ABSTRACT
As Hammarlund stated in [1], Transient Recovery Voltage (TRV) investigation can never be finished completely, as the
progress of circuit breaker construction and network design goes on. The most common approach to TRV investigation
is concerning the so called prospective TRV, in which an assumption of neglecting interaction between circuit breaker
itself and the inherent system recovery voltage is being made. However, it still seems to be worthy to investigate how
circuit breaker affects TRV. In presented paper such an influence is being investigated in some detail, with use of black-
box Habedank circuit breaker model [2], in exemplary MV large industrial network [3]. The influence of reactance of
inductive fault current limiter as well as distance to fault in short line fault condition on rate of rise of recovery voltage
has been investigated. The investigation has been made by means of simulation performed using Matlab/Simulink
programme.
Keywords: transient recovery voltage, black-box circuit breaker modelling, short line fault, Matlab/Simulink.
1 MOTIVATION AND SCOPE OF THE PAPER The scope of presented paper is to investigate how
distance to fault in SLF condition and reactance of FCL
In MV industrial networks power is being consume influence RRRV, and how the model of circuit breaker
mostly by high voltage motors supplied by short cable that is used in simulation affects this influence. The
lines, at attendance of fault current limiters (FCL) – simulation was performed with use of two models of
with up to 80% share in exemplary networks circuit breaker: ideal and Habedank, as introduced in
investigated in [4, 5]. Short line faults (SLF) are [2].
characterized by much higher frequency range than
terminal faults, reaches 100 kHz as reported in [6] and The second aim of presented paper is to extend the
even higher as reported in [3]. Also, natural frequencies previous research group work, as the new research
of FCL are much higher than those produced by system group has arisen in the field of TRV investigation in
or transformer [6]. This frequency components are MV industrial networks at Warsaw University of
determining one of the most important factor of TRV Technology (WUT). For this reason, in section 2 the
severity, namely rate of rise of recovery voltage main papers of the previous group will be recall briefly
(RRRV), defined as uc/t3, where uc is peak value of TRV on the background of TRV investigation methods.
and t3 is time parameter obtained from envelope of TRV
as defined in [7] and depicted in Figure 1. This implies
the importance of investigation on RRRV in SLF 2 TRV INVESTIGATION METHODS
condition at attendance of FCL.
Transient recovery voltage has a great history of
investigation, beginning in the early years of XX
century. Presumably the first author [1] who gave a
clear mathematical description of the phenomena was
Slepian, in 1923 [8]. He found out that circuit breaker
interrupting capacity is greatly affected by the system
voltage natural oscillations, when current is interrupted
after the instant of current zero. This TRV stresses the
circuit-breaker gap when the gap conducts from the
state of being good conductor to its normal condition of
a good insulator.
Figure 7 shows how RRRV depends on reactance of Figure 8 shows how RRRV depends on individual
FCL (XFCL) and distance to fault (df). Simulations were parameters of Habedank circuit breaker model, for
performed with use of both circuit breaker models: ideal distance to fault (df) equals 0.2 km and reactance of
(marked as Alpha) and Habedank, for three distances to FCL (XFCL) equals 0.32 Ω. The values of parameters
fault. As it is shown in Figure 7, for ideal model RRRV were deviated in the range of 20%. Because of great
initially increases and then decreases, while for difference in significance between individual
Habedank model RRRV increases in whole range of parameters, the values were plotted in two subplots.
XFCL, reaches a plateau finally. For both models, the
shorter distance to fault implies the higher RRRV.