Professional Documents
Culture Documents
Page 1 of 12
Table of Contents
1. International Standards 3
Page 2 of 12
1 International Standards
IEC 60870-5 Telecontrol equipment and systems.
IEC 61000-4 Electromagnetic compatibility measurement and testing.
IEC 60068-2 Heat tests.
IEC 60529 Degree of protection provided by enclosures (IP code).
IEC 60870-5-104 Telecontrol equipment and system – part5-104: transmission
protocols- network access for IEC 60870-5-101 using standard
transport profiles.
Modbus Standard communication protocol of connecting IEDs with
RTU.
IEC 61131-3 Programming Industrial Automation Systems.
IEC 62351 Security Profiles for TCP/IP used by IEC 60870-5-104.
ISO 27002 ISO standard for information security.
Page 3 of 12
x I/O modules shall be replaced without reprogramming, redefinition of configuration
parameters or rewiring of any RTU part.
x The RTUs to be supplied and installed shall provide at least the following functions:
1. Single command outputs, double command outputs (direct execute & check
back before execute).
2. Single and double state digital inputs.
3. Analogue measured inputs.
4. Sequential Event Recording (SER) with time stamping of events at the RTU.
5. RTU time synchronization from master station via NTP, and all NTP parameters
shall be configurable basis (e.g. polling interval, Sync time out, local time
format, etc.).
6. Self testing and diagnostic functions for detection and reporting of any error.
7. Automatic safe mode re-starting function.
x The RTU should have a common port for parameter / Firmware downloading and
diagnostics capability.
x The RTU shall include a remote downloading and diagnostics communication with
separate authentications.
x RTU shall be capable of operating normally within ambient temperature range up to
+65 Degrees Celsius and humidity up to 95%.
The RTU shall be capable to communicate with two distribution control centers
simultaneously in different modes (e.g. Active-Listen, Controlling-Standby, All active,
etc.) as per standard communication protocols.
The RTU should be implemented with standard IEC 60870-5-104 communication
protocol.
RTU shall have standard Ethernet communication interface port (RJ 45) which shall be
connected to any communication devices via IEC 60870-5-104.
The RTU shall be communicated to distribution control centers over DEWA RF mesh
network by using standard Ethernet communication port (RJ 45) for interface with
DEWA RF mesh network through RF bridge module.
RTU shall have the facility of configuring the following parameters under IEC 60870-5-
104 communications protocol:
x 2 IP addresses for control centers.
x 2 IP addresses for NTP.
x 2 IP addresses for remote access (future use).
x 2 IP addresses for syslogs (future use).
x Gateway IP addresses.
x Subnet IP addresses.
Page 4 of 12
x RTU IP addresses.
All details and parameter settings used under IEC 60870-5-104 protocol shall be
provided.
Time out parameters under IEC 60870-5-104 communications protocol (i.e. t0, t1,
t2 and t3) shall be configurable basis.
The RTU shall be capable to interface with IEDs (e.g. Advanced DC charger) available
within distribution secondary substation via standard Modbus protocol interface in
case required.
RTU shall have dedicated communication interface ports (RS485) to be connected to
available IEDs.
All details and parameter settings used under Modbus protocol shall be provided.
The digital inputs shall be opto-isolated up to 2.5KV. In digital input points, the status
(open / closed) of two state devices such as Load Break Switch, Fault Interrupting
Switch, etc. shall be acquired by 2 independent potential - free contacts, one for each
position and shall be reported as douple point indication. Position indications shall be
checked for validity and undefined states like open and closed (1 | 1) or neither open
nor closed (0 | 0) shall be alarmed. The RTU shall provide for run-time-monitoring,
adjustable to the device operation parameters, to avoid alarming of undefined states
while the equipment is operating. Also chatter blocking function and delay function up
to 60 seconds as a minimum should be configurable for each individual digital point
through RTU programming.
The digital input points shall be used as input to PLC logics for generating logical
operation status and transmit it to SCADA system for Load Break Switchs, transformer
CBs and Earth switchs (in case required).
Page 5 of 12
The RTU shall allow the SCADA system to demand - scan digital input data even if the
data has not changed.
In analogue measurements, the information to the analog input modules of the RTU
shall be given in the form of analog current supplied by the output of measuring
transducers or from CT & VT sensors. Analogue measurements shall be transmitted to
the master station 15 bit + sign bit.
For DC analog input modules, the following current input ranges shall be available:
- Unipolar 0-10 mA, 0-20 mA.
- Bipolar +/- 10 mA, +/- 20 mA.
Analogue signal parameters for each individual input shall be configurable through
RTU programming (e.g. Threshold level, polarity, input range, cyclic transmission, etc.).
The circuits of the analog input module shall be totally separate (i.e. each input has
own + and – point at the module).
For direct CT analog module, CT input range shall be configurable 5 Amp / 1 Amp; and
all the signal parameters for each individual input shall be configurable through RTU
programming (e.g. Threshold level, zero suppression, etc.). The primary current from
field transformer shall be configurable up to 3000 Amp in RTU configuration
RTD analogue inputs shall be available for measuring temperature with all normal
analog point configuration setting (e.g. Threshold level, polarity, input range, cyclic
transmission, etc.).
The cyclic transmission period shall be configurable up to 15 minutes as a minimum.
The Contractor shall use standard firmware as much as possible. It shall not be
necessary to perform modification to firmware, logic, or data for expansion within the
sizing parameters defined for the RTU. Contractor shall deliver all firmware files and
any required tools.
At the time the RTU is accepted, all firmware delivered must be up to date and in final
form, including all standard firmware changes and field changes initiated by the
Contractor or the Contractor's suppliers prior to acceptance. The firmware
documentation must reflect these changes.
Any Firmware update requirements (e.g. due to required functionality or required
security updates) during project execution till final issuing of Defect Liability Clearance
Certificate, shall be provided and implemented by the Contractor or the Contractor's
suppliers with official release note after DEWA approval.
In any case, changing of EPROMs or similar devices shall not be necessary when
updating RTUs firmware.
Page 6 of 12
2.8 RTU Enclosures
The Contractor shall provide and install enclosures meeting the following
requirements:
1. Protection class of the enclosures shall be IP64 as minimum. The conducted
environmental tests shall be verified by DEWA and test certificates shall be provided.
2. Provisions for bottom cable entry shall be provided with proper sealing to maintain
the IP protection class of the enclosures.
3. Suitable safety ground within the enclosure shall be earthed through copper wire
of at least 16 sq. mm to main substation earth bar, and enclosure door shall be
earthed through flexible copper braided wires of at least 16 sq. mm.
4. Miniature Circuit Breakers (MCBS) with alarm contact shall be used for main RTU
DC supply, AC supply, DC supply for digital input and DC supply for digital output.
5. Convenience outlets at 230 V AC, shall be provided.
6. Sensors for temperature alarm and heater with controller.
7. Lighting System with door limit switch.
8. Door limit switch with free contacts for door open alarm.
9. Dummy control test point device should be included for testing purpose (i.e.
double point indication & double command).
10. Clear labling for all components and wires.
11. Ventilation System (in case required) with necessary protections that provides
sufficient cooling for the components inside the enclosure to maintain high
operation performance of RTU.
12. Separate padlocks shall be provided for RTU enclosure and Local operation
switches.
Local control facility shall be provided through selector switch with spring return for
the Local close/open operation for each RMU motor (SW1 & SW2) at RTU panel to
control RMU switches when the selector (Local/Supervisory) switch of related RMU set
to Local; and local control shall be disabled when the selector (Local/Supervisory)
switch of related RMU set to Supervisory.
Page 7 of 12
2.11 Interconnections
All connections between the RTU's termination facilities and field signal wiring shall be
done by contractor through barrier-terminal blocks with knife-switch isolation,
mounted in the RTU panel to enable isolation for each signal individually and should
have clear label indications. CT/VT terminal blocks shall be provided to islolate CT/VT
connection during measurment transducer maintenance.
The above mentioned I/O signal type points plus 10% spare points from each signal
type shall be available and fully wired up to RTU terminal block interface.
Full detailes of RTU module structure to accommodate the I/O point capacity plus the
10% spare points as well as 25% space spare shall be provided.
The Contractor shall furnish a list of recommended spare parts to maintain reliable
RTU operation. The contractor shall also include a separate price schedule of 10 %
spare as minimum for all breakdown RTU components to be valid till final issuing of
Page 8 of 12
Defect Liability Clearance Certificate, and DEWA reserve the right to request quantity
fully or partialy.
The Contractor shall supply 5 portable RTU test sets (latest version notebooks) with all
required RTU software licences, tools and cables to carry out RTU configuration and
diagnostics. Each test set shall be capable of emulating communications from both the
SCADA system and the RTU. Test sets shall be capable of passively monitoring all
communication traffic on a channel without interfering with channel operation.
In addition, one complete RTU (with full card capacity) shall be provided as test RTU
along with required simulating kit for maintenance, testing and training purposes.
RTU training shall be conducted by certified trainer from OEM to get full RTU
engineering knowledge and all required facilities for theoretical and practical training
shall be available. Training plan shall be approved by DEWA, to give full knowledge on
all engineering activities related to the RTU and develop the skill and competence of
the trainees so that they can maintain, troubleshoot and configure RTU for existing
data structure or to meet the expansion of data structure in future.
Class room training for minimum 5 working days shall be conducted for 5 engineers at
least before starting commissioing activities, and In addition active participation
during installation, commissioning and testing including instructor lessons to refresh
the given training.
Contractor shall arrange documentations in separate parts namely: design,
installation, configuration and maintenance.
As built drawings for outstation equipment including but not limited to, Functional
design specification, wiring lists, data sheets and configuration shall be provided.
In addition to the supplied documents mentioned above, the contractor shall also
supply a softcopy form for all the documents.
The RTU shall have passed type test carried out at approved labs and in
accordance with IEC standers to demonstrate that the RTU comply with the
ratings stated in these standards. As a minimum, following type tests shall be
furnished:
- Dry heat test.
- Dielectric test.
- Impulse voltage withstand test.
- High frequency disturbance test.
- Mechanical requirement test.
- Contact performance test.
- Electrostatic discharge (ESD) test.
Page 9 of 12
- Electromagnetic radiation susceptibility test.
SAT shall be performed for each site to provide sufficient evidence of correct
configuration, testing and commissioning of the Remote Terminal Unit for the
Substation. SAT test book covering all tests along with connection diagrams (i.e.
for current available signals and future required signals), Point to point test for all
signals, acceptance norms and details of test instruments shall be submitted well
in advance for DEWA approval.
2.21 Warranty
Two years warranty shall be provided on materials, design and workmanship from the
date of Taking Over Certificate (TOC to be issued after 60 days of reliability run period)
after final commissioning.
Defect liability clearance certificate (DLCC) shall be issued to contractor after
successful completion of warranty period.
Page 11 of 12
x Contractor shall install separate MCB inside RTU Cabinet for RF Remote Bridge DC
Cable connectivity.
x DC system shall be provided to feed RF mesh remote bridge with 24 VDC power
supply and current rating of 0.5 Ampere, with backup supply for four hours backup
battery through safely and smooth charger in full load during interruption of AC
supply.
4 General Requirements
Page 12 of 12