You are on page 1of 165

Contents

Related catalogues
Low-Voltage Controls and
Distribution
SIRIUS SENTRON SIVACON
Order No.:
Catalog
E86060-K1002-A101-A7-7600
Technical Information incl.

Low-Voltage
Controls and Components
for Applications according to UL
Order no.:
E86060-K1816-A101-A1-7600

Industrial Communication
Industrial Communication
for Automation and Drives
Order No.:
E86060-K6710-A101-B6-7600
E86060-K6710-A121-A2-7600

LV 1
LV 1 T

LV 16

IK PI
IK PI N

Systems Controlgear: Contactors and contactor assemblies,


solid-state switching devices Protection equipment Load
feeders, motor starters and soft starters Monitoring and
control devices Detecting devices Commanding and
signaling devices Transformers Power supplies Planning
and configuration with SIRIUS Power Management System
SIVACON Power, distribution boards, busway and cubicle
systems SENTRON switching and protection devices for
power distribution Air circuit breakers, molded case circuit
breakers, switch disconnectors Software for power distribution
BETA low-voltage circuit protection

SIRIUS 3RV17 and 3RV18 circuit breakers according to


UL 489 SIVACON Components for 8US Distribution Systems
according to UL 508A SENTRON 3WL5 air circuit
breakers/non-automatic air circuit breakers according to UL
489/IEC SENTRON 3VL Molded Case Circuit Breakers
according to UL 489/IEC ALPHA Devices according to UL
Standard BETA Devices according to UL standard
PROFINET/Industrial Ethernet Industrial Mobile
Communicaton PROFIBUS to IEC 61158/EN 50170 SIMATIC
ET 200 distributed I/Os AS-Interface to EN 50295/IEC 61158
Remote operation with SINAUT Telecontrol Routers
ECOFAST system

LV 50

System cubicles Cubicle modifications Cubicle expansion


components Accessories Special cubicles Cubicle solutions
in applications Cubicle air-conditioning Special colors

SIDAC
Reactors and Filters
Order No.:
E86060-K2803-A101-A4-7600

LV 60

Commutating reactors for converters Mains reactors for


frequency converters Iron-core output reactors Ferrite output
reactors Iron-core smoothing reactors Smoothing air-core
reactors Filter reactors Application-specific reactors Radio
interference suppression filters dv/dt filters Sinewave filters

SIVACON 8PS
CD-K, BD01, BD2
Busbar Trunking Systems
up to 1250 A
Order No.:
E86060-K1870-A101-A3-7600

LV 70

Busbar trunking systems, overview CD-K system


(25 A to 40 A) BD01 system (40 A to 160 A) BD2 system (160
A to 1250 A)

Automation & Drives


The A&D Offline Mall
CD-ROM:
E86060-D4001-A110-C6-7600
DVD:
E86060-D4001-A510-C6-7600

CA 01

All Automation and Drives products,


including those in the catalogs listed above.

SICUBE
System Cubicles and
Cubicle Air-Conditioning

Order No.:
E86060-K1920-A101-A3-7600

A&D Mall
Internet:
http://www.siemens.com/automa
tion/mall

All Automation and Drives products,


including those in the catalogs listed above.

Catalog-PDF
Internet:
http://www.automation.
siemens.com/cd

All catalogs for low-voltage controls and distribution can be


downloaded as PDF files.

Registered trademarks
All product designations may be registered trademarks or
product names of Siemens AG or other supplying
companies. Third parties using these trademarks or product
names for their own purposes may infringe upon the rights of
the trademark owners.
Further information about low-voltage controls is available on
the Internet at:
http://www.siemens.com/lowvoltage

Technical Assistance
Expert technical assistance for
Low-voltage controls and
electrical installation.
Tel.: +49 (9 11) 8 95-59 00
Fax: +49 (9 11) 8 95-59 07
E-Mail: technicalassistance@siemens.com

sivacon S4
Power Distribution Boards

Introduction

Power Distribution Boards

Standard Configurations

Cubicles, Supporting Structure and


Enclosures

Busbar System

Assembly Kits for Switching Devices

Covers, Modular Doors, Mounting Plates,


19 Rack

Internal Separation

Air-conditioning Products

Catalogue LV 56 2008

The products listed in


this catalogue are manufactured at production units working according to a quality system
certified for conformity
to EN 29001 (ISO 9001)

Not valid:
Catalogue LV 56 2006
Contact your local Siemens
representative for further information
Siemens AG 2008

Accessories

10

Mechanical Dimensions

11

Planning and Configuration

12

Appendix

13

Explanations

Information on catalogue LV 56 2008 and Manual SIVACON S4 2008


Catalogue LV 56 2008 contains the data relevant
to selection and ordering.

Additional information is given in SIVACON S4 Manual.

Delivery class (DC)1)


The delivery class indicates a products delivery time
in working days from order receipt to product ready
for dispatching from the warehouse.

Price1)
The stated price is in and refers to the price per
unit (PU).

Price unit (PU)


The price unit specifies to how many items (IT), sets
(ST) or metres (M) the stated price and weight
applies.

Price group (PG)1)


Each product is assigned to a price group.

Dimensions
All dimensions are expressed in mm.

1)

Information is provided on a separate price list.

Siemens LV 56 2008

Total deliver time is given by the sum of order processing time in the country of
origin, predetermined delivery time and transport time.

Introduction

1/2

Siemens Automation and Drives


Welcome

1/4

Sharpen your competitive edge


Totally Integrated Automation

1/6

Low-Voltage Power Distribution


with SIVACON, SENTRON and SIMARIS

Siemens LV 56 2008

Siemens Automation and Drives.


Welcome

More than 60,000 people aiming for the same goal: increasing your competitiveness. That's Siemens Automation and Drives.
We offer you a comprehensive portfolio for sustained
success in your sector, whether youre talking automation engineering, drives or electrical installation systems. Totally Integrated Automation (TIA) and Totally Integrated Power (TIP) form the core of our offering. TIA
and TIP are the basis of our integrated range of products
and systems for the manufacturing and process industries as well as building automation. This portfolio is
rounded off by innovative services over the entire life cycle of your plants.
Learn for yourself the potential our products and systems offer. And discover how you can permanently increase your productivity with us.
Your regional Siemens contact can provide more information. He or she will be glad to help.

1/2

Siemens LV 56 2008

Siemens LV 56 2008

1/3

Integrated energy distribution


from a single source.
Totally Integrated Power

Totally Integrated Power (TIP) brings together all the components


of electrical energy distribution into an integrated whole. Thus TIP
provides the answer to growing market demands in the planning,
construction and use of utility buildings and industrial buildings.
On the basis of TIP, we offer integrated solutions for energy distribution, from medium voltage to the power outlet. Totally Integrated Power is based here on integration in planning and configuring as well as on perfectly matched products and systems.

1/4
1/4

Siemens LV 56 2008

Siemens IK PI 2000

Totally Integrated Power offers communication


and software modules for connecting the energy
distribution systems to industrial automation and
building automation. This enables the implementation of significant savings potential.

Siemens LV 56 2008

1/5

Low-voltage power distribution with


SIVACON, SENTRON and SIMARIS
Non-residental buildings and industrial plants have one thing in
common: without electricity, everything comes to a halt. The availability, safety and cost effectiveness of the power distribution system is of utmost importance from the medium voltage supply
point through to the socket outlet. And only integrated solutions
can ensure maximum efficiency for planning, configuration and
SIVACON power distribution boards

operation.
The concept is called Totally Integrated Power from Siemens.
Total integration in planning and configuration creates synergies
and saves costs. Perfectly matched products and systems provide efficient engineering and reliable operation. In the field of
low-voltage power distribution, the following product ranges are
available:
SIVACON: From flexible busbar trunking systems through to safe
power distribution boards and motor control centers.
SENTRON: From well-proven switch disconnectors through to intelligent circuit breakers.

SENTRON switching devices

Software for power distribution: Everything for dimensioning,


configuring, visualizing and controlling your power distribution.

SIMARIS software for power distribution

1/6

Siemens LV 56 2008

SIVACON S4
Power Distribution Boards

2/2

Introduction

2/3

General Data

2/6

Technical Data

2/7

Declaration of conformity

Siemens LV 56 2008

SIVACON S4 Power Distribution Boards


Introduction

Front view

SIVACON S4 is an AS (TTA-TSK) switchgear and controlgear


system, type tested according to IEC 60439-1, CEI EN 60439-1,
for installation as primary or secondary boards in industrial and
service sector facilities, including hospitals, shopping centres,
banks, schools. etc. The SIVACON S4 energy distribution
concept consists of a full line-up of boards in galvanised

2/2

Siemens LV 56 2008

chromed sheet steel, of sturdy design, suitable for any


installation modality: self-standing, flush or wall-mounted.
SIVACON S4 low-voltage power distribution boards are
constructed according to a modular design system and, by
means of ad hoc assembly kits, can be combined to meet all
power distribution needs.

SIVACON S4 Power Distribution Boards


General data

Description
System
SIVACON S4 is a system of low-voltage power distribution
boards, for indoor use, panelled on four sides, suitable for selfstanding or wall-mounted installation.

The cubicle
The constituent elements of the cubicle framework, having a
2.5mm thick profile, are inserted into one another to form a
parallelepiped shaped column. This provides the bearing
structure supporting all add-on interior switchgear components,
i.e., assembly kits, busbar systems, mounting plates, etc. Stable
and rugged construction is ensured through the use of Torx selftapping screws. Equipotential and safe grounding of all parts
are also achieved.
The enclosure
Enclosure parts made of galvanised sheet steel are
dimensioned as a function of the cubicle they are fitted to.
Different versions make it possible to achieve various degrees of
protection: IP 30/31, IP 40/41 or IP 55. Walls and doors are
coated with slightly embossed RAL 7035 powder-paint. In
addition to the standard two-way interlocking system, the doors
can be equipped with numerous types of operating mechanism
including rotary handles, with or without locks, to meet any need.
Assembly kit covers are secure by means of captive quickrelease screws. Opening and closing is by rotating the handle
by 1/4 turn. Using the hinge option, the covers may open to the
right or to the left.
Busbar system
The main busbar system of SIVACON S4 offers an appropriate
scaling of rated currents, matched to a rated current of up to
4000 A and short-circuit currents of standard transformers.
It is possible to set up systems with network configurations such
as TN-C, TN-S, IT and TT. Vertical distribution busbar systems
are available as cascaded versions up to 1600 A or noncascaded versions up to 2700 A.
Internal separation

Assemly kits
For open and enclosed automatic breakers, disconnectors,
SENTRON circuit breakers, modular units as well as contactors,
a wide range of dedicated kits are available. Modular adjustable
mounting plates or plates for electrotechnical use, as well as
dedicated ventilation and air-conditioning components
complete the line-up of parts for the construction of boards as
typically used at industrial facilities or for automation purposes.
The items available include a range of assembly kits for Siemens
Sentron WL and VL circuit breakers, in fixed, plug-in and
drawout versions, as well as kits with DIN rails, according to DIN
43656, for the wide range of the Beta Series modular devices.
The components of the cubicle and the assembly kits are
made of galvanised chromed sheet.
The components of the enclosure, such as panels and doors
are coated with slightly embossed RAL 7035 powder-paint.
Air-conditioning components complete the line-up of
SIVACON S4 system components.

Depending on individual requirements, internal partitions are


available from form 1 to form 4.

Siemens LV 56 2008

2/3

SIVACON S4 Power Distribution Boards


General Data

Applications
Main features

Type AS (TTA-TSK) power distribution boards according to


CEI EN 60439-1.
Modular systems supplied loose (supplied as assembly kits
with individually packaged components, including fasteners;
assembly instructions for do-it-yourself installation).
New design, ventilation and closing system.
Slightly embossed RAL 7035 powder coating.
Doors with universal stop.
Degree of protection IP30, IP31, IP40, IP41, IP55
Busbar system rated current up to 4000 A
Busbar system short-circuit current Icw up to 100 kA (1s).
Busbar system peak current Ipk up to 220 kA.
Height 2000 mm
Width 400, 600, 800, 1000, 1200 mm.
Depth 400, 600, 800 mm.
Kits for Sentron 3WL, 3VL, 3KA, 3KL circuit breakers, Beta
modular devices on DIN rails.
Kits of prefabricated bars for Sentron 3WL, 3VL circuit
breakers.
Internal separation form 1, 2, 3, 4.
Easy design and configuration with the SCFB software tool.
Construction and testing modalities
All installation and wiring operations must be performed in
keeping with the information and data given in the catalogues
and the assembly manuals.
The installation and individual testing of the low-voltage boards
must be performed according to standards IEC 60439-1 and
CEI EN 60439-1.
Protection of the environment
To the best of our knowledge, our materials do not contain
materials in concentrations or applications prohibited by
directive 2002/95/EC (RoHs).
All the materials used are recyclable.

2/4

Siemens LV 56 2008

SIVACON S4 Power Distribution Boards


Quick and easy assembly

Exploded view
5

2
6
15

13
11
8

4
9

16

12

14

7
6

10

16

17

01724

18

2
3

1 Cubicle

7 Giugiaro Design glazed wall

2 Base with front covers

8 Front frame

13 Horizontal busbars
Vertical distribution busbars,
14 non-cascaded

3 Base side covers

9 Cable compartment cover

15 Real panel

4 Supporting Structure

10 Covers for equipment kits

Mounting plate for


16 Sentron VL circuit breaker

5 Blind top plate

11 Segregation for horizontal busbars

17 Blind bottom plate

6 Side panel with design

12 Segregation for vertical


distribution busbars

18 Main grounding bar PE


Siemens LV 56 2008

2/5

SIVACON S4 Power Distribution Boards


Technical Data

Overview

Standards and regulations

Type AS (TTA-TSK) assembled protection and circuit


breakers for low-voltage (L.V. boards)

Air clearances and creepage distances

Rated impulse withstand voltage (Uimp)


Overvoltage category
Pollution degree

IEC 60439-1, EN 60439-1


12 kV
IV
3
1, 2b, 3b,
4a, 4b

Internal separation forms

1000 V

Rated insulation voltage (Ui)


Up to

Rated operational voltage (Ue)

50/60 Hz

Rated frequency
Rated current (In) of
(3-pole and 4-pole) busbar system

Main horizontal bars

Protection of people in the event of internal arcs Type tested according to IEC 61641
Degree of protection IP40, without glazed door

Rated current
Rated peak current of busbar
system (Ipk)
Rated short-time current of
busbar system (Icw)

Up to
Up to

Rated utilisation voltage


Rated short-time current without extra kit
Length of internal arc without extra kit
Length of internal arc with extra kit
Galvanised
Epoxy resin
Cold phosphatised
Thickness of coating

20 m
RAL 7035

min.

70 m

Insulation class

According to IEC 61140, EN 61140

Degree of protection

According to IEC 60529, EN 60529

IP 30, IP 31, IP 40, IP 41, IP 55

Resistance to mechanical impacts

According to IEC 62262, paragraph 9.6

IP 3X
IP 4X

Additional static loads on frame components

Front frame

revolving
fixed
with quick closing screws, H 50-300mm
with quick closing screws, H 350-550mm
with quick closing screws, H 600-800mm
with hinges

Internal inner door


Internal door / double door
Door module

400 V
50 kA
100 ms
300 ms

min.

Cubicle, interior components, enclosure


Coated with RAL 7035 powder

Covers

4000 A
220 kA

Up to 100 kA, 1s

Surface treatment

SK1

IK08
IK10

W 400, 600mm
W 800mm
W 1000, 1200mm
H 150-200mm
H 250-350mm
H 400-800mm

Exterior covers
Max construction weight

690 V

According to IEC 62208, paragraph 9.3, 9.4,


Type tested with static load by lifting a cubicle

1,0 kg
5,0 kg
0,5 kg
1,0 kg
2,0 kg
0,0 kg
2,5 kg
10,0 kg
5,0 kg
2,5 kg
0,5 kg
1,5 kg
3,0 kg
10,0 kg
1200 kg

Operating conditions
Ambient temperature1)
Installation altitude

 35 C
 2000 m

Frame parts:

2.5 mm Galvanised chromed sheet steel, with 25mm hole pattern according to DIN 43 660

Dimensions

Exterior dimensions

Height:
Width:
Depth:

2000 mm
400, 600, 800, 1000, 1200 mm
400, 600, 800 mm

Base

Height:

100, 200 mm

1)

For different ambient temperatures and installation altitudes, take into account the appropriate correction factors (see chapter on Planning and Configuration)

2/6

Siemens LV 56 2008

SIVACON S4 Power Distribution Boards


Declaration of conformity

Overview

Siemens LV 56 2008

2/7

SIVACON S4 Power Distribution Boards


Declaration of conformity

Overview

2/8

Siemens LV 56 2008

Standard Configurations

3/2

SIVACON S4 with Sentron 3VL


circuit breakers and modular
devices

3/3

SIVACON S4 with Sentron 3WL


circuit breakers

3/4

SIVACON S4 with Sentron 3VL


circuit breakers

3/5

SIVACON S4 with Sentron 3WL,


3VL circuit breakers and modular
devices

Siemens LV 56 2008

Standard Configurations
SIVACON S4 with Sentron 3VL
circuit breakers and modular devices

Power distribution board data


Height x Width x Depth
Height of base,
Degree of protection
Main busbar system
Vertical busbar system
Front
Internal separation

Assembly kit
2000mm x 1200mm x 400mm
100mm
IP55
without
cascaded 1250 A, 50kA
covers, full height door
2b

Infeed

Sentron 3VL1250, cable entry from


top, terminals for cables,
extended terminal covers
Sentron 3VL,
extended terminal covers, modular
devices

Starters

Cubicle, base, Supporting Structure, enclosures


8PQ1202-4BA02
8PQ3000-1BA38
8PQ3000-1BA43
8PQ1012-0BA01
8PQ1010-4BA01
8PQ2000-6BA04
8PQ2197-2BA14
8PQ2197-6BA14
8PQ2197-4BA05
8PQ2302-4BA04
8PQ2306-4BA05
8PQ2304-4BA05
8PQ2302-4BA01
8PQ2420-2BA01
8PQ2520-4BA01

1
2
2
1
1
1
1
1
1
1
1
1
1
1
1

Cubicle H2000/B1200/T400
Bottom plate partition crossbar
Exterior intermediate supporting structure
Base H100/B1200
Base side covers H100/P400
Fixed front frame H1800/B600
Cable compartment cover B200
IP55 glazed door, right/2-way interlock./H1975/B600
IP55 door, left/2-way interlock./H1975/B400
Bottom plate IP55/B200/P400
Bottom plate IP55/B600/P400
Bottom plate IP55/B400/P400
Top plate IP55/B1200/P400
Rear panel IP55/H2000/B1200
Side panel with design/H2000/P400

1
8
1

Support for vertical busbars, cascaded, 30x30


Copper busbar 30x10/L2000
Copper busbar 30x5 /L2000

Busbar system
02001

8PQ4000-0BA32
8PQ4000-0BA86
8PQ4000-0BA85

Kits for switchgear, covers, mounting plates


8PQ2020-6BA02
8PQ6000-3BA11
8PQ2060-6BA03
8PQ2020-6BA01
8PQ6000-3BA36
8PQ2015-6BA07
8PQ6000-3BA18
8PQ2020-6BA04
8PQ6000-2BA87
8PQ2025-6BA02

1
1
1
1
1
1
2
2
1
1

Instrum. cover 4X72x72 + 1 sw./H200/B600


Kit for 3VL 7, 3/4 poles, vertical/H600/P600
Cover 3VL 7 3/4 poles, vertical/H600 B600
Cover H200/B600
DIN 24UM/B600 rail assembly kit
Cover for modular elements 24UM/H150/B600
Assembly kit for 3VL 2, 3, 4 poles, horiz./H200/B600
Cover for 3VL 1 3,3, 4 poles, horiz./H200/B600
Assembly kit 3VL 4, 4 poles, horiz./H250/B600
Cover for 3VL4, horiz. fixed, remov./H250/B600

Kits for switchgear, busbar connection


8PQ6000-1BA64
8PQ6000-1BA66

2
1

Vertical busbar connection kit for 3VL 3./4p/horiz./fixed


Vertical busbar connection kit for 3VL 4 /4p/horiz./fixed

Vertical partition for distribution busbars, form 2b H1900/P400

1
1
1
1
1
1

SIVACON SIEMENS cubicle ID plate


Cable anchoring brackets C30/P400 (600, 800)
Flat head square screws DIN 603 M10X55
Nuts M10 ISO 4032/M10
Clamping washer DIN 6796/10
Busbar connect. kit
cable, conductors, small parts, screws, nuts, washers with locking
edges for cable connection

Internal separation
8PQ4000-0BA06

Accessories

02003

02002

8PQ9400-0BA06
8PQ3000-0BA38
8PQ9500-1BA36
8PQ9500-0BA05
8PQ9500-0BA60
8PQ9400-0BA02

3/2

Siemens LV 56 2006

Standard Configurations
SIVACON S4 with Sentron 3WL circuit breakers

Power distribution board data


Height x Width x Depth
Height of base
Degree of protection
Main busbar system
Distribution busbar system, vertical
Front
Internal segregation

Assembly kit
2000mm x 2000mm x 600mm
100mm
IP30
Standard at top, 3200A, 65kA
cascaded, 2 x 1600A
panels, cover
4b

Infeed / starters

Sentron 3WL Gr. II, fixed, connection


to distribution busbars.
Cables from top/bottom
Max 12 cables per phase per M12
cable terminal

02004

Cubicle, base, Supporting structure, enclosure


8PQ1208-6BA01
8PQ1204-6BA01
8PQ3000-0BA01
8PQ3000-0BA03
8PQ1204-4BA05
8PQ1018-0BA01
8PQ1014-0BA01
8PQ1010-6BA01
8PQ2000-8BA03
8PQ2000-8BA03
8PQ2197-8BA11
8PQ2197-8BA11
8PQ2308-6BA06
8PQ2304-6BA05
8PQ2308-6BA03
8PQ2308-6BA02
8PQ2304-6BA02
8PQ2420-8BA02
8PQ2420-4BA02
8PQ2520-6BA01

2
1
2
1
2
2
1
1
2
1
2
1
1
1
1
1
1
2
1
1

Cubicle H2000/ B800/P600


Cubicle H2000/B400/P600
Interior side upright H1600/P600
Interior side upright H1800/P600, 800
Board coupling kit
Base with front covers H100/B800
Base with front covers H100/B400
Base side covers H100/P600
Fixed front frame H1600/B800
Exterior cover IP4X/H1975/B400
Finishing frame IP3X/H1975/B800
Bottom plate IP55/B800/P600
Bottom plate IP4X/cables/B800/P600
Bottom plate IP55/B400/P600
Top plate IP4X/cables/B800/P600
Top plate IP4X//B800/P600
Top plate IP4X/B400/P600
Rear panel IP4X/H2000/B800
Rear panel IP4X/H2000/B400
Side panel with design H2000/P600

2
1
1
2
2
16
16
2

Main busbars holder 3200 A


Flying support (reinforcement)
Support for grounding bar PE
Support for vertical cascaded busbar /30x40
Kit for vertic./horiz. busbars 30x40/P600, 800
Copper busbar 50x10/L2000
Copper busbar 40x10/L2000
Copper busbar 40x5 / L2000

Busbar system
8PQ4000-0BA04
8PQ4000-0BA37
8PQ4000-0BA82
8PQ4000-0BA63
8PQ4000-0BA74
8PQ4000-0BA18
8PQ4000-0BA17
8PQ4000-0BA80

Kits for switchgear, covers, mounting plates


8PQ6000-3BA32
8PQ2055-8BA05
8PQ2055-8BA01
8PQ2050-8BA01

2
2
2
2

Kit for 3WL11 12,3/4 poles/fixed H550/B800


Cover for 3WL12/4P/H550/B800
Cover H550/B800
Cover H500/B800

Kits for switchgear, busbar connection


8PQ6000-0BA47
8PQ6000-0BA65

2
2

prefabricated distribution bars for 3WL1232/fixed/B800


prefabricated bars to cables for 3WL 1232/fixed/B800

1
1
1
2
2
2
2

Separation form 2b, main busbars B800/P600


Separation form 2b, distribution bars H1900/P600
Separation form 2b, distribution bars H1600/P600
Partition supporting rail H1600
Separation form 3 3WL12/3-4 poles/pull-out/H550/B800
Separation form 4 3WL12/3-4 poles/vert. bars/B800
Separation form 4 3WL12/3-4 poles/cables/B800

1
3
1
2
3
3
2
2

SIEMENS SIVACON column ID plate


Busbar connection kit
Flat head screw DIN 603/M10x45
Flat head screw DIN 603/M10x65
Clamping washer DIN 6796/10
Hexagonal nut ISO4032/M10
Cable anchoring bracket
Cable anchoring bracket C30/B800
cable, conductors, small parts, screws, nuts, washers with locking
edges for cable connection

02005

Internal separation
8PQ3000-0BA54
8PQ4000-0BA03
8PQ4000-0BA07
8PQ3000-0BA82
8PQ5000-0BA10
8PQ5000-0BA21
8PQ5000-0BA38

Accessories

02006

8PQ9400-0BA06
8PQ9400-0BA02
8PQ9500-0BA16
8PQ9500-1BA25
8PQ9500-0BA60
8PQ9500-0BA05
8PQ3000-0BA73
8PQ3000-0BA43

Siemens LV 56 2008

3/3

Standard Configurations
SIVACON S4 with Sentron 3VL
and modular devices

Power distribution board data


Height x Width x Depth
Height of base
Degree of protection
Main busbar system
Distribution busbar system, vertical
Front
Internal separation

Assembly kit
2000mm x 1400mm x 400mm
100mm
IP55
without
non-cascaded 630 A, 15kA
covers, full height door
1

Infeed

Sentron 3VL 630, cable entry from


top, terminals for several wires,
extended terminal covers
Sentron 3VL
extended terminal covers, modular
devices

Starters

Cubicle, base, Supporting structure, enclosure


8PQ1206-4BA01
8PQ1208-4BA01
8PQ3000-1BA38
8PQ3000-1BA42
8PQ1204-4BA05
8PQ1204-4BA04
8PQ1016-0BA01
8PQ1018-0BA01
8PQ1010-4BA01
8PQ2000-6BA04
8PQ2000-2BA01
8PQ2197-8BA14
8PQ2197-6BA10
8PQ2302-4BA04
8PQ2306-4BA05
8PQ2308-4BA01
8PQ2306-4BA01
8PQ2420-8BA01
8PQ2420-6BA01
8PQ2520-4BA01

02007

1
1
1
1
1
1
1
1
1
2
1
1
1
1
2
1
1
1
1
1

Cubicle H2000/ B600/P400


Cubicle H2000/B800/P400
Bottom plate partition crossbar P400
Exterior intermediate upright for covers
Board coupling kit
Switchboard coupling gasket IP55
Base with front covers H100/B600
Base with front covers H100/B800
Base side covers H100/P400
Fixed front frame H1800/B600
Covers for cable compartment IP3X/H2000/B200
IP55 glazed door/right/2-way interlock./H1975/B800
IP55 glazed door/left/2-way interlock./H1975/B600
Bottom plate IP55/B200/P400
Bottom plate IP55/B600/P400
Top plate IP55/B800/P400
Top plate IP4X/B600/P400
Rear panel IP55/H2000/B800
Rear panel IP55/H2000/B600
Side panel with design H2000/P400

10
2
8
1

Main busbar holder 30x10.50mm


Exterior intermediate upright for covers
Copper busbars 30x10/L2000
Copper busbars 20x5 / L2000

Busbar system
8GF5763
8PQ3000-1BA42
8PQ4000-0BA86
8PQ4000-0BA83

Kits for switchgear, covers, mounting plates


8PQ2020-6BA02
8PQ3000-1BA56
8PQ6000-3BA05
8PQ2040-6BA08
8PQ6000-3BA18
8PQ2020-6BA04
8PQ2020-6BA12
8PQ6000-3BA36
8PQ3000-1BA61
8PQ2040-6BA01
8PQ6000-3BA22
8PQ2035-6BA03
8PQ2005-6BA01

1
1
1
1
1
1
8
8
1
1
2
2
2

Cover for 4 instruments 1 sw. 72x72 H200/B600


Blind mounting plate kit H200/B600
Assembly kit for 3VL5 3, 4 poles/vertic. H400/B600
Cover for 3VL5 3, 4 poles/vertic./fixed, rim H400/B600
Assembly kit for 3VL2 3, 4 poles/horiz./fixed/H200/B600
Cover for 3VL1 3, 4 poles/horiz./fixed H200 B600
Cover for modular devices, 1 row, 24 UM/H200/B600
Modular DIN rails kit. 1 row, 24 UM/B600
Modular mounting plate H400/B600
Cover H400/B600
Assembly kit for 3VL2 3, 4 poles/vertic./fixed/H350/B600
Cover for 3VL1 3,4 poles/vertic./fixed, remov. H350/B600
Cover H50/B600

1
1
1
1
1

SIEMENS SIVACON column ID plate


Cable anchoring brackets
Cable anchoring brackets C30/B600
Horizontal raceway fastening bracket
35mm DIN rail for terminal board L1600
cable, conductors, small parts, screws, nuts, washers with locking
edges for cable connection

Accessories

02009

02008

8PQ9400-0BA06
8PQ3000-0BA73
8PQ3000-0BA42
8PQ6000-0BA16
8PQ9600-0BA01

3/4

Siemens LV 56 2006

Standard Configurations
SIVACON S4 with Sentron 3WL,
Sentron 3VL and modular devices

Power distribution board data


Height x Width x Depth
Height of base
Degree of protection
Main busbar system
Distribution busbar system, vertical
Front
Internal separation

Assembly kit
2000mm x 2200mm x 600mm
100mm
IP30
without
cascaded, 1600A, 50 kA 50mm
System
covers, glazed door
4b

Infeed
Connector
Starters

Sentron 3WL Gr. I, fixed, central


connection to main busbars, cable
entry from top/bottom
Sentron 3WL, Gr. I, fixed
Sentron 3VL with rear attachments
for cable connection at rear
Modular devices

02019

Cubicle, base, Supporting structure, enclosure


8PQ1206-6BA01
8PQ1208-6BA01
8PQ3000-1BA40
8PQ3000-0BA03
8PQ3000-1BA36
8PQ3000-1BA42
8PQ1204-4BA05
8PQ1016-0BA01
8PQ1018-0BA01
8PQ1010-6BA01
8PQ2000-6BA04
8PQ2000-2BA01
8PQ2197-6BA10
8PQ2197-8BA10
8PQ2302-6BA04
8PQ2306-6BA05
8PQ2306-6BA02
8PQ2308-6BA02
8PQ2420-6BA02
8PQ2420-8BA02
8PQ2520-6BA01

1
2
2
3
2
2
2
1
2
1
3
2
1
2
2
3
1
2
1
2
1

Cubicle H2000/ B600/P600


Cubicle H2000/B800/P600
Bottom plate partition crossbar P600
Interior side upright H1800/P600, 800
Interior side upright H1800/P600
Exterior intermediate upright
Board coupling kit
Base with front covers H100/B600
Base with front covers H100/B800
Base side covers H100/P600
Fixed front frame H1800/B600
Covers for cable compartment IP3X/H2000/B200
IP55 glazed door/left/2-way interlock./H1975/B600
IP55 glazed door/left/2-way interlock./H1975/B800
Bottom plate IP55/B200/P600
Bottom plate IP55/B600/P600
Top plate IP4X/B600/P600
Top plate IP4X/B800/P600
Rear panel IP4X/H2000/B600
Rear panel IP4X/H2000/B800
Side panel with design H2000/P600

2
1
4
16
9

Support for distribution busbars, cascaded 30x40


Support for busbar PE
Support for busbars 20x5.50mm
Copper busbars 40x10/L2000
Copper busbars 20x5/L2000

Busbar system
8PQ4000-0BA63
8PQ4000-0BA82
8GF5762
8PQ4000-0BA17
8PQ4000-0BA83

02020

Kits for switchgear, covers, mounting plates


8PQ6000-3BA31
8PQ2055-6BA07
8PQ6000-2BA87
8PQ2025-6BA02
8PQ6000-3BA18
8PQ2020-6BA04
8PQ6000-3BA10
8PQ2035-6BA04
8PQ6000-3BA36
8PQ2020-6BA12
8PQ3000-1BA65
8PQ2040-6BA01
8PQ2060-6BA01
8PQ2030-6BA01
8PQ2025-6BA01

2
2
2
2
2
2
1
1
6
6
1
1
1
2
1

Kit for 3WL11 3, 4 poles/3WL12/3p/H550/B600


Cover for 3WL11/4p/H550/B600
Kit for 3VL4/4p/horiz./H250/B600
Cover for 3VL4/4p/horiz./fixed, remov./H250/B600
Kit for 3VL2-3, 4 poles/horiz./fixed/H200/B600
Cover for 3VL1 3, 4 poles/horiz./fixed, remov./H200/B600
Kit for 3VL5 4 poles/horiz./H350/B600
Cover for 3VL 5/4poles/horiz./fixed, remov./H350/B600
Modular DIN rails kit, 1 row, 24 UM/B600
Modular cover, 1 row, 24 UM/B600
Modular mounting plate H600/B600
Cover H400/B600
Cover H600/B600
Cover H300/B600
Cover H250/B600

Siemens LV 56 2008

3/5

Standard Configurations
SIVACON S4 with Sentron 3WL,
Sentron 3VL circuit breakers and modular device
Kits for switchgear, busbar connection
8PQ6000-0BA34
8PQ6000-0BA52
8PQ6000-1BA64
8PQ6000-1BA66
8PQ6000-1BA68

3
1
2
2
1

Distribution busbar connection kit for 3WL11 16/fixed/B600


Cable connection kit for 3WL11 16/fixed/B600
Distribution busbar connection kit for 3VL3/4p/horiz./fixed
Distribution busbar connection kit for 3VL4/4p/horiz./fixed
Distribution busbar connection kit for 3VL5/horiz./fixed

2
3
7
1
1
2
2
2
3
1
2
2
5

Separ. form 2b for vertical bars H1900/P600


Supporting rail for crossbars and partitions H1800
Separ. form 3, horizontal/B600
Separ. form 3, vertic./rear/H350/B600
Separ. form 3, vertic./later./H350
Separ. form 3, vertic./rear/H200/B600
Separ. form 3, vertic./later./..250A/H200
Separ. form 3, 3WL11/3, 4 poles/estraib./H550/B600
Separ. form 4, 3WL11/3, 4 poles/cables/B600
Separ. form 4, 3WL11/3, 4 poles/distribuz./B600
Separ. form 3, vertic./rear/H250/B600
Separ. form 3, vertic./later./..400..630A/H250
Protective bellows

2
2
2
2
2
1
1

SIEMENS SIVACON column ID plate


Busbar connection kit
Flat head screw DIN 603/M10x65
Clamping washer DIN 6796/10
Hexagonal nut ISO4032/M10
Cable anchoring bracket
Cable anchoring bracket C30/B800
without screws, nuts and washers with locking edges for cable connection

Internal separation
8PQ4000-0BA03
8PQ3000-0BA83
8PQ5000-2BA61
8PQ5000-2BA57
8PQ5000-2BA36
8PQ5000-2BA54
8PQ5000-2BA30
8PQ5000-0BA07
8PQ5000-0BA30
8PQ5000-0BA14
8PQ5000-2BA55
8PQ5000-2BA33
8PQ9400-0BA03

02021

Accessories
8PQ9400-0BA06
8PQ9400-0BA02
8PQ9500-1BA25
8PQ9500-0BA60
8PQ9500-0BA05
8PQ3000-0BA73
8PQ3000-0BA42

3/6

Siemens LV 56 2006

Cubicle, Supporting Structure


and Enclosure

4/2

General Data

4/4

Cubicles and Supporting Structure

4/8

Base

4/9

Enclosure

Siemens LV
Siemens
LV56
56 2008
2008

Cubicle, Supporting Structure and Enclosure


General Data

Overview

10

10
5

NSE0_01670

2
6

1 Cubicle

6 Base besides covers

2 Base with front covers

7 Bottom plate

3 Glazed door Giugiaro Design

8 Top plate

4 Rear wall

9 Supporting structure for main busbars


in standard position
10 Supporting structure for main busbars in standard position
and riser compartment 600mm + 200mm

5 Side panel with design bar

4/2

Siemens LV 56 2008

Cubicle, Supporting Structure and Enclosure


General Data

Overview
Cross section of possible combinations of cubicles, Supporting
structureand enclosures seen from above.

6
1

2 Internal cover B200

1 Supporting structure external for cover

3 Cover frame

02022

4 Cubicle panelling IP3X or

5 Door IP4X, IP55

6 Cubicle

6
1

2 Outer plate B200, 400 or door B400, 600


3

3 Cover frame

02023

4
2

1 Supporting structure external for door

4 Cubicle panelling IP3X or

5 Door IP4X, IP55


6 Cubicle

4
1

02024

2
2

1 Supporting structure external for door


2 Outer plate B200, 400 or door B400, 600

3 Modular door
4 Cubicle

Siemens LV 56 2008

4/3

Cubicle, Supporting Structure and Enclosure


Cubicle and supporting structure

Description

Configuration

The cubicle is a framework consisting of vertical and horizontal


sections plus the fasteners necessary to assemble them.
This provides the bearing structure support to all add-on interior
switchgear components. Stable and rugged construction is
achieved through the use of galvanised sections and self-tapping
screws. Equipotential and safe grounding of all constituent parts
are also achieved.

The values quoted below are the external dimensions.


A complete configuration is made of the following elements:
cubicle, bottom plate partition crossbar and supporting structure
for equipment heights of 1600mm or 1800mm.
To assemble two or more cubicles by width or depth, request the
board coupling kit for each coupling point.

The cubicle uprighte have holes spaced 25 mm apart for


anchoring to the base or the floor. In the upper part these holes
make it possible to fit crossbars, or eyebolts for board handling
purposes.
The installation of interior components, kits, crossbars, supporting
parts, etc., is facilitated by the presence of height, width and
depth locators.
The supporting structure is made up of a vertical section,
crossbars and fastening screws.
In cubicles of various heights and width it ensures segregation
between the equipment compartment and the busbar
compartment, partitioning the cubicles into equipment
compartments and main, or distribution, busbars compartments.

Bottom plate partition not required


+++ Function performed by the cubicle

Selection and ordering data

Height
mm

Width
mm

Dept
mm

Cubicle

02027

02026

02025

Supporting strucutre

01797

Bottom plate
partition

1800 mm

Equipment height
1600 mm

Cubicle and supporting structure with one section


2000

400

400

8PQ1204-4BA01

+++

8PQ3000-0BA65

2000

600

400

8PQ1206-4BA01

+++

8PQ3000-0BA65

2000

800

400

8PQ1208-4BA01

+++

8PQ3000-0BA65

2000

1000

400

8PQ1201-4BA02

8PQ3000-1BA38

+++

8PQ3000-0BA65

2000

1200

400

8PQ1202-4BA02

8PQ3000-1BA38

+++

8PQ3000-0BA65

2000

400

600

8PQ1204-6BA01

8PQ3000-0BA03

8PQ3000-0BA01

2000

600

600

8PQ1206-6BA01

8PQ3000-0BA03

8PQ3000-0BA01

2000

800

600

8PQ1208-6BA01

8PQ3000-0BA03

8PQ3000-0BA01

2000

1000

600

8PQ1201-6BA02

8PQ3000-1BA40

8PQ3000-0BA03

8PQ3000-0BA01

2000

1200

600

8PQ1202-6BA02

8PQ3000-1BA40

8PQ3000-0BA03

8PQ3000-0BA01

2000

400

800

8PQ1204-8BA01

8PQ3000-0BA03

8PQ3000-0BA02

2000

600

800

8PQ1206-8BA01

8PQ3000-0BA03

8PQ3000-0BA02

2000

800

800

8PQ1208-8BA01

8PQ3000-0BA03

8PQ3000-0BA02

2000

1000

800

8PQ1201-8BA03

2x 8PQ3000-1BA38 8PQ3000-0BA03

8PQ3000-0BA02

2000

1200

800

8PQ1202-8BA02

2x 8PQ3000-1BA38 8PQ3000-0BA03

8PQ3000-0BA02

4/4

Siemens LV 56 2008

Cubicle, Supporting Structure and Enclosure


Cubicle and Supporting structure

Description

Configuration

The supporting structure external is made up of a vertical


section and the relative fasteners.

The values quoted below are the external dimensions.

The Supporting structure for internal covers constitutes a


cubicle upright that makes it possible to fit a front frame and an
interior cover in front of a cubicle part 200mm in width.
The Supporting strucutre for outer covers/door constitutes two
cubicle uprights and makes it possible to fit modular doors/a front
frame and a door/exterior cover.

A complete configuration is made up of the following elements:


cubicle, bottom plate partition crossbar, supporting structure, for
an equipment height of 1800mm or 1600mm, and an supporting
structure external for the installation of interior covers or an
exterior cover/doors.
For separation forms >1 when using 200mm, 400mm, 600mm
cubicles, as cable compartment or equipment compartment
request an additional supporting structure, see page 4/7.
A combination of supporting structure external for internal covers
and modular doors is not possible.
To assemble two or more cubicles by width or depth, request the
board coupling kit for each coupling point.
not possible
+++ Function performed by the supporting structure external

Selection and ordering data


Supporting structure external

Height
mm

Width
mm

Depth
mm

Cubicle
partition

Cubicle

Bottom plate
crossbar

02030

02029

02028

02025

01797

Interior intermediate side upright

Equipment height

For upgrade

1800 mm

1600 mm

Internal covers

Door auter covers

Cubicles and Supporting structure with division into two sections


2000

800

400

600+200

8PQ1208-4BA01

8PQ3000-1BA38

+++

8PQ3000-0BA65
8PQ3000-1BA31

8PQ3000-1BA42

8PQ3000-1BA43

2000

1000

400

600+400

8PQ1201-4BA02

8PQ3000-1BA38

+++

8PQ3000-0BA65
8PQ3000-1BA31

8PQ3000-1BA43

2000

1000

400

800+200

8PQ1201-4BA02

8PQ3000-1BA38

+++

8PQ3000-0BA65
8PQ3000-1BA31

8PQ3000-1BA42

8PQ3000-1BA43

2000

1200

400

600+600

8PQ1202-4BA02

8PQ3000-1BA38

+++

8PQ3000-0BA65
8PQ3000-1BA31

8PQ3000-1BA43

2000

800

600

600+200

8PQ1208-6BA01

8PQ3000-1BA40

8PQ3000-0BA03
8PQ3000-1BA36

8PQ3000-0BA01
8PQ3000-1BA32

8PQ3000-1BA42

8PQ3000-1BA43

2000

1000

600

600+400

8PQ1201-6BA02

8PQ3000-1BA40

8PQ3000-0BA03
8PQ3000-1BA36

8PQ3000-0BA01
8PQ3000-1BA32

8PQ3000-1BA43

2000

1000

600

800+200

8PQ1201-6BA02

8PQ3000-1BA40

8PQ3000-0BA03
8PQ3000-1BA36

8PQ3000-0BA01
8PQ3000-1BA32

8PQ3000-1BA42

8PQ3000-1BA43

2000

1200

600

600+600

8PQ1202-6BA02

8PQ3000-1BA40

8PQ3000-0BA03
8PQ3000-1BA36

8PQ3000-0BA01
8PQ3000-1BA32

8PQ3000-1BA43

2000

800

800

600+200

8PQ1208-8BA01

2x 8PQ3000-1BA38 8PQ3000-0BA03
8PQ3000-1BA37

8PQ3000-0BA02
8PQ3000-1BA34

8PQ3000-1BA42

8PQ3000-1BA43

2000

1000

800

600+400

8PQ1201-8BA03

2x 8PQ3000-1BA38 8PQ3000-0BA03
8PQ3000-1BA37

8PQ3000-0BA02
8PQ3000-1BA34

8PQ3000-1BA43

2000

1000

800

800+200

8PQ1201-8BA03

2x 8PQ3000-1BA38 8PQ3000-0BA03
8PQ3000-1BA37

8PQ3000-0BA02
8PQ3000-1BA34

8PQ3000-1BA42

8PQ3000-1BA43

2000

1200

800

600+600

8PQ1202-8BA02

2x 8PQ3000-1BA38 8PQ3000-0BA03
8PQ3000-1BA37

8PQ3000-0BA02
8PQ3000-1BA34

8PQ3000-1BA43

Siemens LV 56 2008

4/5

Cubicle, Supporting Structure and Enclosure


Cubicle supporting structure

Description

Configuration

The supporting structrure external is made up of a vertical


section and the relative fasteners.
The supporting structure external of internal covers
constitutes a cubicle upright and makes it possible to fit a front
frame and an interior cover in front of a cubicle part 200mm in
width.
The supporting structure external outer cover/doors
constitutes two cubicle uprights and makes it possible to fit
externally modular doors/a front frame and a door/ cover.

The values quoted below are the external dimensions.


A complete configuration is made up of the following elements:
cubicle, bottom plate partition crossbar, side supporting structure
for an equipment height of 1800mm or 1600mm and an
intermediate upright.
The exterior intermediate upright consists of the following
combination of:
2 Supporting structure external for internal covers
or
1 Supporting structure external for internal covers and
1 intermediate upright for exterior cover/door.
or
2 Supporting structure external for outer cover/door
A combination of exterior intermediate upright for interior covers
and modular doors is not possible.

For separation forms >1 when using 200mm, 400mm, 600mm


cubicles, as cable compartment or equipment compartment
request an additional intermediate upright, see page 4/7.
To assemble two or more cubicles by width or depth, request the
board coupling kit.
+++ Function performed by the exterior supporting structure

Selection and ordering data

Width
mm

Depth Cubicle submm


division into
sections

Cubicle

Bottom plate partition crossbars

02033

02032

02031

01797

Height
mm

Equipment height
1800 mm

1600 mm

02034

Supporting structure external

Supporting structure

For upgrade
Interior covers

Modular doors/exterior covers

Cubicle and supporting structure with subdivision into three sections


2000

1000

400

200+600+200

8PQ1201-4BA02

2x 8PQ3000-1BA38 +++

8PQ3000-0BA65
8PQ3000-1BA42
2x 8PQ3000-1BA31

8PQ3000-1BA43

2000

1200

400

400+600+200

8PQ1202-4BA02

2x 8PQ3000-1BA38 +++

8PQ3000-1BA42
8PQ3000-0BA65
2x 8PQ3000-1BA31

8PQ3000-1BA43

2000

1200

400

200+800+200

8PQ1202-4BA02

2x 8PQ3000-1BA38 +++

8PQ3000-0BA65
8PQ3000-1BA42
2x 8PQ3000-1BA31

8PQ3000-1BA43

2000

1000

600

200+600+200

8PQ1201-6BA02

8PQ3000-1BA42
2x 8PQ3000-1BA40 8PQ3000-0BA03
8PQ3000-0BA01
2x 8PQ3000-1BA36 2x 8PQ3000-1BA32

8PQ3000-1BA43

2000

1200

600

400+600+200

8PQ1202-6BA02

8PQ3000-1BA42
2x 8PQ3000-1BA40 8PQ3000-0BA03
8PQ3000-0BA01
2x 8PQ3000-1BA36 2x 8PQ3000-1BA32

8PQ3000-1BA43

2000

1200

600

200+800+200

8PQ1202-6BA02

8PQ3000-1BA42
2x 8PQ3000-1BA40 8PQ3000-0BA03
8PQ3000-0BA01
2x 8PQ3000-1BA36 2x 8PQ3000-1BA32

8PQ3000-1BA43

2000

1000

800

200+600+200

8PQ1201-8BA03

8PQ3000-1BA42
4x 8PQ3000-1BA38 8PQ3000-0BA03
8PQ3000-0BA02
2x 8PQ3000-1BA37 2x 8PQ3000-1BA34

8PQ3000-1BA43

2000

1200

800

400+600+200

8PQ1202-8BA02

8PQ3000-1BA42
4x 8PQ3000-1BA38 8PQ3000-0BA03
8PQ3000-0BA02
2x 8PQ3000-1BA37 2x 8PQ3000-1BA34

8PQ3000-1BA43

2000

1200

800

200+800+200

8PQ1202-8BA02

4x 8PQ3000-1BA38 8PQ3000-0BA03
8PQ3000-0BA02
8PQ3000-1BA42
2x 8PQ3000-1BA37 2x 8PQ3000-1BA34

8PQ3000-1BA43

4/6

Siemens LV 56 2008

Cubicle, Supporting Structure and Enclosure


Cubicle and Supporting structure

Description
The supporting structure is made up of vertical and horizontal
sections and the relative fasteners.
In cubicles of different depths the supporting structure ensures
the creation of equipment and cable compartments and divides
the cubicle into equipment compartment, main or distribution
busbars compartment as well as cable compartment.

Configuration
For sepation forms 2, 3, 4 when using 200mm, 400mm or 600mm
cubicles, in a cubicle partitioned on the left/right as cable
compartment or equipment compartment, order an supporting
structure kit as an additional component.
1 required only for supporting structure external for internal covers

02035

02036

Supporting structure

Height
mm

Depth
mm

Equipment height
1800 mm

1600 mm

Supporting structure
2000

400

8PQ3000-1BA42 1

8PQ3000-1BA31

2000

600

8PQ3000-1BA36

8PQ3000-1BA32

2000

800

8PQ3000-1BA37

8PQ3000-1BA34

Description
The kit for coupling two or more boards by width or depth consists
of fastening plates and screws.
The board coupling gasket kit with degree of protection IP55
consists of a self-adhesive gasket roll.
.

Configuration
To assemble two or more cubicles by width or depth, request a
board coupling kit for each coupling point.
For a degree of protection IP55, order an IP55 board coupling
gasket kit as an additional component.
Ordering code

UI

Board coupling by width or depth kit 8PQ1204-4BA05

8PQ1204-4BA05

IP55 board coupling gasket 8PQ1204-4BA04

8PQ1204-4BA04

Board coupling kit

Siemens LV 56 2008

4/7

Cubicle, Supporting Structure and Enclosure


Base

Description

Configuration

The base kit is made of the following elements: corner pieces,


front covers and the relative fasteners.
Ad hoc covers to be order separately are available for the side
covers. The covers of the base are not suitable for board
transport and handling.

For each board, consisting of one or more cubicles, the side


covers kit must be ordered once for the H 100 base and twice
for the H 200 base.

For special situations, such as rolling, moving the cubicles on


roller an ad hoc reinforcement kit is available (that can be
applied along the width or the depth of the cubicle as a function
of the direction of movement). Base reinforcements are mounted
internally, at the front, back or side.

Selection and ordering data


Height
mm

Depth
mm

Ordering code

UI

01798

01642

Base with front covers


100

400

8PQ1014-0BA01

100

600

8PQ1016-0BA01

100

800

8PQ1018-0BA01

100

1000

8PQ1011-0BA01

100

1200

8PQ1012-0BA01

200

400

8PQ1024-0BA01

200

600

8PQ1026-0BA01

200

800

8PQ1028-0BA01

200

1000

8PQ1021-0BA01

200

1200

8PQ1022-0BA01

1
2

01643

Base covers besides


100

400

8PQ1010-4BA01

100

600

8PQ1010-6BA01

100

800

8PQ1010-8BA01

Base reinforcement
100

400

8PQ1014-0BA02

100

600

8PQ1016-0BA02

100

800

8PQ1018-0BA02

100

400

8PQ1014-0BA02

100

600

8PQ1016-0BA02

100

800

8PQ1018-0BA02

100

1000

8PQ1011-1BA01

100

1200

8PQ1012-2BA01

01078

01079

01644

Width
mm

Transport with base and lift truck

4/8

Siemens LV 56 2008

Transport with reinforced base and rollers

Cubicle, Supporting Structure and Enclosure


Enclosure

Description

Configuration

The front or blind covers of the various assembly kits are


anchored to a cover frame by means of quick locking screws
(a hinge kit can be an option to obtain a rotary cover).
A cover frame 1600 or 1800 mm high in fixed or swivel versions
is available. In the frame there is room to house the front covers
of the assembly kits. The rotary mechanism enables the frame to
be rotated over a 180 angle.
This gives full access to the interior components of the board.

The cover frame are available for 600 mm and 800 mm wide
cubicles.
Frame types available:
H 1600 mm frame for assembly kits with built-in covers for
busbar systems in the upper part and grounding bars in the
lower part.
H 1800 mm frame for assembly kits. For a rear upper busbar
system, the space available in the upper section is 150 mm
high and only 300 mm deep. This module can be used only
for covers and DIN rail kits for modular units.
For an exact selection, see also the notes in chapter 5 busbar
systems.

Selection and ordering data


Height for equipment
mm

Width
mm

Ordering code

1600

600

8PQ2000-6BA03

1600

800

8PQ2000-8BA03

UI

01802

Fixed cover frame for front main busbars

Fixed cover frame without or with rear main busbars


600

8PQ2000-6BA04

1800

800

8PQ2000-8BA04

01803

1800

Swivel cover frame for front main busbars


600

8PQ2000-6BA02

1600

800

8PQ2000-8BA02

01626

1600

Swivel cover frame without or with rear main busbars


600

8PQ2000-6BA01

800

8PQ2000-8BA01

01625

1800
1800

Siemens LV 56 2008

4/9

Cubicle, Supporting Structure and Enclosure


Enclosure

Description

Configuration

For 200mm wide cubicle sections, an internal cover that can be


mounted behind the door is available.
The kit is made up of a cover, an anchoring support and
fasteners. This cover must be used in conjunction with a cover
frame and can be placed behind the door.

When a 200mm section is produced in a cubicle, this section


can be placed indifferently on the left or the right side, and is
closed with an interior cover.
For use only in conjunction with an supporting structure externa
for internal covers.

Selection and ordering data


Height of cover

Width
mm

Degree
of protection

Ordering code

UI

200

IP30

8PQ2000-2BA01

Internal cover for 200mm section

Description

Configuration

A outer cover can be instead a door of 200mm and 400mm wide


compartments.

The covers can be can be mounted as desired on the front or the


back of the cubicle.

The kit includes a painted cover, a green column identification


strip, an anchoring support and the relative fasteners. This cover
must be used in conjunction with the cover frame or as an
alternative to the door.

For use only in conjunction with the supporting structure external


for outer covers/door.

Selection and ordering data


Height cover

Width
mm

Degree
of protection

Ordering code

UI

Cubicle height

200

IP40

8PQ2197-2BA15

Cubicle height

400

IP40

8PQ2197-4BA02

Cubicle height

200

IP55

8PQ2197-2BA14

Cubicle height

400

IP55

8PQ2197-4BA01

01663

Outer cover

Description

Configuration

For 600mm and 800mm wide cubicles with front frame, cubicle
panelling are available as an alternative to doors.

For use only in conjunction with a front frame.


Only for 600mm and 800mm wide cubicles.

With its thickness, the finishing frame ensures the same height
as an adjacent door, as well as the same height of the cover of
the uprights of the galvanised chromed cubicle.
Cubicle panelling, covers and finishing frame achieve a degree
of protection of IP30/31.

Selection and ordering data


Height

Width
mm

Degree
of protection

Ordering code

UI

Cubicle height

600

IP30

8PQ2197-6BA11

Cubicle height

800

IP30

8PQ2197-8BA11

Cubicle panelling

01636

01799

Cubicle height

4/10

Siemens LV 56 2008

Cubicle, Supporting Structure and Enclosure


Enclosure

Description

Configuration

The SIVACON S4 door kit is made up of Giugiaro Design glazed


doors or metal plate doors, a green column identification strip,
hinges and preassembled bar lock closing system with two-way
interlocking mechanism.

Standard version doors use a 3mm two-way interlocking system.

The two-way interlocking mechanism can be replaced with a


rotary handle (standard doors are not suitable for semicylindrical profiles).

In cubicles with degree of protection IP40 the top plate, the


doors and the rear wall must have the same degree of
protection.

The doors can be mounted indifferently to the front or back of the


cubicle.

Thanks to the new hinge and locking system, the door hinges
can be fitted either on the left or the right.
The position of the hinges can be easily modified at a later stage.
If it is deemed necessary to fit a closing system with rotary
handle and semi-cylindrical profile with security key, on account
of cylinder depth, a series of dedicated doors with right or left
side hinges are available.

Selection and ordering data

4
Door type

Door height Door width


mm
mm

Degree of
protection

Hinge position

Ordering code

UI

01634

01633

01635

Cubicle door with two-way interlocking system


Finned plate door

1975

400

IP40

left

8PQ2197-4BA08

Finned plate door

1975

600

IP40

left

8PQ2197-6BA06

Finned plate door

1975

800

IP40

left

8PQ2197-8BA06

Finned plate door

1975

1000

IP40

left

8PQ2197-1BA06

Finned plate door

1975

400

IP40

right

8PQ2197-4BA11

Finned plate door

1975

600

IP40

right

8PQ2197-6BA13

Finned plate door

1975

800

IP40

right

8PQ2197-8BA13

Finned plate door

1975

1000

IP40

right

8PQ2197-1BA18

Plate door

1975

400

IP55

left

8PQ2197-4BA05

Plate door

1975

600

IP55

left

8PQ2197-6BA03

Plate door

1975

800

IP55

left

8PQ2197-8BA03

Plate door

1975

1000

IP55

left

8PQ2197-1BA03

Plate door

1975

400

IP55

right

8PQ2197-4BA10

Plate door

1975

600

IP55

right

8PQ2197-6BA12

Plate door

1975

800

IP55

right

8PQ2197-8BA12

Plate door

1975

1000

IP55

right

8PQ2197-1BA17

Glazed door

1975

600

IP55

left

8PQ2197-6BA10

Glazed door

1975

800

IP55

left

8PQ2197-8BA10

Glazed door

1975

1000

IP55

left

8PQ2197-1BA10

Glazed door

1975

600

IP55

right

8PQ2197-6BA14

Glazed door

1975

800

IP55

right

8PQ2197-8BA14

Glazed door

1975

1000

IP55

right

8PQ2197-1BA20

Siemens LV 56 2008

4/11

Cubicle, Supporting Structure and Enclosure


Enclosure

Description

Configuration

The SIVACON S4 door kit is made up of Giugiaro Design glazed


doors or metal doors, a green column identification strip, hinges
and preassembled bar lock closing system with rotary handle
mechanism for semi-cylindrical profile.

Standard version doors use a two-way interlocking mechanism.


Semi-cylindrical profile: see chapter s10 Accessories.
The doors can be mounted indifferently to the front or back of the
cubicle.
The hinges for double doors are hooked onto the cubicle
externally.
The double doors of 1000mm wide cubicles are split into a
600mm left section and a 400mm right section. Opening
sequence: right and then left.
The double doors of 1200mm wide cubicles are split 50/50.
Opening sequence: right and then left.

Selection and ordering data


Door type

Door height Door width


mm
mm

Degree of
protection

Hinge position

Ordering code

UI

01806

01805

01804

Door with rotary handle for semi-cylindrical profile DIN 18252/18254, 8 x 45


Finned plate door

1975

400

IP40

left

8PQ2197-4BA06

Finned plate door

1975

600

IP40

left

8PQ2197-6BA04

Finned plate door

1975

800

IP40

left

8PQ2197-8BA04

Finned plate door

1975

1000

IP40

left

8PQ2197-1BA07

Finned plate door

1975

400

IP40

right

8PQ2197-4BA07

Finned plate door

1975

600

IP40

right

8PQ2197-6BA05

Finned plate door

1975

800

IP40

right

8PQ2197-8BA05

Finned plate door

1975

1000

IP40

right

8PQ2197-1BA08

Plate door

1975

400

IP55

left

8PQ2197-4BA03

Plate door

1975

600

IP55

left

8PQ2197-6BA01

Plate door

1975

800

IP55

left

8PQ2197-8BA01

Plate door

1975

1000

IP55

left

8PQ2197-1BA04

Plate door

1975

400

IP55

right

8PQ2197-4BA04

Plate door

1975

600

IP55

right

8PQ2197-6BA02

Plate door

1975

800

IP55

right

8PQ2197-8BA02

Plate door

1975

1000

IP55

right

8PQ2197-1BA05

Glazed door

1975

600

IP55

left

8PQ2197-6BA07

Glazed door

1975

800

IP55

left

8PQ2197-8BA07

Glazed door

1975

1000

IP55

left

8PQ2197-1BA11

Glazed door

1975

600

IP55

right

8PQ2197-6BA08

Glazed door

1975

800

IP55

right

8PQ2197-8BA08

Glazed door

1975

1000

IP55

right

8PQ2197-1BA12

Double door with two-way interlocking mechanism


1975

1000

IP40

8PQ2197-1BA14

Finned plate door

1975

1200

IP40

8PQ2197-2BA11

Plate door

1975

1000

IP55

8PQ2197-1BA13

Plate door

1975

1200

IP55

8PQ2197-2BA10

01696

Finned plate door

Double door with rotary handle for semi-cylindrical profile


Finned plate door

1975

1000

IP40

8PQ2197-1BA16

Finned plate door

1975

1200

IP40

8PQ2197-2BA13

Plate door

1975

1000

IP55

8PQ2197-1BA15

Plate door

1975

1200

IP55

8PQ2197-2BA12

01698

In cubicles with degree of protection IP40, the top plate, the


doors and the rear wall must have the same degree of
protection.

4/12

Siemens LV 56 2008

Cubicle, Supporting Structure and Enclosure


Enclosure

Description

Configuration

The inner door kit includes a door and hinges. The inner door is
mounted behind the main cubicle door and in front of the largesized mounting plate for electrotechnical applications.

The inner door requires a depth of 30 mm and cannot be used


in conjunction with a cover frame.

Selection and ordering data


Height

Width
mm

Ordering code

UI

Inner door
600

8PQ2000-6BA05

Cubicle height

800

8PQ2000-8BA05

Cubicle height

1000

8PQ2000-1BA01

01699

Cubicle height

Siemens LV 56 2008

4/13

Cubicle, Supporting Structure and Enclosure


Enclosure

Description

Configuration

Bottom plates are available with degree of protection IP55


without cable entry opening and with degree of protection IP40
with variable cable entry opening.

For 800mm wide cubicles, order two 400mm deep bottom


plates.
For 800mm, 1000mm, 1200mm wide cubicles, bottom plate
selection depends on the combination of variants
corresponding to cubicle subdivision.

Selection and ordering data


Width
mm

Depth
mm

Degree
of protection

Ordering code

UI

200

400

IP55

8PQ2302-4BA04

400

400

IP55

8PQ2304-4BA05

600

400

IP55

8PQ2306-4BA05

800

400

IP55

8PQ2308-4BA05

200

600

IP55

8PQ2302-6BA04

400

600

IP55

8PQ2304-6BA05

600

600

IP55

8PQ2306-6BA05

800

600

IP55

8PQ2308-6BA05

400

400

IP40

8PQ2304-4BA06

600

400

IP40

8PQ2306-4BA06

800

400

IP40

8PQ2308-4BA06

400

600

IP40

8PQ2304-6BA06

600

600

IP40

8PQ2306-6BA06

800

600

IP40

8PQ2308-6BA06

Bottom plate without cable entry

01631

Bottom plate with variable cable entry

01632

1) Lieferbar ab 02/2007.

4/14

Siemens LV 56 2008

Cubicle, Supporting Structure and Enclosure


Enclosure

Description

Configuration

Top plates are available with degree of protection IP55 and IP40
without cable entry opening. A version with degree of protection
IP40 with variable cable entry opening is also available. The top
plates with degree of protection IP55 are secured with screws on
one side and snap into the board structure on the other. By
means of a further upgrade, degree of protection IPX1 can be
achieved.

For cubicles with degree of protection IP 40, the top plates, the
bottom plates, the doors and the panels must have the same
degree of protection IP 40.
With the IPX1 upgrade, cubicles with degree of protection IP30
and IP40 can achieve degree of protection IP31 and IP41
respectively. Column height is increased by 62 mm.

Selection and ordering data


Width
mm

Depth
mm

Degree
of protection

Ordering code

UI

400
400
400
600
600
600
800
800
800
1000
1000
1000
1200
1200
1200
400
400
400
600
600
600
800
800
800
1000
1000
1000
1200
1200
1200

400
600
800
400
600
800
400
600
800
400
600
800
400
600
800
400
600
800
400
600
800
400
600
800
400
600
800
400
600
800

IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP55
IP55
IP55
IP55
IP55
IP55
IP55
IP55
IP55
IP55
IP55
IP55
IP55
IP55
IP55

8PQ2304-4BA02
8PQ2304-6BA02
8PQ2304-8BA02
8PQ2306-4BA02
8PQ2306-6BA02
8PQ2306-8BA02
8PQ2308-4BA02
8PQ2308-6BA02
8PQ2308-8BA02
8PQ2301-4BA02
8PQ2301-6BA02
8PQ2301-8BA02
8PQ2302-4BA02
8PQ2302-6BA02
8PQ2302-8BA02
8PQ2304-4BA01
8PQ2304-6BA01
8PQ2304-8BA01
8PQ2306-4BA01
8PQ2306-6BA01
8PQ2306-8BA01
8PQ2308-4BA01
8PQ2308-6BA01
8PQ2308-8BA01
8PQ2301-4BA01
8PQ2301-6BA01
8PQ2301-8BA01
8PQ2302-4BA01
8PQ2302-6BA01
8PQ2302-8BA01

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

400
400
400
600
600
600
800
800
800

400
600
800
400
600
800
400
600
800

IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP40
IP40

8PQ2304-4BA03
8PQ2304-6BA03
8PQ2304-8BA03
8PQ2306-4BA03
8PQ2306-6BA03
8PQ2306-8BA03
8PQ2308-4BA03
8PQ2308-6BA03
8PQ2308-8BA03

1
1
1
1
1
1
1
1
1

400
400
400
600
600
600
800
800
800
1000
1000
1000
1200
1200
1200

400
600
800
400
600
800
400
600
800
400
600
800
400
600
800

IPX1
IPX1
IPX1
IPX1
IPX1
IPX1
IPX1
IPX1
IPX1
IPX1
IPX1
IPX1
IPX1
IPX1
IPX1

8PQ2304-4BA04
8PQ2304-6BA04
8PQ2304-8BA04
8PQ2306-4BA04
8PQ2306-6BA04
8PQ2306-8BA04
8PQ2308-4BA04
8PQ2308-6BA04
8PQ2308-8BA04
8PQ2301-4BA03
8PQ2301-6BA03
8PQ2301-8BA03
8PQ2302-4BA03
8PQ2302-6BA03
8PQ2302-8BA03

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Top plate without cable entry

01628

01627

Top plate with cable entry

01630

Top plate upgrade for IPX1

01629

Siemens LV 56 2008

4/15

Cubicle, Supporting Structure and Enclosure


Enclosure

Description

Configuration

Rear panels are available with degrees of protection IP40 and


IP55. Rear panels with degree of protection IP40 are galvanised
chromed, and those with degree of protection IP55 are slightly
embossed, RAL 7035 powder-coated.

For cubicles with degree of protection IP 40, the top plates, the
bottom plates, the doors and the rear panels must have the
same degree of protection IP 40.

Selection and ordering data


Width
mm

Depth
mm

Degree
of protection

Ordering code

UI

2000
2000

400

IP40

8PQ2420-4BA02

600

IP40

8PQ2420-6BA02

2000

800

IP40

8PQ2420-8BA02

2000

1000

IP40

8PQ2420-1BA02

2000

1200

IP40

8PQ2420-2BA02

2000

400

IP55

8PQ2420-4BA01

2000

600

IP55

8PQ2420-6BA01

2000

800

IP55

8PQ2420-8BA01

2000

1000

IP55

8PQ2420-1BA01

2000

1200

IP55

8PQ2420-2BA01

01637

Description

Configuration

The side panels are powder-coated and are available with


degree of protection IP 55, with or without Design bar.

For each board, order one kit of side panels.

Selection and ordering data


Width
mm

Depth
mm

Degree
of protection

Ordering code

UI

2000

400

IP55

8PQ2520-4BA01

2000

600

IP55

8PQ2520-6BA01

2000

800

IP55

8PQ2520-8BA01

2000

400

IP55

8PQ2520-4BA02

2000

600

IP55

8PQ2520-6BA02

2000

800

IP55

8PQ2520-8BA02

01640

Side panel with design

Side panel without design

01639

01789

Rear panel

4/16

Siemens LV 56 2008

Busbar System

5/2

General Data

5/3

Main busbar system

5/7

Vertical distribution busbar


system

5/11

Compact busbar systems

5/13

Copper bars

5/14

Busbar connection fasteners

Siemens LV
Siemens
LV56
56 2008
2008

Busbar System
General Data

Overview

2
4

1 System of main busbar with


rectangular profile
2 Main busbar extension kit
01676

3 Grounding bar PE
3

4 Busbar holder
5 Reinforcement

5/2

Siemens LV 56 2008

Busbar System
Main busbar system

Technical specifications
Admissible rated current for main busbar systems
No. of bars per phase

Dimensions
[mm]
20 10
30 10
20 10
30 10
40 10
50 10
20 10
30 10

2
2
4
4
4
4
24
24

Rated current at an ambient temperature of 35 C


Depth of cubicle 400mm
IP IP41
1190
1630
1920
2460
2980
3220

IP 55
965
1310
1420
1790
2150
2330

Depth of cubicle 600mm


IP IP41
1190
1630
1920
2490
3040
3320

IP 55
965
1310
1540
1950
2350
2570

Depth of cubicle 800mm


IP IP41
1190
1630
1930
2510
3100
3410
3700
4660

IP 55
965
1310
1650
2110
2560
2820
3000
3680

These values refer to normal operating conditions and indoor installation in accordance with IEC 60439-1, in particular, at an ambient temperature of 35C (24h average).
In different operating conditions, the correction factors given in the Planning and Configuration chapter have to be taken into account.

Cross-sections for PE conductor


No. of bars

Dimensions
[mm]

Icw
1s

20 5

30 5

85 kA

40 5

100 kA

30 10

100 kA

65 kA

The cross-sections specified for PE conductors were type tested according to IEC 60439-1. According to IEC 60439-1 a PE conductor cross-section corresponding to
25% the cross-section of main conductors is also admissible.

Determination of the number of reinforcements as a function of short-circuit current and cubicle width
Busbar cross-section
No of bars
2

Dimensions
[mm]
20 10

30 10

20 10

30 10

40 10

50 10

241

20 10

241

30 10

No. of reinforcements as a function of Ipk, Icw and cubicle width

Width [mm]

400
600
800
1000
1200
400
600
800
1000
1200
400
600
800
1000
1200
400
600
800
1000
1200
400
600
800
1000
1200
400
600
800
1000
1200
400
600
800
1000
1200
400
600
800
1000
1200

Icw = 25 kA
Ipk = 52,5 kA
0
0
1
1
2

Icw = 35 kA
Ipk = 73,5 kA
0
0
1
1
2
0
0
1
1
2
0
0
1
2
2
0
0
1
2
2

Icw = 50 kA
Ipk = 105 kA

0
1
1
2
2
0
0
1
2
2
0
0
1
2
2
0
0
1
1
2
0
0
1
1
2

Icw = 65 kA
Ipk = 143 kA

Icw = 85 kA
Ipk = 187 kA

Icw = 100 kA
Ipk = 220 kA

0
1
2
3
3
0
1
2
3
3
0
0
1
1
2
0
0
1
1
2
0
1
2
3
4
0
1
2
3
4

0
1
2
3
3
0
1
2
3
3
0
1
2
3
3
0
1
2
3
4
0
1
2
3
4

0
1
2
3
4
0
1
2
3
4
0
1
2
3
4
0
1
2
3
4

1) The number of reinforcements applies to a main busbar system. Since the 3700 A and 4000 A main busbar system is made up of two systems mounted in parallel,
the number of reinforcements to be ordered must be doubled.

For the determination of the distances between busbar holders and reinforcements, refer to the SIVACON S4 Manual.
Siemens LV 56 2008

5/3

Busbar System
Main busbar system

Description
The main busbar system of SIVACON S4 offers an appropriate
scaling of rated currents, matched to the rated currents of
standard version circuit breakers and transformers.
The busbar holders have been designed for the use of
rectangular copper profiles.
By using 2, 4 or 8 sub-conductors per phase, it is possible to
achieve high resistance to short-circuits and make the
connections without having to drill holes. This arrangement also
simplify handling of one or more cubicles.

The main horizontal busbar system provides for a variety of


network configurations such as TN-C, TN-S, IT and TT.
The connection of the PE bar to the cubicle is type-tested
(resistance to short-circuits) and ensures a safe transfer of fault
currents to the cubicle.
For TN-C network systems, a type-tested connection (PEN
jumper) between the PEN bar and the cubicle is available.

Configuration

01702

SIVACON S4 main busbar system in standard position


- Installation position: front top
- Cubicle depth 600 mm
- Rated current up to 3200 A
- Side upright for 1600mm high modules
- Front frame for 1600mm high modules

01703
01704

SIVACON S4 main busbar system in standard position


- Installation position: front rear
- Cubicle depth 800 mm
- Rated current up to 3200 A
- Side upright for 1600mm high modules
- Front frame for 1600mm high modules or
- Front frame for 1800mm high modules mm; the 150mm high upper module must be used only to fit the front cover

01705

SIVACON S4 main busbar system in standard position


- Installation position: front top and rear (double upper system)
- Cubicle depth 800 mm
- Rated current up to 4000 A
- Side upright for 1600mm high modules
- Front frame for 1600mm high modules

01701

SIVACON S4 main busbar system in standard position


- Installation position: front top
- Cubicle depth 400 mm
- Rated current up to 3200 A
- Side upright for 1600mm high modules
- Front frame for 1600mm high modules

01692

SIVACON S4 main busbar system in optional position


- Installation position: at different heights at rear
- Cubicle depth 800 mm
- Rated current up to 3200 A
- Side upright for 1800 mm high modules
- Front frame for 1800 mm high modules
- To position the busbars at an optional height other than in the upper part of the cubicle, order two 350mm long crossbars per
cubicle

01706

Main busbar system with PEN jumper


- The PEN jumper establishes the connection between the PEN bar and the cubicle. 1 PEN jumper per cubicle is required

PE bar connection
- The connection of the PE bar to the cubicle is included in the main busbar kit

01710

SIVACON S4 main busbar system in standard position


- Installation position: front top
- Cubicle depth 800 mm
- Rated current up to 3200 A
- Side upright for 1600mm high modules
- Front frame for 1600mm high modules

5/4

Siemens LV 56 2008

Busbar System
Main busbar systems

Selection and ordering data


1

1
2

1
2

1
2

02038

02037

Single-cubicle transport unit

Main busbar holder

Reinforcement

Multi-cubicle transport unit

The number of reinforcements to be used depends on the value of the short-circuit current and cubicle width.
The additional internal arc protection kit is required for arcing times of between 100 ms and 300 ms. Order one kit per side panel.

Selection and ordering data


Dimensions
mm mm

Ordering code

UI

8PQ4000-0BA04

20 10, 30 10, 40 10, 50 10

8PQ4000-0BA60

20 10, 30 10, 40 10, 50 10

8PQ4000-0BA37

8PQ9400-0BA21

Main busbar holder kit up to 3200 A, with PE grounding bar connection to cubicle

01685

20 10, 30 10, 40 10, 50 10

01686

Main busbar holder kit up to 4000 A, with PE grounding bar connection to cubicle

01687

Busbar reinforcement kit

02039

Additional internal arc protection kit

Siemens LV 56 2008

5/5

Busbar System
Main busbar system

Selection and ordering data


Dimensions
mm mm

Ordering code

UI

01674

Main busbars extension kit for L1, L2, L3, N or PEN1


20 10

8PQ4000-0BA53

30 10

8PQ4000-0BA54

40 10

8PQ4000-0BA56

50 10

8PQ4000-0BA57

20 5, 30 5, 30 10

8PQ4000-0BA52

40 5, 40 10, 50 10

8PQ4000-0BA67

8PQ4000-0BA62

8PQ4000-0BA12

10

8PQ4000-0BA82

01673

Extension kit for PE grounding bar

01790

PEN jumper for main busbar system1

01706

PE bar connection to cubicle (accessory)

01710

Connection kit for double main busbar system 1


(order 1 per cubicle; cannot be installed in 400mm wide cubicles)

1) Without screws, washers and nuts.

5/6

Siemens LV 56 2008

Busbar System
Vertical distribution busbar system

Cascaded distribution busbar system with profiled


busbars
Double arrangement, side-by-side

Cascaded distribution busbar system with rectangular bars


Double arrangement, aligned

02042

Non-cascaded distribution busbars system with


regular busbars
Single arrangement

02045

Cascaded distribution busbar system with rectangular bars


Single arrangement

02044

02043

Cascaded distribution busbar system with profiled


busbars
Single arrangement

02041

02040

Overview

Non-cascaded distribution busbar system with


rectangular bars
Double arrangement, aligned

Siemens LV 56 2008

5/7

Busbar System
Vertical distribution busbar system

Technical specifications
Admissible rated current values for cascaded vertical distribution busbars
The rated sort-time current Icw for a cascaded vertical
busbar system is determined on the basis of no. of busbars,
No. of bars per phase

Dimensions
[mm]

Admissible current for


a temperature of 35 C
IP IP41

1
1
2
2
Profiled busbar
Profiled busbar
2x2
2x2
2 x Profiled busbar
2 x Profiled busbar

30 10
40 10
30 10
40 10
30 30
40 30
30 10
40 10
30 30
40 30

busbar size and shape, and the number of busbar


holders.

922
1100
1530
1651
1289
1518
3060
3302
2578
3036

IP 55
837
980
1337
1543
1066
1217
2674
3086
2132
2434

No. of holders per cubicle and per system


Icw = 25 kA
Ipk = 52,5 kA
4
4
4
4
4
4

Icw = 35 kA
Ipk = 73,5 kA
4
4
4
4
4
4

Icw = 50 kA
Ipk = 105 kA

4
4
4
4
4
4
4
4

Icw = 65 kA
Ipk = 143 kA

5
5
5
5
5
5
5
5

Icw = 85 kA
Ipk = 187 kA

8
8
8
8

These values refer to normal operating conditions and indoor installation in accordance with IEC 60439-1, in particular, at an ambient temperature of 35C (24h average).
In different operating conditions, the correction factors given in the Planning and Configuration chapter have to be taken into account.

Admissible rated current values for non-cascaded vertical distribution busbars


The rated sort-time current Icw of a non-cascaded vertical
busbar system is determined on the basis of no. of busbars,
busbar size, and number of reinforcements.
No. of bars per phase

Dimensions
[mm]

Admissible current for a


temperature of 35 C
IP IP41

20 10
30 10
20 10
30 10
40 10
50 10

2
2
4
4
4
4

For each cubicle, order one kit (3 pcs.) of non-cascaded busbar


holders.

1010
1390
1630
2091
2533
2737

IP 55
820
1110
1207
1520
1825
1980

No. of reinforcements per cubicle


Icw = 25 kA
Ipk = 52 kA
0
0
0
0
0
0

Icw = 35 kA
Ipk = 73 kA
0
0
0
0
0
0

Icw = 50 kA Icw = 65 kA Icw = 85 kA Icw = 100 kA


Ipk = 105 kA Ipk = 143 kA Ipk = 187 kA Ipk = 220 kA
2
2
2
0
0

2
2
2
2

2
2
2

4
4

These values refer to normal operating conditions and indoor installation in accordance with IEC 60439-1, in particular, at an ambient temperature of 35C (24h
average).
In different operating conditions, the correction factors given in the Planning and Configuration chapter have to be taken into account.

5/8

Siemens LV 56 2008

Busbar System
Vertical distribution busbar system

Configuration
Cascaded vertical distribution busbar system
For profiled busbars, the connections are made by
means of T-head screws. When using rectangular busbars,

the connections are made by means of screws


and connection kits.

Selection and ordering data


Busbar dimensions
mm mm

Busbar shape

Cubicle
width
mm

Cubicle
depth
mm

Position of
main busbars

Position of
vertical distribution busbars

Ordering code

UI

01690

Busbar holder kit for cascaded vertical distribution busbars


40 30

Profiled busbar

200

8PQ4000-0BA63

40 10

Rectangular
busbar

200

8PQ4000-0BA63

30 30

Profiled busbar

200

8PQ4000-0BA32

30 10

Rectangular
busbar

200

8PQ4000-0BA32

20 10, 30 10, 40 10, 50 10 Rectangular


busbar

200

8PQ4000-0BA77

20 10, 30 10, 40 10, 50 10 Rectangular


busbar

400

8PQ4000-0BA31

8PQ4000-0BA37

01688

Busbar holder kit for non-cascaded vertical distribution busbars

Busbar reinforcement kit

01687

20 10, 30 10, 40 10, 50 10 Rectangular


busbar

End support for non-cascaded vertical busbars

200

8PQ4000-0BA78

400

8PQ4000-0BA61

8PQ4000-0BA11

01689

Anchoring support for N or PE bars in cable compartment

01707

Siemens LV 56 2008

5/9

Busbar System
Vertical distribution busbar system

Selection and ordering data


Bus bar dimensions
mm mm

Busbar shape

Cubicle
width
mm

Cubicle
depth
mm

Position of
main busbars

Position of
vertical distribution busbars

Ordering code

UI

01718

Connection kit between cascaded vertical busbars/horizontal busbars 1


30 30, 30 10

400

front

right

8PQ4000-0BA45

40 30, 40 10

400

front

right

8PQ4000-0BA47

30 30, 30 10

600, 800 front

right

8PQ4000-0BA46

40 30, 40 10

600, 800 front

right

8PQ4000-0BA48

30 30, 30 10

800

rear

right

8PQ4000-0BA50

40 30, 40 10

800

rear

right

8PQ4000-0BA51

30 30, 30 10

400

front

left

8PQ4000-0BA73

40 30, 40 10

400

front

left

8PQ4000-0BA75

30 30, 30 10

600, 800 front

left

8PQ4000-0BA72

40 30, 40 10

600, 800 front

left

8PQ4000-0BA74

30 30, 30 10

800

rear

left

8PQ4000-0BA70

40 30, 40 10

800

rear

left

8PQ4000-0BA71

Connection kit between non-cascaded vertical busbars/horizontal busbars1

01675

20 10, 30 10

400

front

8PQ4000-0BA38

40 10, 50 10

400

front

8PQ4000-0BA41

20 10, 30 10

600, 800 front

8PQ4000-0BA40

40 10, 50 10

600, 800 front

8PQ4000-0BA42

20 10, 30 10

800

rear

8PQ4000-0BA43

40 10, 50 10

800

rear

8PQ4000-0BA44

8PQ9400-0BA02

20

Busbar clamp kit for M10 screw

01743

1) without screws, washers and nuts

5/10

Siemens LV 56 2008

Busbar System
Compact busbar system

Overview
Compact busbar systems may be arranged as desired with uprights and crossbars.

02047

02046

Compact busbar systems 8GF57


non-cascaded, anchored to crossbars

Non-cascaded busbar support

Cascaded busbar support

Crossbars for anchoring width-wise

Crossbars for anchoring depth-wise

Supporting structure

Compact busbar systems 8GF57


cascaded, anchored to crossbars

Siemens LV 56 2008

5/11

Busbar System
Compact busbar system

Technical specifications
Admissible rated current for copper busbars, for an ambient temperature of 35 C according to DIN 43671
No. of busbars

Rated current at a temperature of

Dimensions
[mm]

65 C

85 C

Holder spacing [mm]


Icw = 5 kA

105 C

Icw = 10 kA

Icw = 15 kA

Icw = 20 kA

Icw = 25 kA

15 5

222

293

349

600

400

20 5

274

362

430

600

600

30 5

379

500

595

600

600

450

352

300

30 10

573

756

900

600

600

400

300

250

Description
Compact busbar systems are used for the distribution of
currents up to 630A and rated short-time currents Icw upto 25
kA.

400

Configuration
Compact busbar systems, with pole centre distance of 50mm,
can be used in conjunction with the rapid wiring assembly
system for modular devices SIKclip.
For compact busbar systems, with pole centre distance of
60mm, a wide range of adapters for SIRIUS, SENTRON 3VL is
available together with many other accessories.

Selection and ordering data


Description

No. of
poles

Busbar dimensions
mm mm

Busbar shape

Arrangement

Ordering code

UI

Busbar holder

15 5, 20 5, 30 5

Rectangular

non-cascaded

8GF5762

Busbar holder

30 10

Rectangular

non-cascaded

8GF5763

Busbar holder

15 5, 20 5, 30 5

Rectangular

cascaded

8GF5760

Busbar holder

30 10

Rectangular

cascaded

8GF5761

02049

02048

Compact busbar system, 50mm pole centre distance

Compact busbar holder system, 60mm pole centre distance


3

15 5, 20 5, 30 5, 30 10

Rectangular

non-cascaded

8US1923-3AA01

Busbar holder

15 5, 20 5, 30 5, 30 10

Rectangular

non-cascaded

8US1923-4AA00

Busbar holder end cover

8US1922-1AC00

Busbar holder end cover

8US1922-1AB00

Busbar cover section

20 5, 30 5

Rectangular

8US1922-2AA00

Busbar cover section

20 10, 30 10

Rectangular

8US1922-0BA00

Bild 5-9 BUS 2

Bild 5-9 BUS 1

Busbar holder

Bild 5-9 BUS 3

5/12

Siemens LV 56 2008

Busbar System
Copper bars

Selection and ordering data


Dimensions
mm mm

Threading

Current
A

T
K

Length
mm

Ordering code

UI

15 5

M6

2000

8GF5751

20 5

M6

2000

8GF5737

30 5

M6

2000

8GF5742

40 5

for M10

2000

8PQ4000-0BA81

60 5

for M10

1750

8PQ4000-1BA05

80 5

for M10

2000

8PQ4000-1BA06

100 5

for M10

2000

8PQ4000-1BA07

30 10

for M10

2000

8GF5752

40 10

for M10

2000

8PQ4000-0BA24

20 5

2000

8PQ4000-0BA83

30 5

2000

8PQ4000-0BA85

40 5

2000

8PQ4000-0BA80

15 10

2000

8PQ4000-1BA04

20 10

2000

8PQ4000-0BA84

30 10

2000

8PQ4000-0BA86

40 10

2000

8PQ4000-0BA17

50 10

2000

8PQ4000-0BA18

60 10

2000

8PQ4000-0BA87

80 10

2000

8PQ4000-0BA88

100 10

2000

8PQ4000-1BA00

120 10

2000

8PQ4000-1BA01

01679

Rigid busbar, perforated, with threading

01679

Rigid busbar, perforated

01678

Rigid busbar

01680

PVC insulated flexible busbar


13 3 0,5

160

20

2000

8GF5680

13 3 0,5

160

40

2000

8GF5686

20 5 1

250

20

2000

8GF5681

16 4 0,8

250

40

2000

8GF5687

32 5 1

400

20

2000

8GF5682

24 4 1

400

40

2000

8GF5688

40 8 1

630

20

2000

8GF5683

40 5 1

630

40

2000

8GF5690

40 10 1

800

30

2000

8PQ4000-1BA03

40 10 1

1000

40

2000

8PQ4000-1BA03

40 10 1

1250

50

2000

8PQ4000-1BA03

50 10 1

1250

20

2000

8PQ4000-1BA02

30 30

1610

8PQ4000-0BA27

40 30

1610

8PQ4000-0BA26

01677

Rigid busbar, H shaped

Siemens LV 56 2008

5/13

Busbar System
Fasteners for connections
between copper busbars

Description

Configuration

To ensure a reliable connection of the copper busbars, it is


important to select quality fasteners, of the right size, suitable
and appropriately treated for the task.
The table below provides an overview of the various copper
busbars - fasteners combination options, so as to facilitate
selection and ordering.

The stated quantity of fasteners applies to a 4-pole


arrangement.
Rules for the calculation of the screw length for different busbar
dimensions:
Length of screw with M8 threading = busbars profile + 15 mm
Length of screw with M10, M12 threading = busbars profile +
20 mm

Selection and ordering data


Profile

Dimensions
mm mm

Quantity

Ordering code

Description

Profiled busbar

30 30, 40 30

Rectangular busbar

2 30 10

Rectangular busbar

2 40 10

Rectangular busbar

2 20 10, 2 40 10

Rectangular busbar

4 40 10, 4 50 10

Rectangular busbar

2 20 10, 2 30 10

4
8
12
12
4
8
8
12
12
4
8
8
12
12
12
12
12
8
8
16
16
8
8
8
2
1
1
1

8PQ9500-0BA14
8PQ9500-0BA01
8PQ9500-0BA60
8PQ9500-0BA05
8PQ9500-0BA14
8PQ9500-1BA36
8PQ9400-0BA02
8PQ9500-0BA60
8PQ9500-0BA05
8PQ9500-0BA14
8PQ9500-1BA25
8PQ9400-0BA02
8PQ9500-0BA60
8PQ9500-0BA05
8PQ9500-0BA14
8PQ9500-0BA60
8PQ9500-0BA05
8PQ9500-0BA14
8PQ9500-0BA16
8PQ9500-0BA60
8PQ9500-0BA05
8PQ9500-0BA16
8PQ9500-0BA60
8PQ9500-0BA05
8PQ9500-0BA34
8PQ9500-0BA14
8PQ9500-0BA60
8PQ9500-0BA05

DIN 603 - M10x35 non-cascaded square screw


M10x25 T-head screw
DIN 6796 10 clamping washer
Hexagonal nut ISO 4032 M10
DIN 603 - M10x35 non-cascaded square screw
DIN 603 - M10x55 non-cascaded square screw
Rail clamp
DIN 6796 - 10 clamping washer
ISO 4032 - M10 hexagonal nut
DIN 603 - M10x35 non-cascaded square screw
DIN 603 - M10x65 non-cascaded square screw
Rail clamp
DIN 6796 - 10 clamping washer
ISO 4032 - M10 hexagonal nut
DIN 603 - M10x35 non-cascaded square screw
DIN 6796 - 10 clamping washer
ISO 4032 - M10 hexagonal nut
DIN 603 - M10x35 non-cascaded square screw
DIN 603 - M10x45 non-cascaded square screw
DIN 6796 - 10 clamping washer
ISO 4032 - M10 hexagonal nut
DIN 603 - M10x45 non-cascaded square screw
DIN 6796 - 10 clamping washer
ISO 4032 - M10 hexagonal nut
DIN7500 - M6x10 self-tapping screw
DIN 603 - M10x35 non-cascaded square screw
DIN 6796 - 10 clamping washer
ISO 4032 - M10 hexagonal nut

4
8
8
12
12
4
8
8
12
12
4
8
12
12
12
12
12
16
16
16
8
8
8
16
16
16
2
1
1
1

8PQ9500-0BA16
8PQ9500-0BA01
8PQ9400-0BA02
8PQ9500-0BA60
8PQ9500-0BA05
8PQ9500-0BA16
8PQ9500-1BA36
8PQ9400-0BA02
8PQ9500-0BA60
8PQ9500-0BA05
8PQ9500-0BA16
8PQ9500-1BA25
8PQ9500-0BA60
8PQ9500-0BA05
8PQ9500-0BA16
8PQ9500-0BA60
8PQ9500-0BA05
8PQ9500-0BA16
8PQ9500-0BA60
8PQ9500-0BA05
8PQ9500-0BA16
8PQ9500-0BA60
8PQ9500-0BA05
8PQ9500-0BA16
8PQ9500-0BA60
8PQ9500-0BA05
8PQ9500-0BA34
8PQ9500-0BA16
8PQ9500-0BA60
8PQ9500-0BA05

DIN 603 - M10x45 non-cascaded square screw


M10x25 T-head screw
Rail clamp
DIN 6796 10 clamping washer
Hexagonal nut ISO 4032 M10
DIN 603 - M10x45 non-cascaded square screw
DIN 603 - M10x55 non-cascaded square screw
Rail clamp
DIN 6796 - 10 clamping washer
ISO 4032 - M10 hexagonal nut
DIN 603 - M10x45 non-cascaded square screw
DIN 603 - M10x65 non-cascaded square screw
DIN 6796 - 10 clamping washer
ISO 4032 - M10 hexagonal nut
DIN 603 - M10x45 non-cascaded square screw
DIN 6796 - 10 clamping washer
ISO 4032 - M10 hexagonal nut
DIN 603 - M10x45 non-cascaded square screw
DIN 6796 - 10 clamping washer
ISO 4032 - M10 hexagonal nut
DIN 603 - M10x45 non-cascaded square screw
DIN 6796 - 10 clamping washer
ISO 4032 - M10 hexagonal nut
DIN 603 - M10x45 non-cascaded square screw
DIN 6796 - 10 clamping washer
ISO 4032 - M10 hexagonal nut
DIN7500 - M6x10 self-tapping screw
DIN 603 - M10x45 non-cascaded square screw
DIN 6796 - 10 clamping washer
ISO 4032 - M10 hexagonal nut

Main busbar systems with 2 bars per phase


Connection from
main busbars to:

Cascaded vertical
busbars

5
Non-cascaded
vertical busbars

Connection between cubicle and


main busbars

L1...3, N (PEN)

Connection between main busbar PEN ands


cubicle

PEN (per cubicle)

Main busbar systems with 4 bars per phase


Connection from
main busbars to:

Cascaded vertical
busbars

Non-cascaded
vertical busbars

Connection between cubicle and


main busbars

Connection between main busbar PEN and


cubicle

5/14

L1...3, N (PEN)

Profiled busbar

30 30, 40 30

Rectangular busbar

2 30 10

Rectangular busbar

2 40 10

Rectangular busbar

2 20 10, 2 40 10

Rectangular busbar

4 40 10, 4 50 10

Rectangular busbar

4 20 10, 4 30 10

Rectangular busbar

4 40 10, 4 50 10

PEN (per cubicle)

Siemens LV 56 2008

Assembly Kits for Switching


Devices

6/2

General Data

6/3

Assembly kit for


SENTRON 3WL circuit
breakers

6/9

Assembly kit for


SENTRON 3VL moulded case
circuit breakers

6/20

Assembly kit for


SENTRON 3VT moulded case
circuit breakers

6/23

Assembly kit for


SENTRON 3K disconnectors

6/26

Assembly kit for in-line fuse


switch disconnectors
SENTRON 3NJ4

6/29

Assembly kit for in-line fuse


switch disconnectors
SENTRON 3NJ6

6/32

Assembly kit for modular


installation devices

Siemens LV 56 2008

Assembly Kits for Switching Devices


General Data

Overview

6
1
2

4
1 Assembly kit for SENTRON 3WL
circuit breakers
2 DIN rail for BETA modular devices
01694

3 Assembly kit for SENTRON 3VL


case circuit breakers, horizontal intallation
4 Assembly kit for SENTRON 3VL
case circuit breakers, vertical installation

6/2

Siemens LV 56 2008

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3WL
circuit breakers

Overview

9
1
11
21

25

19

10

18

22
23

12

6
24

20

13
17

15
14

16

1 Fixed part for draw-out version

14 Emergency stop button, locking key

2 Front attachments, flanged, horizontal, vertical

15 Motorised mechanism

3 Switch position indicator contacts

16 Operation counter

4 Grounding contact

17 Breaker Status Sensor (BSS)

5 Protective louvers

18 Electronic overcurrent release (ETU)

6 PROFIBUS COM 15 communication module

19 Reset solenoid

7 CubicleBUS external modules

20 BDA (Breaker Data Adapter) module

8 Auxiliary disconnectors, closing solenoid

21 4-line LCD display

9 Connector system for auxiliary units

22 Earth fault protection module

10 Auxiliary contact modules

23 Rating Plug

11 Front frame

24 Measuring function module

12 Support for locking devices

25 SENTRON WL circuit breaker

13 Clear cover

Siemens LV 56 2008

6/3

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3WL
circuit breakers

Technical specifications
Switching capacity
Size

Type

3WL11

II

Switching capacity class

3WL12
S

Rated operating voltage Ue


up to AC 415 V
Icu

kA

55

66

66

80

100

Ics

kA

55

66

66

80

100

Icm

kA

121

145

145

176

220

Icu

kA

55

66

66

80

100

Ics

kA

55

66

66

80

100

Icm

kA

112

145

145

176

220

Icu

kA

42

50

50

75

85

Ics

kA

42

50

50

75

85

Icm

kA

88

105

105

165

187

Rated operating voltage Ue


up to AC 500 V

Rated operating voltage Ue


up to AC 690 V

Rated operating voltage Ue


up to AC 1000 V

Icu

kA

45

Ics

kA

45

Icm

kA

95

Rated short-time current Icw of circuit breaker


Size

Type

3WL11

Switching capacity class

II
3WL12
N

0,5 s

kA

50

66

66

80

100

1s

kA

42

50

55

66

80

2s

kA

29,5

35

39

46

501)/562)

3s

kA

24

29

32

37

401)/502)

Rated short-circuit current Icc of circuit breaker


Size

Type

3WL11

II

Switching capacity class

3WL12
N

up to AC 500 V

kA

50

66

66

80

100

up to AC 690 V

kA

42

50

50

75

85

1) Size II with In max 2500 A.


2) Size II with In max 3200 A.

Size

Type

up to
3WL11 12 3WL11 16 3WL12 08 3WL12 10 3WL12 12 3WL12 16 3WL12 20 3WL12 25 3WL12 32
3WL11 10

Minimum
phase size

II

Busbars, Cu,

piece

bare

mm2

60 10

40 10

50 10

50 10

60 10

40 10

50 10

50 10

100 10

100 10

Busbars, Cu

piece

insulated, black

mm2

60 10

40 10

50 10

50 10

60 10

40 10

50 10

50 10

100 10

100 10

For further information, see the technical documents on SENTRON 3WL

6/4

II

Siemens LV 56 2008

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3WL
circuit breakers

Description

Configuration

The assembly kit for SENTRON 3WL circuit breakers is made up of:
Mounting plate
Crossbars
Cover with cut-out and fast closing screws (designed for the
installation of the Sentron 3WL with cover frame)
Separation partition
Fasteners

The assembly kits for Sentron 3WL circuit breakers are suitable
for currents of up to 3200 A.

The horizontal plate is suitable for the installation of circuit


breakers, in fixed and draw out versions of different sizes.
Horizontal separation ensures the required arcing spaces.

The cover has a cut-out to fit the relative frame 3WL 91110AP01-0AA0.

The Sentron 3WL 1240 circuit breaker can be installed only in


800mm deep cubicles.
The assembly kit for Sentron 3WL circuit breakers can be
installed only in 600mm and 800mm deep cubicles.

Selection and ordering data


No. of poles

Width
mm

Module height
mm

Mounting plate
SENTRON 3WL

Cover
SENTRON 3WL

02051

02050

Size

Assembly kit for Sentron 3WL, in fixed and draw out versions
BG I, BG II

600

550

8PQ6000-3BA31

8PQ2055-6BA05

BG I

600

550

8PQ6000-3BA31

8PQ2055-6BA07

BG I

3/4

800

550

8PQ6000-3BA32

8PQ2055-8BA04

BG II

800

550

8PQ6000-3BA32

8PQ2055-8BA07

BG II

800

550

8PQ6000-3BA32

8PQ2055-8BA05

Description

Configuration

The support kit consists of a strip in fibreglass reinforced plastic


sized 25x25mm and the relative fasteners to secure it to the
cubicle or to the side upright.

The distance between the circuit breaker terminal bar and the
support and the distance between two supports is 100mm.

Selection and ordering data


No. of poles

Width
mm

Support
Ordering code

UI

02057

Size

Support for Sentron 3WL, in fixed and draw out versions


BG I

3/4

600

8PQ6000-4BA35

BG II

600

8PQ6000-4BA36

BG I

3/4

800

8PQ6000-4BA37

BG II

3/4

800

8PQ6000-4BA38

Siemens LV 56 2008

6/5

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3WL
circuit breakers

Description

Configuration

The support kit is made up of crossbars, corner pieces and the


fasteners to secure the support to the structure or the side
upright.

For the arrangement of supports in standard position in the


SIVACON S4 system, see chapter 11 Dimensions.
The connection of distribution busbars is not included in the kit.
The busbars must be mounted by the board installation
technician.

Selection and ordering data


No. of poles

Width
mm

Support
Ordering code

UI

NSE0_02058

Size

Support for busbar connection kit for Sentron 3WL, in fixed and draw out versions
BG I

3,4

600

8PQ3000-1BA70

BG II

600

8PQ3000-1BA70

BG I, BG II

3,4

800

8PQ3000-1BA71

02211

Support busway connection SIVACON 8PS

6/6

Siemens LV 56 2008

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3WL
circuit breakers

Description

Configuration

The connections to SIVACON 8PS busways are optimised for the


connection of Sentron 3WL circuit breakers in the SIVACON S4
system.

It is important to select the correct combination of circuit breaker,


busway connection and busway.

Selection and ordering data


Sentron 3WL
GR I

Sentron 3WL
GR II

Sentron 3WL
GR I

Sentron 3WL
GR II

Busway
connection
Ordering code

Conductor
configuration

Suitable for
busways
In [A]

Suitable for
busways
In [A]

Suitable for
busways
In [A]

BVP:660299

100% PEN

LDA3423(5)-...
1600

LDA2423(5)-...
1250

LDA1423(5)-...
1100

BVP:660300

100% N

LDA3623(5)-...
1600

LDA2623(5)-...
1250

LDA1623(5)-...
1100

BVP:660301

100% PEN

LDA4423(5)-...
2000

BVP:660302

100% N

LDA2623(5)-...
2000

BVP:660303

100% PEN

LDA3423(5)-...
2600

LDA2423(5)-...
2000

BVP:660304

100% N

LDA3623(5)-...
2600

LDA2623(5)-...
2000

BVP:660305

50% PEN

LDA6413(5)-...
3000

LDA5413(5)-...
2500

LDA4413(5)-...
2000

BVP:660306

100% PEN

LDA6423(5)-...
3000

LDA5423(5)-...
2500

LDA4423(5)-...
2000

BVP:660307

50% N

50% PE

LDA6613(5)-...
3000

LDA5613(5)-...
2500

LDA4613(5)-...
2000

BVP:660308

100% N

50% PE

LDA6623(5)-...
3000

LDA5623(5)-...
2500

LDA4623(5)-...
2000

BVP:660309

50% PEN

LDA6413(5)-...
3400

BVP:660310

100% PEN

LDA6423(5)-...
3400

BVP:660311

50% N

50% PE

LDA6613(5)-...
3400

BVP:660312

100% N

50% PE

LDA6623(5)-...
3400

Busway
connection
Ordering code

Conductor
configuration

Suitable for
busways
In [A]

Suitable for
busways
In [A]

Suitable for
busways
In [A]

Suitable for
busways
In [A]

Suitable for
busways
In [A]

BVP:660321

100% PEN

LXC0341-... 1400

LXC0141-... 1000

LXA0141-... 800

BVP:660322

100% N

LXC0351-... 1400

LXC0151-... 1000

LXA0151-... 800

BVP:660323

100% PEN

LXA0541-... 1600

LXC0441-... 1600

LXA0441-... 1250

LXC0241-... 1250

LXA0241-... 1000

BVP:660324

100% N

BVP:660325

100% PEN

BVP:660326

100% N

BVP:660327

100% PEN

BVP:660328

100% N

BVP:660329

100% PEN

BVP:660330

100% N

BVP:660331

100% PEN

BVP:660332

100% N

BVP:660333

100% PEN

BVP:660334

100% N

100% PE

100% PE

100% PE

100% PE
100% PE
100% PE
100% PE
100% PE
100% PE
100% PE

LXA0551-... 1600

LXC0451-... 1600

LXA0451-... 1250

LXC0251-... 1250

LXA0251-... 1000

LXA0641-... 2000

LXC0541-... 2000

LXA0651-... 2000

LXC0551-... 2000

LXC0641-... 2500

LXC0651-... 2500

LXA0741-... 2500

LXA0751-... 2500

LXC0741-... 3200

LXC0751-... 3200

LXA0841-... 3200

LXA0851-... 3200

Siemens LV 56 2008

6/7

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3WL
circuit breakers

Description

Configuration

The prefabricated Cu busbar kit for Sentron 3WL circuit breakers


is made up of:
Crossbars
Support
Reinforcement
Copper busbars
Protective isolation shield
Fasteners

The Cu connecting busbar kit for Sentron 3WL circuit breakers


going to the cable connection system occupies the heights of
the module specified above or below the circuit breaker.

With the cable entry variants and connection to the vertical


distribution busbars variants, the system offers connection kits
type tested in terms of CT mounting and number of connection
points, in cascaded form, for the respective circuit breaker rated
currents. Through the combination of variants it is possible to
achieve functions such as incomer, outgoing and coupler.

Construction of connecting busbars for Sentron 3WL circuit


breakers with flanged terminal bars for draw out versions.

To be able to anchor, bend and connect the cables it is


necessary to leave enough space for the assembly operations.
Construction of connecting busbars for Sentron 3WL circuit
breakers with horizontal rear terminal bars for fixed versions.

Selection and ordering data


Module height
Size

Current

No. of
poles

Version

Width
mm

above the breaker


mm

below the breaker


mm

Ordering code

UI

300
300
300
300
350
350
350
350

8PQ6000-0BA34
8PQ6000-0BA33
8PQ6000-2BA45
8PQ6000-2BA44
8PQ6000-0BA41
8PQ6000-0BA40
8PQ6000-0BA47
8PQ6000-0BA46

1
1
1
1
1
1
1
1

250
250
250
250
400
400
400
400

8PQ6000-0BA52
8PQ6000-0BA51
8PQ6000-2BA47
8PQ6000-2BA46
8PQ6000-0BA58
8PQ6000-0BA57
8PQ6000-0BA65
8PQ6000-0BA64

1
1
1
1
1
1
1
1

Kit of prefabricated busbars for Sentron 3WL for connection to the vertical bars, cascaded
1600A
1600A
1600A
1600A
2000A
2000A
3200A
3200A

3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4

Fixed
Draw out
Fixed
Draw out
Fixed
Draw out
Fixed
Draw out

600
600
800
800
800
800
800
800

250
250
250
250
300
300
300
300

Kit of prefabricated busbars for Sentron 3WL for connection to the connecting cables
1600A
1600A
1600A
1600A
2000A
2000A
3200A
3200A

3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4

Fixed
Draw out
Fixed
Draw out
Fixed
Draw out
Fixed
Draw out

600
600
800
800
800
800
800
800

200
200
200
200
350
350
350
350

02055

BG I
BG I
BG I
BG I
BG II
BG II
BG II
BG II

02054

BG I
BG I
BG I
BG I
BG II
BG II
BG II
BG II

Sentron 3WL with horizontal rear terminal bars, for fixed version

6/8

Siemens LV 56 2008

Sentron 3WL with flanges, for draw out version

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3VL
moulded case circuit breakers

Overview
9

10

11

10

14

12

21

15

20
18

17

16

13
4

19

8
9

1 Fixed part for plugin version

12 Direct rotary operating mechanism

2 Side panels for draw out version

13 Door locking rotary operating mechanism

3 Phase separators

14 SENTRON VL circuit breaker

4 Front terminal bars, divergent

15 Internal accessories

5 Front terminal bars, straight

16 Electronic overcurrent release

6 Terminals for Al/Cu cables

17 Thermal/magnetic overcurrent release

7 Terminals for copper cables and busbars

18 DI module - RCD

8 Terminal cover, extended

19 Rear connections - flat and round

9 Terminal cover, standard

20 COM 10 PROFIBUS-DP communication module

10 Front frame

21 Handheld testing device

11 Motorised operating mechanism


with spring accumulator

Siemens LV 56 2008

6/9

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3VL
moulded case circuit breakers

Technical specifications
VL 160X
3VL1

Type

VL 160
3VL2

VL 250
3VL3

VL 400
3VL4

VL 630
3VL5

VL 800
3VL6

VL 1250
3VL7

VL 1600
3VL8

Connection dimensions and types for main circuits


Box terminals
mm2

2,5-95

2,5-95

25-185

50-300

Flexible wire with sleeve connector

mm2

2,5-50

2,5-50

25-120

50-240

Busbar

mm

12 10

12 10

17 10

25 10

Clamp for flexible bar

mm

2 pieces
6 32

mm2

16-70

16-70

25-185

50-300

mm2

10-50

10-50

25-120

50-240

mm2

2 pieces
50-120

2 pieces
50-240

3 pieces
50-240

4 pieces
50-240

mm2

2 pieces
50-95

2 pieces
50-185

3 pieces
50-185

4 pieces
50-185

mm

17 7

22 7

24 7

32 10

40 10

2 40 10 2 50 10 3 60 10

M5

M5

M8

M8

M6

M8

Single- or multi-wire cable

only copper

Power supply terminals with multiple


cables
Single- or multi-wire cable

copper or Al

Flexible wire with sleeve connector


Multiple feed-in terminal
Power supply terminals for cables

copper or Al

Flexible wire with end terminal


Direct busbar connection
Screw type for screwed connection

6/10

Siemens LV 56 2008

copper or Al

M8

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3VL moulded
case circuit breaker, horizontal installation

Description

Configuration

The equipment support assembly kit contains a deep mounting


plate for front and rear terminal bars and fastening crossbars.
For installation on the front frame, choice of covers includes
versions suitable for direct, motorised and rotary front operating
mechanisms. The covers are secured to the front frame by means
of fast closing screws (1/4 of a turn).
Hinges to be fitted to the individual covers are available as an
option.
The Link-N kit includes support, cover and fasteners. In the 3and 4-pole moulded case circuit breaker combination this kit
provides the internal separation for a branch unit.

For horizontal installation and front connections, extended


terminal covers have to be ordered.
A combination of front frame and covers with modular doors in a
cubicle is not possible.

Selection and ordering data


Cover with cut-out for
type of op. mechanism

Height
mm

Width
mm

Depth1 Max no.


of circuit
mm
breakers

Link-N support

Equipment
mounting plate

Cover

02059

02060

No. Connection
of
poles

02064

Circuit
breaker

Sentron 3VL moulded case circuit breakers, fixed, horizontal installation


VL 160X
VL 160X
VL 160/250
VL 160/250
VL 400
VL 400
VL 630
VL 630
VL 800
VL 800

3
4
3
4
3
4
3
4
3
4

front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
rear
rear

Direct, mot. rotary front mech.


Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.

150
200
150
200
200
250
300
350
300
350

600
600
600
600
600
600
600
600
600
600

Description

400
400
400
400
400
400
400
400
400
400

1
1
1
1
1
1
1
1
1
1

8PQ6000-3BA52
8PQ6000-3BA52
8PQ6000-3BA53
8PQ6000-3BA54

8PQ6000-2BA74
8PQ6000-2BA80
8PQ6000-3BA13
8PQ6000-3BA18
8PQ6000-2BA84
8PQ6000-2BA87
8PQ6000-3BA01
8PQ6000-3BA10
8PQ6000-3BA08
8PQ6000-4BA16

8PQ2015-6BA03
8PQ2020-6BA04
8PQ2015-6BA03
8PQ2020-6BA04
8PQ2020-6BA06
8PQ2025-6BA02
8PQ2030-6BA03
8PQ2035-6BA04
8PQ2030-6BA02
8PQ2035-6BA05

Configuration

The prefabricated Cu busbar kit for Sentron 3VL moulded case


circuit breakers for horizontal installation is made up of:
Crossbars
Support
Plastic reinforcement
Copper busbars
Protective isolation shield
Fastening screws
With the cable entry variants and connection to the vertical
distribution busbars variants, the system offers connection kits
type-tested in terms of CT mounting and number of connection
points to the busbars, in cascaded form, for the respective
circuit breaker rated currents.

The height of the connecting busbars kit matches the type of


circuit breaker.
The connecting busbar kit is suitable for branch units without
differential module.
In addition to the copper busbars and the cover, the connecting
busbar kit for Sentron VL circuit breakers for connection to the
cables contains lateral partitions with connecting terminals.
When fitting connecting busbar kit for Sentron VL circuit breakers
for connection to the cascaded vertical busbars in a 600 mm
cubicle, the vertical distribution busbar system must be housed in
the same cubicle (800 mm cubicle with riser compartment 600 +
200 mm).

Selection and ordering data


Circuit
breaker

No. of
poles

Version

Ad hoc covers for type


of op. mech.

Max. no. of
switches

Height of module
mm

Width
mm

Ordering code

UI

01652

Kit of connecting bars for Sentron 3VL for connection to cascaded vertical distribution bars
VL 250

fixed

direct

150

600

8PQ6000-1BA63

VL 250

fixed

direct

200

600

8PQ6000-1BA64

VL 400

fixed

direct

200

600

8PQ6000-1BA65

VL 400

fixed

direct

250

600

8PQ6000-1BA66

VL 630

fixed

direct

300

600

8PQ6000-1BA67

VL 630

fixed

direct

350

600

8PQ6000-1BA68

1
1

01653

Kit of connecting bars for Sentron 3VL for connection to the cables

VL 250

fixed

direct

150

600

8PQ6000-1BA70

VL 250

fixed

direct

200

600

8PQ6000-1BA71

VL 400

fixed

direct

200

600

8PQ6000-1BA72

VL 400

fixed

direct

250

600

8PQ6000-1BA73

VL 630

fixed

direct

300

600

8PQ6000-1BA74

VL 630

fixed

direct

350

600

8PQ6000-1BA75

minimum depth

Siemens LV 56 2008

6/11

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3VL moulded
case circuit breaker, for horizontal installation

Description

Configuration

The equipment support assembly kit contains a deep mounting


plate for front and rear terminal bars and fastening crossbars.

For horizontal installation and front connections, extended


terminal covers have to be ordered.

For installation on the front frame, choice of covers includes


versions suitable for direct, motorised and rotary front operating
mechanisms. The covers are secured to the front frame by means
of fast closing screws (1/4 of a turn).

To improve the stability of the kits for VL 400 and 630 in plug-in
version it is necessary to fit a reinforcement kit for each branch
unit.

Hinges to be fitted to the individual covers are available as an


option.

A combination of front frame and covers with modular doors in a


cubicle is not possible.

The Link-N kit includes support, cover and fasteners. In the 3and 4-pole moulded case circuit breaker combination this kit
provides for the internal separation for a branch unit.

Selection and ordering data


Height of Width Depth
module
mm mm
mm

Max. no. N-Link support


of circuit
breakers

Equipment
mounting plate

Cover

02060

Ad hoc cover for type of


op. mech.

02059

No. Connecof
tion
poles

02064

Circuit
breaker

Sentron 3VL moulded case circuit breakers, plug-in, for horizontal installation
VL 160X
VL 160X
VL 160/250
VL 160/250
VL 400
VL 400
VL 400
VL 400
VL 630
VL 630
VL 630
VL 630

3
4
3
4
3
3
4
4
3
3
4
4

front, rear
front, rear
front, rear
front, rear
front
rear
front
rear
front
rear
front
rear

Direct, mot. rotary front mech.


Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.

Minimum depth

6/12

Siemens LV 56 2008

150
200
150
200
200
200
250
250
300
300
350
350

600
600
600
600
600
600
600
600
600
600
600
600

400
400
400
400
400
600/800
400
600/800
400
600/800
400
600/800

1
1
1
1
1
1

8PQ6000-3BA52
8PQ6000-3BA52

8PQ6000-3BA53
8PQ6000-3BA53
1
1
1
1

8PQ6000-3BA54
8PQ6000-3BA54

8PQ6000-3BA24
8PQ6000-3BA27
8PQ6000-3BA24
8PQ6000-3BA27
8PQ6000-2BA84
8PQ6000-2BA84
8PQ6000-2BA87
8PQ6000-2BA87
8PQ6000-3BA01
8PQ6000-3BA01
8PQ6000-3BA10
8PQ6000-3BA10

8PQ2015-6BA03
8PQ2020-6BA04
8PQ2015-6BA03
8PQ2020-6BA04
8PQ2020-6BA06
8PQ2020-6BA06
8PQ2025-6BA02
8PQ2025-6BA02
8PQ2030-6BA03
8PQ2030-6BA03
8PQ2035-6BA04
8PQ2035-6BA04

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3VL moulded
case circuit breaker, for horizontal installation

Description

Configuration

The equipment support assembly kit contains a deep mounting


plate for front and rear terminal bars and fastening crossbars.
For installation on the front frame, choice of covers includes
versions suitable for direct, motorised and rotary front operating
mechanisms. The covers are secured to the front frame by means
of fast closing screws (1/4 of a turn).
Hinges to be fitted to the individual covers are available as an
option.
The Link-N kit includes support, cover and fasteners. In the 3and 4-pole moulded case circuit breaker combination this kit
provides for the internal separation for a branch unit.

For horizontal installation and front connections, extended


terminal covers have to be ordered.
A combination of front frame and covers with modular doors in a
cubicle is not possible.

Selection and ordering data


Ad hoc cover for type of op.
mech.

Height of Width Depth1 Max. no.


module
mm mm
of circuit
mm
breakers

Equipment
mounting plate

Cover

02140

No. of Connecpoles tion

02059

Circuit
breaker

Sentron 3VL moulded case circuit breaker, draw out, for horizontal installation
front, rear
front, rear
front, rear
front, rear

3/4
3/4
3
4

Circuit
breaker

No. of Connecpoles tion

Direct, mot. rotary front mech.


Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.

250
300
300
350

Ad hoc cover for type of op.


mech.

Height of Width Depth1 Max. no.


module
mm mm
of circuit
mm
breakers

600
600
600
600

400
400
400
400

1
1
1
1

8PQ6000-3BA27
8PQ6000-2BA87
8PQ6000-3BA01
8PQ6000-3BA10

8PQ2020-6BA21
8PQ2025-6BA11
8PQ2030-6BA17
8PQ2035-6BA17
Reinforcement

02139

VL 160/250
VL 400
VL 630
VL 630

Reinforcement per Sentron 3VL circuit breaker kit, draw out, horizontal installation

Circuit
breaker

No. of Connecpoles tion

Ad hoc cover for type of


op. mech.

400
400
400

1
1
1

8PQ6000-4BA17
8PQ6000-4BA20
8PQ6000-4BA18

Height of Width Depth1 Max. no. N-Link


module
mm mm
of circuit
mm
breakers

Equipment
mounting plate

Cover

02063

600
600
600

02062

3/4
3
4

02064

VL 400
VL 630
VL 630

Sentron 3VL compact moulded case circuit breaker with RCD, with fixed mounting technology,
mounted horizontally

No. of Connecpoles tion

Direct, mot. rotary front mech.


Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Ad hoc cover for type of op.
mech.

150
200
150
200

600
600
600
600

400
400
400
400

1
1
1
1

8PQ6000-3BA52
8PQ6000-3BA52

Height of Width Depth1 Max. no. N-Link


module
mm mm
of circuit
mm
breakers

8PQ6000-2BA73
8PQ6000-2BA78
8PQ6000-3BA14
8PQ6000-3BA20

8PQ2015-6BA05
8PQ2020-6BA08
8PQ2015-6BA04
8PQ2020-6BA05

Equipment
mounting plate

Cover

02063

front, rear
front, rear
front
rear

02064

Circuit
breaker

3
4
3
4

02062

VL 160X
VL 160X
VL 160/250
VL 160/250

Sentron 3VL compact moulded case circuit breaker, with plug-in technology, mounted
horizontally
VL 160X
VL 160X
VL 160/250
VL 160/250
1

Minimum depth

3
4
3
4

front, rear
front, rear
fron
rear

Direct, mot. rotary front mech.


Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.

150
200
150
200

600
600
600
600

400
400
400
400

1
1
1
1

8PQ6000-3BA52
8PQ6000-3BA52

8PQ6000-2BA75
8PQ6000-2BA81
8PQ6000-2BA75
8PQ6000-2BA81

8PQ2015-6BA06
8PQ2020-6BA07
8PQ2015-6BA04
8PQ2020-6BA05

Siemens LV 56 2008

6/13

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3VL moulded
case circuit breaker, for horizontal installation

Description

Configuration

The equipment support assembly kit contains a deep mounting


plate for front and rear terminal bars and fastening crossbars.

For horizontal installation and front connections, extended


terminal covers have to be ordered.

The modular doors kit with degree of protection IP4X with holes for
the 8UC door locking mechanism contains a door, hinges,
individual cover and fasteners.

A combination of front frame and covers with modular doors in a


cubicle is not possible.

The Link-N kit includes support, cover and fasteners. In the 3and 4-pole moulded case circuit breaker combination this kit
provides for the internal separation for a branch unit.

For a degree of protection IP55 an upgrade to IP55 is available


(see chapter 7, modular doors).
a Due to the length of the operating mechanism, an height 50mm
module above the assembly kit should be provided for at the
design stage.

Selection and ordering data


Height of Width Depth1
module
mm mm
mm

Max. no. N-Link support


of circuit
breakers

Equipment
mounting plate

Modular door

02061

Ad hoc cover for type of


op. mech.

02059

No. of Connecpoles tion

02064

Circuit
breaker

Sentron 3VL moulded case circuit breaker, fixed, for horizontal installation
VL 160X
VL 160X
VL 160/250
VL 160/250
VL 400
VL 400
VL 630
VL 630
VL 800
VL 800

3
4
3
4
a 3
4
3
4
3
4

front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
rear
rear

8UC-door locking mech., Gr. 2


8UC-door locking mech., Gr. 2
8UC-door locking mech., Gr. 2
8UC-door locking mech., Gr. 2
8UC-door locking mech., Gr. 2
8UC-door locking mech., Gr. 3
8UC-door locking mech., Gr. 3
8UC-door locking mech., Gr. 3
8UC-door locking mech., Gr. 3
8UC-door locking mech., Gr. 3

150
200
150
200
200
250
300
350
300
350

Ad hoc cover for type of


op. mech.

Height of Width Depth1


module
mm mm
mm

600
600
600
600
600
600
600
600
600
600

400
400
400
400
400
400
400
400
400
400

1
1
1
1
1
1
1
1
1
1

8PQ6000-3BA52
8PQ6000-3BA52
8PQ6000-3BA53
8PQ6000-3BA54

8PQ6000-2BA74
8PQ6000-2BA80
8PQ6000-3BA13
8PQ6000-3BA18
8PQ6000-2BA84
8PQ6000-2BA87
8PQ6000-3BA01
8PQ6000-3BA10
8PQ6000-3BA08
8PQ6000-4BA16

8PQ2015-6BA14
8PQ2020-6BA16
8PQ2015-6BA14
8PQ2020-6BA16
8PQ2020-6BA20
8PQ2025-6BA10
8PQ2030-6BA15
8PQ2035-6BA15
8PQ2030-6BA16
8PQ2035-6BA16

Equipment
mounting plate

Modular door

Max. no. N-Link support


of circuit
breakers

02061

No. of Connecpoles tion

02064

Circuit
breaker

02059

Selection and ordering data

Sentron 3VL moulded case circuit breaker, plug-in, for horizontal installation
VL 160X
VL 160X
VL 160/250
VL 160/250
VL 400
VL 400
VL 630
VL 630

3
4
3
4
a 3
4
3
4

front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear

8UC-door locking mech., Gr. 2


8UC-door locking mech., Gr. 2
8UC-door locking mech., Gr. 2
8UC-door locking mech., Gr. 2
8UC-door locking mech., Gr. 3
8UC-door locking mech., Gr. 3
8UC-door locking mech., Gr. 3
8UC-door locking mech., Gr. 3

Minimum depth

6/14

Siemens LV 56 2008

150
200
150
200
200
250
300
350

600
600
600
600
600
600
600
600

400
400
400
400
400
400
400
400

1
1
1
1
1
1
1
1

8PQ6000-3BA52
8PQ6000-3BA52
8PQ6000-3BA53
8PQ6000-3BA54

8PQ6000-3BA24
8PQ6000-3BA27
8PQ6000-3BA24
8PQ6000-3BA27
8PQ6000-2BA84
8PQ6000-2BA87
8PQ6000-3BA01
8PQ6000-3BA10

8PQ2015-6BA14
8PQ2020-6BA16
8PQ2015-6BA14
8PQ2020-6BA16
8PQ2020-6BA20
8PQ2025-6BA10
8PQ2030-6BA15
8PQ2035-6BA15

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3VL moulded
case circuit breaker, for horizontal installation

Description

Configuration

The equipment support assembly kit contains a deep mounting


plate for front and rear terminal bars and fastening crossbars.

For horizontal installation and front connections, extended


terminal covers have to be ordered.

The modular doors kit with degree of protection IP4X with holes for
the 8UC door locking mechanism contains a door, hinges,
individual cover and fasteners.

A combination of front frame and covers with modular doors in a


cubicle is not possible.

The Link-N kit includes support, cover and fasteners. In the 3and 4-pole moulded case circuit breaker combination this kit
provides for the internal separation for a branch unit.

For a degree of protection IP55 an upgrade to IP55 is available


(see chapter 7, modular doors).

Selection and ordering data


Height of Width Depth1
module
mm mm
mm

Max. no. N-Link support


of circuit
breakers

Equipment
mounting plate

Modular door

02061

Ad hoc cover for type of


op. mech.

02062

No. of Connecpoles tion

02064

Circuit
breaker

Sentron 3VL moulded case circuit breaker with differential module, fixed, for horizontal
installation
VL 160/250
VL 160/250

3
4

front, rear
front, rear

8UC-door locking mech., Gr. 2


8UC-door locking mech., Gr. 2

150
200

Ad hoc cover for type of


op. mech.

Height of Width Depth1


module
mm mm
mm

600
600

400
400

1
1

8PQ6000-3BA52

8PQ6000-3BA14
8PQ6000-3BA20

8PQ2015-6BA16
8PQ2020-6BA17

Equipment
mounting plate

Modular door

Max. no. N-Link support


of circuit
breakers

02061

No. of Connecpoles tion

02064

Circuit
breaker

02062

Selection and ordering data

Sentron 3VL moulded case circuit breaker with differential module, plug-in,
for horizontal installation
VL 160/250
VL 160/250

Minimum depth

3
4

front, rear
front, rear

8UC-door locking mech., Gr. 2


8UC-door locking mech., Gr. 2

150
200

600
600

400
400

1
1

8PQ6000-3BA52

8PQ6000-2BA75
8PQ6000-2BA81

8PQ2015-6BA16
8PQ2020-6BA17

Siemens LV 56 2008

6/15

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3VL moulded
case circuit breaker, for vertical installation

Description

Configuration

The equipment support assembly kit contains a deep mounting


plate for front and rear terminal bars and fastening crossbars.

Shielding is provided for the motorised operating mechanism with


spring accumulator.

For installation on the front frame, choice of covers includes


versions suitable for direct, motorised and rotary front operating
mechanism. The covers are secured to the front frame by means
of fast closing screws (1/4 of a turn).

For circuit breaker, base or rack and motorised operating


mechanism combinations, take into due account the indications
given in the dimensional drawings 11/15.

Hinges to be fitted to the individual covers are available as an


option.

b For front terminal bars, two additional covers, height 100mm


each, are required. Moreover, extended terminal covers have
to be ordered for the respective circuit breaker.

The Link-N kit includes support, cover and fasteners. In the 3and 4-pole moulded case circuit breaker combination this kit
provides for the internal separation for a branch unit.

Selection and ordering data


Height of Width Depth1
module
mm mm
mm

Max. no. N-Link support


of circuit
breakers

Equipment
mounting plate

Cover

02066

Ad hoc cover for type of


op. mech.

02065

No. of Connecpoles tion

02070

Circuit
breaker

Sentron 3VL moulded case circuit breaker, fixed, for vertical installation
VL 160X
VL 160X
VL 160/250
VL 160/250
VL 400
VL 400
VL 630
VL 630
VL 160X
VL 160X
VL 160/250
VL 160/250
VL 400
VL 400
VL 630
VL 630

b
b
b
b

b
b
b
b

3
4
3
4
3
4
3/4
3
3
4
3
4
3
4
3
4

front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear

Direct, mot. rotary front mech.


Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.

350
350
350
350
400
400
400
400
350
350
350
350
400
400
400
400

Ad hoc cover for type of


op. mech.

Height of Width Depth1


module
mm mm
mm

600
600
600
600
600
600
600
600
800
800
800
800
800
800
800
800

400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400

1-4
1-3
1-4
1-3
1-3
1-2
1
1-2
1-5
1-4
1-5
1-4
1-4
1-3
1-3
1-2

8PQ6000-3BA54

8PQ6000-2BA76
8PQ6000-2BA82
8PQ6000-3BA16
8PQ6000-3BA22
8PQ6000-2BA85
8PQ6000-2BA88
8PQ6000-3BA05
8PQ6000-3BA02
8PQ6000-2BA77
8PQ6000-2BA83
8PQ6000-3BA17
8PQ6000-3BA23
8PQ6000-2BA86
8PQ6000-3BA00
8PQ6000-3BA03
8PQ6000-3BA06

8PQ2035-6BA02
8PQ2035-6BA03
8PQ2035-6BA02
8PQ2035-6BA03
8PQ2040-6BA07
8PQ2040-6BA05
8PQ2040-6BA08
8PQ2040-6BA06
8PQ2035-8BA02
8PQ2035-8BA03
8PQ2035-8BA02
8PQ2035-8BA03
8PQ2040-8BA08
8PQ2040-8BA07
8PQ2040-8BA06
8PQ2040-8BA05

Equipment
mounting plate

Cover

Max. no. N-Link support


of circuit
breakers

02066

No. of Connecpoles tion

02070

Circuit
breaker

02141

Selection and ordering data

Sentron 3VL moulded case circuit breaker, fixed, for vertical installation
VL 800
VL 1250
VL 1600

b 3/4
b 3/4
b 3/4

front, rear
front, rear
front, rear

Direct, mot. rotary front mech. 600


Direct, mot. rotary front mech. 600
Direct, mot. rotary front mech. 700

Minimum depth

6/16

Siemens LV 56 2008

600
600
600

400
400
400

1
1
1

8PQ6000-3BA55
8PQ6000-3BA56
8PQ6000-3BA56

8PQ6000-3BA07
8PQ6000-3BA11
8PQ6000-3BA12

8PQ2060-6BA02
8PQ2060-6BA03
8PQ2070-6BA01

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3VL moulded
case circuit breaker, for vertical installation

Description

Configuration

The equipment support assembly kit contains a deep mounting


plate for front and rear terminal bars and fastening crossbars.
For installation on the front frame, choice of covers includes
versions suitable for direct, motorised and rotary front operating
mechanism. The covers are secured to the front frame by means
of fast closing screws (1/4 of a turn).

a For front terminal bars, two additional covers, H50mm each,


are required. Moreover, extended terminal covers have to be
ordered for the respective circuit breaker.
b For front terminal bars, two additional covers, H100mm each,
are required. Moreover, extended terminal covers have to be
ordered for the respective circuit breaker.

Hinges to be fitted to the individual covers are available as an


option.

Shielding is provided for the motorised operating mechanism with


spring accumulator.

The Link-N kit includes support, cover and fasteners. In the 3and 4-pole moulded case circuit breaker combination this kit
provides for the internal separation for a branch unit.

For circuit breaker, base or rack and motorised operating


mechanism combinations, take into due account the indications
given in the dimensional drawings 11/15.

Selection and ordering data


Height of Width Depth1
module
mm mm
mm

Max. no. N-Link support


of circuit
breakers

Equipment
mounting plate

Cover

02066

Ad hoc cover for type of


op. mech.

02065

No. of Connecpoles tion

02070

Circuit
breaker

Sentron 3VL moulded case circuit breaker, plug-in, for vertical installation
VL 160X
VL 160X
VL 160/250
VL 160/250
VL 400
VL 400
VL 630
VL 630
VL 160X
VL 160X
VL 160/250
VL 160/250
VL 400
VL 400
VL 630
VL 630

a
a
a
a
b
b
b
b
a
a
a
a
b
b
b
b

Minimum depth

3
4
3
4
3
4
3/4
3
3
4
3
4
3
4
3
4

front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear

Direct, mot. rotary front mech.


Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.
Direct, mot. rotary front mech.

350
350
350
350
400
400
400
400
350
350
350
350
400
400
400
400

600
600
600
600
600
600
600
600
800
800
800
800
800
800
800
800

400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400

1-4
1-3
1-4
1-3
1-3
1-2
1
1-2
1-5
1-4
1-5
1-4
1-4
1-3
1-3
1-2

8PQ6000-3BA54

8PQ6000-3BA25
8PQ6000-3BA28
8PQ6000-3BA25
8PQ6000-3BA28
8PQ6000-2BA85
8PQ6000-2BA88
8PQ6000-3BA05
8PQ6000-3BA02
8PQ6000-3BA26
8PQ6000-3BA30
8PQ6000-3BA26
8PQ6000-3BA30
8PQ6000-2BA86
8PQ6000-3BA00
8PQ6000-3BA03
8PQ6000-3BA06

8PQ2035-6BA02
8PQ2035-6BA03
8PQ2035-6BA02
8PQ2035-6BA03
8PQ2040-6BA07
8PQ2040-6BA05
8PQ2040-6BA08
8PQ2040-6BA06
8PQ2035-8BA02
8PQ2035-8BA03
8PQ2035-8BA02
8PQ2035-8BA03
8PQ2040-8BA08
8PQ2040-8BA07
8PQ2040-8BA06
8PQ2040-8BA05

Siemens LV 56 2008

6/17

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3VL moulded
case circuit breaker, for vertical installation

Description

Configuration

The equipment support assembly kit contains a deep mounting


plate for front and rear terminal bars and fastening crossbars.
For installation on the front frame, choice of covers includes
versions suitable for direct, motorised and rotary front operating
mechanism. The covers are secured to the front frame by means
of fast closing screws (1/4 of a turn).
Hinges to be fitted to the individual covers are available as an
option.

For circuit breaker, base or rack and motorised operating


mechanism combinations, take into due account the indications
given in the dimensional drawings 11/15.
a For front terminal bars, two additional covers, height 50mm
each, are required. Moreover, extended terminal covers have
to be ordered for the respective circuit breaker.
b For front terminal bars, two additional covers, height 100mm
each, are required. Moreover, extended terminal covers have
to be ordered for the respective circuit breaker.

Selection and ordering data


Ad hoc cover for type of
op. mech.

Height of Width Depth1


module
mm mm
mm

Max. no.
of circuit
breakers

Equipment
mounting plate

Cover

1
1
1-3
1-2
1-2
1
1

8PQ6000-2BA88
8PQ6000-3BA05
8PQ6000-3BA26
8PQ6000-3BA30
8PQ6000-2BA86
8PQ6000-3BA00
8PQ6000-3BA06

8PQ2040-6BA17
8PQ2060-6BA12
8PQ2035-8BA08
8PQ2040-8BA15
8PQ2040-8BA16
8PQ2040-8BA17
8PQ2040-8BA20

Max. no.
of circuit
breakers

Equipment
mounting plate

Cover

1
1
1
1

8PQ6000-3BA87
8PQ6000-3BA88
8PQ6000-4BA00
8PQ6000-4BA01

02067

No. of Connection
poles

02065

Circuit
breaker

Sentron 3VL moulded case circuit breaker, draw out, for vertical installation
VL 400
VL 630
VL 160/250
VL 160/250
VL 400
VL 400
VL 630

b
b
a
a
b
b
b

3/4
3/4
3
4
3
4
3/4

front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear

Direct, rotary front


Direct, rotary front
Direct, rotary front
Direct, rotary front
Direct, rotary front
Direct, rotary front
Direct, rotary front

400
400
350
350
400
400
400

600
600
800
800
800
800
800

400
400
400
400
400
400
400

No. of Connection
poles

Ad hoc cover for type


of op. mech.

Height of Breite Depth1


module
mm mm
mm

02068

Circuit breaker

02069

Selection and ordering data

Sentron 3VL moulded case circuit breaker, draw out, vertical installation
VL 800
VL 800
VL 1250/1600
VL 1250/1600

b
b
b
b

3
4
3
4

front, rear
front, rear
front, rear
front, rear

Minimum depth

6/18

Siemens LV 56 2008

Direct
Direct
Direct
Direct

600
600
650
650

600
600
600
600

600/800
600/800
600/800
600/800

8PQ2060-6BA13
8PQ2060-6BA14
8PQ2065-6BA05
8PQ2065-6BA06

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3VL moulded
case circuit breaker, for vertical installation

Description

Configuration

The equipment support assembly kit contains a deep mounting


plate for front and rear terminal bars and fastening crossbars.

Extended terminal covers have to be ordered for front terminal


bars.

The modular doors kit with degree of protection IP4X with holes for
the 8UC door locking mechanism contains a door, hinges,
individual cover and fasteners.
The Link-N kit includes support, cover and fasteners. In the 3and 4-pole moulded case circuit breaker combination this kit
provides for the internal separation for a branch unit.

Selection and ordering data


Height of Width
module
mm
mm

Depth1
mm

Max. no. N-Link support


of circuit
breakers

Equipment
mounting plate

Cover

02061

Ad hoc cover for type of


op. mech.

02065

No. of Connecpoles tion

02070

Circuit
breaker

Sentron 3VL moulded case circuit breakers, plug-in, for horizontal installation
VL 630
VL 630
VL 800
VL 800
VL 1250
VL 1250
VL 1600
VL 1600

Minimum depth

3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4

rear
front
rear
front
rear
front
rear
front

8UC-door locking mech., Gr. 3


8UC-door locking mech., Gr. 3
8UC-door locking mech., Gr. 3
8UC-door locking mech., Gr. 3
8UC-door locking mech., Gr. 3
8UC-door locking mech., Gr. 3
8UC-door locking mech., Gr. 3
8UC-door locking mech., Gr. 3

400
600
600
800
600
800
700
900

600
600
600
600
600
600
600
600

400
400
400
400
400
400
400
400

1
1
1
1
1
1
1
1

8PQ6000-3BA54
8PQ6000-3BA54
8PQ6000-3BA55
8PQ6000-3BA55
8PQ6000-3BA56
8PQ6000-3BA56
8PQ6000-3BA56
8PQ6000-3BA56

8PQ6000-3BA05
8PQ6000-3BA05
8PQ6000-3BA07
8PQ6000-3BA07
8PQ6000-3BA11
8PQ6000-3BA11
8PQ6000-3BA12
8PQ6000-3BA12

8PQ2040-6BA16
8PQ2060-6BA17
8PQ2060-6BA10
8PQ2080-6BA05
8PQ2060-6BA11
8PQ2080-6BA06
8PQ2070-6BA02
8PQ2090-6BA01

Siemens LV 56 2008

6/19

Assembly Kits for Switching Devices


Assembly kit for 3VT moulded
case circuit breakers

Overview

2
2

02157

1 Assembly kit for 3VT1, fixed, vertical


2 Assembly kit for 3VT2, fixed horizontal
with mechanical lock
3 Assembly kit for 3VT3, draw out, vertical

6/20

Siemens LV 56 2008

Assembly Kits for Switching Devices


Assembly kit for 3VT moulded
case circuit breakers, for horizontal installation

Description

Configuration

The equipment support assembly kit contains a deep mounting


plate for front and rear terminal bars and fastening crossbars.

For the connection always use insulated busbars or cables.

For installation on the front frame, choice of covers includes


versions suitable for direct, motorised and rotary front operating
mechanism. The covers are secured to the front frame by means
of fast closing screws (1/4 of a turn).
Hinges to be fitted to the individual covers are available as an
option.

Selection and ordering data


Ad hoc cover for type of
op. mech.

Height of Width Depth1


module
mm mm
mm

Max. no.
of circuit
breakers

Equipment
mounting plate

Cover

02143

No. of Connecpoles tion

02142

Circuit
breaker

3VT moulded case circuit breakers, fixed and plug-in, for horizontal installation
3VT1 (160A)
3VT2 (250A)
3VT2 (250A)
3VT3 (630A)
3VT3 (630A)

3/4
3
4
3
4

front, rear
front, rear
front, rear
front, rear
front, rear

Direct
Direct, motorised
Direct, motorised
Direct, motorised
Direct, motorised

150
150
200
200
250

600
600
600
600
600

400
400
400
400
400

1
1
1
1
1

8PQ6000-4BA21
8PQ6000-4BA23
8PQ6000-4BA24
8PQ6000-4BA27
8PQ6000-4BA26

8PQ2015-6BA17
8PQ2015-6BA18
8PQ2020-6BA22
8PQ2020-6BA23
8PQ2025-6BA14

Selection and ordering data


Ad hoc cover for type of
op. mech.

Height of Width
module
mm mm
mm

Max. no.
of circuit
breakers

Equipment
mounting plate

1
1

8PQ6000-4BA22
8PQ6000-4BA25

Cover

02145

No. of Connecpoles tion

02144

Circuit
breaker

Depth1

3VT moulded case circuit breakers, draw out, for horizontal installation
3VT2 (250A)
3VT3 (630A)

3/4
3/4

front, rear
front, rear

Direct, motorised
Direct, motorised

250
300

600
600

Description

400
400

8PQ2025-6BA13
8PQ2030-6BA20

Configuration

The mechnical interlock assembly kit contains a device holder


with holes to fit the locking elements, the supporting rails and the
fasteners.

For the mechanical coupling of 2 circuit breakers installed in the


horizontal position use the mechanical interlocking assembly and
the relative accessories.

Selection and ordering data


Ad hoc cover for type of
op. mech.

Height of Width Depth1


module
mm mm
mm

Equipment
mounting plate

Cover

02147

No. of Connecpoles tion

02146

Circuit
breaker

Mechanical lock for Sentron 3VT moulded case circuit breaker, for horizontal installation
3VT2, 3VT3

Minimum depth

100

600

400

8PQ6000-4BA34

8PQ2010-6BA01

Siemens LV 56 2008

6/21

Assembly Kits for Switching Devices


Assembly kit for 3VT moulded case circuit
breakers, for vertical installation

Description

Configuration

The equipment support assembly kit contains a deep mounting


plate for front and rear terminal bars and fastening crossbars.
For installation on the front frame, choice of covers includes
versions suitable for direct, motorised and rotary front operating
mechanism. The covers are secured to the front frame by means
of fast closing screws (1/4 of a turn).
Hinges to be fitted to the individual covers are available as an
option.

For the connection always use insulated busbars or cables.


a Front terminal bars and a breaking capacity 35 kA require
two additional covers, 150mm each. Moreover, the phase
separators and the terminal covers have to ordered.
b Front terminal bars and a breaking capacity 65 kA require
two additional covers, 200mm each. Moreover, the phase
separators and the terminal covers have to ordered.

Selection and ordering data


No. of Connection
poles

Ad hoc cover for


type of op. mech.

Height of Width Depth1


module
mm mm
mm

Max. no.
of circuit
breakers

DIN rail

Cover

1-5
1-2
1-3
1-2

8PQ6000-3BA36
8PQ6000-3BA36
8PQ6000-3BA36
8PQ6000-3BA36

8PQ2045-6BA07
8PQ2045-6BA07
8PQ2045-6BA07
8PQ2045-6BA07

Max. no.
of circuit
breakers

Equipment
mounting plate

Cover

1-3
1-2
1-2
1-2

8PQ6000-4BA28
8PQ6000-4BA30
8PQ6000-4BA31
8PQ6000-4BA32

8PQ2035-6BA18
8PQ2035-6BA20
8PQ2040-6BA18
8PQ2040-6BA20

Max. no.
of circuit
breakers

Equipment
mounting plate

Cover

1-2
1-2
1-2
1

8PQ6000-4BA28
8PQ6000-4BA30
8PQ6000-4BA31
8PQ6000-4BA33

02149

02148

Circuit breaker

Sentron 3VT moulded case circuit breakers, fixed, for vertical installation
3VT1 (160A)
3VT1 (160A)
3VT1 (160A)
3VT1 (160A)

front
front
front
front

Direct
Motorised
Direct
Motorised

450
450
450
450

Ad hoc cover for


type of op. mech.

Height of Width Depth1


module
mm mm
mm

600
600
600
600

400
400
400
400

No. of Connection
poles

02150

Circuit breaker

02151

Selection and ordering data

3VT moulded case circuit breakers, fixed and plug-in, for vertical installation
3VT2 (250A)
3VT2 (250A)
3VT3 (630A)
3VT3 (630A)

a,b
a,b
a,b
a,b

3
4
3
4

front, rear
front, rear
front, rear
front, rear

Direct, motorised
Direct, motorised
Direct, motorised
Direct, motorised

350
350
400
400

Ad hoc cover for


type of op. mech.

Height of Width Depth1


module
mm mm
mm

600
600
600
600

400
400
400
400

Circuit breaker

No. of Connection
poles

02153

Selection and ordering data

02152

3
3
4
4

3VT moulded case circuit breakers, draw out, for vertical installation
3VT2 (250A)
3VT2 (250A)
3VT3 (630A)
3VT3 (630A)

a,b
a,b
a,b
a,b

3
4
3
4

front, rear
front, rear
front, rear
front, rear

Minimum depth

6/22

Siemens LV 56 2008

Direct, motorised
Direct, motorised
Direct, motorised
Direct, motorised

350
350
400
400

600
600
600
600

400
400
400
400

8PQ2035-6BA18
8PQ2035-6BA20
8PQ2040-6BA18
8PQ2040-6BA21

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3K disconnectors

Overview

6
5

2
6

1 BS 88 fuse from IEC NH to British standard


2 IP20 fuse cover
3 IP20 single-pole cover, from 63 to 630 A
4 Standard products from the 3SB1 range
are used as auxiliary contacts

Choice of
5 8UC9 handle fox fixed installation in standard version
(black) and emergency version (red)
6 8UC6 door locking handle witx 5 mm adaption
tolerance in horizontal/vertical direction
Standard version (black) and emergency version
(red/yellow)
All disconnector components up to the operating
mechanism are provided with unique identificazion
features

Siemens LV 56 2008

6/23

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3K disconnectors

Technical specifications
Standard

IEC 60947-1, IEC 60947-3, VDE 0660 Teil 107


3KL50

3KL52

3KL53

3KL551)

3KL571)

3KL611)

Rated continuous current Iu


for fuses according to DIN 43620

A
Size

63
00 u. 000

125
00 u. 000

160
00 u. 000

250
1 and 2

400
1 and 2

630
3 and 2

Cable lug, max (multiwire) conductor size

mm2

35

70

120

150

2 150
or
1 240

2 240

Tightening torque
Connecting screw

Nm

6 ... 7,5
M6

7 ... 10
M6

18 ... 22
M8

35 ... 45
M10

35 ... 45
M10

56
M12

Type

1) Technical specifications for CSA approval upon request.


Type

3KA71 1

Rated continuous current Iu

32

45

63

80

100

125

Cable lug, max (multiwire) conductor size

mm2

50

50

50

50

50

50

Busbar size

mm2

163

163

163

163

163

163

Type

3KA71 2

Rated continuous current Iu

160

200

250

Cable lug, max (multiwire) conductor size

mm2

120

120

120

Busbar size

mm2

205

205

205

Type

3KA71 3

Rated continuous current Iu

315

400

Cable lug, max (multiwire) conductor size

mm2

2150

2150

Busbar size

mm2

2255

2255

Type

3KA71 4

Rated continuous current Iu

630

Cable lug, max (multiwire) conductor size

mm2

2185

Busbar size

mm2

2326

Type

3KA71 5

Rated continuous current Iu

800

1000

1250

1600

2000

2500

3150

Cable lug, max (multiwire) conductor size

mm2

2240

Busbar size

mm2

2505

2506

2508

3508

35012

45012

85012

Type

3KA71 6

Rated continuous current Iu

1600

2000

2500

3150

Cable lug, max (multiwire) conductor size

mm2

Busbar size

mm2

28010

28010

38010

210010

Type

3KL71 1

Rated continuous current Iu

32

45

63

80

Cable lug, max (multiwire) conductor size

mm2

25

25

25

25

Busbar size

mm2

123

123

123

123

Type

3KL71 2

Rated continuous current Iu

100

125

160

Cable lug, max (multiwire) conductor size

mm2

70

70

70

Busbar size

mm2

164

164

164

Type

3KL71 3

Rated continuous current Iu

200

250

Cable lug, max (multiwire) conductor size

mm2

120

120

Busbar size

mm2

254

254

Type

3KL71 4

Rated continuous current Iu

315

400

Cable lug, max (multiwire) conductor size

mm2

240

240

Busbar size

mm2

325

325

Type

3KL71 5

Rated continuous current Iu

630

800

Cable lug, max (multiwire) conductor size

mm2

2185

2185

Busbar size

mm2

2406

2406

6/24

Siemens LV 56 2008

Assembly Kits for Switching Devices


Assembly kit for SENTRON 3K disconnectors

Description

Configuration

The assembly kit for 3K disconnectors is made up of:


Mounting plate
Crossbars
Cover with holes to fit a door locking mechanism and fast
closing screws
Fastening screws

a Due to the size of its handle, the 1250A/50 kA 3KA715


disconnector requires an additional H = 200mm cover to be
placed in the upper part (kit height + 200 mm).

The depth adjustable mounting plate is mounted on crossbars


and is suitable for front or rear terminal bars for the connection of
cables or busbars.

The respective terminal covers must be ordered too for the


disconnector

b Due to the size of its handle, the 3KA715 disconnector can be


installed only in versions up to 1250A/35 kA.

Selection and ordering data


Height of Width Depth1
module
mm mm
mm

Max. no.
of circuit
breakers

Equipment
mounting plate

Door-coupling rotary operating mechanism


Door-coupling rotary operating mechanism
Door-coupling rotary operating mechanism
Door-coupling rotary operating mechanism
Door-coupling rotary operating mechanism
Door-coupling rotary operating mechanism
Door-coupling rotary operating mechanism
Door-coupling rotary operating mechanism

300
350
550
200
250
300
350
450

1
1
1
1
1
1
1
1

8PQ6000-2BA65
8PQ6000-2BA71
8PQ6000-2BA50
8PQ6000-2BA52
8PQ6000-2BA55
8PQ6000-2BA58
8PQ6000-2BA62
8PQ6000-2BA67

8PQ2030-6BA06
8PQ2035-6BA08
8PQ2055-6BA02
8PQ2020-6BA10
8PQ2025-6BA03
8PQ2030-6BA04
8PQ2035-6BA06
8PQ2045-6BA02

Ad hoc cover for type of op. mech.

Height of Width Depth1


module
mm mm
mm

Max. no.
of circuit
breakers

Equipment
mounting plate

Cover

250
350
450
200
250
300
350
450
200
250
300
350
450

1
1
1
1
1
1
1
1
1
1
1
1
1

8PQ6000-2BA66
8PQ6000-2BA72
8PQ6000-2BA51
8PQ6000-2BA53
8PQ6000-2BA56
8PQ6000-2BA60
8PQ6000-2BA63
8PQ6000-2BA68
8PQ6000-2BA54
8PQ6000-2BA57
8PQ6000-2BA61
8PQ6000-2BA64
8PQ6000-2BA70

Ad hoc cover for type of op. mech.

Cover

02072

No. of Connecpoles tion

02071

Circuit breaker

Sentron 3K disconnector, horizontal installation


3KL50, 3KL52
3KL55, 3KL57
3KL61
3KL711, 3KA711
3KL712, 3KA712
3KL713, 3KA713
3KL714, 3KA714
3KL715, 3KA715

3/4
3/4
3/4
3/4
3/4
3/4
3/4
a 3/4

front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear

600
600
600
600
600
600
600
600

400
400
400
400
400
400
400
400

No. of Connecpoles tion

02073

Circuit breaker

02074

Selection and ordering data

Sentron 3K disconnector, vertical installation


3KL50, 3KL52
3KL55, 3KL57
3KL61
3KL711, 3KA711
3KL712, 3KA712
3KL713, 3KA713
3KL714, 3KA714
3KL715, 3KA715
3KL711, 3KA711
3KL712, 3KA712
3KL713, 3KA713
3KL714, 3KA714
3KL715, 3KA715

Minimum depth

3/4
3/4
3
3/4
3/4
3/4
3/4
b 3/4
3/4
3/4
3/4
3/4
3/4

front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear
front, rear

Door locking mech.


Door locking mech.
Door locking mech.
Door locking mech.
Door locking mech.
Door locking mech.
Door locking mech.
Door locking mech.
Door locking mech.
Door locking mech.
Door locking mech.
Door locking mech.
Door locking mech.

600
600
600
600
600
600
600
600
800
800
800
800
800

400
400
400
400
400
400
400
400
400
400
400
400
400

8PQ2025-6BA05
8PQ2035-6BA10
8PQ2045-6BA01
8PQ2020-6BA11
8PQ2025-6BA04
8PQ2030-6BA05
8PQ2035-6BA07
8PQ2045-6BA03
8PQ2020-8BA04
8PQ2025-8BA02
8PQ2030-8BA02
8PQ2035-8BA04
8PQ2045-8BA01

Siemens LV 56 2008

6/25

Assembly Kits for Switching Devices


Assembly kit for in-line fuse switch disconnectors
SENTRON 3NJ4

Overview

02075

6/26

Siemens LV 56 2008

Assembly Kits for Switching Devices


Assembly kit for in-line fuse switch disconnectors
SENTRON 3NJ4

Technical Data
Standards

IEC 60947-1, IEC 60947-3, VDE 0660 Teil 107

Type

3NJ41 0
3NJ5 0

3NJ41 2

3NJ41 3

3NJ41 4

Conventional thermal current


in free air Ith 1)
in enclosed place Ithe 2)

A
A

160
160

250
225

400
360

630
567

Rated insulation voltage Ui

750

1000

1000

1000

Rated operating voltage Ue

AC 40 Hz
... 60 Hz V

690

690

690

690

kA
(actual value)
A
kA
(peak value)
size/A

50

50

50

50

160
15

250
28

400
39

630
52

00/160

1/250

1 und
2/250 und
400

2 und
3/400 und
630

IP30

IP30

IP30

IP30

Rated conditional short-circuit current with fuses


from AC 40 Hz to 60 Hz 690 V
max. rated current of fuses In
admissible fuse cut-off current
For fuse kit
according to standard IEC 60269-2-1 or sectioning
brackets
Degree of protection
with open handle insert
with side cover and clamps
with closed handle insert

IP10

IP10

IP10

IP10

Power dissipated from main current lines Ith

18

23

49

110

Main conductor connection


Connecting screws
Flat rails
Terminal, max. size of (multiwire) conductor
Tightening torque
Bracket / V-clamp

mm
mm2
Nm
mm2

M8
24
95
10 ... 15
1,5 ... 70

M10
42
240
30 ... 35
25 ... 300

M12
42
240
30 ... 35
25 ... 300

M12
42
2403)
30 ... 35
25 ... 300

Nm

M8
16 ... 18

M12
35 ... 40

M12
35 ... 40

M12
35 ... 40

Fastening screws
for installation on busbars
tightening torque required

1) When using different devices, take into account the load factor specified in standard EN 60439 part 1/DIN VDE 0660 part 500, Table 1
2) The minimum space needed for the casing is 0,185 m3.
3) A special kit supplied on request is necessary for the 2 x 240 mm2 connection.

Rated currents for the horizontal distribution rails


No. of bars

Dimensions Rated current at 35 C ambient temperature


[mm]

IP IP41

IP 55

60 x 10

1560

1280

80 x 10

1740

1430

100 x 10

2180

1790

The data refer to normal operating conditions for indoor models as specified in standard IEC 60439-1, in particular with reference to an
ambient temperature of 35 C (24 h average). In different operating conditions, take into account the correction factors given in the
chapter on Planning and configuration.

Siemens LV 56 2008

6/27

Assembly Kits for Switching Devices


Assembly kit for in-line fuse switch disconnectors
SENTRON 3NJ4

Description

Configuration

The device holder is made up of crossbars and depth adjustable


corner supports for the horizontal installation of distribution
busbars. The panels are secured to the frame by means of a
snap-in system.

The device holder is suitable for use behind a closed door.


Kit for the connection of cables from the bottom and from the top.
Copper busbars are not included in the kit.
Two supports for the distribution busbars must be ordered.

Selection and ordering data


Width Switches
mm for kit

Device holder

800
800

600
800

8PQ6000-2BA48
8PQ6000-2BA48

Support for
distribution
busbars

Direct activation
panel

02078

Height
mm

02077

Num- Installation
ber of technique
poles

02076

Switch

Sentron 3NJ4 disconnector with fuses


3NJ4, BG 1, 2, 3
3NJ4, BG 1, 2, 3

3
3

fixed
fixed

4
6

3NJ5974-0AB
3NJ5974-0AB

02079

02080

Configuration for cable entry from the bottom

6/28

Siemens LV 56 2008

Configuration for cable entry from the top

8PQ2000-6BA06
8PQ2000-8BA06

Assembly Kits for Switching Devices


Assembly kit for in-line fuse switch disconnectors
SENTRON 3NJ6

Overview

2
3

1 Fixed cover for busbars


2 3NJ6 in-line fuse disconnectors

3N76

3 Cable connection compartment door


4 Fixed cover for PE busbars

Siemens LV 56 2008

6/29

Assembly Kits for Switching Devices


Assembly kit for in-line fuse switch disconnectors
SENTRON 3NJ6

Technical Data
Standards

IEC 60947-1

Type
Breaking capacity

3NJ60 0.-1
S

3NJ60 1.-1
S

3NJ60 1.-3
H

3NJ60 2.-1
S

3NJ60 2.-3
H

3NJ60 3.-1
S

3NJ60 3.-3
H

Rated uninterrupted current Iu1)


for kit wtih fuses according to standard IEC
60269

160

Rated operating current Ue


with a rated current of

AC V
Hz

690
50/60

Rated insulation voltage Ui

1000

Rated impulse current Uimp

8000

Rated conditional short circuit current


Short-circuit resistance (actual value)
Short-circuit switching capacity (actual
value)

kA
kA

100
55

66

55

66

55

66

55

66

A
A
A
A

160

160

160
160
160
125

250

200

250
250
200
200

400

400

400
400
400
315

630

630

630
630
630
500

A
A
A
A

480

480

480
1280
480
1000

750

600

750
2000
600
1600

1200

1200

1200
3200
1200
2520

1890

1890

1890
5040
1890
4000

Rated operating current Ie


with AC 500 V
AC-22B
AC-23B
with AC 690 V
AC-22B
AC23B
Short-circuit breaking power
with AC 500 V
cos = 0,65
cos = 0,35
with AC 690 V
cos = 0,95
cos = 0,35
Operating life
overall
mechanical

3NJ60 0.-3
H

electrical (690 V, cos = 0,65)

Power dissipated
(including NH fuses with lower dissipation
power according to VDE 0636 part 2)

400

630

operat- 1600
ing cycles
operat- 1400
ing cycles
operat- 200
ing cycles

1600

1000

1000

1400

800

800

200

200

200

73

114

215

39

Permissible operating position

horizontal

Degree of protection (in operating conditions)

IP41

Main conductor connection


Terminal connection
Conductor size
Al/Cu, single or multiwire
according to DIN 46235 (Cu) and DIN
46239 (Al)
screw dimensions
tightening torque
Clamp connection
conductor size (Al/Cu), rn
conductor size (Al/Cu), re
conductor size (Al/Cu), sm
conductor size (Al/Cu), se
tightening torque required

250

mm2

1 x 10 ... 95

1 x 95 ... 240

1 x 300,
2 x 95 ... 240

1 x 300,
2 x 95 ... 240

Nm

M8
15

M12
30

2 x M12
30

2 x M12
30

mm2
mm2
mm2
mm2
Nm

1 x 10 ... 50
1 x 10 ... 50
1 x 35 ... 95
1 x 50 ... 95
10

1 x 16 ... 35
1 x 16 ... 70
1 x 35 ... 240
1 x 35 ... 300
25

2 x 16 ... 35
2 x 16 ... 70
2 x 35 ... 240
2 x 35 ... 300
25

2 x 16 ... 35
2 x 16 ... 70
2 x 35 ... 240
2 x 35 ... 300
25

1) Standard IEC 60439 requires that rated uninterrupted current be reduced if busbars are installed in the control board.
Rated currents for the vertical distribution busbar system
No. of bars

Dimensions Rated current at 35 C ambient temperature


[mm]

IP IP41

60 x 10

1560

80 x 10

2100

The data refer to normal operating conditions for indoor models as specified in standard IEC 60439-1, in particular with reference to an
ambient temperature of 35 C (24 h average). In different operating conditions, take into account the correction factors given in the
chapter on Planning and configuration.

6/30

Siemens LV 56 2008

Assembly Kits for Switching Devices


Assembly kit for in-line fuse switch disconnectors
SENTRON 3NJ6

Description

Configuration

The assembly kit for Sentron 3NJ6 in-line fuse disconnectors in


horizontal configuration contains vertical bars and busbar
supports suitable for 3- and 4-pole versions.

Depending on the interior organisation of the rack, configure the


rack, interior bearing structures with a usable height of 1600
mm, exterior bearing structures and partitions.

The device compartment consists of a modular door, vertical


and horizontal partitions, a device holder.

The assembly kit can be used with racks 1000mm or 1200mm


width and 400mm, 600mm or 800mm deep, and it occupies a
width of 600 mm.
For each assembly kit for Sentron 3NJ6 in-line fuse
disconnectors, configure 8 protective covers 3NJ6916-4EA00.
The 400mm and 600mm wide cable connecting compartment
can be equipped with standard components for N and PE
busbars, and cable supporting brackets.
Depending on field conditions, it is necessary to configure a
fixed cover before the busbars, a fixed cover before the PE
busbars and a door (for the cable connecting compartment).
Max degree of protection IP41
Copper busbars are not included in the kit.

Selection and ordering data


Number
of poles

Installation
technique

Height
mm

Width
mm

Ordering code

UI

8PQ3000-1BA48

Assembly kit for Sentron 3NJ6 in-line fuse disconnectors, plug-in installation, horizontal configuration
3/4

steck

1600

600

02082

Compartment with modular door for on site installation of Sentron 3NJ6 in-line fuse disconnectors
600
600

8PQ3000-1BA50
8PQ3000-1BA51

1
1

3NJ6916-4EA00

02083

200
400

02084

Protective covers for Sentron 3NJ6 in-line fuse disconnectors

Siemens LV 56 2008

6/31

Assembly Kits for Switching Devices


Assembly kits for modular installations devices

Overview

02090

6/32

Siemens LV 56 2008

Assembly Kits for Switching Devices


Assembly kit for modular installation devices

Description

Configuration

The kit for modular devices mounted on DIN rails is made up of:
Support brackets
Variable depth 35mm DIN rail in ALU
Cover with cut-out DIN and fast closing screws (1/4 turn)
Fastening screws
The multiple DIN rail makes it possible to snap the Sikclip wiring
system onto the rear side.
The DIN rail can be modifies and adjusted for depth as desired.
The horizontal raceway fastening kit contains the support and the
necessary fasteners.

The DIN rail can be adjusted for a distance from the front cover of
47.5mm, 56.5mm and 75.5mm.
The support bracket makes it possible to fit a vertical raceway up
to 60mm in width.
For each row, order 1 DIN rail kit of matching width.

Selection and ordering data


Height of module
mm

Width
mm

Modular units

DIN rail

Cover

02092

02091

Row centre distance


mm

DIN rail assembly kit for modular devices, 1 row


150

150

600

24

8PQ6000-3BA36

8PQ2015-6BA07

200

200

600

24

8PQ6000-3BA36

8PQ2020-6BA12

150

150

800

36

8PQ6000-3BA37

8PQ2015-8BA03

200

200

800

36

8PQ6000-3BA37

8PQ2020-8BA05

Width
mm

Modular units

DIN rail

Cover

Selection and ordering data


Height of module
mm

02093

02091

Row centre distance


mm

DIN rail assembly kit for modular devices, 2 row


150

300

600

48

2 x 8PQ6000-3BA36

8PQ2030-6BA07

200

400

600

48

2 x 8PQ6000-3BA36

8PQ2040-6BA10

150

300

800

72

2 x 8PQ6000-3BA37

8PQ2030-8BA03

200

400

800

72

2 x 8PQ6000-3BA37

8PQ2040-8BA10

Width
mm

Modular units

DIN rail

Cover

Selection and ordering data


Height of module
mm

02094

02091

Row centre distance


mm

DIN rail assembly kit for modular devices, 3 row


150

450

600

72

3 x 8PQ6000-3BA36

8PQ2045-6BA04

200

600

600

72

3 x 8PQ6000-3BA36

8PQ2060-6BA04

150

450

800

108

3 x 8PQ6000-3BA37

8PQ2045-8BA02

200

600

800

108

3 x 8PQ6000-3BA37

8PQ2060-8BA02

Row centre
distance

Height of module
mm

Width
mm

Modular units

Ordering code

UI

8PQ6000-0BA16

Horizontal raceway fastening brackets


600/800

01660

Siemens LV 56 2008

6/33

Assembly Kits for Switching Devices


Assembly kit for modular installation devices

Description
fixing with clips onto the back of the DIN rail (top hat rail).

Sikclip is a quick wiring system simplifying the connection of


flush-mounted circuit breakers.

Distribution terminal blocks with IMQ label, in 2-pole or 4-pole


versions, for currents up to 125 A. Icw up to 4.3 kA and
Ipk up to 22 kA. For direct fastening onto the DIN rails.

for direct mounting on the rear vertical CU busbar

Technical specifications
Max. rated operating current In

250 A at 40 C ambient temperature

Max. rated output current In

63 A at 40 C ambient temperature

Rated operating voltage Un

AC 400 V

Rated insulation voltage

AC 660 V

Test voltage

2,5 kV, 50 Hz

Degree of protection

IP20

Connecting conductors

40 A (6 mm2), 63 A (10 mm2)

Type of connecting conductor

H07VK

Colour

RAL 7035

Operating temperature

5 C to +60 C

Applicable standards

EN 60947-1, EN 60439-3

Selection and ordering data


Model

Length

Colour

Ordering code

Sikclip wiring system

12 TE

5ST2 520

24 TE

5ST2 521

36 TE

5ST2 522

Connecting conductors
6 mm2

120 mm

10 mm2

120 mm

6 mm2

220 mm

10 mm2

220 mm

black

5ST2 523

blue

5ST2 524

black

5ST2 525

blue

5ST2 526

black

5ST2 527

blue

5ST2 528

black

5ST2 530

blue

5ST2 531

Push-in connector
Brackets

5ST2 532
for anchoring to back of DIN rail (pair)

Model

TE

Distribution terminal blocks


100 A

7 openings per pole

5 1,5 up to 6 mm2 +
2 6 up to 16 mm2
125 A

6/34

Siemens LV 56 2008

5ST2 533

Icw (1 s) Ipk
kA
kA

Ordering code

2 poles

3,1

20

8GF9 871

4 poles

3,1

20

8GF9 872

11 openings per pole

2 poles

4,3

22

8GF9 873

7 1,5 up to 6 mm2 +
2 6 up to 16 mm2 +
2 16 up to 35 mm2

4 poles

4,2

22

8GF9 874

15 openings per pole

2 poles

4,2

22

8GF9 875

11 1,5 up to 6 mm2 +
2 6 up to 16 mm2 +
2 16 up to 35 mm2

4 poles

4,3

22

8GF9 876

Covers, Modular Doors,


Mounting Plate, 19 Rack

7/2

Covers

7/4

Modular doors

7/7

Modular mounting plates

7/8

Mounting plate for


electrotechnical applications

7/9

19 rack

Siemens LV 56 2008

Covers, Modular Doors, Mounting Plate, 19 Rack


Covers

Description

Configuration

The kit consists a cover and guick-release locks.


The covers are secured to the board frame by means of captive
fast closing screws (1/4 of a turn).

If the fast closing screws are replaced with hinges, the holes
must be closed with plugs.
Use a pair of hinges per cover.

1/4 turn screws are tightened and loosened by means of a


flathead screwdriver.
In addition to fastening the cover, the screw also performs a
grounding function for the cover.
Using the hinge options, the cover can be hinged on the right or
the left as desired.
The hinges are mounted without having to use any additional
mechanical parts and also perform a grounding function for the
cover.

Selection and ordering data


Cut-out

Height of module
mm

Width
mm

Ordering code

UI

50

600

8PQ2005-6BA01

100

600

8PQ2010-6BA01

150

600

8PQ2015-6BA02

200

600

8PQ2020-6BA01

250

600

8PQ2025-6BA01

300

600

8PQ2030-6BA01

350

600

8PQ2035-6BA01

400

600

8PQ2040-6BA01

500

600

8PQ2050-6BA01

550

600

8PQ2055-6BA01

600

600

8PQ2060-6BA01

650

600

8PQ2065-6BA01

800

600

8PQ2080-6BA01

50

800

8PQ2005-8BA01

100

800

8PQ2010-8BA01

150

800

8PQ2015-8BA02

200

800

8PQ2020-8BA01

250

800

8PQ2025-8BA01

300

800

8PQ2030-8BA01

350

800

8PQ2035-8BA01

400

800

8PQ2040-8BA01

500

800

8PQ2050-8BA01

550

800

8PQ2055-8BA01

600

800

8PQ2060-8BA01

650

800

8PQ2065-8BA01

800

800

8PQ2080-8BA01

2 instruments 72 x 72 mm + 2 change-over switches

200

600

8PQ2020-6BA03

4 instruments 72 x 72 mm + 1 change-over switch

200

600

8PQ2020-6BA02

2 instruments 72 x 72 mm + 2 change-over switches 200

800

8PQ2020-8BA03

4 instruments 72 x 72 mm + 1 change-over switch

800

8PQ2020-8BA02

Covers with cut-outs

01693

01661

Covers without cut-outs

7/2

Siemens LV 56 2008

200

Covers, Modular Doors, Mounting Plate, 19 Rack


Covers

Description

Configuration

The kit consists a cover and guick-release locks.


The covers are secured to the board frame by means of captive
fast closing screws (1/4 of a turn).

If the fast closing screws are replaced with hinges, the holes
must be closed with plugs.
Use a pair of hinges per cover.

1/4 turn screws are tightened and loosened by means of a slot


or cross-slot screwdriver.
In addition to fastening the cover, the screw also performs a
grounding function for the cover.
Using the hinge options, the cover can be hinged on the right or
the left as desired.
The hinges are mounted without having to use any additional
mechanical parts and also perform a grounding function for the
cover.

Selection and ordering data


Height of module
mm

Width
mm

Ordering code

2 instruments 96 x 96 mm + 2 change-over switches

400

600

8PQ2040-6BA04

4 instruments 96 x 96 mm + 1 change-over switch

400

600

8PQ2040-6BA03

2 instruments 96 x 96 mm + 2 change-over switches

400

800

8PQ2040-8BA04

4 instruments 96 x 96 mm + 1 change-over switch

400

800

8PQ2040-8BA03

Cut-out

UI

01810

01809

Covers 400mm with cut-outs

Covers with ventilation fins


100

600

8PQ2010-6BA02

ventilated

100

800

8PQ2010-8BA02

8PQ2000-0BA01

10

8PQ2000-0BA02

10

01811

ventilated

01697

Cover hinges kit

Closing plugs for cover holes

01812

Siemens LV 56 2008

7/3

Covers, Modular Doors, Mounting Plate, 19 Rack


Modular doors

Overview

1 Exterior front cover for main busbars


2 Modular door
3 Cover for degree of protection IP55

02095

4 Exterior front cover for PE bar


4

7/4

Siemens LV 56 2008

Covers, Modular Doors, Mounting Plate, 19 Rack


Modular doors

Description

Configuration

The exterior front covers kit for the main busbars and the PE
bar contains the cover and an anchoring support.

Each cubicle with modular doors must be fitted with a front cover
before the busbars and the PE bar.

Height of module
mm

02097

02096

Selection and ordering data

Width
mm

Ordering code

IP55 upgrade

Exterior front cover for main busbars


8PQ2022-6BA01

8PQ2022-6BA02

8PQ2022-8BA01

8PQ2022-8BA02

Height of module
mm

Width
mm

Ordering code

IP55 upgrade

02098

600
800

02158

225
225

Exterior front cover for PE bars


175

600

8PQ2000-6BA07

8PQ2015-6BA13

175

800

8PQ2000-8BA07

8PQ2015-8BA08

Siemens LV 56 2008

7/5

Covers, Modular Doors, Mounting Plate, 19 Rack


Modular doors

Description

Configuration

The modular doors kit contains a door with degree of protection


IP4X, door hinge support, hinges, green column identification
strip and two-way interlocking mechanism.
The front covers kit contains the cover and an anchoring
support.

A combination of front frame and covers with modular doors in a


cubicle is not possible.
When using the equipment with modular doors, the remaining
heights must be closed with 50mm or 100mm height front
covers.

Height of module
mm

02053

02159

Selection and ordering data

Width
mm

Ordering code

IP55 upgrade

Modular doors
8PQ2015-6BA10

8PQ2015-6BA12

8PQ2020-6BA14

8PQ2020-6BA15

250

600

8PQ2025-6BA07

8PQ2025-6BA08

300

600

8PQ2030-6BA10

8PQ2030-6BA12

350

600

8PQ2035-6BA12

8PQ2035-6BA13

400

600

8PQ2040-6BA12

8PQ2040-6BA13

450

600

8PQ2045-6BA05

8PQ2045-6BA06

500

600

8PQ2050-6BA03

8PQ2050-6BA04

550

600

8PQ2055-6BA04

8PQ2055-6BA06

600

600

8PQ2060-6BA06

8PQ2060-6BA07

650

600

8PQ2065-6BA03

8PQ2065-6BA04

700

600

8PQ2070-6BA03

8PQ2070-6BA04

750

600

8PQ2075-6BA01

8PQ2075-6BA02

800

600

8PQ2080-6BA03

8PQ2080-6BA04

150

800

8PQ2015-8BA05

8PQ2015-8BA07

200

800

8PQ2020-8BA07

8PQ2020-8BA08

250

800

8PQ2025-8BA04

8PQ2025-8BA05

300

800

8PQ2030-8BA05

8PQ2030-8BA06

350

800

8PQ2035-8BA06

8PQ2035-8BA07

400

800

8PQ2040-8BA12

8PQ2040-8BA13

450

800

8PQ2045-8BA03

8PQ2045-8BA04

500

800

8PQ2050-8BA03

8PQ2050-8BA04

550

800

8PQ2055-8BA03

8PQ2055-8BA06

600

800

8PQ2060-8BA04

8PQ2060-8BA05

650

800

8PQ2065-8BA03

8PQ2065-8BA04

700

800

8PQ2070-8BA01

8PQ2070-8BA02

750

800

8PQ2075-8BA01

8PQ2075-8BA02

800

800

8PQ2080-8BA03

8PQ2080-8BA04

Height of module
mm

Width
mm

Ordering code

IP55 upgrade

02100

600
600

02099

150
200

Front covers

7/6

50

600

8PQ2005-6BA04

8PQ2005-6BA03

100

600

8PQ2010-6BA04

8PQ2010-6BA03

50

800

8PQ2005-8BA04

8PQ2005-8BA03

100

800

8PQ2010-8BA04

8PQ2010-8BA03

Siemens LV 56 2008

Covers, Modular Doors, Mounting Plate, 19 Rack


Modular mounting plates

Description

Configuration

The modular mounting plate kit is made up of:


Mounting plate
Crossbars
Cover and fast closing screws
Fastening screws

In mounting plates with holes, hole spacing is 25 x 25 mm.


Hole diameter is 5.4 mm and the holes are suitable for M6 selftapping screws.

The mounting plate can be ordered with or without holes and


can be adjusted for depth.

Selection and ordering data


Height of module
mm

Width
mm

Ordering code

UI

02101

Mounting plate kit without holes


200

600

8PQ3000-1BA56

400

600

8PQ3000-1BA61

600

600

8PQ3000-1BA65

800

600

8PQ3000-1BA26

200

800

8PQ3000-1BA58

400

800

8PQ3000-1BA63

600

800

8PQ3000-1BA67

800

800

8PQ3000-1BA28

200

600

8PQ3000-1BA57

400

600

8PQ3000-1BA62

600

600

8PQ3000-1BA66

800

600

8PQ3000-1BA27

200

800

8PQ3000-1BA60

400

800

8PQ3000-1BA64

600

800

8PQ3000-1BA68

800

800

8PQ3000-1BA30

02102

Mounting plate kit with holes

Siemens LV 56 2008

7/7

Covers, Modular Doors, Mounting Plate, 19 Rack


Mounting plate for electrotechnical applications

Description

Configuration

The mounting plate kit for electrotechnical applications


contains the mounting plate and the brackets to fasten it to the
cubicle.

By means of 6 additional crossbars the mounting plate can be


adjusted for depth.
The crossbars are described in the chapter on Accessories.

The brackets are fastened to the side upright or to the rear part
of the cubicle.
To facilitate the installation of the mounting plate, the lower
fastening brackets are designed for slanted plate insertion when
the plate has been made ready and wired on the work bench.
The connecting panel kit makes it possible to create an
uninterrupted surface when two or more adjacent boards have
to be mechanically connected.

Selection and ordering data


Height of module
mm

Width
mm

Ordering code

UI

01672

Mounting plate
1600

400

8PQ3000-0BA33

1600

600

8PQ3000-0BA35

1600

800

8PQ3000-0BA37

1600

1000

8PQ3000-1BA06

1600

1200

8PQ3000-1BA07

1900

400

8PQ3000-0BA32

1900

600

8PQ3000-0BA34

1900

800

8PQ3000-0BA36

1900

1000

8PQ3000-1BA04

1900

1200

8PQ3000-1BA05

1600

8PQ3000-1BA10

1900

8PQ3000-1BA08

Connecting panel

01700

7/8

Siemens LV 56 2008

Covers, Modular Doors, Mounting Plate, 19 Rack


19 rack

Description

Configuration

For the installation of a 19 rack, a fixed version kit for 600mm


wide cubicles and a swivel version kit for 800mm wide cubicles
are available.

1 height unit (HE) = 44.45 mm.


Swivel version kit for use with right or left hinges.
The maximum weight of the rack is 160 kg.

Selection and ordering data


Equipment height
mm

Height of electronic unit


HE

Cubicle width
mm

Version

1800

39

600

fixed

8PQ3000-1BA11

1800

39

800

swivel

8PQ3000-1BA12

Ordering code

UI

NSEX_00007

Kit per 19 rack

Siemens LV 56 2008

7/9

Covers, Modular Doors, Mounting Plate, 19 Rack


Notes

7/10

Siemens LV 56 2008

Internal Separation

8/2

General Data

8/4

Main busbar system

8/7

Vertical distribution busbar


system

8/9

Modular Separation for


Switching Devices

Siemens LV 56 2008

Internal Separation
General Data

Overview
A fundamental characteristic of switchgear is the presence of
internal separation forms as required by the applicable standards.
The main purpose of internal partitions is to make sure that all
switching, control and maintenance operations can be performed in
full safety, while ensuring uninterrupted system operation.
Advantages
Reduction of possible hazards during connection, scheduled
maintenance and extraordinary maintenance operations
Attenuation of consequences of local faults and faster resumption
of regular operation
Applications:
Protection against contact between live parts belonging to
adjacent functional units. Degree of protection required: IP2X or
IPXXB;
Protection against the intrusion of foreign bodies from a functional
unit into an adjacent functional unit. Degree of protection required:
IP 2X or higher;
Low risk of internal arc triggering.
Functional unit (definition): part of a switchgear containing all the
electrical and mechanical components that contribute to the
fulfilment of the same function, e.g., infeed and outfeed circuit
breakers, measuring unit, etc.

SIVACON S4
With SIVACON S4, internal separation form 2b is achieved by
separating the main busbar systems and the distribution busbars by
means of partitions and covers.
Assembly kits for switching and protection devices which comply
with internal separation form 1 in their basic version do not require
any additional separation to achieve internal separation form 2b.
If only 1 circuit breaker per cubicle is used, form 3b corresponds to
form 4b (3b = 4b).

8/2

Siemens LV 56 2008

Definitions according to IEC 60439-1, CEI EN 60439-1

Form 1

No internal separation

Form 2

Separation between busbars and functional


units

Form 2a

Separation between busbars and functional


units, no separation between connections
and busbars

Form 2b

Separation between busbars and functional


units, separation between connections and
busbars

Form 3

Separation between busbars and all


functional units
Separation between all the functional units
Separation between the connections of
conductors going to the exterior and the
functional units, but no separation between
the connections and the functional units

Form 3a

No separation between connections and


busbars

Form 3b

Separation between connections and


busbars

Form 4

Separation between busbars and all


functional units
Separation between all the functional units
Separation between the connections of
conductors going to the exterior which are
associated with functional units and the
connections of all the other functional units
and the busbars

Form 4a

Connections in the same cell as the


functional unit concerned

Form 4b

Connections not in the same cell as the


functional unit concerned

Special separation forms or higher degrees of protection must be


agreed upon by the manufacturer and the user.

Internal Separation
General Data

Form 1

Functional unit
Input and output connections

Main busbars

Distribution busbars

3
4

Input circuit
Output circuit

01734

Form 3a

01736

Form 2b

01735

Form 2a

Form 3b

01740

Form 4b

01739

Form 4a

01738

01737

Siemens LV 56 2008

8/3

Internal Separation
Main busbar system

02104

02103

02106

Overview

Main busbar system in standard


position, top front depth 400mm

Main busbar system in standard


position, top front depth 600mm

Main busbar system in standard


position, top front - rear depth
800mm

Main busbar system in standard


position, top front and rear depth
800mm

8/4

Siemens LV 56 2008

02107

02105

Main busbar system in standard


position in optional adjustable
position, rear depth 800mm

Internal Separation
Main busbar system

Description

Configuration

The form 2b separation kit for horizontal main busbar systems


contains the metal parts and the fastening screws need to
achieve this separation form.

One piece per cubicle corresponding to the relative dimensions


for equipment compartment or cable compartment.
To use a section as a riser duct it is necessary to use a side
upright matching the equipment height and depth, with no
bottom plate partition.

Selection and ordering data


Position of main busbars

Width
mm

Cubicle depth
mm

Height of
module
mm

Ordering code

UI

01726

Busbar system in standard position, form 2b separation


front

top

200

600

225

8PQ3000-1BA53

front

top

400

600

225

8PQ3000-0BA52

front

top

600

600

225

8PQ3000-0BA53

front

top

800

600

225

8PQ3000-0BA54

front

top

1000

600

225

8PQ3000-1BA14

front

top

1200

600

225

8PQ3000-1BA16

front or rear

top

200

800

225

8PQ3000-1BA54

front or rear

top

400

800

225

8PQ3000-0BA55

front or rear

top

600

800

225

8PQ3000-0BA56

front or rear

top

800

800

225

8PQ3000-0BA57

front or rear

top

1000

800

225

8PQ3000-1BA17

front or rear

top

1200

800

225

8PQ3000-1BA18

front or rear

top

200

800

225

8PQ3000-1BA55

front or rear

top

400

800

225

8PQ3000-0BA58

front or rear

top

600

800

225

8PQ3000-0BA60

front or rear

top

800

800

225

8PQ3000-0BA61

front or rear

top

1000

800

225

8PQ3000-1BA20

front or rear

top

1200

800

225

8PQ3000-1BA21

front

top

200

400

225

8PQ3000-1BA52

front

top

400

400

225

8PQ3000-0BA67

front

top

600

400

225

8PQ3000-0BA68

front

top

800

400

225

8PQ3000-0BA70

front

top

1000

400

225

8PQ3000-1BA13

front

top

1200

400

225

8PQ3000-1BA15

rear

variable

400

400*, 600*, 800

250

8PQ3000-0BA78

rear

variable

600

400*, 600*, 800

250

8PQ3000-0BA80

rear

variable

800

400*, 600*, 800

250

8PQ3000-0BA81

rear

variable

1000

400*, 600*, 800

250

8PQ3000-1BA22

rear

variable

1200

400*, 600*, 800

250

8PQ3000-1BA23

01728

01727

Busbar system in free position, form 2b separation

* with modular door.

Siemens LV 56 2008

8/5

Internal Separation
General Data

Overview

01725

1 Form 2b separation for horizontal main busbar system


2 Form 2b separation for vertical distribution busbars

8/6

Siemens LV 56 2008

Internal Separation
Vertical distribution busbar system

Description

Configuration

The form 2b vertical distribution busbar separation kit contains


the parts and the fasteners needed to achieve this separation
form.

For cubicles placed side-by-side, order an additional separation


kit to obtain form 2b for the vertical busbars or separation
between cubicles.
The protective front separation for the busbar compartment
cannot be fitted to the back of 400 mm deep cubicles.

Selection and ordering data


Position of main busbars

Width
mm

Cubicle depth
mm

Ordering code

UI

Vertical distribution busbar system with main busbars at the top, form 2b separation
200, 400

400

8PQ4000-0BA05

front

200, 400

600

8PQ4000-0BA07

front and rear

200, 400

800

8PQ4000-0BA64

front and rear

200

800

8PQ4000-0BA02

front and rear

400

800

8PQ4000-0BA01

01741

01723

01722

front

01729

Vertical distribution busbar system without main busbars, form 2b separation


200, 400

400

8PQ4000-0BA06

200, 400

600

8PQ4000-0BA03

1
1

front and rear

200, 400

800

8PQ4000-0BA76

01741

front and rear


front and rear

Additional front cover for vertical busbar compartment


200

8PQ3000-0BA50

400

8PQ3000-0BA51

01665

Siemens LV 56 2008

8/7

Internal Separation
Vertical distribution busbar system

Description

Configuration

The separation between cubicles kit is symmetrically split and is


provided with removable pre-sectioning units for use in
conjunction with horizontal busbar systems.

For 800 mm deep cubicles, order two 400 mm deep separation


kits.

Selection and ordering data


Cubicle depth
mm

Height

Ordering code

UI

400

cubicle height

8PQ3000-0BA15

600

cubicle height

8PQ3000-0BA16

01641

Vertical separation between cubicles

8/8

Siemens LV 56 2008

Internal Separation
Modular Separation for Switching Devices

Description

Configuration

The crossbars and separation supporting rails kit makes it


possible to fasten the rear of the kit supporting crossbars without
having to use screws.

Order 1 crossbars and separation supporting rails kit for


cubicles sized 600 mm or 800 mm.
Required to achieve separation forms 3 and 4.

It is also used to fasten the horizontal and vertical partitions in


the rear part of the cubicle in form 2b without having to use
screws.

Selection and ordering data


Equipment height
mm

Ordering code

UI

1600

8PQ3000-0BA82

1800

8PQ3000-0BA83

02109

01744

Crossbars and separation supporting rails kit, for forms 3 and 4 separation

02108

Siemens LV 56 2008

8/9

Internal Separation
Modular Separation for Switching Devices

Description

Design

The form 3 separation kit for Sentron 3WL circuit breakers


ensures rear and side separation.

The form 3 separation kit for Sentron 3WL circuit breakers can
be installed only in 600mm and 800mm deep cubicles.
This separation cannot be used for circuit breaker 3WL 1240.

Selection and ordering data


Size

No. of poles

Width
mm

Height of module
mm

Ordering code

UI

Sentron 3WL, fixed version, form 3 separation


3/4

600

550

8PQ5000-0BA08

Gr II

600

550

8PQ5000-0BA13

Gr I

3/4

800

550

8PQ5000-1BA65

Gr II

3/4

800

550

8PQ5000-0BA11

01648

Gr I

Sentron 3WL, draw out version, form 3 separation


3/4

600

550

8PQ5000-0BA07

Gr II

600

550

8PQ5000-0BA12

Gr I

3/4

800

550

8PQ5000-1BA66

Gr II

3/4

800

550

8PQ5000-0BA10

Size

Current

No. of poles

Ordering code

UI

01648

Gr I

Selection and ordering data


Version

Width

mm

Height of module
above the
circuit
breaker
mm

under the
circuit
breaker
mm

Sentron 3WL, connection to the cables, form 4 separation


1600

3/4

Fixed/Draw out

600

200

250

8PQ5000-0BA30

Gr I

1600

3/4

Fixed/Draw out

800

200

250

8PQ5000-1BA68

Gr II

3200

3/4

Fixed/Draw out

800

350

400

8PQ5000-0BA38

01650

Gr I

Sentron 3WL, connection to the vertical distribution busbars, form 4 separation


1600

3/4

Fixed/Draw out

600

250

300

8PQ5000-0BA14

Gr I

1600

3/4

Fixed/Draw out

800

250

300

8PQ5000-1BA67

Gr II

3200

3/4

Fixed/Draw out

800

300

350

8PQ5000-0BA21

02110

01649

Gr I

Cubicle with built-in busbars and form 3


and 4b separation

8/10

Siemens LV 56 2008

Internal Separation
Modular Separation for Switching Devices

Overview

01638

Separation for 400mm deep cubicles

2
3

01816

1 Horizontal partition
1

2 Vertical separation on connecting cable side


3 Rear vertical separation

Separation for 600mm and 800mm deep cubicles

Siemens LV 56 2008

8/11

Internal Separation
Modular Separation for Switching Devices

Description

Configuration

For assembly kits such as Sentron 3VL, 3VT, 3K, modular


devices on DIN rail and modular mounting plates, a modular
separation system is available.

For modular devices on DIN rail supporting crossbars must also


be provided.

Equipment assembly kits achieve form 1 separation.

400mm deep cubicles require a horizontal partition and a


vertical partition for each branch unit.

Form 2b is achieved through the separation of main bars and


vertical distribution busbars.

600mm and 800mm deep cubicles require a horizontal partition


and a vertical partition for each branch unit.

Form 4b is achieved through the combination of horizontal,


vertical and rear partitions.

For 50mm high vertical partitions, order 2 25mm kits.

Height of module
mm

Width
mm

Cubicle depth
mm

Branch current
A

Ordering code

UI

25

400, 600, 800

8PQ5000-2BA63

600
800

400, 600, 800


400, 600, 800

8PQ5000-2BA61
8PQ5000-2BA62

1
1

25
100
150
200
200
250
250
300
300
300
350
350
400
450
500
550
600
600
650
700
700
800

400, 600, 800


400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800
400, 600, 800

250
400
250
400
250
400
800

800

800

800

8PQ5000-2BA63
8PQ5000-2BA27
8PQ5000-2BA28
8PQ5000-2BA30
8PQ5000-2BA31
8PQ5000-2BA32
8PQ5000-2BA33
8PQ5000-2BA34
8PQ5000-2BA35
8PQ5000-2BA46
8PQ5000-2BA36
8PQ5000-2BA47
8PQ5000-2BA37
8PQ5000-2BA38
8PQ5000-2BA40
8PQ5000-2BA41
8PQ5000-2BA42
8PQ5000-2BA48
8PQ5000-2BA43
8PQ5000-2BA44
8PQ5000-2BA50
8PQ5000-2BA45

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

02111

Fastening crossbars

02112

Horizontal partition

Vertical separation on connecting cable side

02113

02114

Rear vertical separation

8/12

Siemens LV 56 2008

50

600

600, 800

8PQ5000-2BA51

100

600

600, 800

8PQ5000-2BA52

150

600

600, 800

8PQ5000-2BA53

200

600

600, 800

8PQ5000-2BA54

250

600

600, 800

8PQ5000-2BA55

300

600

600, 800

8PQ5000-2BA56

350

600

600, 800

8PQ5000-2BA57

450

600

600, 800

8PQ5000-2BA58

550

600

600, 800

8PQ5000-2BA60

Internal Separation
Modular Separation for Switching Devices

Description

Configuration

Form 4 separation kit per Sentron 3VL in draw out version,


consisting of horizontal, vertical and rear partitions.

For each Sentron 3VL kit in draw out version, order 1 separation
kit.

Selection and ordering data


Circuit breaker

No. of
poles

Height of
module
mm

Width
mm

Cubicle depth
mm

Cable
connection

Ordering code

UI

02115

Sentron 3VL, horizontal installation, form 4 separation


VL160, VL250

3/4

250

600

400

front

8PQ5000-1BA76

VL400

3/4

300

600

400

front

8PQ5000-1BA77

VL630

350

600

400

front

8PQ5000-1BA80

VL630

300

600

400

front

8PQ5000-1BA81

VL160, VL250

3/4

250

600

600, 800

front, rear

8PQ5000-1BA82

VL400

3/4

300

600

600, 800

front, rear

8PQ5000-1BA84

VL630

3/4

1)

VL160, VL250

3/4

350

600

400, 600, 800

front, rear

8PQ5000-1BA86

VL400, VL630

3/4

400

600

400, 600, 800

front

8PQ5000-1BA87

1
1

VL800

3/4

600

600

600, 800

front, rear

8PQ5000-1BA88

VL1250/VL1600

3/4

650

600

600, 800

front, rear

8PQ5000-2BA00

VL160, VL250

3/4

350

800

400, 600, 800

front, rear

8PQ5000-2BA01

VL400/630

3/4

400

800

400, 600, 800

front, rear

8PQ5000-2BA02

02117

02116

Sentron 3VL, pull-out, vertical installation, form 4 separation

1) siehe modulare Unterteilung Kapitel 8/13

Siemens LV 56 2008

8/13

Internal Separation
Modular Separation for Switching Devices

Description

Configuration

The connecting terminal kit achieves separation from form 4a


to form 3b.

In addition to the partitions, the required number of terminals


(with or without copper busbars) has to be ordered.

Separation from form 3b to form 4b is achieved through the


combination of connecting terminal and protective bellows.

When using the connecting busbar assembly kit for SENTRON


3VL circuit breakers, terminals need not be ordered.

Selection and ordering data


Busbar
mm mm

Ordering code

UI

01716

01732

01683

Current
A

2 25 5

1 30/40 10

Connecting terminal, separation installation from 4a to 3b

without busbar

8PQ5000-0BA05

250 A

2 25 5

8PQ5000-0BA72

400 A

1 30 10

8PQ5000-0BA73

630 A

1 40 10

8PQ5000-0BA74

8PQ9400-0BA03

Bellows, separation installation from 3b to 4b

8/14

Siemens LV 56 2008

Air-Conditioning Products

9/2

Introduction

9/2

Filter Fans

9/3

Air-Conditioning/Cooling Units

9/4

Heat Exchangers

9/5

Fan Heaters

9/5

Thermostats

Siemens LV 56 2008

Air-Conditioning Products
Introduction

Overview
When selecting the individual air-conditioning units, the following factors must be taken into account: ambient temperature,
power dissipated from the devices installed, maximum admissible temperatures of the devices, heat dissipated via the cubicle, and degree of protection required.

Switchgear may be subject to overheating, condensate or


mould formation due to the presence of hot, cold or moist air in
the immediate surroundings.
In this case, the cubicle should be air-conditioned.
The following air-conditioning units are available for this purpose:
Filter fans
Air-conditioning/cooling units
Heat exchangers
Heaters/thermostats

The installation of air-conditioning devices improves the reliability of switchgear and controlgear, making for enhanced machine and system availability.

Filter fans

Description

Configuration

Using fans and equipping the switchgear enclosures with ventilation fins are the most economical methods to control the temperature inside a cubicle.
However, the temperature reached inside the board is higher
than ambient temperature.

When adopting filter fans the temperature via the board enclosure must not be considered.
Filter fans must be installed in the lower part of the board. If possible, outlet filters must be installed in the upper part, on the door
or a side panel.
The use of thermostats makes for longer filter fan and filter life.
Outlet filters should be at least the same size as the cut-out
made in the door for the filter fan.
A simple formula to determine the quantity of air needed is:
Air needed = 1,2 x Pv / t
t = interior temperature - ambient temperature
Pv = Installed power dissipated
For an exact determination, computation software can be supplied on request.
Notice - the standard colour is RAL 7032: special colour orders
must be defined with -Z Z = specify the RAL.

Selection and ordering data


Size
V AC

Air flow-rate
through free intake
IP54
W/K

Air flow-rate
with outlet filter
IP54

Exterior
dimensions
mm x mm

Cut-out in
door
mm x mm

Ordering code

UI

15 (IP43)
15 (IP43)
43
43
108
108
231
231
368
368
437
437

105 x 105
105 x 105
150 x 150
150 x 150
250 x 250
250 x 250
250 x 250
250 x 250
325 x 325
325 x 325
325 x 325
325 x 325

92 x 92
92 x 92
125 x 125
125 x 125
223 x 223
223 x 223
223 x 223
223 x 223
291 x 291
291 x 291
291 x 291
291 x 291

8MR3101-0MA
8MR3101-0JA
8MR3102-0MA
8MR3102-0JA
8MR3103-0MA
8MR3103-0JA
8MR3104-0MA
8MR3104-0JA
8MR3105-0MA
8MR3105-0JA
8MR3106-0MA
8MR3106-0JA

1
1
1
1
1
1
1
1
1
1
1
1

346 (IP33)
540 (IP33)

417 x 367
530 x 350

345 x 265
345 x 265

8MR3140-1DA
8MR3180-1DA

1
1

105 x 105
150 x 150
250 x 250
325 x 325

92 x 92
125 x 125
223 x 223
291 x 291

8MR3111-0AA
8MR3112-0AA
8MR3113-0AA
8MR3115-0AA

1
1
1
1

Filter fans with standard filter mat for door-mounted installation


230
115
230
115
230
115
230
115
230
115
230
115

24 (IP43)
24 (IP43)
58
58
155
155
255
255
478
478
606
606

Filter fan for top plate installation with standard filter mat
230
230

450 (IP33)
800 (IP33)

Outlet filter with standard filter mat for door-mounted installation

9/2

Siemens LV 56 2008

Air-Conditioning Products
Air-Conditioning/cooling Units

Description

Applications

Air-conditioners are used for ambient temperatures higher than


the temperature admissible for the equipment installed in the
cubicle. All the units work with FCC free cooling systemsAir-conditioners dehumidify the air inside the cubicle.

Cooling units for door, side panel or roof mounting


Two separate cooling circuits ensure that no hot air remains
inside the cubicle.
High-performance radial fans provide for effective air circulation
inside the cubicle.
Temperature controller with built-in thermostat (roof mounted).
Side-panel mounted units
Standard electronic components, technical characteristics:
Test module
Temperature limit
Time lat at start-up
Door contact function
Fault indicator contact
On-site diagnostics
UL approval.
Notice - the standard colour is RAL 7032: special colours orders
must be defined with -Z Z = specify the RAL.

Selection and ordering data


Power
W

Voltage
V

Ordering code

UI*

Panel or door (flush) mounted air-conditioners


1000

230

1500
2000

400/440

2500

8MR5 5101TE

1 piece

8MR5 5151TE

1 piece

8MR5 5201TE

1 piece

8MR5 5251TE

1 piece

9
Filter fans with standard filter mat
320

115/320

8MR4 0321SA

1 piece

500

8MR4 0501SA

1 piece

820

8MR5 0821SA

1 piece

1100

8MR5 1101SA

1 piece

1400

8MR5 1401SA

1 piece

1400

400/440

1800
2500
3200

230

5000

8MR5 1441SA

1 piece

8MR5 1801SA

1 piece

8MR5 2501SA

1 piece

8MR4 3202SB

1 piece

8MR4 5002SB

1 piece

Roof-mounted air-conditioners
810

230

1150
1600
3000

400

3200

400

5000

8MR5 0811DA

1 piece

8MR5 1151DA

1 piece

8MR5 1601DA

1 piece

8MR5 3001DA

1 piece

8MR4 3202DB

1 piece

8MR4 5002DB

1 piece

* You can order this quantity or multiples thereof.


Siemens LV 56 2008

9/3

Air-Conditioning Products
Heat Exchangers

Description
Air-air principle (8ME78)

Air-water principle (8MR5)

The heat exchangers working according to the air-air principle


use two fully separate air circuits: an exterior circuit and an inner
circuit.

The heat exchangers working according to the air-water


principle use 1 air circuit.

A fan draws in cold air from the exterior. By means of another fan
the hot interior air is conveyed to an element separated by
laminas, which, in its turn, conveys the air onto the exterior
circuit.

A fan conveys the hot air inside the cubicle to the heat
exchanger.
In this manner, the heat is transferred to the cooling medium
(water) and the temperature of the air inside the cubicle is
reduced.
Notice - the standard colour is RAL 7032: special colour orders
must be defined with -Z Z = specify the RAL.

Selection and ordering data


Version

Voltage
V

Size

Ordering code

UI*

Aluminium, not treated

220-240

16/06

8ME7 844-0

1 piece

Painted RAL 7032

220-240

16/06

8ME7 844-1

1 piece

Aluminium, not treated

220-240

20/06

8ME7 864-0

1 piece

Painted RAL 7032

220-240

20/06

8ME7 864-1

1 piece

Power
W

Voltage
V

HWD
mm

Ordering code

UI*

Heat exchangers

35 C
Hot air from
the equipment

Cubicle

Cold air
recirculation

25 C

NSE0_01391

Heat exchangers for side mounting


500 200 100

8MR5 065-2WS

1 piece

1000

500 200 100

8MR5 100-2WS

1 piece

1450

1350 390 189

8MR5 145-2WS

1 piece

1500

950 400 115

8MR5 150-2WS

1 piece

650

2450

230

230

3000

1350 390 189

8MR5 245-2WS

1 piece

950 400 190

8MR5 300-2WS

1 piece

4000

860 560 137

8MR5 400-2WS

1 piece

5000

1400 460 235

8MR5 500-2WS

1 piece

Heat exchangers for roof mounting


1450
2100

230

600 390 140

8MR5 145-2WD

1 piece

720 465 190

8MR5 210-2WD

1 piece

* You can order this quantity or multiples thereof.

9/4

Siemens LV 56 2008

Air-Conditioning Products
Fan Heaters

Applications

Configuration

Cubicle heaters are used to prevent malfunctions probably


caused by condensation formation and corrosion phenomena
as well as to maintain a minimum interior temperature.
The design of the aluminium profile ensures even temperature
distribution, making for optimised heating effects.

To prevent corrosion problems, the difference between exterior


and interior temperatures must be about 5K.
The required heating power can be determined from the Pv /T
diagram given in chapter 12/9.
PHeizung = Pv x k3 x k4 x k5 x k6

Selection and ordering data


Power
W

Voltage
V

10

110-250

Series

Ordering code

UI*

Heaters
20
30
15

110-250

HGK047

8MR2 110-0B

2 pieces

HGK047

8MR2 110-2B

2 pieces

HGK047

8MR2 110-3B

2 pieces

HG140

8MR2 130-1A

2 pieces

20

HG140

8MR2 130-3A

2 pieces

45

HG140

8MR2 130-4A

1 piece

60

HG140

8MR2 130-6A

1 piece

75

HG140

8MR2 130-7A

1 piece

100

HG140

8MR2 130-0A

1 piece

150

HG140

8MR2 130-5A

1 piece

Thermostats

Applications
The (NC/NO) thermostats installed in cubicles are used to
control the interior temperature and make sure that the
admissible temperatures of the devices are not exceeded.

They are used to control the operation of cooling units, filter fans,
heat exchangers.

Selection and ordering data


Version

Temperature
C

Series

Ordering code

UI*

0 ... + 60

KTO 01140

8MR2 170-1BA

3 pieces

10 ... + 50

KTO 01140

8MR2 170-1CA

3 pieces

+ 20 ... + 80

KTO 01140

8MR2 170-1DA

3 pieces

0 ... + 60

KTS 01141

8MR2 170-1BB

3 pieces

10 ... + 50

KTS 01141

8MR2 170-1CB

3 pieces

+ 20 ... + 80

KTS 01141

8MR2 170-1DB

3 pieces

+ 20 ... + 80

ZR 011

8MR2 170-1E

2 pieces

Thermostats
NC

NO

Twin thermostat
NC/NO

Mechanical thermostats
CO

+ 10 ... + 60

FZK 011

8MR2 170-1A

2 pieces

20 ... + 30

FZK 011

8MR2 170-1B

1 piece

* You can order this quantity or multiples thereof.


Siemens LV 56 2008

9/5

Air-Conditioning Products
Notes

9/6

Siemens LV 56 2008

10

Accessories

10/2

Fasteners

10/3

Miscellaneous Parts

Siemens LV 56 2008

Accessories
Fasteners

Selection and ordering data


Description

Ordering code

UI

01719

Fasteners for mechanical connections


Self-tapping screw DIN 7500 - M6x10

8PQ9500-0BA34

100

Self-tapping screw DIN 7500 - M6x16

8PQ9500-0BA32

100

Self-tapping screw DIN 7500 - M6x20

8PQ9500-0BA31

100

RAL7035 caps for self-tapping screws

8PQ9400-0BA14

100

Self-tapping hex-head screw DIN 7500 - M6x12

8PQ9500-1BA07

100

Description

Ordering code

UI

Carriage bolt DIN 603 - M10x35

8PQ9500-0BA14

50

Carriage bolt DIN 603 - M10x45

8PQ9500-0BA16

50

Carriage bolt DIN 603 - M10x55

8PQ9500-1BA36

50

Carriage bolt DIN 603 - M10x65

8PQ9500-1BA25

50

Busbar connection kit for M10 screw

8PQ9400-0BA02

20

Description

Ordering code

UI

01743

01720

Fasteners for electrical connections, rectangular profiles 1

01742

Fasteners for busbar electrical connections, with H profiles H1


T-head screw - M10x25

8PQ9500-0BA01

100

T-head screw - M10x35

8PQ9500-0BA02

100

Description

Ordering code

UI

Fasteners for electrical connections1

10

Hexagon-head screw ISO 4017 - M8x25

8PQ9500-0BA77

50

Hexagon-head screw ISO 4017 - M8x35

8PQ9500-0BA78

50

Hexagon-head screw ISO 4017 - M12x40

8PQ9500-0BA88

50

Hexagon-head screw ISO 4014 - M12x50

8PQ9500-0BA64

50

Hexagon-head screw ISO 4014 - M12x60

8PQ9500-1BA02

50

Hexagon-head screw ISO 4014 - M12x80

8PQ9500-1BA51

50

Hexagonal nut ISO 4032 - M8

8PQ9500-0BA07

50

Hexagonal nut ISO 4032 - M10

8PQ9500-0BA05

50

Hexagonal nut ISO 4032 - M12

8PQ9500-0BA04

50

Clamping washer DIN 6796 - 8

8PQ9500-0BA58

50

Clamping washer DIN 6796 - 10

8PQ9500-0BA60

50

Clamping washer DIN 6796 - 12

8PQ9500-0BA61

50

Washer DIN 125 - 8.4

8PQ9500-0BA70

50

Washer DIN 125 - 10.5

8PQ9500-0BA67

50

Washer DIN 125 - 13

8PQ9500-1BA33

50

Lock washer BN208012 - 8

8PQ9500-0BA48

50

Lock washer BN208012 - 10

8PQ9500-0BA50

50

Lock washer BN208012 - 12

8PQ9500-0BA51

50

1) For electrical connections make exclusive use of 8.8 strength class fasteners.

10/2

Siemens LV 56 2008

Accessories
Miscellaneous Parts

Selection and ordering data


Description

Ordering code

UI

SIVACON SIEMENS ID plate

8PQ9400-0BA06

1/4 turn screws

8PQ9400-0BA17

20

Rotary handle with flat cylinder, hinged on left side

8PQ9400-0BA07

Button operated handle, lockable, hinged on left side

8PQ9400-0BA08

Semi-cylindrical profile acc. to DIN 18252/18254 8x45, adjustable, various locks

8PQ9400-0BA26

Key with two-way locking mechanism, 3mm

8PQ9400-0BA12

10

Crossbar for installation in cubicle, 400mm wide


Crossbar for installation in cubicle, 600mm wide
Crossbar for installation in cubicle, 800mm wide
Crossbar for installation in cubicle, 1000mm wide
Crossbar for installation in cubicle, 1200mm wide
Crossbar for installation in cubicle, 400mm deep, with side upright or 600mm, 800mm deep
Crossbar for installation in cubicle, 600mm deep (without side upright)
Crossbar for installation in cubicle, 800mm deep (without side upright)
Universal mounting bracket

8PQ3000-0BA12
8PQ3000-0BA71
8PQ3000-0BA72
8PQ3000-0BA84
8PQ3000-0BA85
8PQ3000-0BA10
8PQ3000-1BA24
8PQ3000-1BA25
8PQ9400-0BA01

2
2
2
2
2
2
2
2
10

Cable bracket, C30 profile, cubicle depth 400mm, 600mm, 800mm


Cable bracket, C30 profile, cubicle width 400mm
Cable bracket, C30 profile, cubicle width 600mm
Cable bracket, C30 profile, cubicle width 800mm
Cable bracket, C30 profile, cubicle width 1000mm
Cable bracket, C30 profile, cubicle width 1200mm
Corner piece to fasten cable brackets

8PQ3000-0BA38
8PQ3000-0BA41
8PQ3000-0BA42
8PQ3000-0BA43
8PQ3000-0BA86
8PQ3000-0BA87
8PQ3000-0BA73

5
5
5
5
5
5
10

Double profile DIN rail, 35mm, L = 1600mm

8PQ9600-0BA01

Lifting eyebolts
Lifting brackets for 400mm wide cubicle
Lifting brackets for 600mm wide cubicle
Lifting brackets for 800mm wide cubicle
Lifting brackets for 1000mm wide cubicle
Lifting brackets for 1200mm wide cubicle

8PQ9400-0BA11
8PQ3000-0BA88
8PQ3000-1BA00
8PQ3000-1BA01
8PQ3000-1BA02
8PQ3000-1BA03

4
2
2
2
2
2

02120

Column ID plate

00004

02122

02121

01717

02154

Door and special covers

01715

01669

01684

01682

01668

01681

Mechanical accessory parts

Siemens LV 56 2008

10/3

10

Accessories
Miscellaneous Parts

Selection and ordering data


Description

Ordering code

UI

Electrical accessories
8MF4900

Schuko socket max 250 V, with 6,3 A fuse, mounting on 35 mm DIN rail

8MF9300

Schuko socket max 250 V, without 16 A fuse, mounting on 35 mm DIN rail

8MF9005

Limit switch for single door, 1 NO/NC

8MF4310

Limit switch for double door, 1 NO/NC

8MF4311

Door grounding strip, 6mm2

8PQ9400-0BA15

10

Cable entry for segregation

8PQ9400-0BA16

20

Bit for Torx screwdriver M6 1/4 50mm

8PQ9400-0BA05

Bit for Torx screwdriver M6 1/4 200mm

8PQ9400-0BA10

Screwdriver with case and charger

8PQ9400-0BA22

Spray - RAL 7035

8GF9388-2

Spray basic blue-green colour

8PQ9400-0BA04

Solid frames for modular devices 12 UM

8GK9910-0KK00

Depth adapters for modular devices from 70 to 55mm deep

8GF9670-1

Cover for modular devices

5ST3800

Instrument plug 72mm x 72mm

8GF7770-4

Instrument plug 96mm x 96mm

8GF7770-5

Plastic diagram pocket DIN A4

8GD9132

ID stickers, L1, L2, L3, N, PE

8GK9920-0KK27

02155

02127

02126

02125

02124

Lamp with 11 W fluorescent tube, Schuko socket, On/Off switch and magnetic clamp

02156

Tools

Repair paint

Other parts

10

10/4

Siemens LV 56 2008

1
10

11

Mechanical Dimensions

11/2

Cubicle

11/3

Base and Enclosure

11/4

Enclosure

11/6

Busbar System

11/8

Terminals

11/9

Mounting Plates

11/10

Covers, modular doors

11/11

SIVACON 8PS Duct Connections

11/15

SENTRON 3VL with Motorised


Operating Mechanism

Siemens LV 56 2008

Mechanical Dimensions
Cubicle

Structure

01750

W
Width

d
Depth

h
Height

400

400

2000

600

600

800

800

1000
1200

Floor anchoring of cubicle without base

L2

L2

400

350,0

400

250,0

400

350,0

400

310,0

600

550,0

600

450,0

600

550,0

600

510,0

800

750,0

800

650,0

800

750,0

800

710,0

1000

850,0

1000

910,0

1200

1050,0

1200

1110,0

11/2

Siemens LV 56 2008

L1

01753

01752

11

L1

Mechanical Dimensions
Base and Enclosure

01755

01754

Base

L2

400

350,0

400

250,0

600

550,0

600

450,0

800

750,0

800

650,0

1000

850,0

1200

1050,0

L1

Door, rear and side panel, with and without design strip
Rear panel

Side panel
without
design strip

01756

01757

Side panel
with
design strip

Door

Top plate upgraded to IP X1

11

Side view

01759

01758

Front view

Siemens LV 56 2008

11/3

Mechanical Dimensions
Enclosure

01762

Top plate with cable entry

01763

11

11/4

Siemens LV 56 2008

Mechanical Dimensions
Enclosure

01760

Bottom plate with cable entry

01761

11

Siemens LV 56 2008

11/5

Mechanical Dimensions
Busbar System

01764

01765

01767

Main busbar systems in standard position

01766

Busbar systems in free position

Grounding bar PE

NSEX_00006

01768

11

11/6

Siemens LV 56 2008

Mechanical Dimensions
Busbar System

01771

01772

Vertical busbar systems, cascaded

01769

Vertical busbar systems, non-cascaded

01770

11

Siemens LV 56 2008

11/7

Mechanical Dimensions
Terminals

01783

01784

Terminal

Busbar arrangement

01749

11

up to 250 A

11/8

Siemens LV 56 2008

up to 400 A

up to 630 A

Mechanical Dimensions
Mounting Plates

01781

Modular mounting plates, with and without holes

01778

01779

01777

Position

86,0

106,0

126,0

145,0

175,0

204,0

210,0

229,0

249,0

264,0

284,0

600

253

800

353

Galvanised chrome plate for electrotechnical applications

320

600

520

800

720

1000

920

1200

1120

01774

01773

01775

400

Siemens LV 56 2008

11/9

11

Mechanical Dimensions
Covers, Modular Doors

Cover

02183

Cover

Interior door or modular door

02129

02128

Modular door

11

11/10

Position

170

190

210

229

259

288

294

313

333

330

368

Siemens LV 56 2008

Mechanical Dimensions
SIVACON 8PS Duct Connections

02179

02180

SIVACON 8PS with connections to top

02182

SIVACON 8PS with connections to bottom

02181

11

Siemens LV 56 2008

11/11

Mechanical Dimensions
SIVACON 8PS Duct Connections

02161

02160

Cut-out in top plate for combination of RX duct with Sentron 3WL Gr I, 3, 4 poles and 3WL Gr. II, 3 poles

Cut-out in top plate for combination of LX duct with Sentron 3WL Gr I, 3, 4 poles and 3WL Gr. II, 3 poles

02163

02162

11

11/12

Siemens LV 56 2008

Mechanical Dimensions
SIVACON 8PS Duct Connections

02165

02164

Cut-out in top plate for combination of DX duct with Sentron 3WL Gr II, 3 and 4 poles

Cut-out in top plate for combination of duct LX05..., LX06..., LX07 with Sentron 3WL Gr. II, 3 and 4 poles

02167

02166

11

Siemens LV 56 2008

11/13

Mechanical Dimensions
SIVACON 8PS Duct Connections

02169

02168

Cut-out in top plate for combination of duct LX08... with Sentron 3WL gr. II, 3 and 4 poles

11

11/14

Siemens LV 56 2008

Mechanical Dimensions
SENTRON 3VL with Motorised
Operating Mechanism

02212

Dimensions for equipment combination including, circuit breaker, removable or fixed door and motorised operating mechanism

Equipment mounting plate installed in the deepest mounting position. For rear terminal bars, the use of rear vertical partitions is limited.
Dimensions when set to ON * [mm]
Above the cover
A

Above the cubicle


B

Above the inner door


C

VL 160-250

50

-12

-37

VL 400

72

10

-14

VL 630

111

48

23

VL 800

105

43

18

VL 1250/1600

126

62

37

* In sectioning position, the dimensions increase from 27 to 32mm.


Take into account the additional space necessary to pull out the equipment.

11

Siemens LV 56 2008

11/15

Mechanical Dimensions
Notes

11

11/16

Siemens LV 56 2008

12

Planning
and Configuration

12/2

SIMARIS CFB

12/3

Configuration Procedure

12/4

Check List for SIVACON S4

12/6

Correction Factors

12/8

Internal Temperature of
Low-Voltage Power Distribution
Boards

12/10

Example

Siemens LV 56 2008

Planning and Configuration


SIMARIS CFB

Overview

With SIMARIS CFB easy planning and programming


SIMARIS CFB facilitates offer processing and project execution
thanks to the following functions:
Management of project and customer data

Output functions: list of components, images, SingleLine, bid


documents

Configuration of SIVACON S4 low-voltage distribution board


with integrated selection of specific equipment and devices
as a function of geographic location
It is always possible to integrate new products, such as Alpha
small distribution boards, at any time

Advantages
Easy to manage Windows interface
Integrated product database, updated by download
Rule-based configuration with choice of characteristics not
depending on product
A detailed knowledge of products and systems is not required

12

Possibility to make changes with ease at both offer and


construction stage
Many output functions
Order placement by e-mail
Reduced workload
Price determination/calculation

12/2

Siemens LV 56 2008

Planning and Configuration


Configuration Procedure

Overview
The planning and configuration of low-voltage power distribution
boards is an important, cost-determining factor within the scope
of power distribution board construction. The following notes are
based on a network calculated with a special procedure. This
chapter is to support the manufacturer of power distribution

boards with the planning and configuration of low-voltage power


distribution boards. Additionally, the manufacturer has to comply
with international standards and regional provisions. The terms
used are explained in the Appendix.

Configuration procedure
1. Reading of specification and determination of characteristics
(check list)
- Network system, voltage level
- Transformer power, input currents, short-circuit strength
- Ambient temperature, degree of protection
- Mounting type (single-front / back-to-back / free-standing /
wall)
- Arrangement of power distribution board / installation
surface (operating and maintenance aisles, escape
direction)
- Type of connection (cable or busbar)
- Access to cable, busbar connection (front, rear)
- Cable/busbar entry (top, bottom)
- Ambient conditions (condensation, chemical emissions)
- Device installation systems (fixed, plug-in, withdrawable
design)
- Safety requirements (internal separation, resistance to
internal arcs)
- Date of delivery (tender / order)
- Reserve
2. Configuration of power distribution board (conversion of
characteristics into power distribution board technology)
- Determination of the busbar system
- Arrangement of incoming feeders and couplings
- Determination of feeders
- Feeder-section allocation

3. Optimisation of power distribution boards


- Optimised space utilisation concerning:
Device selection
Feeder arrangement
- Cost optimisation concerning:
Device selection
Busbar version (reduced cross-section with centre
infeed)
4. Testing of power distribution board configuration
- Determination of the power loss per section
- Determination of the section's internal temperature
- Verification that the sections internal temperature <= max.
ambient temperature of the applied devices
- Determination of the reduction factors in accordance with
the calculated ambient temperature of the applied devices
- Verification that max. operating current <= rated current x
reduction factor
- If one of the conditions to be verified is not complied with,
the power distribution board configuration has to be
modified concerning
device selection
feeder arrangement
and the tests must be repeated..

12

Siemens LV 56 2008

12/3

Planning and Configuration


Check List for SIVACON S4

Check List for SIVACON S4


Project name: ______________________________________________________________________________________
Customer:

_______________________________________________________________________________________

Planner:

_______________________________________________________________________________________

Date of delivery:__________________
Installation site/height:

_______ m (above MSL)

Ambient temperatue:

_______ C

Relative air humidity: ______________ %

 yer

Condensation risk?

 no

Harmful substance:_____________________________________
Mounting type:

 single-front  back-to-back

Degree of protection to interior:

IP _______________

Degree of protection to cable floor:

IP _______________

Requirements regarding resistence to internal arcs:

 yes

 wall

 free-standing

Internal separation: form _____________

 no

 which: _______________________

Maximum distribution board dimensions:

W H D ______________ mm

Maximum transport dimensions:

W H D ______________ mm

Network type:

 TN-S

Cross-section PEN/N:
Cross-section PE:

 TN-C

Room height: __________ mm

 TN-C-S

 TT

 reduced ________%

 full 100%

 IEC

 acc. to type test

 25% of external conductor cross-section

Transformer power:

________________________ kVA

Rated current of infeed:

________________________ A

Frequency:

________________________ Hz

Rated operating voltage:

________________________ V

Rated short-time withstand current Icw (1 sec.)

________________________ kA

12

12/4

Siemens LV 56 2008

 IT

Planning and Configuration


Check List for SIVACON S4

Infeeds
Connection:

 busbar

 cable

Access to calbe/busbar entry:

 from the front

 from the rear

Cable / busbar entry:

 top

 bottom

 fixed-mounted

 withdrawable

Intallation system for switching devices:


Air circuit breakers(ACB):

Molded case circuit breakers (MCCB) 630A:  fixed-mounted

 withdrawable

Molded case circuit breakers (MCCB) <= 630A:  fixed-mounted

 withdrawable

 plug-in design

 fuseless

 fused

Switch disconnectors (LBS)


Remarks:

 fixed-mounted

__________________________________________________________________________________
__________________________________________________________________________________

Feeders
Connection:

 busbar

 cable

Access to calbe/busbar entry:

 from the front

 from the rear

Cable / busbar entry:

 top

 bottom

 fixed-mounted

 withdrawable

Intallation system for switching devices:


Air circuit breakers(ACB):

Molded case circuit breakers (MCCB) 630A:  fixed-mounted

 withdrawable

Molded case circuit breakers (MCCB) <= 630A:  fixed-mounted

 withdrawable

 plug-in design

 fuseless

 fused

Switch disconnectors (LBS)


Remarks:

 fixed-mounted

__________________________________________________________________________________
__________________________________________________________________________________

Feeder reserve:

_______________ %

Empty space reserve:

_______________ %

Miscellaneous:

__________________________________________________________________________________
__________________________________________________________________________________

Siemens LV 56 2008

12/5

12

Planning and Configuration


Correction Factors

Rated currents and initial short-circuit AC currents of three-phase distribution transformers with 50 to 3150 KVA
Rated
voltage UcT

400/230, 50 Hz

Rated value of the


short-circuit voltage ukt

525 V, 50 Hz

4% 1)

6% 2)

690/400 V, 50 Hz
4% 1)

6% 2)

4% 1)

6% 2)

Rated power

Rated
current Ir

Initial short-circuit
AC current Ik 3)

Rated
current Ir

Initial short-circuit
AC current Ik 3)

Rated
current Ir

Initial short-circuit
AC current Ik 3)

kVA

50

72

1933

1306

55

1473

995

42

1116

754

100

144

3871

2612

110

2950

1990

84

2235

1508

160

230

6209

4192

176

4731

3194

133

3585

2420

200

288

7749

5239

220

5904

3992

167

4474

3025

250

360

9716

6552

275

7402

4992

209

5609

3783

315

455

12247

8259

346

9331

6292

262

7071

4768

400

578

15506

10492

440

11814

7994

335

8953

6058

500

722

19438

13078

550

14810

9964

418

11223

7581

630

910

24503

16193

693

18669

12338

525

14147

800

1154

20992

880

15994

670

9349

1000

1444

26224

1100

19980

836

15140

1250

1805

32791

1375

24984

1046

18932

1600

2310

41857

1760

31891

1330

24265

2000

2887

52511

2200

40008

1674

30317

2500

3608

65547

2749

49941

2090

37844

3150

4550

82656

3470

62976

2640

47722

12120

1) ukr = 4%, standardised in accordance with DIN 42503 for Srt = 50 ... 630 kVA
2) ukr = 6%, standardised in accordance with DIN 42511 for Srt = 100 ... 1600 kVA
3) Ik Unaffected initial short-circuit AC current of the transformer upon connection to a network with unlimited short-circuit power considering the voltage factor
and the correction factor of the transformer impedance in acc. with DIN EN 60909 I DIN VDE 0102 (July 2002)

Correction factors for installation heights over 2000 m above MSL


The low air density at altitudes over 2000 m affects the electrical
characteristics of the power distribution board. The rated

currents are subject to the following correction factors for


installation heights above 2000 m over MSL..

Correction factors for installation heights over 2000 m above MSL


Altitude of
installation site

K1 for the load

up to

2200 m
2400 m
2500 m
2700 m
2900 m

0,88
0,87
0,86
0,85
0,84

up to

3000 m
3300 m
3500 m

0,83
0,82
0,81

up to

4000 m
4500 m

0,78
0,76

up to

5000 m

0,74

In = In <= 2000 m x k1

12

Reduced switching capacity for erection heights over 2000 m above MSL
If the boards are erected at altitudes over 2000 m, the devices'
reduced switching capacity must be taken into account. For the

12/6

Siemens LV 56 2008

correction factors, refer to the technical documents of the


devices.

Planning and Configuration


Correction Factors

Correction factors for busbar systems at ambient temperatures of <> 35 C


The rated currents for main busbar and distribution busbar
systems indicated in the catalogue refer to the ambient
temperatures for indoor installation described in IEC/EN
60439-1.
Consequently, the ambient temperature for low-voltage power

distribution boards does not exceed +40 C and the average


value of a period of 24 h is not higher than +35 C. For ambient
temperatures, whose average value deviates from this ambient
temperature, the following correction factors must be observed.

1,15

1,1

1,05

K2

0,95

0,9

0,85

0,8
15

20

25

30

35

40

45

50

55

Ambient temperature [C]


(1) Main busbars
(2) Vertical disribution busbars

In = In 35 C x K2

Correction factors for devices


At ambient temperatures of >40 C, the rated operating current
has to be derated for devices. The ambient temperature of the
devices complies with the internal temperature of the lowvoltage

power distribution boards at the installation site. For the


correction factors, refer to the technical documents of the
devices.

12

Siemens LV 56 2008

12/7

Planning and Configuration


Internal Temperature
of Low-Voltage Power Distribution Boards

Determination of the internal temperature of low-voltage power distribution boards


With a calculation in accordance with IEC 60890, the internal
temperature of low-voltage power distribution boards can be
specified on the basis of the total power loss and the system
structure.
1. Power loss of busbar systems per section
For the determination of the power loss of main busbars and
distribution busbar systems, the operating current [A] on the
respective length [m] has to be specified. The power loss
assigned to the respective busbar configuration is illustrated in
the following diagram.
Main busbar systems
1000
800
Pv [W/m]

600

3
1

400

(1) 2x(20x10) mm2


(2) 2x(30x10) mm2
(3) 4x(20x10) mm2
(4) 4x(30x10) mm2

200
0
0

500

1000

1500

2000

2500

I [A]
1200
7

Pv [W/m]

1000

6
8

800

600
400
(5) 4x(40x10) mm2
(6) 4x(50x10) mm2
(7) 2x4x(20x10) mm2
(8) 2x4x(30x10) mm2

200
0

500

1000 1500 2000 2500 3000 3500 4000


I [A]

Distribution busbar systems


600
500

10

Pv [W/m]

11

400
12

300
200
(9) DIN rail 30x30 mm
(10) DIN rail 40x30 mm
(11) 2x(30x10) mm2
(12) 2x(40x10) mm2

100

12

0
0

200

400

600

800

1000

1200

1400

I [A]
PV Main busbar system
= PV [W/m] x Lnge [m]
= PV [W/m] x Lnge [m]
PV Distribution busbar system
PV Busbar system/section= PV main busbar system+ PV distribution busbar system

12/8

Siemens LV 56 2008

Planning and Configuration


Internal Temperature
of Low-Voltage Power Distribution Boards

Determination of the internal temperature of low-voltage power distribution boards


2. Power loss of devices per section

4. Determination of the sections internal temperature

For the power loss, refer to the technical documents of the


devices. In this context, the actual utilisation (operating current,
temporal simultaneousness, rated load factor) has to be
observed.

The diagram below illustrates the correlation between the


installed power loss and the temperature difference, based on
the calculation procedure of IEC 60890 as well as the specific
data of SIVACON S4. The diagram refers to a section in degree
of protection IP55 which is installed side-by-side with a free roof
and rear panel. In case of deviating conditions, the correction
factors of the following table have to be considered.

For terminal bars, cables and lines as well as for small devices,
a percentage increase of 10% has to be considered.
Ir = operating current
In = rated current
PV device = PV devicet x (Ir /

In)2

PV device / section = total (PV device) x 1,1


3. Installed power loss per section
The installed power loss per section is the sum of the power loss
of busbar systems and devices.
PV section = PV busbar system / section+ PV device/section

Ventilated section
Degree of protection <= IP4X
k3

Section with free


side panel
k4

1,65

1,09

Roof not free

Rear panel not free

k5

k6

0,95

0,92

PV section

PV =

k3 x k4 x k5 x k6
40,0
35,0
1

30,0

3
4

25,0

5
7

dT [K]

PVn device = power loss device at rated current

20,0
15,0
10,0
5,0
0,0
0

100

200

300

400

500

Pdiss [W]
Height x width x depth [mm] of the section
(1) 2000x400x600
(2) 2000x400x800
(3) 2000x600x400
(4) 2000x600x600

(5) 2000x600x800
(6) 2000x800x400
(7) 2000x800x600
(8) 2000x800x800

The determined temperature difference refers to the average


height in the section. The temperature linearly increases from the
average section height to the complete section height with
sufficient accuracy and has to be specified for SIVACON S4 with
a correction factor of 1.4.
Internal temperature in average section height [C] =
Ambient temperature of the power distribution board [C] +
temperature difference dT [K]
Internal temperature in complete section height [C] =
Ambient temperature of power distribution board [C] +
Temperature difference dT [K] x 1.4

Siemens LV 56 2008

12/9

12

Planning and Configuration


Example

Example for a power distribution board configuration test


Power distribution board data

Determination of the power loss per section

Rated operating voltage Ue


Rated short-time current Icw
Rated load factor
Degree of protection
Ambient temperature
Section height
Base height
Section depth
Cable connection infeed
Cable connections outputs

400V / 50Hz
35kA
0.8
IP40
35 C
2000mm
100mm
600mm
from the top
rear bottom
(rear panel free)

PV section 1 = (PV busbar system section 1 + PV device section 1) x 1,1 =


743,81 W
PV section 2 = (PV busbar system section 2 + PV device section 2) x 1,1 =
354,82 W
Determination of the internal temperature
Factors section 1
k3 1.65
k4 1.09
k5 0.85
k6 1

Front view
Factors section 2

k3 1.65
k4 1.09
k5 1
k6 1
PV section 1 =
PV section 2 =

486.56 W
197.29 W

Internal temperature in acc. with diagram page

12/9

Temperature difference in half section height section 1


Temperature difference in half section height section 2

22 K
12 K

Internal temperature in half section height for section 1


Internal temperature in half section height for section 2

57 C
47 C

Internal temperature in section height for section 1


Internal temperature in section height for section 2

66 C
52 C

Configuration test
According to the technical documents of the devices, the limit
temperatures are not exceeded.

01625

The devices are able to carry the specified rated currents.

Determination of the power loss of the busbar systems per section


In 0,8 [A]
Section 1

Lenght [m]

PV busbar system
[W/m]

PV busbar system
[W]

200

0,45

520

0,2

50

10

904

0,3

160

48

704

0,25

100

25

PV busbar section 1 =

3,6

86,6 W

Determination of devices power lass per section

12

Section 1

Section 2

Location

In [A]

In x 0,8 [A]

PV device max [W]

PV device [W]

Infeed

01.D1

1424

825

495.06

Output

01.J1

250

200

80

51.20

Output

01.K1

250

200

80

51.20

Output

02.D1

250

200

80

51.20

Output

02.F1

400

320

170

108.80

Output

02.K2

630

504

254

162.56

PV device section 1 =

597.46 W x 1.1 = 657.21 W

PV device section 2 =

322.56 W x 1.1 = 354.82 W

12/10

Siemens LV 56 2008

13

Appendix

13/2

Glossary

13/8

Order Information

13/10

Standards and Approvals

13/11

Quality Management

13/12

Online Services

13/13

Customer Support

13/14

Training

13/15

Subject Index

13/16

Conditions of Sale and


Delivery, Export Regulations

Siemens LV 56 2008

Appendix
Glossary

Rated values/definitions
The terms defined below are used in the present catalogue in
accordance with IEC 60439-1 and EN 60439-1.

Section panel
IEC/EN 60439-1; 2.2.2

Low-voltage switchgear and controlgear assembly


IEC/EN 60439-1; 2.1.1

Component of a switchgear and controlgear assembly positioned


between two superimposed horizontal limiting levels inside a
section.

Assembly of one or more switching devices combined with


corresponding operating equipment for control, measuring and
signalling tasks and with protective and control devices, etc. The
individual devices are completely assembled by the manufacturer,
including all internal electrical and mechanical connections and
construction components.
Type-tested low-voltage switchgear and controlgear assembly
(TTA)
IEC/EN 60439-1; 2.1.1.1
Low-voltage switchgear and controlgear assembly which complies
with the original type or system of the switchgear and controlgear
assembly type-tested in accordance with this standard without
significant deviations.
Functional unit
IEC/EN 60439-1; 2.1.5
Part of a switchgear and controlgear assembly with all electrical and
mechanical components which contribute to the execution of the
same function.
Cubicle
IEC/EN 60439-1; 2.4.1
Component of a switchgear and controlgear assembly which serves
the accommodation of various components of a switchgear and
controlgear assembly or of an enclosure.
Section
IEC/EN 60439-1; 2.2.1

Compartment
IEC/EN 60439-1; 2.2.3
Section or section panel which is encased with the exception of
openings required for connection, control or ventilation.
Transport unit
IEC/EN 60439-1; 2.2.4
Part of a switchgear and controlgear assembly or complete switchgear
and controlgear assembly which is not disassembled for transportation.
Rated diversity factor
IEC/EN 60439-1; 4.7
The rated diversity factor of a switchgear and controlgear assembly
or of a component of a switchgear and controlgear assembly (e.g.
section, section panel) which comprises several main circuits is the
ratio of the largest sum of all currents which are to be expected in the
respective main circuits at any given time to the sum of the rated
currents of all main circuits of the switchgear and controlgear
assembly or of the affected part of the switchgear and controlgear
assembly. If the manufacturer states a rated diversity factor, this
value must be taken as a basis for the temperature-rise test.

Number of main current circuits

Rated diversity factor

2 and 3
4 and 5
6 up to and including 9
10 uand more

0.9
0.8
0.7
0.6

Component of a switchgear and controlgear assembly positioned


between two successive vertical limiting levels.
Rated values
In accordance with IEC/EN 60439-1;4, the manufacturers of lowvoltage
switchgear and controlgear assemblies state rated values. These rated
values apply to the specified operating conditions and characterise the
usability of switchgear and controlgear assemblies. The coordination of
the operating equipment or the configuration of the switchgear and
controlgear assemblies must be based on these rated values.
Rated short-time withstand current (Icw)
IEC/EN 60439-1; 4.3
As the effective short-circuit current value, the rated short-time
withstand current characterises the thermal strength of switchgear
and controlgear assembly circuits during a short-time load. The
rated short-time withstand current is normally determined for the
duration of 1 sec; deviating time values must be indicated. The rated
short-time withstand current is stated for the distribution and/or main
busbars of switchgear and controlgear assemblies.
Rated peak withstand current (Ipk)
IEC/EN 60439-1; 4.4

13

As peak value of the peak current, the rated peak withstand current
characterises the dynamic strength of switchgear and controlgear
assembly circuits. The rated peak withstand current is stated for the
distribution and/or main busbars of switchgear and controlgear
assemblies.

13/2

Siemens LV 56 2008

Rated conditional short-circuit current (Icc)


IEC/EN 60439-1; 4.5
The rated conditional short-circuit current corresponds to the
uninfluenced short-circuit current which a circuit of the switchgear
and controlgear assembly, that is protected by short-circuit
protective devices, may carry without damage (for a limited time).
The rated conditional short-circuit current is therefore stated for
outgoing and/or incoming feeders, e.g. with circuit breakers.
Rated impulse withstand voltage (Uimp)
IEC/EN 60947-1; 4.3.1.3
Parameter for the resistance of clearances inside switching devices
to impulse overvoltages. The application of suitable switching
devices prevents disconnected system parts from transmitting
overvoltages from the network in which they are applied.

Appendix
Glossary
Rated current (In) (of circuit breakers)
IEC/EN 60947-2; 4.3.2.3

Rated continuous current (Iu)


IEC/EN 60947-1; 4.3.2.4

Current which, for circuit breakers, corresponds to the rated


continuous current and the conventional thermal current.
Rated continuous current

Current which can be carried by switching devices in continuous


operation (for weeks, months or years).

Rated control voltage (Uc)


IEC/EN 60947-1; 4.5.1

Rated making capacity


IEC/EN 60947-1; 4.3.5.2

Voltage applied to the actuating NO contact of a control circuit. It


may deviate from the rated control supply voltage if transformers or
resistors are connected to the control circuit.

Current which can be switched on by switching devices with the


respective rated operating voltage in accordance with the utilisation
category.
Rated operating voltage

Rated ultimate short-circuit breaking capacity (Icu)


IEC/EN 60947-2; 4.3.5.2.1

Rated frequency
IEC/EN 60947-2; 4.3.3

Maximum short-circuit current which can be interrupted by a circuit


breaker (test O CO). After a short-circuit switch-off, the circuit
breaker is able to trip with increased tolerances in the case of
overload.

Frequency for which switching devices are dimensioned and to


which the other characteristic data refer.
Rated operating voltage, rated continuous current

Rated service short-circuit breaking capacity (Ics)


IEC/EN 60947-2; 4.3.5.2.2
The short-circuit current depending on the rated operating voltage
which can be repeatedly interrupted by a circuit breaker (test O
CO CO). After the short-circuit breaking, the circuit breaker is able
to continue to carry the rated current in the case of increased
selfheating and to trip in case of overload.
Rated continuous current
Rated operating voltage

Rated insulation voltage (Ui)


IEC/EN 60947-1; 4.3.1.2
Voltage to which the insulation tests and creepage distances refer.
The maximum rated operating voltage must, in no case, exceed the
rated insulation voltage.
Rated operating voltage
Rated short-circuit breaking capacity (Icn)
IEC/EN 60947-1; 4.3.6.3

Rated operating capacity


IEC/EN 60947-1; 4.3.2.3

Maximum current which can be switched off by switching devices


with the rated operating voltage and frequency without causing
damage. The value is stated as effective value.
Rated operating voltage

Capacity which can be switched by switching devices with the


assigned rated operating voltage in accordance with the utilisation
category, e.g. power contactor of utilisation category AC-3: 37 kW at
400 V.

Rated short-circuit breaking capacity (Icm)


IEC/EN 60947-1; 4.3.6.2

Rated operating voltage (Ue)


IEC/EN 60947-1; 4.3.1.1
Voltage to which the characteristic values of switching devices are
referred to. The maximum rated operating voltage must, in no case,
exceed the rated insulation voltage.
Rated insulation voltage

Maximum current which can be switched on by switching devices


with a certain rated operating voltage and frequency without
causing damage. Deviating from the other characteristic data, the
value is stated as peak value.
Rated operating voltage

Rated operating current (Ie)


IEC/EN 60947-1; 4.3.2.3
Current which can be carried by switching devices in consideration
of the rated operating voltage, the operating time, the utilisation
category and the ambient temperature.
Rated operating voltage

13
Siemens LV 56 2008

13/3

Appendix
Glossary

Ambient conditions / Degrees of protection


The climate and external ambient conditions (natural impurities,
toxic chemically active substances, small animals) may have severe
repercussions on the functionality of electrical systems.
The effect depends on the climatic protection of the room in which
the system is installed.
In the presence of high concentrations of toxic substances it is
advisable to adopt appropriate measures to reduce them, for
example:
Intake of air from an area with a lower pollution level

Exposing the area to a mild overpressure (e.g., introducing non


polluted air into the system)
Climate control of the room where the system is installed
(reducing the temperature, relative humidity of the air < 60%,
possible installation of a purifying filter)
Attenuation of overheating (overdimensioning of electrical
equipment and components such as main busbars and
distribution busbars)

Ambient conditions

Class

Classification of ambient conditions with the relative limit values


(defined according to standard IEC 60721-3-3)

Measurements

Climatic

3K4

Minimum temperature of the air


Maximum temperature of the air

Minimum relative humidity of the air


Maximum relative humidity of the air
Minimum absolute humidity of the air
Maximum absolute humidity of the air
Temperature variation rate
Minimum air pressure
Maximum air pressure
Solar radiation
Thermal radiation
Movement of the air
Condensate formation
Matter deposited by the wind
Water (other than rain)
Ice accumulation
Other ambient climatic
conditions

Biological

3Z1

Thermal radiation is negligible

3Z7
3Z9
3Z10

Water drops as defined in standard IEC 60068-2-18


Water spray as defined in standard IEC 60068-2-18
Water jets as defined in standard IEC 60068-2-18

3B2

5 C 1)
+ 40 C
+ 35 C (24h-Mittel) 2)
5%
95 %
1 g/m_
29 g/m_
0,5 C/min
70 kPA
106 kPA
700 W/m2

1,0 m/s
possible

Provide heating,
if frequent 1 per day
for 2 hours

No
See other ambient climatic
conditions
No

IPX1
IPX4
IPX5

Flora

Mold formation

Fauna

Presence of rodents and other


harmful animals, other than
termites

IP4X, including protection for technical floors

Chemically active
substances

3C3

Marine salt
Sulphurous anhydride SO2
Hydrogen sulphide H2S
Chlorine Cl2
Hydrogen chloride HCl
Hydrofluoric acid HF
Ammonia NH3
Ozone O3
Nitrogen oxide NOx

Salt mist 2 mg/dm2


5,0 mg/m3 (2 ppm)
3,0 mg/m3 (2 ppm)
0,3 mg/m3 (0,1 ppm)
1,0 mg/m3 (0,7 ppm)
0,1 mg/m3 (0,06 ppm)
10,0 mg/m3 (14,3 ppm)
0,1 mg/m3 (0,05 ppm)
3,0 mg/m3 (1,66 ppm)

Mechanically active
substances

3S1

Sand in the air


Dust (matter in suspension)
Dust (matter deposited)

0,01 mg/m3
0,4 mg/(m2 * h)

< IP5X

3S3

Sand in the air


Dust (matter in suspension)
Dust (matter deposited)

300 mg/m3
0,4 mg/m3
15 mg/(m2 * h)

IP5X

1) According to standard IEC60721-3-3 the minimum admissible air temperature is + 5 C


2) Higher values can be admitted on request (see dimensioning tables)

13
13/4

Siemens LV 56 2008

Appendix
Glossary

Network systems
Distribution systems (network types) in acc. with IEC 60364-3
(DIN VDE 0100-300)
Determination of protective measures and selection of the electrical
operating equipment according to the distribution system.

L1

TN systems

L2

TN-S system
The neutral conductor and protective conductor
function are consistently separated in this system.

L3
N
PE

L1

TN-C system
The neutral conductor and protective conductor
function are composite throughout the entire
system.

L2
L3
PEN

L1

TN-C-S system
Combination of the neutral and the protective
conductor function. In one part of the system, they
are composite in one conductor, while they are
separated in another part.

L2
L3
PEN

PE
N

13

1
1 Body
Siemens LV 56 2008

13/5

Appendix
Glossary

Network systems
Distribution systems (network types) in acc. with IEC 60364-3
(DIN VDE 0100-300)
Determination of protective measures and selection of the electrical
operating equipment according to the distribution system.

L1

TT system
In the TT system, one point is directly earthed; the
elements of the electrical system are connected to
earth electrodes which are separated from the signal
earth. The TT system corresponds to the system in
which today the protective measures protective
earthing, RCCB and fault-voltage circuit breaker are
applied.

L2
L3
N

PE
1
L1

IT system
The IT system features no direct connection between
active conductors and earthed parts; the elements of
the electrical system are earthed. The IT system
corresponds to the system in which today the
protective conductor system protective measure is
applied.

L2
L3
2
PE
1
1 Body

2 Impedance

First letter = Earthing condition of the


supplying current source

Second letter = Earthing condition of the


elements of the electrical system

Further letters = Arrangement of the neutral


and the protective conductor

T = Direct earthing of one point


I = Either insulation of all active parts of the
earth or connection of one point to the
earth via impedance

T = Elements are directly earthed,


irrespective of a possible earthing of
one point of the current supply
N = Elements are directly connected to the
signal earth; in AC current networks, the
earthed point is generally the star point

S = Neutral and protective conductor


function by means of separated
conductors
C = Neutral and protective conductor
function combined in one conductor
(PEN)

13
13/6

Siemens LV 56 2008

Appendix
Glossary

Operating and maintenance aisles

2000

1)

(in acc. with DIN VDE 0100 Part 729)

500
700

600

700

700

700

1) Minimum passage height beneath covers or casings.

Minimum passage height beneath covers or casings.

Minimum aisle width


700 or 600 mm

Escape direction

Free minimum
clearance 500 mm 1)

2)

1) With opposing power distribution board fronts, constriction by open doors (i.e. doors which do not close towards the escape direction) is only accounted
for on one side.
2) Door widths must be observed, i.e. a minimum door opening angle of 90.

13
Siemens LV 56 2008

13/7

Appendix
Order Information

Logistics
General

Packaging, packing units

Our logistics service offers quality from the order to the


delivery pertaining to delivery service, communication and
environmental protection. To maintain this high quality, we focus
on the optimisation of the logistical procedures on the basis of a
customised infrastructure and automatic DP order processing.

Our device and shipping packagings offer protection against


dust and mechanical damage during transport, thus ensuring
that the customer receives the devices in a flawless condition.
When selecting and designing our packagings, we set great
value upon environmental compatibility, re-usability (e. g.
crumpled paper instead of styrofoam chips as transport
protection in shipping packages up to 32 kg) and above all,
upon waste prevention.

We attach major importance to personal support, deliveries in


due time and area-wide transportation.
The DIN-ISO-9001 certification and a consistent quality
management are vital issues for us.
The automatic DP order processing is fast, cost-effective and
fail-safe. If you would like to exploit these benefits, please do not
hesitate to contact us.

13
13/8

Siemens LV 56 2008

Unless otherwise stated in the selection and ordering data of this


catalogue, our devices are supplied in separate individual
packages.
The device order numbers can be easily identified by means of
the EAN bar code, which simplifies both order and warehouse
logistics. The low-voltage controls and distribution master data
include the allocation of order numbers and EAN code for data
processing.

Appendix
Order Information

Ag and Cu surcharges
Surcharges for copper (Cu) and silver (Ag) will be added to the
prices of certain products. The amount of the surcharge
depends on the percentage taken from the current list price.
Calculation of the surcharges is governed by the official Ag
quotation for refined silver and the applicable Cu-DEL quotation
on the date of receipt of order or of call-off.

Small orders
When small orders are placed, the costs associated with order
processing are greater than the order value. We recommend
therefore that you combine several small orders. Where this is
not possible, we unfortunately find it necessary to charge a
processing supplement of 20.-- to cover our costs for order
processing and invoicing for all orders with a net goods value of
less than 250.--.

The prices for products include the price of copper calculated


on the basis of a list price of 150/100 kg.

Orders for special designs


For ordering products that differ from the versions listed in the
catalog, the order number specified in the catalog must be
supplemented with Z; the required features must be
specified by means of the alphanumeric order codes or in plain
text.

13
Siemens LV 56 2008

13/9

Appendix
Standards and Approvals

CE mark of conformity
Manufacturers of products which fall within the subject area to
which EU directives apply must identify their products,
instruction manuals or packaging with a CE mark of conformity.
The CE mark of conformity confirms that a product fulfills the
appropriate basic requirements of all pertinent directives. The
mark of conformity is a mandatory requirement for putting
products into circulation throughout the EU.

All the products in this catalog are in conformance with the EU


directives and bear the CE mark of conformity.
Low-voltage directive (NS 73/23/EU)
EMC directive (EMC 89/336/EU)
The manufacturer of the system assembled from individual
modules is responsible for the preparation of the EC declaration
of conformity.

ALPHA/LOVAG
The Low-Voltage Controls and Distribution Division of Siemens
AG is a member of the "Gesellschaft zur Prfung und
Zertifizierung von Niederspannungsgerten e.V. ALPHA"
(Society for Testing and Certification of Low-Voltage Equipment),
Frankfurt am Main.
The responsibility of manufacturers and the high quality of
products are promoted by ALPHA by means of supportive
procedural guidelines for testing equipment according to the
currently valid standards.
Providing specific conditions are fulfilled, ALPHA can also issue
officially recognized product certificates if required. As a
member of LOVAG, ALPHA is also working towards obtaining
international recognition for declarations of conformity and
certificates.
LOVAG (Low-Voltage Agreement Group) is a body comprising
international specialists from certification bodies and industry
who are working together to create a standardized European
certificate.

13
13/10

Siemens LV 56 2008

List of LOVAG members


ALPHA
ASEFA
ACAE
CEBEC
Intertek Semko AB
APPLUSS

Germany
France
Italy
Belgium
Sweden
Spain

Appendix
Quality Management

Quality management
The quality management system of our A&D division complies
with the international standard EN ISO 9001.
The products and systems described in this catalog are sold
under application of a quality management system certified by
DQS and TV Management Service GmbH in accordance with
ISO 9001. The certificates are recognized in all IQ Net countries.

DQS Registered Certificate Nos.:


Siemens AG
Automation and Drives
Industrial Automation Systems
Reg. No.: 001323 QM
Industrial Communication SIMATIC NET
Reg. No.: 002613 QM.
TV (German Technical Inspectorate)
Registered Certificate No.:
Siemens AG
Automation and Drives
Low-Voltage Controls
Reg. No.: 12 100 16950 TMS.
BVQI Registered Certificate No.:
Siemens AG
Automation and Drives
Electrical Installation Technology
Reg. No.: 117779

13
Siemens LV 56 2008

13/11

Appendix
Online-Services

A&D in the WWW


A detailed knowledge of the range of products and services
available is essential when planning and configuring automation
systems. It goes without saying that this information must always
be fully up-to-date.
The Siemens Automation and Drives Group (A&D) has therefore
built up a comprehensive range of information in the World Wide
Web, which offers quick and easy access to all data required.
Under the address
http://www.siemens.com/automation
you will find everything you need to know about products, systems and services.

Product selection using the Offline Mall of Automation and Drives


Detailed information together with convenient interactive functions:
The Offline Mall CA 01 covers more than 80,000 products and
thus provides a full summary of the Siemens Automation and
Drives product base.
Here you will find everything that you need to solve tasks in the
fields of automation, switchgear, installation and drives. All information is linked into a user interface which is easy to work with
and intuitive.
After selecting the product of your choice you can order at the
press of a button, by fax or by online link.
Information on the interactive catalog CA 01 can be found on the
Internet under
http://www.siemens.com/automation/ca01
or on CD-ROM and DVD..

Easy shopping with the A&D Mall


The A&D Mall is the virtual department store of Siemens AG in
the Internet. Here you have access to a huge range of products
presented in electronic catalogs in an informative and attractive
way.
Data transfer via EDIFACT allows the whole procedure from selection through ordering to tracking of the order to be carried out
online via the Internet.
Numerous functions are available to support you.
For example, powerful search functions make it easy to find the
required products, which can be immediately checked for availability. Customer-specific discounts and preparation of quotes
can be carried out online as well as order tracking and tracing.
Please visit the A&D Mall on the Internet under:
http://www.siemens.com/automation/mall

13
13/12

Siemens LV 56 2008

Appendix
Customer Support

Configuration and software engineering


Support in configuring and developing with customeroriented
services from actual configuration to implementation of the automation project.2)

Technical support
.I

Competent consulting in technical questions covering a wide


range of customer-oriented services for all our products and systems.

In the face of harsh competition you need optimum conditions to


keep ahead all the time:
A strong starting position. A sophisticated strategy and team for
the necessary support - in every phase.
Service & Support from Siemens provides this support with a
complete range of different services for automation and drives.

Tel.: +49 (0) 180 50 50 222


Fax: +49 (0) 180 50 50 223

In every phase: from planning and startup to maintenance and


upgrading.

http://www.siemens.com/
automation/support-request

Our specialists know when and where to act to keep the productivity and cost-effectiveness of your system running in top form.

Service on site

Online support

With service on site we offer services for startup and maintenance, essential for ensuring
system availability.

The comprehensive information


system available round the
clock via Internet ranging from
Product Support and Service &
Support services to Support
Tools in the Shop.
http://www.siemens.com/
automation/service&support

Technical consulting

Tel.: +49 (0) 180 50 50 444 2)

Repairs and spare parts


Support in the planning and designing of your project from detailed actual-state analysis,
target definition and consulting
on product and system questions right to the creation of the
automation solution.2)

Technical assistance
Expert technical assistance1)
for Low-voltage controls and
electrical installation.
Tel.: +49 (0) 9 11 8 95-59 00
Fax: +49 (0) 9 11 8 95-59 07

In the operating phase of a machine or automation system we


provide a comprehensive repair
and spare parts service ensuring the highest degree of operating safety and reliability.
Tel.: +49 (0) 180 50 50 446 2)

Optimization and upgrading


To enhance productivity and
save costs in your project we offer high-quality services in optimization and upgrading.2)

E-Mail: technical-assistance
@siemens.com

1) Contact:
Technical assistance for product selection Old/new coding
Competitor coding Special versions Special requirements Sales
promotion (Infoline).
Your regional contacts for sales support (prices, discounts, delivery times).
Technical Support for commissioning support and after-sales service.

2) For country-specific telephone numbers go to our Internet site at:


http://www.siemens.com/automation/service&support

13
Siemens LV 56 2008

13/13

Appendix
Training

Training is decisive for your success


SITRAIN

- the Siemens Training for Automation and Industrial


Solutions - provides you with comprehensive support when solving your tasks.
Training by the market leader in automation, plant installation
and support permits you to make your decisions with certainty
and full command. Especially where the optimum and efficient
use of products and plants are concerned. You can eliminate
deficiencies in existing plants, and exclude expensive faulty
planning right from the beginning.
All in all, this represents an enormous gain for your company: shortened startup times, optimized plant components,
faster troubleshooting, reduced down times. In other words,
increased profits and lower costs.

The right mixture: Blended Learning


Blended learning is understood to be the combination of various
training media and sequences. For example, a local attendance
course in a Training Center can be optimally supplemented by a
teach-yourself program as preparation or follow-up. Furthermore, SITRAIN utilizes supported online training for live instruction on the Internet at agreed times.
The right mixture is the solution. Therefore blended learning
can convey complex topics well, and train networked thinking. Additional effect: reduced travelling costs and periods
of absence through training sequences independent of location and time.

The international training portal


http://www.siemens.com/sitrain
All training facilities at a glance: search in the worldwide range
of courses at leisure, call up all course dates online, utilize the
daily updated display of vacant course spaces - and register directly.

Customer comments on Sitrain


" ... the good course documents, competence and flexibility convinced me.
[Manfred Riek from Festo Systemtechnik, responsible for planning the basic and further training of project engineers]
" ... represents effective training, constructive dialogs, and solutions which provide great help."
[Gnter Niedermaier, electrical design manager at AMT, Aalen]

Contact
Visit us on the Internet at:
http://www.siemens.com/sitrain
or let us advise you personally. You can request our latest training catalog from:
Top trainers
Our trainers know their topics in practice, and possess comprehensive didactic experience. Course developers have a direct
wire to product development, and directly pass on their knowledge to the trainers.
Practical experience
The practical experience of our trainers makes it possible for
them to pass on theoretical matter in a plausible manner. But
since it is known that all theory is drab, we attach great importance to practical exercises which can comprise up to half of the
course time. You can therefore immediately implement your new
knowledge in practice. We train you on state-of-the-art methodically/didactically designed training equipment. You feel absolutely certain when trained in this manner.
Wide variety
With a total of approx. 300 local attendance courses, we train the
complete range of A&D products and a large portion of the system solutions from I&S. Telecourses, teach-yourself software
and seminars presented on the Web supplement our classical
range of courses.
Close to our customers

13

The distance is short. You can find us approx. 60 times in Germany, and worldwide in 62 countries. You wish to have individual
training instead of one of our 300 courses? No problem: we will
provide a program tailored exactly to your personal requirements. Training can be carried out in our Training Centers or at
your company.

13/14

Siemens LV 56 2008

Course office, Infoline Germany:


Tel.: +49 (0)1805 / 23 56 11 (0.12 /Min)
Fax: +49 (0)1805 / 23 56 12

Appendix
Subject Index

13
Siemens LV 56 2008

13/15

Appendix
Terms and conditions of sale and delivery
Export regulations

Terms and conditions of sale and delivery


By using this catalog you can acquire hardware and software
products described therein from Siemens AG subject to the following terms. Please note! The scope, the quality and the conditions for supplies and services, including software products,
by any Siemens entity having a registered office outside of Germany, shall be subject exclusively to the General Terms and
Conditions of the respective Siemens entity. The following terms
apply exclusively for orders placed with Siemens AG.
For customers with a seat or registered office in Germany
The General Terms of Payment as well as the General Conditions for the Supply of Products and Services of the Electrical
and Electronics Industry shall apply.
For software products, the General License Conditions for Software Products for Automation and Drives for Customers with a
Seat or registered Office in Germany shall apply.
For customers with a seat or registered office outside
of Germany
The General Terms of Payment as well as the General Conditions for Supplies of Siemens, Automation and Drives for Customers with a Seat or registered Office outside of Germany shall
apply.
For software products, the General License Conditions for Software Products for Automation and Drives for Customers with a
Seat or registered Office outside of Germany shall apply.
General
The dimensions are in mm. In Germany, according to the German law on units in measuring technology, data in inches only
apply to devices for export.
Illustrations are not binding.
Insofar as there are no remarks on the corresponding pages, especially with regard to data, dimensions and weights given these are subject to change without prior notice.
The prices are in (Euro) ex works, exclusive packaging.
The sales tax (value added tax) is not included in the prices. It
shall be debited separately at the respective rate according to
the applicable legal regulations.
Prices are subject to change without prior notice. We will debit
the prices valid at the time of delivery.
Surcharges will be added to the prices of products that contain
silver, copper, aluminum, lead and/or gold if the respective basic
official prices for these metals are exceeded. These surcharges
will be determined based on the official price and the metal factor of the respective product.
The surcharge will be calculated on the basis of the official price
on the day prior to receipt of the order or prior to the release order.
The metal factor determines the official price as of which the metal surcharges are charged and the calculation method used.
The metal factor, provided it is relevant, is included with the price
information of the respective products.

13
13/16

Siemens LV 56 2008

An exact explanation of the metal factor and the text of the Comprehensive Terms and Conditions of Sale and Delivery are available free of charge from your local Siemens business office under the following Order Nos.:
6ZB5310-0KR30-0BA1
(for customers based in Germany)
6ZB5310-0KS53-0BA1
(for customers based outside Germany)
or download them from the Internet
http://www.siemens.com/automation/mall
(Germany: A&D Mall Online-Help System)

Export regulations
The products listed in this catalog / price list may be subject to
European / German and/or US export regulations.
Therefore, any export requiring a license is subject to approval
by the competent authorities.
According to current provisions, the following export regulations
must be observed with respect to the products featured in this
catalog / price list:
AL

Number of the German Export List


Products marked other than N require an
export license.
In the case of software products, the export designations of the relevant data medium must also
be generally adhered to.
Goods labeled with an AL not equal to N are
subject to a European or German export authorization when being exported out of the EU.

ECCN

Export Control Classification Number


Products marked other than N are subject to a
reexport license to specific countries.
In the case of software products, the export designations of the relevant data medium must also
be generally adhered to.
Goods labeled with an ECCN not equal to N
are subject to a US re-export authorization.

Even without a label or with an AL: N or ECCN: N, authorization may be required due to the final destination and purpose for
which the goods are to be used.
The deciding factors are the AL or ECCN export authorization indicated on order confirmations, delivery notes and invoices.
Errors excepted and subject to change without prior notice.
A&D/VuL_ohne MZ/En 05.09.06

You might also like