(i) In load case 11,15,19 & 23 impact factor for live load considered is 15%, but
as per IS 4651(Part-III), Clause no 5.1.3, it should be 25%.please clarify??
(ii) In load case 43, member load defined as
116 TO 128 UNI GX 2.125, but it should be 97 TO 110 UNI GX 2.125 please
modify. case no 93, differential shrinkage of concrete is not considered. Please
consider differential shrinkage in terms of temp. difference