 1 + TN = 1 +
RN
B ~
Power
tM
Transmission andtMDistribution
T
N TS
(e TN e TS
K ' 'TF = 1 +
TN TS
Author
Practical CT requirements
Transient over-dimensioning factors KTF (AR not considered)
Distance
7SA6 and 7SA522
Overcurrent
7SJ56
Close-in fault:
KTF 5
External fault
Transformer Differential
7UT6
KTF 0.75
(Saturation free
time 4 ms)
KTF 1.2
(Saturation free
time 5 ms)
Line differential
7SD61
KTF 0.5
(Saturation free
time 3 ms)
KTF 1.2
Power Transmission and Distribution
(Saturation free
time 5 ms)
Bus differential
7SS52
Page 263
Author
KTF 0.5
(Saturation free
time 3 ms)
2007-08
Author
KTF 0.5
(Saturation free
time 3 ms)
Copyright Siemens AG 2007. All rights reserved.
PTD SE PTI
CT dimensioning for
Example differential protection (1)
1. Calculation of fault currents
110 kV, 3 GVA
F1
110/20 kV
40 MVA
uT=12%
F2
OH-line:
l = 8 km,
zL= 0,4 /km
F3
F4
Net
300/1A
IT
7UT61
Transf. :
IL
7SD61
IL
Net :
200/1A
200/1A
1200/1A
U N 2 kV 2
110 2
ZN =
=
= 4.03
SSC ' ' [MVA ] 3000
U N 2 kV 2
Author
uT [% ] 110 2 12 %
ZT =
= 36.3
PN -T [MVA ] 100
40 100
Net :
Transf. :
U N 2 kV 2
Power Transmission
20 2
and Distribution
ZN =
=
= 0.13
SSC ' ' [MVA ] 3000
U N 2 kV 2
uT [% ] 20 2 12 %
ZT=
= 1.2
PN -T [MVA ] 100
40 100
2007-08
Author
CT dimensioning for
Example differential protection (2)
1.1 U N / 3 1.1 110kV/ 3
=
= 17.3 kA
ZN
4.03
F1
I F1 =
F2
F3
F4
I F3 =
I F4 =
1.1 U N / 3
1,1 20kV/ 3
=
= 2.8 kA
Z N + Z T + Z L 0.13 + 1.2 + 3.2
I
17300
ALF' K TF F1 = 0,75
= 43
IN
300
I
1730
ALF' K TF F2 = 1,2
=7
IN
300
2007-08
Author
CT dimensioning for
Example differential protection (3)
We try to use a CT type: 300/1, 10 VA, 5P?, internal burden 2 VA.
Pi + Poperation
2 + 2.5
ALF
ALF ' =
43 = 16.1
Pi + Prated
2 + 10
Chosen, with a security margin : 300 /1 A, 5P20, 10 VA, R2 2 Ohm (Pi 2VA)
Specification of the CTs at the 20 kV side of the transformer:
It is good relaying practice to choose the same dimensioning as for the CTs on the 110 kV side:
1200/1, 10 VA, 5P20, R2 2 Ohm (Pi 2VA)
Dimensioning of the 20 kV CTs for line protection:
1) Saturation free time 3ms for internal faults
2) Over-dimensioning factor KTF 1.2
for through flowing currents
(external
faults)
Power
Transmission
and Distribution
Page 266
2007-08
Author
I
2800
ALF' KTF F4 = 1.2
= 16.8
IN
200
Author
CT dimensioning for
Example differential protection (4)
For the 20 kV line we have considered the CT type: 200/5 A, 5 VA, 5P?, internal burden ca. 1 VA
Pi + Poperation
1+1
ALF ' =
24 = 8
ALF
1+ 5
Pi + Prated
Author
Page 267
2007-08
Author