You are on page 1of 8

1194 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO.

2, APRIL 2007

On the Analysis of Voltage and Current


Transients in Three-Phase Power Systems
Math H. J. Bollen, Fellow, IEEE, and Irene Yu-Hua Gu, Senior Member, IEEE

AbstractThis paper proposes a method for analyzing measure- shorter duration, transients require a wider band-width measure-
ments of voltage transients in three-phase systems. The method is ment circuit and higher sampling rate. Therefore, large-scale
based on the Clarke transform introduced in 1950 for calculations data collection of transients is much less common than data col-
of travelling waves along three-phase transmission lines. The pro-
posed method also shows close similarities with the classification lection for dips and interruptions. All of this has led to an un-
of three-phase unbalanced voltage dips. After extracting the actual derexposure of transients in the power-quality literature. How-
transient (e.g., by using a notch filter centered on the power-system ever, also voltage transients may have adverse consequences on
frequency), the three signals are decomposed into seven compo- end-user equipment, including maloperation and damage.
nents. From the relation between these seven components, the dom- Low-frequency transients (from 250 Hz up to several hundred
inant component is identified. The method is successfully applied
to a number of measured transients. The paper also identifies the Hertz) due to capacitor-bank energizing have received the most
limitations of the method and gives suggestions for future work. attention in the power-quality literature due to their adverse im-
pact on adjustable speed drives (e.g., [8] and [9]). Phenomena,
Index TermsCapacitor energizing, electromagnetic compat- such as current-chopping and restrike after capacitor de-ener-
ibility (EMC), power quality, power-system transients, power gizing, may also lead to severe transients and equipment mal-
transmission and distribution.
operation or damage.
Different methods are available for the analysis and charac-
terization of transients, but all of these methods consider each
I. INTRODUCTION phase separately. No method is available for addressing tran-
sient multiphase measurements. Transients in three-phase sys-
tems are complicated, especially when switching actions in the
RANSIENTS are subcycle deviations from the normal
T voltage or current waveform. A number of causes of
transients can be identified: lightning strokes, switching actions
three phases take place close together in time. The development
of a three-phase analysis or classification method for power-
system transients would simplify the characterization of three-
in the distribution or transmission system, self-clearing faults phase transients. More importantly, it would allow the further
or faults cleared by current-limiting fuses, and the switching of development of methods for extracting additional information
end-user equipment. The latter mainly causes local transients from recordings of voltage and current transients in three-phase
within the customer premises, whereas distribution or trans- systems, such as direction and origin.
mission-system switching causes transients for a larger number Motivated by the above issues, a method will be proposed
of customers. The origin of transients in the grid is described in in this paper for the decomposition of voltage and current tran-
detail in a number of books: [1], [2] and more recently [3]. sients in three-phase systems. The paper starts with a general
In the power-quality literature, transients are mainly treated discussion on analysis of transients in Section II, to explain the
as a disturbance occurring at the terminals of equipment, where role of the proposed method in the overall processing of tran-
the emphasis is on single-event characteristics as rise-time, peak sients. The theoretical foundation of the decomposition method
voltage and duration. A good overview of transient test wave- is presented in Section III. Section III also shows the equiv-
forms and their origin is presented in [4, Ch. 10]. Transients alence between the proposed method and the classification of
are an important part of the power-quality mitigation issues dis- three-phase unbalanced voltage dips and discusses a method for
cussed in [5]. Transients are further treated in [6, Ch. 4] and [7, determining the dominant component. A number of measure-
Ch. 6 and 7]. ment examples are presented in Section IV. Some limitations
Transients do not normally cause the widespread inconve- and implementation issues are described in Section V. As this
nience as interruptions or dips. The consequences of a tran- is a new method a discussion on further work including testing
sient are in many cases limited to local equipment. Because the is part of Section VI. Finally, Section VI concludes the paper.

Manuscript received November 7, 2005; revised June 5, 2006. Paper no. II. ANALYSIS OF TRANSIENTS
TPWRD-00651-2005.
M. H. J. Bollen is with STRI AB, Ludvika, 771 80, Sweden and also The overall analysis of transients in three-phase systems, as
with Lule University of Technology, Skellefte 931 87, Sweden (e-mail: envisaged by the authors, is shown schematically in Fig. 1. From
math.bollen@stri.se). the three measured voltages the actual transient is extracted. The
I. Y. H. Gu is with the Department of Signals and Systems, Chalmers Uni-
versity of Technology, Gothenburg 412 96, Sweden. decomposition algorithm proposed in this paper is applied to
Digital Object Identifier 10.1109/TPWRD.2007.893613 the extracted transient, resulting in seven components. After the
0885-8977/$25.00 2007 IEEE
BOLLEN AND GU: ON THE ANALYSIS OF VOLTAGE AND CURRENT TRANSIENTS 1195

III. DECOMPOSITION METHOD

A. Clarke Transform
The start of the decomposition method is the so-called Clarke
transform as introduced by E. Clarke [14] to simplify calcu-
lations of travelling waves along overhead transmission lines.
The method is discussed among others in [15, Sec. 5.4] and in
[16, Sec. 6.2.1]. The Clarke transform relates phase voltages and
component voltages through the following matrix expression:
Fig. 1. Analysis chain of transients in three-phase power systems.

selection of the dominant component, the actual analysis takes (1)


place.
The extraction of the actual transient is typically a two-stage
process consisting of triggering and a kind of high-pass The components are referred to as alpha component, beta
filtering to remove the steady-state component. Different component, and zero-sequence component. The advantage
advanced signal-processing methods have been proposed in of this method over the symmetrical component transformation
literature for both triggering and for removing the steady-state is that the transformation matrix only contains real elements.
component. Wavelet filters are the most-commonly proposed This makes it possible to apply the transformation in time do-
method, but model-based methods are proposed for triggering main.
as well.
Methods for removing the steady-state component include B. Voltage Dip Classification
high-pass filters, notch filters and subtracting the fundamental A method for classification of three-phase unbalanced voltage
component or the pre-event waveform. Different methods for dips has been introduced in [17]. The method is based on a
extracting the transient are discussed in [7]. In this paper, a systematic study of the dips due to different types of faults
simple notch filter is used to extract the transient. The record- and their propagation through different types of transformer-
ings analyzed in this paper were obtained by a power-quality winding connections. A mathematical basis for the method, in-
monitor with build-in triggering. Neither triggering nor extrac- cluding a way of extracting the dip characteristics from mea-
tion of the transient will be discussed further in this paper. surements, were developed later [18]. This method has shown
The next step is the decomposition of three phase voltages its use not only in voltage-dip characterization but also in ex-
into seven components in a similar way as the decomposition tracting further information from a voltage recording [19] and
of complex phasors into symmetrical components. This is the in developing a testing protocol for three-phase converters [20].
main subject of this paper; it will be discussed in detail below. The basic classification distinguishes between Type C dips and
Note that the decomposition method results in seven compo- Type D dips, corresponding to phase-to-phase and phase-to-
nents. The selection of the dominant component or components neutral drops in voltage, respectively. The complex voltages in
is needed to create signals that behave as in single-phase sys- the three phases for a type Ca dip are as follows:
tems. Also the selection of the dominant component will be fur-
ther discussed in the remainder of this paper. Further analysis of
the transients may consist of the classical characterization into
a magnitude and duration (e.g., as proposed in an annex to IEC
61000-4-30 [10]). Those characterization methods are applied
(2)
to the dominant component only.
Further analysis should in future also include directional
with the pre-event voltage and the characteristic (residual)
finding, origin of the transient and even system diagnostics.
complex voltage.
For directional finding, the dominant voltage and current
The expressions for a Type Da dip are
components may be compared. Also more advanced analysis
methods can be applied to the dominating component, such as
wavelet decomposition or the ESPRIT method for estimating
the frequency components [11], [12]. For estimating the origin
of the event (e.g. using automatic classification methods like
expert systems or neural networks) or for system diagnostics, (3)
additional information may be extracted from the waveforms
like the amplitude and distortion before and after the transient The alpha-component in (1) gives a voltage in phase a and the
[13] and the point-on-wave at which the transient occurs. As opposite voltage of half the amplitude, in phases b and c. This
the currents and voltages in the dominant component behave corresponds to the type Da dip. The beta-component gives a
as in a single-phase system, the further analysis becomes much voltage in phase b and the opposite voltage in phase c. This
easier. The development of such methods is however outside corresponds to a type Ca dip. The zero-sequence component
of the scope of this paper. results in the same voltage in the three phases. Rewriting (2)
1196 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 2, APRIL 2007

and (3) in terms of changes in complex voltage, results for type with an inverse transformation
Da in

(11)

(4) Note that the zero-sequence component is the same in all three
and for type Ca in cases, so that only seven different components exist. All seven
components can be obtained from the phase voltages by com-
bining (7), (9), and (11), resulting in the following matrix ex-
pression:

(5)

Substituting in (4) and in (5) (12)


results in (1).

C. Seven Transient Components

As shown in the previous section, the alpha and beta compo-


nents in (1) may be referred to as the Da and Ca component,
respectively. The same notation as for voltage dips will be used D. Extracting the Dominant Component
in this paper for transients, so that (1) is written as

At this stage, it is very important to realize that the proposed


(6) decomposition is not the standard decomposition of signals
into orthogonal modes. In other words: these seven com-
ponents are not mutually independent. To understand the cor-
To calculate the component voltages from the phase voltages, relations between these seven components, consider six fun-
the inverse transformation of (6) is needed damental transients corresponding to voltage differences be-
tween phase a and ground; between phase b and ground; be-
tween phase c and ground; between phase b and c; between
(7) phase a and c; and between phase b and c. The fundamental
transients are referred to as Da, Db, Dc, Ca, Cb, and Cc, respec-
tively. For example, six different phase-to-ground and phase-to-
The other dip types can be obtained by cyclic rotation of (6) and phase capacitor switching events will lead to these six funda-
(7). The following expressions hold for the Db and Cb compo- mental transients; switching a capacitor between phase b and c
nents: results in a Ca transient, etc.
Consider a type Da (fundamental) transient. After calculating
the phase voltages from (6) and substituting these into (12), the
(8) seven components result

with an inverse transformation

(9)

(13)
and for the Dc and Cc components
The Da component is the dominating component (the one
with the highest absolute value), but four other components also
have a non-zero value. Only the Ca and zero-sequence compo-
(10) nents are zero: Da, Ca, and the zero-sequence component form
orthogonal bases.
BOLLEN AND GU: ON THE ANALYSIS OF VOLTAGE AND CURRENT TRANSIENTS 1197

The relation between the six fundamental transients and the


six non-zero-sequence components is given by

(14)

Fig. 2. Voltage recording due to capacitor energizing in a three-phase system


(left) and the extracted transient after applying a notch filter (right).
with the following cross-coupling matrix:

The zero-sequence component (not shown in the cross-


coupling matrix) has no cross-coupling with any of the other
components. Equally, no cross-coupling exists between Da and
Ca, between Db and Cb, and between Dc and Cc. Another con-
clusion that can be drawn from the cross-coupling matrix is that
there are only three combinations that form an individual set of
orthogonal bases: ( , Da, Ca), ( , Db, Cb) and ( , Dc, Cc).
The six-by-six cross-coupling matrix in (13) is obtained
by considering one event type at the time, as in the example for
event type Da in the beginning of this section. The cross-cou-
pling between the components implies that there are always
at least four non-zero component voltages. Let the dominating Fig. 3. Original waveforms (top left), extracted transients in the three phases
component (the one corresponding to the event type) have a (top center), and the seven components for a measured transient. Example I.
magnitude of 100%, then two other components will have a
magnitude of 86% and the remaining two 50%.
Therefore, a method is needed to determine which of the a 2-ms window. The dominant component is the one with the
six non-zero-sequence components is dominant. Such a method highest rms value. To verify the result, the difference in rms
could simply select the component with the highest magnitude value between the C and D components is calculated as well
or alternatively detect the pattern between the different compo-
nents. A useful pattern is that the component orthogonal to the
dominant component (Da for Ca, etc.) is in the ideal case zero. In
the implementation to be discussed in Section IV the rms value (15)
over a 2-ms window is used to find the dominant component and
the difference between the dominant component and its orthog- For example, if is the highest, Da or Ca is the dominant
onal components is used as a verification. component.

IV. MEASUREMENT EXAMPLES A. Example I


The method introduced in the previous section has been im- An example of a measured transient is shown on the left-hand
plemented and applied to a number of measured transients. side of Fig. 2. The transient is due to the closing of one phase
The transient is extracted in each of the three phases by of a three-phase capacitor bank.
using a second-order notch-filter centered at the nominal The extracted transient is shown on the right in the same
power-system frequency (50 or 60 Hz) with a bandwidth of 30 figure. The non-zero signal before the start of the event is due
Hz. to the method for extracting the transient being non-ideal. Har-
The seven modes are calculated from the extracted transients monic distortion is not removed by the notch filter. An appro-
at each time instant, by using (12). This results in seven wave- priate high-pass filter would remove the harmonic distortion but
forms as a function of time. The zero-sequence component can would also remove a significant part of the transient as its main
be treated separately because it has no correlation with any of frequency components are around a few hundred Hertz.
the other components. The seven transient components are shown in Fig. 3. Also,
The dominant component is extracted by calculating the rms the original waveform and the extracted transients for the three
value of each of the six non-zero-sequence components over phases are shown.
1198 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 2, APRIL 2007

Fig. 4. The 2-ms rms values for the six components in Example I: Da and Ca
(left); Db and Cb (center); Dc and Cc (right). The D components are indicated
by solid lines; the C components by dashed lines.

Fig. 7. Original waveforms (top left), extracted transients in the three phases
(top center), and the seven components for a measured transient. Example III.

Fig. 8. The 2-ms rms values for the six components in Example III: Da and Ca
Fig. 5. Original waveforms (top left), extracted transients in the three phases (left); Db and Cb (center); Dc and Cc (right). The D components are indicated
(top center), and the seven components for a measured transient. Example II. by solid lines; the C components by dashed lines.

case. Strictly-speaking the zero-sequence component should be


referred to as the dominating component in this case. But in
the same way as for the classification of three-phase unbalanced
voltage dips, the zero-sequence component will be treated sep-
arately. Another interesting observation from the plots is that
and have the most smooth waveform. Methods for ex-
tracting the oscillation frequency and time constant [11], [12]
Fig. 6. The 2-ms rms values for the six components in Example II: Da and Ca
(left); Db and Cb (center); Dc and Cc (right). The D components are indicated will be most successful when applied to these components.
by solid lines; the C components are indicated by dashed lines.
C. Example III
Figs. 7 and 8 show the results of applying the method to
The 2-ms rms values are shown in Fig. 4 for the six non-zero- a third example. This recording contains two transients, about
sequence components. As Dc is the highest and Ca the lowest, one-and-a-half cycle apart in time. The first transient is classi-
Dc is found to be the dominant component and the event is clas- fied as a type Cc transient. A Cc transient corresponds with a
sified as a type Dc transient (i.e., a transient between phase C switching action between phases a and b. With such a switching
and ground). action, one would not expect a zero-sequence component, in the
same way as there is no zero-sequence component associated
B. Example II with type C voltage dips. A closer inspection of the zero-se-
A second example is given in Fig. 5: it is again the transient quence component shows that it is damped very quickly. This
due to closing of one phase of a three-phase capacitor bank. may be due to a small difference in closing instant between the
From the 2-ms rms values shown in Fig. 6, it follows that this is phases a and b. The second transient is of type Dc and is prob-
a type Da transient. ably caused by the closing of the third phase.
Note that the zero-sequence component is much higher than
in the first example. Whereas the zero-sequence component was D. Example IV
about half the dominating component in the first example, it is An example of a current transient is shown in Figs. 9 and 10.
even somewhat higher than the dominating component in this The recording is obtained in a low-voltage network close to a
BOLLEN AND GU: ON THE ANALYSIS OF VOLTAGE AND CURRENT TRANSIENTS 1199

Fig. 11. Original waveforms (top left), extracted transients in the three phases
Fig. 9. Original waveforms (top left), extracted transients in the three phases (top center), and the seven components for a measured transient. Example V.
(top center), and the seven components for a measured transient. Example IV.

Fig. 12. The 2-ms rms values for the six components in Example V: Da and Ca
(left); Db and Cb (center); Dc and Cc (right). The D components are indicated
by solid lines; the C components by dashed lines.
Fig. 10. The 2-ms rms values for the six components in Example IV: Da and Ca
(left); Db and Cb (center); Dc and Cc (right). The D components are indicated
by solid lines; the C components by dashed lines.

medium-size industrial company. The transient is due to load


switching on the customer premises. The event is classified as
a type Ca transient, as a switching action between phases b and
c. The current transient caused a voltage transient that is also
classified as a type Ca transient.

E. Example V

The fifth example is the voltage transient due to synchronized


capacitor energizing. Comparing with the previous examples
clearly shows the mitigating effect of synchronized switching.
The results of applying the decomposition method are shown
in Figs. 11 and 12. The waveform traces for the 6 components do
not reveal any dominant component. The rms values do however Fig. 13. Original waveforms (top left), extracted transients in the three phases
reveal clearly that the transient starts as a type Cc and changes (top center), and the seven components for a measured transient. Example VI.
to a type Dc.
The capacitor bank in this case is star-connected but not
grounded. Two phases are energized at the zero-crossing of F. Example VI
their voltage difference; the third phase is one quarter cycle A final example of a transient is shown in Fig. 13. The origin
later. The CcDc classification is in agreement with this of this transient is unknown. Neither the waveform traces in
switching order. Note that Cc and Dc are the only components Fig. 13 nor the rms traces in Fig. 14 reveal any dominant com-
that show a smooth damped waveform; the other ones are all ponent. The differences between corresponding D and C com-
a superposition of two components. The oscillation frequency ponents, according to (15), are shown in Fig. 15. A sequence
and other single-event indices should be extracted from Cc and CbDcCa would fit with the observations but no conclusion
Dc. about the origin could be derived from that. Further studies
1200 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 2, APRIL 2007

method similar to the one presented here is used for selection


of the faulted phase with some algorithms for travelling-wave
based protection [21], [22]. The coupling between the compo-
nents is also there mentioned as making the selection more dif-
ficult. Note that the superimposed components mentioned in
[22] correspond to the extracted transients in this paper.
The characterization method introduced here for transients
Fig. 14. The 2-ms rms values for the six components in Example VI: Da and Ca
(left); Db and Cb (center); Dc and Cc (right). The D components are indicated
on three-phase systems is comparable to the characterization of
by solid lines; the C components by dashed lines. voltage dips under the assumption that the PN-factor remains
equal to 1 per-unit [18]. This is an acceptable assumption for
single switching events, either between phase and ground or be-
tween two phases. We saw however when analyzing voltage dips
in three phases, that a second characteristic is needed, which
is the PN-factor, to cover dips due to two-phase-to-ground and
three-phase faults. Such an extension may also be needed for
the characterization of transients.

VI. CONCLUSION
Fig. 15. Difference between the rms values for Da and Ca (solid); Db and Cb A method has been proposed for decomposing a three-phase
(dashed); and Dc and Cc (dotted), for Example VI.
voltage or current transient into seven components. The method
is based on the Clarke transform, but contrary to the Clarke
transform the resulting components are non-orthogonal. The re-
are needed to understand such complex transients, for example sult is a cross-coupling between the components. It is shown that
a large number of simulated transients using an electromag- the proposed method is equivalent to a method for classification
netic-transient-type power-system analysis package. of three-phase unbalanced voltage dips and to methods used for
travelling-wave-based protection of transmission lines.
The method has been applied to a number of transients mea-
V. LIMITATIONS OF THE METHOD
sured at different voltage levels. It has been possible to identify
The proposed method for characterization and classification the dominant component for most of the studied cases. A further
of transients in three-phase systems gives a satisfactory result study of a large number of transient recordings, preferably with
for most of the measured transients studied by the authors. The a known origin, is needed to find the limitations of the method.
method is, however, based on the underlying assumption that Simulations are needed to generate further test waveforms, es-
no two switching actions occur at the same time. In Example V pecially for more complex events.
the two switching actions could still be distinguished because Further work is also needed towards the development of a
their time difference was somewhat more than one cycle of the more advanced method for determining the dominant compo-
transient oscillation. Any smaller difference in time will make nent. In this paper a simple rms-based method was used, but
that it is no longer possible to extract a dominant component. this limits the range of oscillation frequencies that can be cov-
The same holds when three switching actions occur shortly after ered. Model-based methods may be more appropriate.
each other. An example of a non-classifiable transient is Ex- The proposed method may find applications in the charac-
ample VI in the previous section. terization of voltage and current transients in three-phase sys-
There are a number of reasons why the classification algo- tems and in the definition of standard waveforms for testing
rithm works less well for transients than for voltage dips. The of end-user equipment against voltage transients. However, the
first reason is due to the measurement method: the harmonic dis- most promising application envisaged by the authors is in auto-
tortion in the original waveform causes an error in the extracted matic and manual methods for extracting additional information
transient. For small transients this may make the classification from disturbance recordings. Advanced signal-processing tools
more difficult. The second source of error is due to the method like wavelet filter banks and ESPRIT frequency decomposition
used for extracting the transient. A change in fundamental com- should be applied to the dominant component.
ponent leads to an oscillation in the output of a notch filter that The analysis method proposed in this paper only considers
adds to the actual transient. phase-to-phase and phase-to-neutral voltages. Transients af-
Another source of error is in the model used for the system. fecting the voltage difference between the neutral and the
The Clarke transform is based on a balanced model of the power protective earth cannot be studied by using this method. Other
system: all three phases are equal and the coupling between methods are needed or the proposed method may have to be
each pair of phases is equal. Whereas this is a reasonable model extended.
for fundamental frequency, it may no longer be acceptable for The proposed method may also be used to study the initia-
higher frequencies. The non-balanced character of the system tion of voltage dips due to fast-developing faults and the voltage
manifests itself as a coupling between the components: thus recovery taking place at different time instants in the different
Ca, Da, and zero-sequence are no longer fully decoupled. A phases after two-phase-to-ground or three-phase faults.
BOLLEN AND GU: ON THE ANALYSIS OF VOLTAGE AND CURRENT TRANSIENTS 1201

ACKNOWLEDGMENT [19] E. Styvaktakis, M. H. J. Bollen, and I. Y. H. Gu, Expert system for


classification and analysis of power system events, IEEE Trans. Power
The authors would like to thank A. Ferguson of Scottish Del., vol. 17, no. 2, pp. 423428, Apr. 2002.
Power, C. Roxenius of Gteborg Energi, H. Seljeseth of Sintef, [20] A. Sannino, M. H. J. Bollen, and J. Svensson, Voltage tolerance testing
and P. Halvarsson of Trinergi for the measurement data used in of three-phase voltage source converters, IEEE Trans. Power Del., vol.
20, no. 2, pt. 2, pp. 16331639, Apr. 2005.
this paper. [21] M. H. J. Bollen, Extensive testing of algorithms for travelling-wave
based protection, in Proc. 4th Int Conf. Developments in Power System
REFERENCES Protection, London, U.K., 1989, Inst. Elect. Eng..
[1] R. Rdenberg, Transient Performance of Electric Power Sys- [22] D. W. P. Thomas, M. S. Jones, and C. Christopoulos, Phase selec-
temsPhenomena in Lumped Networks. Cambridge, MA: MIT tion based on superimposed components, Proc. Inst. Elect. Eng., Gen.,
Press, 1950. Transm. Distrib., vol. 143, no. 3, pp. 295299, May 1996.
[2] A. Greenwood, Electrical Transients in Power Systems, 2nd ed. New
York: Wiley, 1991.
[3] L. van der Sluis, Transients in Power Systems. Chichester, U.K.:
Wiley, 2001. Math H. J. Bollen (M93SM96F04) received the
[4] L. Tihanyi, Electromagnetic Compatibility in Power Electronics. M.Sc and Ph.D. degrees from Eindhoven University
New York: IEEE Press, 1995. of Technology, Eindhoven, The Netherlands, in 1985
[5] W. E. Kazibwe and M. H. Sendaula, Electric Power Quality Control and 1989, respectively.
Techniques. New York: Van Nostrand, 1993. Currently, he is Manager of EMC and Power
[6] R. C. Dugan, M. F. McGranaghan, S. Santoso, and H. W. Beaty, Elec- Quality at STRI AB, Ludvika, Sweden, and Guest
tric Power Systems Quality, 2nd ed. New York: McGraw-Hill, 2003. Professor with EMC-on-Site, Lule University of
[7] M. H. J. Bollen and I. Y. H. Gu, Signal Processing of Power Quality Technology, Skellefte, Sweden. Before joining
Disturbances. New York: Wiley, 2006. STRI in 2003, he was a Postdoctor with Eindhoven
[8] M. F. McGranaghan, T. E. Grebe, G. Hensley, M. Samotyj, and University of Technology, a Lecturer with the
T. Singh, Impact of utility-switched capacitors on customer sys- University of Manchester Institute of Science and
temsPart II: Adjustable-speed drive concerns, IEEE Trans. Power Technology (UMIST), Manchester, U.K., and Professor of electric power
Del., vol. 6, no. 4, pp. 16231628, Oct. 1991. systems at Chalmers University of Technology, Gothenburg, Sweden. His
[9] V. E. Wagner, J. P. Staniak, and T. L. Orloff, Utility capacitor research interests cover a wide range of subjects in power systems, with an
switching and adjustable-speed drives, IEEE Trans. Ind. Appl., vol. emphasis on power quality, reliability, and related issues. He has written many
27, no. 4, pp. 645651, Jul./Aug. 1991. basic papers on voltage-dip analysis and a textbook on power quality.
[10] Electromagnetic Compatibility (EMC) Part 4 Section 30: Power
Quality Measurement Methods, IEC Std. 61000-4-30.
[11] J. Dafis, C. O. Nwankpa, and A. Petropoulu, Analysis of power system
transient disturbances using an ESPRIT-based method, in Proc. IEEE Irene Yu-Hua Gu (M94SM03) received the Ph.D.
Power Eng. Soc. Summer Meeting, 2000, pp. 437442. degree in electrical engineering from Eindhoven Uni-
[12] M. H. J. Bollen, E. Styvaktakis, and I. Y. H. Gu, Categorization and versity of Technology, Eindhoven, The Netherlands,
analysis of power-system transients, IEEE Trans. Power Del., vol. 20, in 1992.
no. 3, pp. 22982306, Jul. 2005. Currently, she is a Professor of Signal Processing
[13] E. Styvaktakis, Automating Power Quality Analysis Ph.D. disser- in the Department of Signals and Systems at
tation, Dept. Signals Syst., Chalmers Univ. Technol., Gothenburg, Chalmers University of Technology, Gothenburg,
Sweden, 2002 [Online]. Available: http://www.elteknik.chalmers.se. Sweden. She was a Research Fellow with Philips
[14] E. Clarke, Circuit Analysis of AC Systems, Symmetrical and Related Research Institute IPO, Eindhoven, and Stafford-
Components. Schenectady, NY: General Electric Co., 1950. shire University, Stafford, U.K., and a Lecturer at
[15] G. W. Stagg and A. H. El-Abaid, Computer Methods in Power System The University of Birmingham, Birmingham, U.K.,
Analysis. Auckland, New Zealand: McGraw-Hill, 1968. between 19921996. Since 1996, she has been with Chalmers University of
[16] N. Watson and J. Arrillaga, Power Systems Electromagnetic Transients Technology. Her current research interests include time-frequency signal pro-
Simulation. London, U.K.: Inst. Elect. Eng., 2003. cessing with applications to power disturbance data analysis, image processing,
[17] M. H. J. Bollen, Characterization of voltage sags experienced by video communications, and object recognition.
three-phase adjustable-speed drives, IEEE Trans. Power Del., vol. 12, Dr. Gu was an Associate Editor with IEEE TRANSACTIONS ON SYSTEMS,
no. 4, pp. 16661671, Oct. 1997. MAN, AND CYBERNETICS, Parts A and B, during 20002005; was Chair of the
[18] L. D. Zhang and M. H. J. Bollen, Characteristics of voltage dips (sags) Signal Processing Chapter in the IEEE Swedish Section during 20022004; and
in power systems, IEEE Trans. Power Del., vol. 15, no. 2, pp. 827832, has been with the editorial board for the EURASIP Journal of Applied Signal
Apr. 2000. Processing since 2005.

You might also like