Document Ref: SX018a-EN-EU Sheet 1 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 2 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
e 1,fp
p1,fp
Lj p1,fp n fp= 8
p1,fp
gv h fp p1,fp,j
p1,fp
Lj p1,fp n fp= 8
p1,fp
This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Steelbiz Licence Agreement
e 1,wp
p 1,wp n wp= 4
t fp
t f,lc
Created on 23 May 2013
Example: Column splice - non-bearing splice
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 3 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
50
80
240 80 n fp= 8
80
10
690 110
80
240 80 n fp= 8
80
50
55 150 55
This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Steelbiz Licence Agreement
260
12.5
25 85
HE 260 A
40
50 80 n wp= 4
10
350 110
80 n wp= 4
40
35 80 35
150
12 HE 300 B
19
Created on 23 May 2013
Example: Column splice - non-bearing splice
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 4 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
Number of bolts between one flange cover plate and upper column nfp = 8
Number of bolts between web cover plate and upper column nwp= 4
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 5 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
Number of bolts between one flange cover plate and upper column nfp = 8
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 6 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
Number of bolts between web cover plate and upper column nwp = 4
This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Steelbiz Licence Agreement
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 7 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 8 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
6 Design model
For maximum design compression force in the flange cover plates and
maximum compression in the web cover plates (see Figure 6.1):
Assumed that all the beams are subjected to permanent and variable
actions in combination.
M Ed
NEd = NEd,G + NEd,Q
N Ed
VEd = VEd,G + VEd,Q
V Ed
MEd is the nominal design moment (see
SN005) (due to permanent and variable
actions) in the upper column, i.e. at the
floor level immediately below the
splice.
= MEd,G + MEd,Q
For evaluation of NEd,fp,c and NEd,wp, see Sections
This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Steelbiz Licence Agreement
7 and 9 respectively.
V Ed
N Ed,fp,c
2 N Ed,wp
Figure 6.1 For maximum compression in flange and web cover plates
For maximum design tension force in the flange cover plates ( Figure 6.2):
For nominal design moment MEd, assume that the beams causing the
moment are subject to permanent and variable actions in combination
For design axial force in the column NEd,G, assume that all the beams are
subject to permanent actions only
M Ed
NEd,G is the axial force in the column due to
N Ed,G permanent action on all the beams
V Ed
VEd = VEd,G + VEd,Q
MEd is the nominal design moment (see
SN005) (due to permanent and variable
actions) in the upper column, i.e. at the
floor level immediately below the splice.
= MEd,G + MEd,Q
For evaluation of NEd,fp,t, see Section 7
N Ed,fp,t
Created on 23 May 2013
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 9 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
N Ed,fp,c =
M Ed
huc
(
+ N Ed,G + N Ed,Q ) AAf,uc
uc
15 32,50
N Ed,fp,c = 3
+ (825 + 942) = 719 kN
260 10 86,80
The maximum tensile design force on the flange cover plate (NEd,fp,t) may be SN023
calculated from:
This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Steelbiz Licence Agreement
M Ed A
N Ed,fp, t = N Ed,G f, uc
huc Auc
15 32,50
N Ed,fp, t = 3
825 = 251 kN
260 10 86,80
Note: Since NEd,fp,t is less than zero, there is no tensile force on the flange
cover plate and check (2) for tension in the flange cover plate is not required.
Design resistance
The design resistance of the flange cover plate in compression (NRd,fp,c) may
be calculated from:
Afp f y,p EN1993-1-1
N Rd,fp,c = if p1,fp,j /tfp 9 (see note 2 in Table 3.3 of EN1993-1-8)
M0 6.2.4(2)
Afp f y,p EN1993-1-1
N Rd,fp,c = N b, Rd,fp = if p1,fp,j /tfp > 9 6.3.1.1(3)
M1
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 10 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
For Lcr = 0,6 p1,fp,j and using buckling curve c, = 1,0 EN1993-1-1
6.3.1.2
1,0 3120 355
N Rd,fp,c = 103 = 1108 kN
1,0
Design check
Since NEd,fp,c < NRd,fp,c (719 kN < 1108 kN), the design axial resistance of the
flange cover plate is adequate.
N Ed,fp,c VRd,fp
where:
f ub
b = d ; ; 1,0
f u,p
e2,fp p2,fp
k1 = min 2 ,8 1,7; 1,4 1,7; 2 ,5
d0 d0
Created on 23 May 2013
Example: Column splice - non-bearing splice
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 11 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
f ub 800
= = 1,57
f u, p 510
Hence:
b = min (0,64; 1,57; 1,0) = 0,64 for end bolts and
2,8e2,fp 2,8 55
1,7 = 1,7 = 4,22
d0 26
1,4 p2,fp 1,4 150
1,7 = 1,7 = 6,38
d0 26
k1 = min(4,22; 6,38; 2,5) = 2,5
Hence:
2,5 0,64 510 24 12
( Fb, Rd ) min = 103 = 188 kN for end bolts, and
1,25
2,5 0,78 510 24 12
( Fb, Rd ) max = 10 3 = 229 kN for inner bolts.
1,25
d 24
= = 8 mm
Created on 23 May 2013
3 3
Example: Column splice - non-bearing splice
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 12 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
Since tpa > d/3, the reduction factor should be applied. EN1993-1-8
3.6.1(12)
9d 9 24
p = = = 0,81
8d + 3t pa (8 24) + (3 25)
As = 353 mm 2
0,81 0,6 800 353
Fv,Rd = 10 3 = 110 kN
1,25
Since Fv,Rd < (Fb,Rd)min i.e 110 kN < 188 kN
VRd, fp = 880 kN
This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Steelbiz Licence Agreement
Design check
Since NEd,fp,c < VRd,fp (719 kN < 880 kN), the design resistance of the flange
cover plate bolt group is adequate.
The compressive design force on one web cover plate (NEd,wp) may be
calculated from:
N Ed Aw, uc
N Ed, wp =
2Auc
1767 21,80
N Ed, wp = = 222 kN
2 86,80
Created on 23 May 2013
Example: Column splice - non-bearing splice
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 13 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
Design resistance
The design resistance of one web cover plate in compression (NRd,wp,c) may be
calculated from:
Awp f y,p
N Rd, wp,c = if p1,wp,j /twp 9 (see note 2 , Table 3.3 of EN1993-1-8) EN1993-1-1
M0 6.2.4(2)
Awp f y,p EN1993-1-1
N Rd, wp,c = N b, Rd, wp = if p1,wp,j /twp > 9 6.3.1.1(3)
M1
Design check
Since NEd,wp < NRd,wp,c (222 kN < 383 kN), the design resistance of the web
cover plate is adequate.
Web cover plates should also be checked for combined bending, shear and
axial force in accordance with 6.2.10 or 6.2.1 (5) of EN1993-1-1.
However in this case the shear force is small and the interaction is judged to
be satisfactory by inspection.
Normally (unless end, edge distances are small) column web bolt group (see
section 11) will be critical, but for completeness the verification for the web
SN023
cover plate bolt group is shown here:
N Ed, wp VRd, wp
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 14 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
Design resistance
The design resistance of the bolt group for Category A bolts (bearing type): EN1993-1-8
Fv,Rd (Fb,Rd )max
3.7
VRd,wp = Fb,Rd if
where:
f ub
This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Steelbiz Licence Agreement
b = min d ; ; 1,0
f u, p
e2, wp p2, wp
k1 = min 2 ,8 1,7; 1,4 1,7; 2 ,5
d0 d0
f ub 800
= = 1,57
f u, p 510
Hence:
b = min (0,51; 1,57; 1,0) = 0,51 for end bolts
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 15 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
2,8e2, wp 2,8 35
1,7 = 1,7 = 2,07
d0 26
1,4 p2, wp 1,4 80
1,7 = 1,7 = 2,61
d0 26
k1 = min(2,07; 2,61; 2,5) = 2,07
Hence:
2,07 0,51 510 24 8
( Fb,Rd ) min = 10 3 = 83 kN for end bolts, and
1,25
2,07 0,78 510 24 8
( Fb,Rd ) max = 10 3 = 126 kN for inner bolts.
1,25
From section 8, the design shear resistance of a single bolt (Fv,Rd), with
reduction factor bp =1.0 (i.e. web packing thickness < d/3) would be:
This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Steelbiz Licence Agreement
Fv, Rd = 136 kN
VRd, wp = 418 kN
Design check
Since NEd,wp < VRd,wp (222 kN < 418 kN), the design resistance of the web
cover plate bolt group is adequate.
Created on 23 May 2013
Example: Column splice - non-bearing splice
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 16 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
N Ed, w VRd, w
The design axial force on the upper column web (NEd,w) may be calculated
from:
N Ed Aw,uc
N Ed, w =
Auc
1767 21,80
N Ed, w = = 444 kN
86,80
Design resistance
The design resistance of the bolt group for Category A bolts (bearing type): EN1993-1-8
Fv,Rd (Fb,Rd )max
3.7
VRd,w = Fb,Rd
This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Steelbiz Licence Agreement
if
The design bearing resistance of a single bolt on the column web (Fb,Rd) is
given by:
k1 b f u, uc d t w, uc
Fb, Rd =
M2
where:
f ub
b = min d ; ; 1,0
f u, uc
p2, wp
k1 = min 1,4 1,7; 2 ,5
do
where:
e1,w 50
d = = = 0,64 for the end bolts and
3d o 3 26
p1,wp
Created on 23 May 2013
1 80 1
d = = = 0,78 for the inner bolts
3d o 4 3 26 4
Example: Column splice - non-bearing splice
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 17 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
f ub 800 EN1993-1-8
= = 1,57 Table 3.4
f u, p 510
Hence:
b = min (0,64; 1,57; 1,0) = 0,64 for end bolts
p2, pw 1,4 80
1,4 1,7 = 1,7 = 2,61
d0 26
k1 = min(2,61; 2,5) = 2,5
Hence:
2,5 0,64 510 24 7,5
( Fb,Rd ) min = 10 3 = 118 kN for end bolts, and
1,25
2,5 0,78 510 24 7,5
This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Steelbiz Licence Agreement
From section 8, the design shear resistance of a single bolt (Fv,Rd), with
reduction factor bp =1.0 (i.e. web packing thickness < d/3) would be:
Fv, Rd = 136 kN
Since ( Fb,Rd ) min < Fv,Rd < ( Fb,Rd ) max i.e 118 kN < 136 kN < 143 kN
VRd, w = n wp ( F b, Rd ) min
VRd, w = 472 kN
Design check
Since NEd,w < VRd,w (444 kN < 472 kN), the design axial resistance of the web
of the upper column is adequate.
Created on 23 May 2013
Example: Column splice - non-bearing splice
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 18 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
N Ed, u N Rd, u
For a non-bearing column splice, there is no need to carry out this check, SN023
because it will always be satisfied, since the tying force will always be less
than the design compression force. However, for a bearing column splice (see
SN019
SN019) this check will be required. But, since there is no worked example for
a bearing column splice, the above check is demonstrated here.
Design tying force
The design tying force on the column is:
N Ed, u = 400 kN
Design resistance
This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Steelbiz Licence Agreement
Conservatively it can be assumed that the tying force at the column splice is
resisted by the flange cover plates only.
Therefore, the design axial resistance of the column splice (in tension) (NRd,u)
is given by:
N Rd, u = 2 N Rd, u, fp
0 ,9 Afp,net f u,p
N Rd,u,fp = min
M,u
; nfp Fv,Rd,u ; b,Rd,u
F
where:
Afp,net = bfp t fp 2d 0 t fp = (260 12 2 26 12 ) = 2496 mm 2
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 19 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
9d 9 24
p = = = 0,81
8d + 3t pa (8 24) + (3 25)
As = 353 mm 2
0,81 0,6 800 353
Fv,Rd = 10 3 = 125 kN
1,1
The design bearing resistance of a single bolt (Fb,Rd) on the flange cover plate
is given by: EN1993-1-8
k1 b f u, p d tfp Table 3.4
Fb, Rd, u =
M, u
This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Steelbiz Licence Agreement
where:
M, u = 1,1 for tying resistance
f ub
b = min d ; ; 1,0
f u,p
e2, fp p2, fp
k1 = min 2 ,8 1,7; 1,4 1,7; 2 ,5
d0 d0
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 20 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
f ub 800
= = 1,57
f u, p 510
Hence:
b = min (0,64; 1,57; 1,0) = 0,64 for end bolts, and
e2,fp 2,8 55
2,8 1,7 = 1,7 = 4,22
d0 26
p2, fp 1,4 150
1,4 1,7 = 1,7 = 6,38
d0 26
0 ,9 Afp, net f u, p
N Rd, u,fp = min ; nfp Fv,Rd, u ; nfp Fb, Rd, u
M, u
N Rd,u,fp = min (1042; 8 125; 2 214 + 6 260 )
Design check
Since NEd,u < NRd,u (400 kN < 2000 kN), the design tying resistance of the
column splice is adequate.
Created on 23 May 2013
Example: Column splice - non-bearing splice
Discuss me ...
Document Ref: SX018a-EN-EU Sheet 21 of 21
CALCULATION SHEET
Title Example: Column splice - non-bearing splice
13 SUMMARY
The following table summarizes the values for all the applicable modes of
failure. The critical values for normal design and tying are shown in bold
type.
Discuss me ...
Example: Column splice - non-bearing splice
SX018a-EN-EU
Quality Record
Reference(s)