ANALYSIS AND PROTECTION OF POWER SYSTEMS COURSE
TUTORIAL. ADVANCED FAULT ANALYSIS
Calculate the fau
rent and the current in the delta winding for
an earth fault at
66kV
lomva ¥
ZB Z,2 20% Zps 210%
Zs-r* 52
Zev 210%} Smva Base
j lomva gase
With reference to the typical power system network used in the tutorial
“System Analysis - Balanced Faults", consider a single phase to earth
fault on busbar “C". Consider all generating plant and transformers in
service except T3 and T4 and assume all breakers at mesh station "E"
be open.
to
Find the per unit phase currents (neglecting load) see
situated on lines Dl and D2 close to busbars "A" and"
and also the per unit phase voltages at these points.
voltage at "Cc" to be 1 piu.
by relays
respectively
Assume pre-fault
Use the positive and negative sequence networks derived in Question 4c)
of the tutorial "Fauit Cateuletion - Balanced Faults and Revision trenste
29. forte
total system to the fault Zi = Z2 = j0.194 p.u.For the fault calculation, use MVAbase = 10 MVA.
Converting Zp-r to 10 MVA base,
pet = 01x)
0.2 pu.
Impedance values for the equivalent "star" network for the transformer
can now be determined
Ze = 0.5(2p-s + Ze-r - 25-7)
= 0,5(0.1 + 0.2 - 0.05) = 0.125 pw
Zs = 0.5(Ze-s + Zs-r - Ze-1)
= 0,5(0.1 + 0.05 - 0.2) = peu
tr = 0,5(2e-r + Zs-1 - Ze-s
= 0,5(0.2 + 0.05 - 0.1) = 0.
The sequence network connection diagram for the earth fault at "F" is
shown below.
0-2 o-125 coos I,
I pow
Ao °, Si0FThe network is reduced as follows :-
Total positive sequence impedance,
Ty = 0.2 4 0.125 - 0.025 = 0.3 pu.
Total negative sequence impedance,
Zz = 0.3 pew
Total zero sequence impedance,
a 0-6359
Ney
=
I,-I,-Te
43x 11 x 108
Therefore, fault current Ir = 4.716 x 524 = 247] amps
Current in delta winding,
loc) =delta winding
‘The complete current distribution
GokV
Pp
Pe