Professional Documents
Culture Documents
12.1.2 STANDARDS:
The RTUs under this tender specification shall have IEC-870-5-101 standard protocol
supported by the Front-end-server. The RTU shall additionally support IEC 61850, IEC
870-5-103, MODBUS & DNP 3.0 protocol and all relevant IEC standards.
12.1.3 TECHNICAL SPECIFICATION:-
This specification covers detailed Design, Engineering, Testing, Supply and
Commissioning of Remote Terminal Units, Interface Cabinets, Multi-Function
Transducers and other associated equipments. Such as suitable test software &
accessories for telemetry of real time electrical data from various EHV Sub-stations and
Power Stations located in Chhattisgarh.
The Load Dispatching functions at SLDC Bhilai is supplemented with the real time
SCADA system, installed & commissioned under ULDC project, using Remote
Terminal Units, which use IEC 870-5-101 protocol.
The RTUs proposed to be procured under this tender specification shall have IEC-870-
5-101 standard protocol supported by the Front-end-server along with support of
IEC61850, IEC 870-5-103 & MODBUS protocol for data acquisition from the field.
201 Volume-II
CSPTCL TR-20/03 132/33 KV S/S Amleshwar
12.1.7 MODEM:
The modem shall be supplied for communication with the front-end server / master
station. A modem combining all of the characteristics defined below is required such
that changing the communication data rate shall only require reconfiguration of the
RTU modem. The modems shall not require manual equalization and shall include self-
202 Volume-II
CSPTCL TR-20/03 132/33 KV S/S Amleshwar
test features such as manual mark/space keying, analog loop-back. The modems shall
provide for convenient adjustment of output level and receive sensitivity. The
configuration of tones and speed shall be programmable and maintained in non-volatile
memory in the modem.
The modems shall meet the following requirements as a minimum:
i) Use CCITT standards including V.24, V.28, V.52 & V.54
ii) Communicate at data rates from 50 to 1200 bits per second, factory set at 200
Bauds.
iii) Use CCITT V.21, V.23, R.35, R.37, R.38a and R.38b standard tones for the
selected data rate.
iv) Use frequency shift keying (FSK) modulation.
v) Use both 2 wire and 4 wire communication lines.
vi) Receive level adjustable from 0 to -40 dBm @ 600 Ohms.
vii) Transmit level adjustable from 0 to -30 dBm @ 600 Ohms.
viii) Have a minimum sensitivity of -48dBm.
ix) LED‟s shall be provided on modem for indicating Tx/Rx activity (ON/OFF) and
carrier fail alarm.
x) The modem shall be fed through the DC auxiliary supply available in the RTU
itself.
xi) Supporting data transmission rate shall be minimum 300-1200 bits per second for
PLCC modems. For RTUs, the data transmission rate shall be 300-19200 bits per
second.
12.1.8 MASTER STATION COMMUNICATION PROTOCOL :
A communication protocol for communicating with the front-end server conforming to
IEC-870-5-101 communication standard shall be provided. The communication
protocol shall be non-proprietary. Complete implementation details of IEC-870-5-101
protocol shall be provided and contractor shall be responsible for tuning / configuring,
in the front-end server/ master station, to establish communication with existing/ new
SCADA computer system.
203 Volume-II
CSPTCL TR-20/03 132/33 KV S/S Amleshwar
The digital status input interface shall be capable of accepting isolated, wet or dry
contract status input. The contractor shall apply necessary sensing voltage, current
limiting, and optical isolation and debounce filtering independently for each digital
status input. The sensing voltage source shall be isolated from that of the RTUs logic
power such that any noise or short circuit across the sensing supply‟s output terminals
would not disrupt the RTU operation other than the shorted digital status input.
The following types of digital inputs shall be supported:
a) Status inputs
b) SOE Inputs
c) BCD inputs
d) Binary Word inputs
e) Pulse accumulator inputs
The following types of status inputs shall be supported:
a) Single Contact Digital Status input (SS)
b) Double Contract Digital Status input point (DS)
c) Three-state status
(b) DIGITAL STATUS OUTPUTS:
For command purpose
12.1.12 CLOCK:
The internal RTU time base shall have a stability of 1 ppm that is 3.6 milli seconds per
hour or better. The RTU time will be set from time synchronization messages received
from a master station. The RTU shall synchronize its internal clock with the master
station system clock when the Time synchronization is available. It shall be possible to
display the RTU time on a local digital clock.
204 Volume-II
CSPTCL TR-20/03 132/33 KV S/S Amleshwar
Pre-wired and standardized solutions for cabling shall be used. This shall enable a few
standardized designs for the interface cabinet to be developed, all of which shall have
identical provision for various types of plug –in Company / modules (e.g. position
indication, MW and MVAR measuring signals).
The interface components for each typical bay shall comprise typical modules and sub-
assemblies logically sorted by type of interface. For example, interface component
associated to a double bus bar type feeder shall consists of a module for the circuit
breaker position indication, a module for the associated bus bar isolators position
indication, a module associated to power measurements and a module associated to
position control. Each module or sub-assembly shall be provided with all testing
(switching, disconnecting and inserting) facilities, allowing easy maintenance.
Wire ways not more than 50% full for maximum RTU configuration, shall be provided
to route the necessary connectors from the CSPTCL‟s choice of top or bottom access to
the I/O terminations. For wire way-sizing purposes, the RTU supplier shall assure that
each point uses a independent cable.
The terminal connectors should be stud type only both in the inter phase cabinet as well
as RTU. The RTU should have minimum 20% spare connectors.
The provided RTU must have 100% expandability. Each RTU shall be provided with 05
Nos of analog input card (each having capacity to accommodate 08 Nos of analog
input) and 06 Nos of digital input cards to accommodate 16 Nos single point
indications. The RTU shall be supplied with 02 Nos of CPU and 02 Nos. of modems
along with rack & power supply. The system provided should be along with basic
licence i.e it should communicate with 101, mod bus, 103 and other international
protocol. It will be the responsibility of the contractor to integrate RTU with our
SCADA. The MFT may be accommodated in respective feeder panel of RTU and
output signal of MFT shall be taken to RTU panel through 1.5 Sq mm multi strand
copper wire. The analog parameters of all 132 KV feeders & provision for 33 KV
feeders for future use, transformers, 132 KV&33KV bus voltages and frequency shall
be measured through MFT (Multi-Functional Transducer) and Breaker ON/OFF
indications shall be double point indication and isolator indication shall be single point
indication and will be coupled to RTU through OPTO isolator print (if digital input card
is provided with opto isolator then separate opto isolator print is not required). The
wiring of digital indication shall be done by 1.5 sq mm multi strand copper wire, Bus
PT voltage and frequency signal shall be terminated to RTU panel.
The RTU provided should be compatible to work with transducers as well as be able to
communicate with energy meters and numerical relays which are working on different
protocols (other than 101) . The supplied RTU‟s should be with 2 Nos. modems along
with power supply unit and other accessories (1 NO. for RTU & 1 NO. for SCADA
end). Opto isolators Print shall be similar to C&R panels size. All digital indication
wiring shall be terminated in this panel and before routing to RTU.
Although the control functions are not being implemented at present, the RTU should
be capable of supporting the same. The supply of digital out put card is not in the scope.
However, RTU should have functionality to support control functions so that as per
requirement CSPTCL may obtain control functions by simply providing digital out put
cards without any further modification in RTU.
205 Volume-II
CSPTCL TR-20/03 132/33 KV S/S Amleshwar
12 Interface Cabinet type & Details Full size floor standing cabinet.
13 Availability of Raw A.C. Supply Yes
206 Volume-II
CSPTCL TR-20/03 132/33 KV S/S Amleshwar
21 Connector types, Tag / Terminal block types Stud and bolt type for D.I.
Disconnecting link type for analog.
22 RTU internal (Inter cabinet & inside panel) and Each component will be identified with
external wiring identification methodology & tag. Each wire will be provided with
Ferruling ferrule no. at both ends. Each cable will
be identified with no. at both ends.
12.1.15 BILL OF MATERIAL OF R.T.U.
*****
207 Volume-II