Prime Power - Stand by PDF
Prime Power - Stand by PDF
Standby Rating
Standby rating applies to installations served by a Average (P1 x T1) + (P2 x T2) + (P3 x T3) + (P4 x T4) + (P5 x T5) +... (Pn x Tn)
=
reliable utility source. Standby power is applicable to Power T + T + T + T + T + T + ... T
1 2 3 4 5 6 n
varying loads for the duration of the utility power P = Power in kW Standby
=
Average Power
T = Time in hours Rating x% Load Factor
interruption. There is no overload capability for the S = Shutdown or nonrunning times
standby rating; use of the generator set above the (not used in calculations)
load operation.
TIB-101 9/00c 1
Prime Power Rating
Prime power rating applies to applications where utility Average (P1 x T1) + (P2 x T2) + (P3 x T3) + (P4 x T4) + (P5 x T5) +... (Pn x Tn)
=
power is unavailable or unreliable. At varying load, the Power T1 + T2 + T3 + T4 + T5 + T6 + ... Tn
number of generator set operating hours at prime rating P = Power in kW Prime Power
=
Average Power
T = Time in hours Rating x% Load Factor
is unlimited. Ratings are in accordance with ISO 8528/1 S = Shutdown or nonrunning times
and overload power is in accordance with ISO 3046/1, (not used in calculations)
Power
400 hours per year.
2 TIB-101 9/00c
Base Load (Continuous) Rating
Base load rating (also referred to as continuous rating)
Base
applies to generator sets operating as utility-type power Load
Power Prohibited
sources where there are nonvarying load factors and/or Rating
constant dedicated loads. Power is continuously
supplied to a constant or nonvarying load up to 100% of
the base load rating for an unlimited number of hours.
No overload capability is available at this rating;
Power
therefore, use above base load rating is prohibited.
Ratings are in accordance with ISO 8528/1, ISO 3046/1,
BS 5514, AS 2789, and DIN 6271.
P1 P2 P3
Typical base load applications include utility, base load,
T1 S T2 S T3
main source of electrical power, and cogeneration. Time
Contact a factory representative for generator set base P = Power in kW
T = Time in hours
load ratings. S = Shutdown or nonrunning times(not used in calculations)
Standby
Load
Limited
Running Prime
Time Base
Load
Engine Life
Increasing
TIB-101 9/00c 3
Engine Rating Tolerances and Load Factors
The following table lists engine rating tolerances and the generator set model family and the industry standards
standby and prime rating load factor percentages by on which the engine ratings are based.
4 TIB-101 9/00c