side 1 von 2

Power Transmission and Distribution

Datum: 22.03.2005
Ref.: App_diff_000x_00 N.M.

7UT613_33_35: Single pole testing of pickup at Delta side

Depending on the configuration the devices 7UT613, 7UT633 and 7UT635 use different
algorithms than the devices 7UT612 or 7UT51! With this a higher sensitivity can be achieved in
case of using an earthing transformer inside the protected zone at the -side.
Example: Test current ITest only in phase L1 at the -side:

I2L1=ITest

Vector group: YNd11


side 2
side 1

2L1

1L1

2L2

1L2

2L3

1L3

1. Address 0323 = isolated

1 3
1
1 + 3 I 2 L1
I2A

I 2 L2 =
I
=
+

1
3
1
3
1
2
B

I 2 3 1
1 + 3 1 3 I 2 L 3
C

1
2.732 I Test
0.732


1
1 0
2.732 0.732
3
2.732 0.732 0
1

I2A
0.732 I Test 0.244 I Test

I 2 B = 2.732 I Test = 0.91 I Test


I 2 3 1 I
0.33 I

Test
Test
C

Idiff A

Idiff B =
Idiff
C

I 2 A 0.244 I Test

I 2 B = 0.91 I Test
I 2 0.33 I

Test
C

Result:
If a test current ITest = INO (nominal object current) is injected in phase L1 at the -side the following
information will be shown in the display:
Diff L1:
0.24
Diff L2:
0.91
Diff L3
0.33
That means, for pickup of the device a test current of 1/0.91 1.1 times the setting IDiff> must be
injected.
In your case: IDiff> = 0.42 I/INO = 1.8A , ITest Pickup 1.11.8A 2A !!

PTD Energy Automation


Product Management

eMail :
Tel :
Fax :

ptd.support@siemens.com
(++49) - 1805 247000
(++49) - 1805 242471

SIEMENS

side 2 von 2

Power Transmission and Distribution

Datum: 22.03.2005
Ref.: App_diff_000x_00 N.M.

7UT613_33_35: Single pole testing of pickup at Delta side


2. Address 0323 = solid earthed (similar to 7UT612 und 7UT51)

1 0 1 I Test
1 0 1 I 2 L1
I 2A


1

1

1 1 0 0
1 1 0 I 2L2 =
I 2B =
3
3


I2
0 1 1 0
0 1 1 I 2 L 3
C
I 2A
I 0.577 I Test

1 Test

I 2B =
I Test = 0.577 I Test
3
I2

0
C
0

Idiff A

Idiff B =
Idiff
C

I 2 A 0.577 I Test

I 2 B = 0.577 I Test
I2

0
C

Result:
If a test current ITest = INO (nominal object current) is injected in phase L1 at the -side the following
information will be shown in the display:
Diff L1:
0.58
Diff L2:
0.58
Diff L3
0.00
That means, for pickup of the device a test current of 1/0.58 3 times the setting IDiff> must be
injected.