The settings for Incomer 1, 2 and bus coupler are as follows:
SETTINGS FOR 415V OUTGOING FROM AUXILIARY TRANSFORMER (415V INCOMER)
Breaker Make GENERAL ELECTRIC Remarks
Breaker type LOW VOLTAGE CIRCUIT BREAKER Trip Unit type ENTELLIGUARD-LSIG Trip Unit size 3200 A Set at 2500 A SETTINGS LT Pickup Setting - 0.95 In LT Band Setting - 1 Sec ST Pickup Setting - 1.5 In ST Band Setting - 2 (I^x)t-OUT Instantaneous Pickup Setting OUT
Ground fault pick-up setting 0.29
Ground Band 3 (I^x)t=OUT
SETTINGS FOR 415V Bus Section
Breaker Make GENERAL ELECTRIC Remarks
Breaker type LOW VOLTAGE CIRCUIT BREAKER Trip Unit type ENTELLIGUARD-LSIG Trip Unit size 3200 A Set at 2500 A SETTINGS LT Pickup Setting - 0.6 In LT Band Setting - 1 Sec ST Pickup Setting - 1.5 In ST Band Setting - 1 (I^x)t-OUT Instantaneous Pickup Setting OUT
Ground fault pick-up setting 0.23
Ground Band 1 (I^x)t=OUT 5.0 CONCLUSION :