1900/65A General Purpose Equipment Monitor

Description
The 1900/65A General Purpose Equipment Monitor is a machinery vibration
monitor designed to continuously monitor and protect equipment that are used in a
variety of applications and industries. The low cost of the 1900/65A makes it an
ideal solution for general-purpose machines and processes that can benefit from
continuous monitoring and protection.

Inputs
The 1900/65A provides four transducer inputs and four temperature inputs.
Software can configure each transducer input to support 2- and 3-wire
accelerometers, velocity sensors or proximity sensors. Each temperature input
supports Type E, J, K, and T thermocouples, and 2- or 3-wire RTDs.

Outputs
The 1900/65A provides six relay outputs. The user can configure the contacts of
these relays to open or close according to the OK, Alert and Danger statuses of any
channel or combination of channels.
The monitor provides four 4-20 mA recorder outputs. Software can configure each
recorder output to output any variable from any channel.
The signal for each transducer input is also available on a dedicated buffered
output.
A Modbus Gateway option is available. This allows the monitor to serve static
variables, statuses, event list, time and date information directly to any Modbus
client, including Distributed Control Systems (DCSs), Supervisory Control and Data
Acquisition (SCADA) systems, Programmable Logic Controllers (PLCs) or System
1. The monitor uses an internal counter and a time reference sent from the
Modbus client/master to generate time and date information. Users can upgrade
monitors ordered without the Modbus Gateway by ordering the 1900/01
Communications Upgrade (see the Ordering Information section). The 1900/65A
provides Modbus via Ethernet and a software-configurable 232/485 serial port.

Configuration
The user defines monitor operation and the Modbus Gateway register map by
creating a configuration file using software running on a laptop or PC and
downloading the file to the monitor through the built-in Ethernet connection. The
1900/65A permanently stores configuration information in non-volatile memory, and
can upload this information to the PC for changes.

Display Module
An optional display/keypad for viewing channel information or making minor
configuration changes allows the 1900/65A to operate as a stand-alone package. If
desired, the user can mount the display up to 75 metres (250 feet) from the Monitor
Module.

FOR REFERENCE ONLY Specifications and Ordering Information Page 1 of 18


REFER TO DOCUMENT #173401
kind of variables or measurement
Feature List values that will be derived from this
Continuous monitoring and protection is suitable for input. Channel Types also define the
auto-shutdown applications kind of sensor that must be used.
Stand-alone operation on general-purpose equipment Transducer Channel Types include:

Optional Modbus communications via Acceleration or Reciprocating


10BaseT/100BaseTX Ethernet, or Acceleration
software-configurable 485/232 serial port Velocity or Reciprocating Velocity
Small package. Monitor Module: 196.9 mm x 149.4 Radial Vibration (shaft vibration)
mm x 74.4 mm (7.75 x 5.88 x 2.93). Monitor
Module with attached Display Module: 196.9 mm x Thrust (shaft axial displacement)
149.4 mm x 97.8 mm (7.75 x 5.88 x 3.85) Position
DIN rail or bulkhead mounting options Speed
18 to 36 Vdc power input. (optional 110-220 Vac Acceleration and
external supply) Reciprocating
24-bit ADC conversion Acceleration
Channel Types
Four vibration/position/speed inputs The Acceleration Channel Type and
Reciprocating Acceleration Channel
Four temperature inputs
Type support two- and three-wire
Configurable scale factors and full scale ranges acceleration sensors. The
Reciprocating Acceleration channel
Up to four processed variables per channel with type has timed OK channel defeat
independent integration and filter control disabled.
Internal OK checking with status Acceleration
Independent Alert and Danger setpoints Variables and
Reciprocating
200-entry event list Acceleration
Variables
Six relay outputs. Relay operation is programmable
Acceleration Variables and
Buffered outputs for each transducer channel Reciprocating Acceleration Variables
are filtered and processed
Four configurable 4-20 mA recorder outputs measurements from raw transducer
Optional NEMA 4X/IP66 fiberglass housing with signals. The Acceleration Channel
window for display Type and Reciprocating Acceleration
Channel Type continuously processes
Painted or stainless steel weatherproof door for panel- up to four variables per channel.
mount display
Vibration:
Hazardous area approvals Up to three bandpass filtered amplitude
measurements.
Acceleration
Specifications Enveloping:
Inputs Users can apply the acceleration
Transducer Inputs enveloping algorithm to one
Acceleration or Reciprocating
Users can configure Channels 1 Acceleration Variable.
through 4 to accept input from
acceleration, velocity or displacement Bias Voltage:
transducers. Users may assign the value of the
transducer bias voltage to any of the
Transducer Channel Types variables.
Channel Types define the
functionality for processing that will
be applied to an input signal and the

FOR REFERENCE ONLY Specifications and Ordering Information Page 2 of 18


REFER TO DOCUMENT #173401
Configuration Integrated:
Options 10 to 100 mm/s (0.4 to 4 in/s) peak and
Each variable is independently RMS
configured with the following options.
Bias Voltage:
Vibration -24 V
Variables:
Accuracy
Peak or RMS
Vibration
Metric or English units Variables:
1% of full scale range
Filter corner frequencies
Input Impedance
Full scale range
3-wire Voltage
Acceleration integrated to velocity Mode:
10 k
Enveloped
Variable: Velocity and
Filter corner frequencies Reciprocating
Velocity Channel
Standard or Enhanced demodulation Type
Filters The Velocity Channel Type and
Vibration Reciprocating Velocity Channel Type
Variable: support two-wire and three-wire piezo-
0.5 Hz 25 kHz configurable 4-pole velocity sensors.
high-pass, 4-pole low-pass Velocity Variables
Enveloping and Reciprocating
High-Pass: Velocity Variables
25 Hz to 5 kHz, configurable 4-pole Velocity Variables and Reciprocating
Velocity Variables are filtered and
Enveloping processed measurements from raw
Low-Pass: transducer signals. The Velocity
125 Hz to 25 kHz, configurable Channel Type and Reciprocating
2-pole Velocity Channel Type support up to
Enveloped four continuously calculated variables
Variable High- per channel.
Pass: Vibration:
0.1 Hz min., but greater than Up to three bandpass filtered amplitude
Enveloped Variable low-pass 2-pole measurements.
Enveloped Bias Voltage:
Variable Low- Users may assign the value of the
Pass: transducer bias voltage to any of the
Greater than Enveloped Variable variables.
high-pass and less than Enveloping
high-pass 4-pole Configurable Options
Each variable is independently
Bias Filter: configured with the following options.
0.01 Hz 1-pole low-pass
Vibration
OK Filter: Variables:
2.4 kHz 1-pole low-pass Peak or RMS
Full Scale Range Metric or English units
Vibration:
20 to 500 m/s2 (2 to 50 g) peak and Filter corner frequencies
RMS Full scale range
Enveloped: Velocity integrated to displacement
20 to 500 m/s2 (2 to 50 g) peak and
RMS

FOR REFERENCE ONLY Specifications and Ordering Information Page 3 of 18


REFER TO DOCUMENT #173401
Filters Vibration
Vibration Variables:
Variables: Metric or English units
0.5 Hz to 5.5 kHz, configurable
Filter corner frequencies
8-pole high-pass, 4-pole low-pass
Number of filter poles
Bias Filter:
0.09 Hz 1-pole low-pass Full scale range
OK Filter: Filters
2.4 kHz 1-pole low-pass Direct Filter 1:
4 to 4000 Hz (240 to 240,000 RPM)
Full Scale Range
Vibration: Direct Filter 2:
10 to 50 mm/s (0.5 to 2 in/s) peak 1 to 600 Hz (60 to 36,000 RPM)
and RMS
Direct Filter
Integrated: Characteristics:
100 to 500 m (5 to 20 mils) peak to High-pass set by attack and decay,
peak 1-pole low-pass
Bias Voltage: Gap Filter:
-24 V 0.09 Hz 1-pole low-pass
Accuracy Vibration
Vibration Variables:
Variables: 0.5 Hz to 4 kHz, configurable
1% of full scale range
1-, 2-, or 4-pole high-pass and low-
Input Impedance pass, configurable
3-Wire Voltage
Mode: OK Filter:
10 k 2.4 kHz 1-pole low-pass

Radial Vibration Full Scale Range


Channel Type Direct:
The Radial Vibration Channel Type 100 to 500 m (3 to 20 mils) peak-to-
measures radial shaft motion using peak
proximity sensors. Gap:
Radial Vibration -24 V
Variables Accuracy
Radial Vibration Variables are filtered Vibration
and processed measurements from Variables:
raw transducer sensors. The Radial 1% of full scale range
Vibration Channel Type supports up
to four continuously calculated Input Impedance
Variables per channel. Non-configurable:
10 k
Direct:
Up to three bandpass filtered
amplitude measurements
Gap:
Gap voltage
Vibration:
Up to three bandpass filtered
amplitude measurements
Configurable
Options
Each variable is independently
configured with the following options.

FOR REFERENCE ONLY Specifications and Ordering Information Page 4 of 18


REFER TO DOCUMENT #173401
Thrust Channel Position:
Type Mechanical position
The Thrust Channel Type measures
Gap:
axial shaft motion using proximity
Gap, voltage or position
sensors.
Configurable Options
Thrust Variables
Each variable is independently
Thrust Variables are filtered and
configured with the following options.
processed measurements from raw
transducer signals. Position
Variables:
Position:
Metric or English units
Axial position of shaft
Full scale range
Gap:
Gap, voltage or position Filters
Direct Filter:
Configurable
1.2 Hz 1-pole low-pass
Options
Each variable is independently Gap Filter:
configured with the following options. 0.41 Hz 1-pole low-pass
Position OK Filter:
Variables: 2.4 kHz 1-pole low-pass
Metric or English units
Full Scale Range
Full scale range Position:
1 to 28 mm (50 to 1100 mils) span with
Filters
adjustable zero position
Direct Filter:
1.2 Hz 1-pole low-pass Gap:
-24 V
Gap Filter:
0.41 Hz 1-pole low-pass Accuracy
Position
OK Filter:
Variables:
2.4 kHz 1-pole low-pass
1% of full scale range
Full Scale Range
Input Impedance
Position:
Non-configurable:
1 to 4 mm (50 to 150 mils) span with
10 k
adjustable zero position
Speed Channel
Gap:
Type
24 V
The Speed Channel Type measures
Accuracy speed using proximity sensors.
Position
Speed Variables
Variables:
Speed Variables are filtered and
1% of full scale range
processed measurements from raw
Input Impedance transducer signals.
Non-
Speed:
configurable:
Up to four speed measurements
10 k
Gap:
Position Channel
Gap, voltage
Type
The Position Channel Type
measures mechanical motion using
proximity sensors.
Position Variables
Position Variables are filtered and
processed measurements from raw
transducer signals.
FOR REFERENCE ONLY Specifications and Ordering Information Page 5 of 18
REFER TO DOCUMENT #173401
Configurable Type J:
Options -210 to 1200 C (-346 to 2192 F)
Each variable is independently
Type K:
configured with the following options.
-200 to 1370 C (-328 to 2498 F)
Gap Filter:
Type T:
0.09 Hz 1-pole low-pass
-200 to 400 C (-328 to 752 F)
OK Filter:
10 Cu
2.4 kHz 1-pole low-pass
=0.00427:
Full Scale Range -200C to 260 C (-328 to 500 F)
Speed:
100 - 100,000 rpm 120 Ni
=0.00672:
Events Per -80C to 260 C (-112 to 500 F)
Revolution
EPR: 100 Pt
0.001 to 1000 =0.00385:
-200 to 850 C (-328 to 1562 F)
Accuracy
Speed 100 Pt
Variables: =0.00392:
0.5 RPM + 0.015% of reading -200C to 700 C (-328 to1292 F)
Input Impedance Accuracy
Non- All Thermocouple
configurable: Types:
10 k 1 C (1.8 F) typical @ 25 C (77
F)
Temperature Inputs (Ch. 5 8)
2.5 C (4.5 F) maximum for
Channels 5 through 8 support Type thermocouple measurements over
E, J, K, and T thermocouples, and 2- 100 C (148 F)
and 3-wire RTDs.
5 C (9 F) maximum for
Temperature thermocouple measurements below
Variable 100 C (-148 F)
Temperature variables are processed
measurements from raw transducer 3-Wire RTD
signals. The temperature channel (except 10
type processes one temperature Cu):
variable per channel. 1.5 C (2.7 F) + 0.5 % full scale
Configurable 3-Wire RTD 10
Options Cu:
Each Variable is independently 3 C (5.4 F) + 0.5 % full scale
configured with the following options.
2-wire RTD
Units: Types:
C or F 2-wire RTDs have additional errors due
to field wire resistance and variations in
Filters
the field wire resistance due to
Analog Filter:
changes in ambient temperature.
50 Hz 1-pole, low-pass
Input Impedance
Digital Filter:
Thermocouple
Notch filter will attenuate the first
Inputs:
5 orders of 50 Hz and 60 Hz (49
>1 M
Hz to 61 Hz) by a minimum of
100 dB.
Full Scale Range
Type E:
-200 to 1000 C (-328 to 1832 F)

FOR REFERENCE ONLY Specifications and Ordering Information Page 6 of 18


REFER TO DOCUMENT #173401
Alarm Status Time Delays Maximum Operands
50 per relay
Position / Vibration Inputs
Minimum Relay Configuration
0.1 second The following configuration options are
independent of the relay logic and can
Maximum
be configured for each relay:
60 seconds
Latching or non-latching
Adjustment
independent of alarm status
Resolution
0.1 second Normally energized or normally de-
energized
Temperature / Speed Inputs
Minimum Normally open and normally closed
1 second via contacts

Maximum Relay Specifications


60 seconds Type
Single pole, double throw (SPDT)
Adjustment
Resolution Maximum Contact
0.1 second Voltage
300 Vrms
Relays
150 Vdc
Relay Logic
The 1900/65A monitor has six relay Minimum Switched
outputs that users can program to Current
open or close contacts according to 100 mA @ 12 Vdc
user-defined logic statements. Logic Maximum Switched
statements use the OK, Alert and Power
Danger statuses of any channel, or 160 W dc
combination of channels as inputs.
1500 VA ac
Contact Life
100,000 cycles @ 5 A, 250 Vac
200,000 cycles @ 1 A, 24 Vdc
Logical Operators
AND (bypassed channels ignored) Sealing
Epoxy
True AND (bypassed channels
included) Insulation
Resistance
OR 1000 M minimum @ 500 Vdc
Logical Operands
Monitor inhibit
Monitor Not OK
Monitor Danger
Monitor Alert
Channel Not OK
Channel Danger
Channel Alert
Variable Danger
Variable Alert

FOR REFERENCE ONLY Specifications and Ordering Information Page 7 of 18


REFER TO DOCUMENT #173401
Inhibit, Reset, and Trip Multiply Inputs Electrical
Activate Reset
Inhibit/Trip Multiply 50 k or less (shorted)
Users can use software to configure
the Inhibit/Trip Multiply input as either De-activate Reset
Inhibit or Trip Multiply. 500 k or greater (open)

When configured for Trip Multiply Transducer Supplies


short-circuiting the Inhibit/Trip All outputs are short-circuit protected.
Multiply contact to RTN will increase
Alert and Danger set points. Two-Wire Current Mode
Current Source
When configured for Inhibit the Inhibit 3.3 mA 5%
input will inhibit (bypass or inactivate)
Alert and Danger statuses. Short Open Circuit
circuiting the INHIBIT contact to Voltage
INHIBIT RTN will: 21 to 24 Vdc
Set all Variable Danger Statuses Three-Wire Voltage Mode
to logic 0 Supply Voltage
Set all Variable Alert Statuses to -24.02 Vdc to 23.47 Vdc
logic 0 Maximum Rated
Set Bypass and Inhibit Statuses to Current
logic 1 15 mA

Modbus Note: Monitor Alarm Inhibit Short Circuit


switch, and Monitor Trip Multiply Current
switch mapped in the Modbus 15.1 mA to 23.6 mA
Gateway will remotely inhibit Alert
4-20 mA Interface
and Danger statuses or activate Trip
Multiply respectfully. Number of Outputs
Four outputs, any of which may be
Electrical configured to provide data from any
Activate Inhibit channel and any variable.
50 k or less (shorted)
Proportional Value
De-activate Inhibit 4 to 20 mA values are proportional to
500 k or greater (open) the channel full-scale.
Reset Loop Supply
Use the Reset input to reset all Voltage
latched alarms and latched relays. If 18 to 36 Vdc
the condition driving the status no Loop Resistance
longer exists, short circuiting the 600 maximum
RESET contact to RESET RTN will:
Accuracy
Reset all latched Alert statuses 2% over operating temperature range
Reset all latched Danger statuses Update Rate
Reset all latched Not OK statuses 100 mS
Reset all latched relays Resolution
10 A
Modbus Note: Writing a non-zero
value to the Modbus register Reset Clamp Current
Latched Statuses mapped in the 2 mA 10% (configurable for Not OK
Modbus Gateway will reset the and Bypass)
monitor remotely.

FOR REFERENCE ONLY Specifications and Ordering Information Page 8 of 18


REFER TO DOCUMENT #173401
Buffered Outputs Display
Liquid Crystal Display (LCD) with
Display Module backlight
A single buffered output on the
Display Module provides access to 68.6 mm (2.7 in) wide x 35.6 mm (1.4
input Channels 1 through 4. The in) high
signal does not have gain, and is not
scaled. This output is buffered to
Power Requirements
provide short circuit and EMI Input Voltage
protection. Range
18 to 36 Vdc
Output Impedance
550 Operating Current
0.35 A typical, 1.0 A maximum
Bandwidth
40 kHz minimum (Display Module Operating Power
attached directly to Monitor) 8.5 W typical, 14 W maximum
8 kHz minimum (75 m (250 ft.) of Physical
cable) Monitor Module
Monitor Module Dimensions (L x W
Each input for channels 1 through 4 x H)
has a dedicated buffered output. The 196.9 mm x 149.4 mm x 74.4 mm
signal does not have gain, and is not (7.75 in x 5.88 in x 2.93 in)
scaled. Each output is buffered to
provided short circuit and EMI Weight
protection. 0.77 kg (1.70 lb)

Output Impedance Display Module


550 Dimensions (L x W
Bandwidth x H)
40 kHz minimum 196.9 mm x 149.4 mm x 32.8 mm
(7.75 in x 5.88 in x 1.29 in)
Indicators
Monitor Module Weight
0.40 kg (0.89 lb)
Status LED
Indicates when the monitor is Mounting
functioning properly DIN Rail Option
Display Module 35 mm DIN rail
OK LED Bulkhead Option
Indicates when the monitor is Bulkhead mounting plate
functioning properly Weatherproof
Alert LED Enclosure Option
Indicates an Alert condition NEMA 4X/IP66 Fiberglass Housing
with window, 300.2 mm x 249.4 mm x
Danger LED 209.8 mm (11.82 in x 9.82 in x 8.26 in)
Indicates a Danger condition
Bypass LED
Indicates that the monitor is in
Bypass mode
Trip Multiply LED
Indicates that the monitor is in Trip
Multiply mode
Channel LED
Indicates channel is active

FOR REFERENCE ONLY Specifications and Ordering Information Page 9 of 18


REFER TO DOCUMENT #173401
Software 10/100BaseT Ethernet interface (10
or 100 Mb/s)
The 1900 Configuration
Software package contains 1024 x 768 screen resolution
everything necessary to install, recommended
configure, and maintain the 1900/65A
monitor. Environmental
Temperature
Features
Tools for installing and Operating
troubleshooting -20 to +70 C
Simple display to help with (-4 to +158 F)
configuration Storage
Ability to browse network for 1900 -30 to +90 C
monitors (-22 to +194 F)
Network configuration
Humidity
Configuration for channels, Operating
variables, setpoints, tag names, 95% non-condensing, maximum
recorders and filters
Storage
Configuration for the optional 95% non-condensing, maximum
Modbus Gateway
Supported Transducers
Configuration for relays and relay
voting logic Channel Type Bently Nevada Transducer
Acceleration and 200350 Accelerometer
Off-line configuration allowing use Reciprocating 330400 Accelerometer
of software when hardware is not Acceleration 330425 Accelerometer
available Velocity and 190501 Velomitor
Firmware upgrade function and Reciprocating Velocity 330500 Velomitor
diagnostics 330525 Velomitor
330750 Velomitor
Change bypass modes and Radial Vibration, 3300 5 & 8 mm Proximitor
setpoints on the fly Thrust, and Speed System
Display component for statuses 3300 XL 8mm Proximitor System
3300 XL 11mm Proximitor System
and variables 3300 XL NSvTM Proximitor System
Display Hardware Identification 7200 5 & 8mm Proximitor System
and manufacturing information 7200 11mm Proximitor System
7200 14 mm Proximitor System
Context-specific help Position 3300 5 & 8 mm Proximitor
System System
Requirements 3300 XL 8mm Proximitor System
3300 XL 11mm Proximitor System
Users may install software on a 3300 XL 25mm Proximitor System
notebook or desktop computer that 3300 XL 50mm Proximitor System
meets these minimum requirements: 3300 XL NSvTM Proximitor System
Microsoft Windows 2000 or 7200 5 & 8mm Proximitor System
7200 11mm Proximitor System
Windows XP operating system 7200 14 mm Proximitor System
800 MHz Pentium III class
processor
Note: The 1900/65A provides default configuration settings for
256 MB RAM Bently Nevada transducers. The user can configure the 1900/65A
to accept other transducers.
8 MB video card
8x or faster CD-ROM drive
100 MB available hard drive space

FOR REFERENCE ONLY Specifications and Ordering Information Page 10 of 18


REFER TO DOCUMENT #173401
CE Mark Directives EN 61010-1
The 1900/65A monitor has the CE
mark and is approved for installation Safety
within the European Union and Requirements
European Environmental Agency Safety Requirements for Measurement,
regions. The monitor has been Control, and Laboratory Use
designed and tested to meet the
EMC Standards
following directives.
This product is tested to meet Council
Directive 89/336/EEC Electromagnetic
EMC Directives Compatibility (EMC) and the listed
standards, in whole or in part,
documented in a technical construction
EN61000-604 file. EN61000-6-4 Generic emission
standard, Part 2, Industrial
Radiated Environment. EN61000-6-2 EMC
Emissions Generic Immunity standard, Part 2,
EN 55011, Class A Industrial Environment.

Conducted
Emissions
Hazardous Area Approvals
EN 55011, Class A
This monitor is not certified for
EN61000-6-2 installation in Class 1 Div 1 locations,
but it will support transducers installed
Electrostatic in Div 1 locations via the use of
Discharge galvanic isolators and barriers. If
EN 61000-4-2, Criteria B galvanic isolators are used, no change
is necessary to the installation. A
Radiated removable ground jumper allows the
Susceptibility monitor to support zener barrier
EN61000-4-3, Criteria A installations. Removing the jumper will
Electrical Fast disconnect circuit common from
Transient chassis at the monitor so that chassis
EN 61000-4-4, Criteria B can be connected at the barrier.

Surge North American


Capability Ex/AEx nA [L] IIC
EN 61000-4-5, Criteria B Class I Division 2 Groups A B C D
Conducted T4 @ -20C Ta 70C
Susceptibility
EN61000-4-6, Criteria A Vn = 18 to 36 Vdc @ Imax = 1A per
drawing 173089
Low Frequency
Conducted European
Susceptibility II 3G Ex nA [nL] IIC T4
IEC 60945, Criteria A @-20C Ta 70C
Low Voltage Directives Sira 06 ATEX 4053X
The 1900/65A Monitor meets Council
Directive 73/23/EEC Low Voltage IECEx SIR 06.0012X per drawing
when the 24 Vdc power source is 173089
approved to the Low Voltage
Directive. Bently Nevada power
supply P/N 02200794 meets this
requirement.

FOR REFERENCE ONLY Specifications and Ordering Information Page 11 of 18


REFER TO DOCUMENT #173401
Ordering Information
1900/65A General Purpose Equipment Monitor
1900/65A-AXX-BXX-CXX-DXX-EXX
A: Power Option
00 18 to 36 Vdc
01 110 to 220 Vac @ 50 to 60
Hz (external supply)
B: Display Option
00 No display
Figure 1: DIN Rail Mount
01 Attached display (no cable)
02 Display with 10 PVC cable 02 Bulkhead Mount (see Figure 2)
03 Display with 10
unassembled PVC cable
04 Display with 10 TEF cable
05 Display with 10
unassembled TEF cable
06 Display with 50 PVC cable
07 Display with 50
unassembled PVC cable
08 Display with 50 TEF cable
09 Display with 50
unassembled TEF cable Figure 2: Bulkhead Mount
10 Display with 100 PVC cable
11 Display with 100 03 Fiberglass NEMA 4X/IP66 WP
unassembled PVC cable housing with window in door
(see Figure 3)
12 Display with 100 TEF cable
13 Display with 100
unassembled TEF cable
14 Display with 250 PVC cable
15 Display with 250
unassembled PVC cable
16 Display with 250 TEF cable
17 Display with 250
unassembled TEF cable
C: Mounting Option
Figure 3: NEMA 4X/IP66 WP Housing
00 None
01 DIN rail mount (see Figure 1)
04 1900/55 replacement kit (see
Figure 4)
Note: Uses existing 1900/55 weather-proof
housing and requires power option A01 (110/220
Vac to 24 Vdc external power supply)

FOR REFERENCE ONLY Specifications and Ordering Information Page 12 of 18


REFER TO DOCUMENT #173401
1900/01 1900/65A General Communications Monitor,
Communications Upgrade
1900/01-AXX-BXX-CXX-DXX
A: Order Type Option
01 New order (CD, key, and
binder)
98 Replacement licenses (key)
99 Update (CD)
B: Communications Option
Figure 4: 1900/55 Replacment Kit 01 Modbus communications
C: License Key Type Option
D: Approvals Option 00 None
00 None 01 USB license key
01 Multiple approvals. See 02 Floppy disk license key
Hazardous Area Approvals
section for specific D: License Quantity Option
certifications. XX Total licenses (1 to 99)
E: Communications Option
00 None
01 Modbus communications

FOR REFERENCE ONLY Specifications and Ordering Information Page 13 of 18


REFER TO DOCUMENT #173401
Accessories
Use the part numbers listed in this section to order spare parts or additional components for your 1900/65A General Purpose
Monitor.
Part Number Description
167699-02 1900/65A Display Module
173400-01 1900/65A Product Manual
172250-01 1900/65 Modbus Gateway Users Guide
173089-01 1900/65A Field Wiring Diagrams
02200794 Power supply, 110/220 Vac to 24 Vdc 2.5 A DIN rail mount
02200121 DIN rail end bracket
168374 35mm DIN rail mounting clip for 1900/65A Monitor Module
168495 Bulkhead mounting plate
168547-0010-01-01 3 m (10 ft) PVC cable, assembled
168547-0010-01-02 3 m (10 ft) PVC cable, unassembled
168547-0010-02-01 3 m (10 ft) TEF cable, assembled
168547-0010-02-02 3 m (10 ft) TEF cable, unassembled
168547-0050-01-01 15 m (50 ft) PVC cable, assembled
168547-0050-01-02 15 m (50 ft) PVC cable, unassembled
168547-0050-02-01 15 m (50 ft) TEF cable, assembled
168547-0050-02-02 15 m (50 ft) TEF cable, unassembled
168547-0100-01-01 30 m (100 ft) PVC cable, assembled
168547-0100-01-02 30 m (100 ft) PVC cable, unassembled
168547-0100-02-01 30 m (100 ft) TEF cable, assembled
168547-0100-02-02 30 m (100 ft) TEF cable, unassembled
168547-0250-01-01 75 m (250 ft) PVC cable, assembled
168547-0250-01-02 75 m (250 ft) PVC cable, unassembled
168547-0250-02-01 75 m (250 ft) TEF cable, assembled
168547-0250-02-02 75 m (250 ft) TEF cable, unassembled
168628 Stainless steel NEMA 4X weatherproof door for panel-mount display assembly
168629 Painted steel NEMA 4 weatherproof door for panel-mount display assembly
168944 Fiberglass NEMA 4X/IP66 weatherproof housing with window in door
02295055 MTL 728(-) barrier
02245002 MTL 796(-) barrier
172555 Modbus/TCP (Ethernet) to Modbus/RTU (Serial) Converter
169825-01 Training CD

FOR REFERENCE ONLY Specifications and Ordering Information Page 14 of 18


REFER TO DOCUMENT #173401
Dimensions
Note: All dimensions shown in millimeters (inches) except as noted.

Figure 5: Monitor Module Dimensions

Figure 6: Display Module Dimensions

FOR REFERENCE ONLY Specifications and Ordering Information Page 15 of 18


REFER TO DOCUMENT #173401
Figure 7: Combined Dimensions

FOR REFERENCE ONLY Specifications and Ordering Information Page 16 of 18


REFER TO DOCUMENT #173401
Figure 8: Weatherproof Housing Dimensions

FOR REFERENCE ONLY Specifications and Ordering Information Page 17 of 18


REFER TO DOCUMENT #173401
Figure 9: Weatherproof Door Drill Pattern

Figure 10: Weatherproof Door Dimensions

2006 Bently Nevada LLC


Proximitor, Velomitor, and NSvTM and System 1 are trademarks of the General Electric Company
Microsoft and Windows are registered trademarks of Microsoft Corporation
CSA is a registered trademark of CSA-International
Modbus is a registered trademark of Schneider Automation, Inc.

FOR REFERENCE ONLY Specifications and Ordering Information Page 18 of 18