Ethernet Bus-I

Ethernet Bus-II

LV Ethernet SW GROUP

SWBD-X

Sec-B

Sec-A

Sec-A

SWBD-1

BIDDER SCOPE OF SUPPLY


ONE Ethernet switch per bussection of EACH PCC / PMCC (can be TWO or more bus sections).

SWBD-Y

Sec-B

SWBD-'n'

Swichboard complete with all bus-sections (can be TWO or more bus sections).

Numerical Relay - IEC61850 compliant with FO ethernet connectivity

Other Intelligent devices with ethernet connectivity

Swichboard Bus section: MCC sec-A devices can be taken in loop / group of PCC / PMCC sec-A

Ethernet Switch for connectivity from SWBD layer. There shall not be spliting of SWBD sections between different group of LV Ethernet SW .
Each switch shall have minimum 30% spare ports

FO cable for connectivity between LV Ethernet SW group to MAIN SCADA Ethernet SW (Per Switch 100 meter
cable shall be included in offer by Bidder. For more than such total qty. unit rates shall be given to operate.)

All interconnectivity cables (FO an/or Cu wires) up to LV Ethernet SW layer, including interconnectivity of LV Ethernet SW layer, shall be
in LV switchboard Bidder's scope.