Catalogue s10 en PDF
Catalogue s10 en PDF
Sepam series 10
Digital protection relays
Catalogue
2008
Sepam series 10 Contents
Introduction 3
Sepam protection relays, the product of experience 3
Presentation 6
Presentation of Sepam series 10 6
Applications 7
Sepam 10 series applications 7
Connection 11
Operating diagram 11
Connection to Sepam series 10 14
Characteristics 15
Protection functions 15
Measurements 16
Electrical characteristics 17
Environmental characteristics 18
Dimensions 20
User-machine interface and dimensions 20
Sensors 21
Core balance CTs CSH120, CSH200, GO110 21
Ordering information 22
Sepam series 10 22
Introduction Sepam protection relays,
the product of experience
Protection relays constantly monitor the power network and trip the circuit breakers
to isolate the faulty portion under fault conditions: overload, short-circuit, insulation
fault.
The Sepam range of protection relays is designed for all protection applications in
medium-voltage public and industrial distribution networks.
It is made up of four series of relays with increasing performance levels:
b Sepam series 10 for simple applications.
b Sepam series 20 for usual applications.
b Sepam series 40 for demanding applications.
b Sepam series 80 for custom applications.
Selection guide Panorama of Sepam applications
for all applications
PB103452-SE_32
DE53462
b 7 relay outputs
b 1 communication port
Sepam series 20
For usual applications
Characteristics
b 10 logic inputs
DE53219
PE50465_SE
b 8 relay outputs
b 1 communication port
b 8 temperature-sensor
inputs
DE53220
Sepam series 40
For demanding applications
Characteristics
b 10 logic inputs
PE50465_SE
DE53221
b 8 relay outputs
b logical-equation editor
b 1 communication port
b 16 temperature-sensor
inputs
Sepam series 80
For custom applications
Characteristics
b 42 logic inputs
PE50463_SE
DE53222
b 23 relay outputs
b logical-equation editor
b 2 communication ports for
multi-master or redundant
architectures
b 16 temperature-sensor
inputs
b removable memory
cartridge containing settings
and parameters for rapid
PE50464_SE
DE53223
return to service
b user-machine interface
with mimic for local control M
in complete safety
b optional Logipam
programming software for
specific functions
DE53224
DE53225
Selection guide Panorama of Sepam applications
for all applications
disconnection by B22
"rate of change of
frequency"
Presentation Presentation of Sepam series 10
Sepam series 10 is a high-quality protection relay that represents the most cost-
PB103446_SE
Applications Sepam series 10 applications
Protection applications
The primary applications for Sepam series 10 are:
b protection of secondary distribution networks (MV/MV and MV/LV substations)
b protection of buildings supplied with medium voltage (MV), including office
buildings, shopping centres, industrial buildings, warehouses, etc.
b protection of low-voltage networks by tripping a Masterpact NW circuit breaker not
equipped with a Micrologic control unit.
Main HV / MV Secondary
Main HV / MV substation
substation substation
Functions Protection functions
Sepam series 10
t
DE53228
Functions Protection and measurement
Sepam series 10 functions
N B A External tripping
A Sepam series 10 A can receive, via a logic input, a tripping order from an external
protection device.
N B A Earth-fault current
This function displays the value of the fundamental of the earth-fault current.
For this measurement and for earth-fault protection (ANSI 50N/51N), the zero-
sequence input must be connected either to the common point of the three phase
CTs or to one earth-fault protection CT or to a CSH120, CSH200 or GO110 core
balance CT.
N B A Phase currents
This function displays the rms phase-current values and takes into account
harmonics up to order 13. On Sepam series 104, this function displays the three
phase currents. On Sepam series 103, only the A and C phases are connected
and displayed.
Functions Control and monitoring
Sepam series 10
Trip Closing Sepam can be used in all types of circuit-breaker control systems.
orders orders
Functions of the output relays
Relay outputs Standard assignment
O1 Circuit-breaker tripping
A 10
Closing inhibit
9 (ANSI86)
O2 Closing inhibited
O2 8
7 O3 Tripping indication
6
5
4
Trip-circuit supervision
O1
3 N B A
This function continuously monitors the trip circuit to make sure that it has not been
interrupted. The system shown opposite runs a low current through the trip circuit.
Sepam checks that the current is effectively present.
Displays the characteristics of the last fault. Sepam indicates the fault source, the
D 18
Trip
orders
Closing
orders value of the three phase currents and the earth current at the time of tripping.
O4 17
The information is stored in memory until the next fault.
Origin of recorded faults : I>, I>>, Io>, Io>> and thermal overload protection.
A 10
Closing inhibit
9
(ANSI86)
O2 8
7
6
5
N B A Record of last five events
O1 4
3
Displays the characteristics of the last five events. For each event, Sepam indicates
the fault source, the value of the three phase currents and the earth current at the
time of the event and the date and time of the event.
D 5 The events are numbered in order of occurrence and the last five are memorized.
I2 4
2
Recorded events:
I1 1 b tripping due to I>, I>>, Io>, Io>>, thermal overload protection
b tripping via input signal from external device
b fault in tripping circuit
b circuit-breaker opening and closing initiated by communication
b tripping due to I>, I>>, Io> or Io>> (logic discrimination back-up)
Shunt trip unit Closing coil
N B A Operating language
On delivery, the default language is English. The languages that may be selected are
UK English, US English, French, German, Italian, Portuguese, Spanish and Turkish.
10
Connection Operating diagram
N B A Sepam series 10 N
IA
DE53186
IB
IC
A 14
B 13
15
O3 12
25 11
14
24
13
23 10
9
Io > S O2 8
7
Io I > R
12 2-240 A
1 S 1
22
R
CSH120 11 6
CSH200 21 Io >> 5
GO110 O1 4
Io 3
0.2-24 A 2
Reset 1
A A
DE53184
DE53185
B B
C C
B B
15 15
25 25
14 14
24 24
13 13
23 23
12 12
CT
22 Io 1A/5A 22 Io
11 11
21 21
Customization via
Relay outputs Standard assignment
parameter settings
O1 Circuit breaker tripping YES
O2 Circuit breaker lockout YES
O3 Tripping indication YES
11
Connection Operating diagram
N B A Sepam series 10 B
IA
DE53189
IB
IC
I> A 14
B I> 13
15 IA
O3 12
25 max 1 S 11
14 IB R
24
13 IC I >>
23 10
9
49 RMS S O2 8
R 7
S 1
R
6
5
Io > O1 4
Io I > 3
2-240 A 2
12 1 S 1
22
R
11
21 Io >>
Io
0.2-24 A
Reset
A A
DE53188
DE53187_SE
B B
C C
15 B 15 B
25 IA 25 IA max
14 14
24 IB 24
13 13
23 IC 23 IC
Io
12 12 2-240 A
CT 22
1A/5A Io 22
11 CSH120 11
21 Io
CSH200 21 0.2 - 24 A
GO110
Customization via
Relay outputs Standard assignment
parameter settings
O1 Circuit breaker tripping YES
O2 Circuit breaker lockout YES
O3 Tripping indication YES
12
Connection Operating diagram
N B A Sepam series 10 A
IA
DE53192
IB
IC
I> A 14
B IA I> 13
15
max O3 12
25 1 S 11
14 IB R
24
13 IC
I >>
23 10
9
49 RMS S O2 8
R 7
S 1
R
6
5
Io > 1 O1 4
3
I > 2
12 Io
1 S 1
22
R
11
21 Io >>
9
D Ext
I4
8 S
Local / remote
Reset
R
7
External I3 1
6
tripping
C RS 485
1 C
COM
2 S
3 D0
D 18
4 D1
O4 17
68
16
D O5 15
5
Circuit breaker I2
4
closed 14
3 O6 13
2
TCS
Circuit I1 Watchdog
1 12
breaker open 11
O7
10
A A
DE53191
DE53190_SE
B B
C C
15 B 15 B
25 IA 25 IA
14 14
24 IB 24 IB
13 13
23 IC 23 IC
Io
12 12 2 - 240 A
CT 22
1A/5A Io 22
11 CSH120 11
21 Io
CSH200 21 0.2-24 A
GO110
Customization via
Logic inputs Standard assignment
parameter settings
I1 Circuit breaker open NO
I2 Circuit breaker closed NO
I3 External tripping YES
I4 Local / remote YES
Customization via
Relay outputs Standard assignment
parameter settings
O1 Circuit breaker tripping YES
O2 Circuit breaker lockout YES
O3 Tripping indication YES
O4 Circuit breaker closing by remote control NO
O5 Blocking send YES
O6 Indication of trip circuit fault (TCS) YES
O7 Watchdog NO
13
Connection Connection to Sepam series 10
DE53230
12 O3
11
7-8 and 9-10 Logic output O2
10
9
8 O2
11-12 and Logic output O3
7 13-14
6
5
4 O1
3
2
1
14
b for standard and sensitive earth-fault protection
B 24 IB
13 b for high sensitivity earth-fault protection (rating
Sepam series 10 N and 10 B. 23 IC
2...240 A)
12
22 Io
2-240 A 11-21 Input for earth-fault current Io, only for high
11
21
Io sensitivity earth-fault protection (rating 0.2..24 A)
0.2-24 A
C 2 Shielding
C S D0 D1
1 2 3 4 3 D0 communication - negative polarity (A)
4 D1 communication - positive polarity (B)
Wiring
Identification Type of terminal Wiring
B Screw, 4 mm (0.16 in) 16 mm2 (AWG 1810) - 2 lugs maximum
Screw clamp, 3 mm b 1 wire: 0,2...2.5 mm (AWG 24...12)
A , C et D
(0,12 in) b 2 wires: 0.2...1 mm (AWG 24...18)
Screw, 4 mm (0,16 in) 6 mm green/yellow wire (AWG 10)
14
Characteristics Protection functions
1000
Tripping curve
b DT: Definite time
b SIT/A: IEC standard inverse
b VIT/B: IEC very inverse
b LTI/B: IEC long-time inverse
b EIT/C: IEC extremely inverse
100 b MI/D: IEEE moderately inverse
b VI/E: IEEE very inverse
b EI/F: IEEE extremely inverse
b RI
I>, I>> set points
DT curve 0.1...24 In (minimum: 1 A)
10
IDMT curves 0.1...2,4 In (minimum: 1 A)
LTI/B
Accuracy 5 % or 0.02 In
RI Drop out/pick up ratio 95 %
SIT/A Transient overshoot < 10 %
Io>, Io>> set points
1
DT curve Standard version Setting range: 0.124 Ino
VIT/B
(minimum: 1 A)
Sensitive version Setting range: 0.012.4 Ino
(minimum: 0.1 A)
EIT/C High sensitivity Rating 0.224 A Setting range: 0.00040.05 Ino
version (Ino = 470 A)
0.1
I/I> Rating 2.0240 A Setting range: 0.0040.5 Ino
1 2 5 10 20
or (Ino = 470 A)
Io/Io> IDMT curves Standard version Setting range: 0.22.4 Ino
IEC curves SI, VI, LTI, EI and RI curve. (minimum: 1 A)
Sensitive version Setting range: 0.010.24 Ino
(minimum: 0.1 A)
Sec
DE53194
15
Characteristics Measurements
16
Characteristics Electrical characteristics
17
Characteristics Environmental characteristics
Power frequency for status inputs IEC 60255-22-7 - 300 V CM (1) ; 150 V DM (2)
IEC 61000-4-16 4
Safety
Safety tests
General IEC 60255-27 - -
Dielectric withstand at power frequency IEC 60255-5 - 2 kV 1 mn: logic input/outputs and supply,
IEC 60255-27 RS485 port
ANSI C37.90 - 1.5 kV ; 1 mn between open contacts
Surges 1.2/50 s IEC 60255-5 5 kV for logic inputs and outputs
IEC 60255-27 3 kV for RS485 port
Insulation resistance IEC 60255-27 - 500 V CM (1) and DM (2)
R > 100 MWB ; R > 10 MWA
18
Characteristics Environmental characteristics
Mechanical robustness
In operation
Vibrations IEC 60255-21-1 2 1 Gn ; 10...150 Hz ; 1 cycle
Shocks IEC 60255-21-2 2 10 Gn for 11 ms
Earthquakes IEC 60255-21-3 2 2 Gn horizontal, 1 Gn vertical
De-energized
Vibrations IEC 60255-21-1 2 2 Gn ; 10...150 Hz ; 20 cycles
Shocks IEC 60255-21-2 2 30 Gn for 11 ms
Bumps IEC 60255-21-2 2 20 Gn for 16 ms
Enclosure protection
Front panel IEC 60529 IP54 -
NEMA 250 Type 12 -
Rear panel IEC 60529 IP40 -
Shocks IEC 62262 IK7 2 Joules
Fire resistance IEC 60695-2-11 - 650 C
19
Dimensions User-machine interface and
dimensions
User-machine interface
1 Back-lit display
DE53450_SE
2 Status LEDs
3 Fault LEDs
4 Button for Sepam reset and maximeter reset
5 Battery housing (Sepam series 10 A)
6 Protection cover for settings
7 Identification zone
8 Lead-seal accessory
9 Button for setting selection and confirmation
10 Buttons for selection in a menu
11 Button to cancel entry
12 Buttons for setting adjustments
13 Button for menu selection and LED test
14 Menu pictograms
15 Cursor for menu selection
Dimensions
DE53451_SE
20
Sensors Core balance CTs
CSH120, CSH200, GO110
Function
The specifically designed CSH120 and CSH200 core balance CTs are used for direct
residual current measurement. The only difference between them is the diameter.
PE50032
Due to their low voltage insulation, they may be used only on cables with earthed
shielding.
Characteristics
CSH120 CSH200 GO110
Inner diameter 120 mm (4.7 in) 200 mm (7.9 in) 110 mm (4.33 in)
Weight 0.6 kg (1.32 lb) 1.4 kg (3.09 lb) 3.2 kg (7.05 Ilb)
Accuracy 5 % 20 C (68 F) < 0,5 % (10...250 A)
6 % max. from -25 C to 70 C < 1,5 % (10...250 A)
Core balance CTs CSH120andCSH200. (-13 F to +158 F)
Transformation ratio 1/470
Maximum permissible current 20 kA - 1 s
Operating temperature -25 C to +70 C (-13 Fto +158 F)
Storage temperature -40 C to +85 C (-40 F to +185 F)
DE53446
Dimensions A B D E F H J K L
CSH120 mm 120 164 44 190 76 40 166 62 35
in 4.72 6.46 1.73 7.48 2.99 1.57 6.54 2.44 1.38
CSH200 mm 200 256 46 274 120 60 257 104 37
in 7.87 10.1 1.81 10.8 4.72 2.36 10.1 4.09 1.46
GO110 mm 110 110 72 148 - 57 - - -
in 4.33 4.33 2.83 5.83 2.24
21
Ordering information Sepam series 10
Catalogue numbers
Sepam series 10
Type Cat. no Quantity
Sepam series 10 N 11 A REL59817
Sepam series 10 N 11 E REL59819
Sepam series 10 N 13 A REL59818
Sepam series 10 N 13 E REL59820
Sepam series 10 B 31 A REL59800
Sepam series 10 B 31 E REL59801
Sepam series 10 B 41 A REL59802
Sepam series 10 B 41 E REL59805
Sepam series 10 B 42 A REL59803
Sepam series 10 B 42 E REL59806
Sepam series 10 B 43 A REL59804
Sepam series 10 B 43 E REL59807
Sepam series 10 A 41 A REL59808
Sepam series 10 A 41 E REL59811
Sepam series 10 A 41 F REL59814
Sepam series 10 A 42 A REL59809
Sepam series 10 A 42 E REL59812
Sepam series 10 A 42 F REL59815
Sepam series 10 A 43 A REL59810
Sepam series 10 A 43 E REL59813
Sepam series 10 A 43 F REL59816
Replacement parts
Type Cat. no Quantity
CCA 680 set of spare connectors REL59798
Core balance CTs
Type Cat. no Quantity
Split core balance CTs, dia. 110 mm GO110 50134
Core balance CTs, dia. 120 CSH120 59635
Core balance CTs, dia. 200 CSH200 59636
Model
Earth-fault protection N
Phase-overcurrent and earth-fault protection B
Phase-overcurrent and earth-fault protection,
A
logic inputs and communication port
Supply voltage
24125 V DC and 100120 V AC A
110250 V DC and 100240 V AC E
220250 V DC and high-threshold logic inputs F
(1) Uses 1 A/5 A sensors.
(2) Uses CSH CTs.
22
Notes
23
Notes
24
ART.833133 2008 Schneider Electric - All rights reserved
Design:
Publication: Schneider Electric
Printed:
SEPED307026EN / 1 12/2008