You are on page 1of 1

ESTIMATED REACTIVE CAPABILITY CURVES

2 Pole 3000 RPM 342640 kVA 15750 Volts 0.800 PF


0.500 SCR 60.00 PSIG H2 Pressure 450 Volts Excitation
40 Deg. C Cold Gas 0 Ft. Altitude
400
Base Capability

35 C Cold Gas 0.30


300 40 C Cold Gas
0.60

0.80

200 62 C Cold Gas


LAGGING

0.90

0.95
100
MEGAVARS

0 1.00
LEADING

-100
0.95

0.30 0.70

-200

101906G1-2a

-300
0 100 200 300 400 500

MEGAWATTS