Professional Documents
Culture Documents
Mp Mp
Auto transformer
The voltage of the intermediate circuit can be cho- A tertiary winding can be foreseen to connect a fil-
sen by the designer. As higher it is, as more so- ter or a power factor correction equipment.
phisticated is the insulation system. But as the cur-
rent is lower at higher voltages, a less expensive 3.1.4.Comparison of the Three
tap changer can be chosen. It is up to the designer
Types
to find the optimum.
The possible range of application of the three types
The switchgear can be included in the intermediate
has been described above. The following compari-
circuit. Due to the reduced voltage of the intermedi-
son is done from an economical point of view.
ate circuit, a less expensive switchgear can be cho-
sen. If the switchgear is open, the booster trans-
The built in power of a furnace transformer is nor-
former will be magnetised from its low voltage
mally much higher than the rated power. This is
winding. This implies, that the booster transformer
determined by the special power demand of such a
is designed for the voltage level of the low voltage
Furnace Transformers Transformatorenwerk Nrnberg
3
transformer and by the chosen concept. The com-
parison is done based on the same tapping range
for all three types e.g.: Umax/Uconstant/Umin = 1 /
0,8 / 0,5. The ratio between built in power and rated
power for the given tapping range is as follows:
Variable flux regulation: 1,63
Intermediate circuit regulation: 1,44
Regulation with auto transformer: 1,56
No load star delta switchover of the high voltage Furnace reactor with attached tap changer to
winding of furnace transformers with variable flux be included in the main transformer tank.
voltage regulation is used to reduce the built in
power in cases where big tapping ranges are re- 3.2. Transformers for DC-Furnaces
quired. If for instance a voltage range Umax/Umin This type of transformer contains some elements
= 1 / 0,33 is foreseen, the built in power is only 1,49 from conventional rectifier transformers (used in
times the rated power if such a switchover connec- electrolysis plants or dc-drives) and other elements
tion is used. (compare also 3.1.4). from ac-furnace transformers.
An individual regulation of each phase can be real- Transformers for dc-furnaces can be built to be
ised. In this case, a zero sequence flux can occur. connected to medium voltage systems and to high
Special measures have to be taken in this case. voltage systems. All kinds of voltage regulation
mentioned above can be foreseen in principle for
this type of transformer too. In many cases rectifi-
Furnace transformers for ac-furnaces can be built
ers with thyristors are used. In this case the voltage
also as single phase units. In the case of the so
regulation can be done via thyristors and there is
called Knappsack-connection, three single phase
only a small tap changing equipment necessary or
units are arranged symmetrically around the fur-
it can be even omitted. If a tap changer is foreseen,
nace. Due to the geometrical symmetry the imped-
it is normally a no load tap changer.
ance of the three phases is nearly the same. This
leads to a uniform load of the three phases. This
advantage is compensated by higher manufactur-
ing cost and greater content of material of the sin-
gle phase units compared with a three phase unit.
The types of conductors used in the low voltage Low voltage leads can carry currents up to 100 kA.
windings are mainly continuously transposed con- Therefore special measures are required to assure
ductors, cylinders of copper, or clamps of copper. a proper current distribution within the windings
In the past also bare conductors have been used. and leads.
The technical data of a furnace transformer with [2] Heindl, H.: Ofen- und Gleichrichtertrans-
variable flux voltage regulation will be discussed formatoren, ETZ-A, Heft 3, 1977
below, based on the data of the rating plate (see
Appendix 1 and 2). [3] Timm, K.: Elektrotechnik des Lichtbo-
genofens, Seminar vom 19. Bis 22. Okto-
Rated Power 105 MVA ber 1999 in Saalfeld
constant up to 837 V
Vector group Dd0
Rated primary voltage 30 kV
Secondary voltage Author:
maximum 960 V Dipl.Ing.Univ. Egon Kirchenmayer
minimum 550 V R&D Department
steps 18 Siemens-Transformatorenwerk Nrnberg
Secondary current 73 kA