The settings for Incomer 1, 2 and bus coupler are as follows:

SETTINGS FOR 415V OUTGOING FROM AUXILIARY TRANSFORMER (415V INCOMER)

Breaker Make GENERAL ELECTRIC Remarks


Breaker type LOW VOLTAGE CIRCUIT BREAKER
Trip Unit type ENTELLIGUARD-LSIG
Trip Unit size 3200 A
Set at 2500 A
SETTINGS
LT Pickup Setting - 0.95 In
LT Band Setting - 1 Sec
ST Pickup Setting - 1.5 In
ST Band Setting - 2 (I^x)t-OUT
Instantaneous Pickup Setting OUT

Ground fault pick-up setting 0.29


Ground Band 3 (I^x)t=OUT

SETTINGS FOR 415V Bus Section

Breaker Make GENERAL ELECTRIC Remarks


Breaker type LOW VOLTAGE CIRCUIT BREAKER
Trip Unit type ENTELLIGUARD-LSIG
Trip Unit size 3200 A
Set at 2500 A
SETTINGS
LT Pickup Setting - 0.6 In
LT Band Setting - 1 Sec
ST Pickup Setting - 1.5 In
ST Band Setting - 1 (I^x)t-OUT
Instantaneous Pickup Setting OUT

Ground fault pick-up setting 0.23


Ground Band 1 (I^x)t=OUT