Size & Short Circuit Capacity of D.

G Sync
DG's

Voltage Rating (KV)

D.G Capacity
(KVA)

1
2
3
4
5
6

0.415
0.415
0.415
0.415
0.415
0.415

1000
1000
2000
2000
2000
1000

Sub Transient
Reactance ( Xd")
in PU
0.14
0.13
0.109
0.109
0.109
0.13

% Reactance
(%Xd")
14
13
10.9
10.9
10.9
13

Total Capacity of Synchronous Panel


Total Fault level
The equivalent Z at theDG Synch panel by parallel method

Short Circuit Current at DG sync panel is the cumulative of all individual DG short circuit
current
OR

Short Circuit Current at DG Synchronous Panel=(Total Fault level /1.732*E*1000)

pacity of D.G Synchronous Panel


Impedence of the DG( Short Ciruit kVA at DG Short Circuit
Zg)
terminal (Psc)
Current( Isc ) in KA
(KVA/%Xd")*100
(Psc/(1.732XEX1000)
(KVxKV/ KVA)x1000
0.1722
7142.8571
9.9374734173
0.1722
7692.3077
10.7018944494
0.0861
18348.6239
25.5274546498
0.0861
18348.6239
25.5274546498
0.0861
18348.6239
25.5274546498
0.1722
7692.3077
10.7018944494

ividual DG short circuit

/1.732*E*1000)

9000

KVA

77573.34
0.0066

KVA
Ohm

97.22

KA

107.92

KA

Jignesh.Parmar, jiguparmar@yahoo.com, www.electricalnotes.wordpress.com

Reactance (Zg) in Ohm


(% Xd"x kVX KV x 10 / kVA)
0.0241115
0.02238925
0.0093862625
0.0093862625
0.0093862625
0.02238925

Equivalent Zg
for Parallel
0.0116
0.0066
0.0047
0.0047
0.0066

0
0
0
0
0