Addendum

Modbus/TCP Communications Board.


Installation:
The Modbus/TCP Device server is designed to plug in to any slot on the MT3000 series
integrators. The Microtech commutations setup is default to factory standard. Go to
Main menu 5 and select Comm A, use down arrow to scroll through setup parameters.
Assure that all comm. boards are addressed at address 1, this is necessary to allow the
communications between the network device server and the Microtech.

Main Menu 5 Scroll


Baud rate port #1 9600
Parity port #1 No parity
Stop Bits port #1 1
Word length port #1 8
Protocol port #1 MODBUS
Clear to send #1 Disabled
Address port #1 1
Access prot port #1 None

The Modbus/TCP server will plug in to any slot on the Microtech 2000 series integrators
but the end plate is tight and may need to be nibbled out. Set up is same as MT3000
series.

Rec4251 Rev A 1 Used with P/N 084727


P/N 085719 Date 3/15/05
The Ethernet address is also referred to as the hardware address or MAC address. The
first three bytes of the Ethernet address are fixed and read 00-20-4A, identifying the unit
as a Lantronix product. The fourth, fifth, & sixth bytes are unique numbers assigned to
each unit.

Mac Address label example


00-20-4A-71-9E-0C

Reference the appropriate Serial Communications manual for your Microtech Integrator
for the Modbus Data address registers.

Model Manual
MT2100, MT3100 REC 3948
MT2001, MT2101, MT2201. MT2301, MT3101 REC 3949
MT2102 REC 4037
MT2104 REC 3951
MT2105, MT2305, MT3105 REC 3952
MT2106, MT3106 REC 3953
MT2107, MT3107 REC 3987

Rec4251 Rev A 2 Used with P/N 084727


P/N 085719 Date 3/15/05
Modbus/TCP Device Server Setup
This appendix covers the required steps to get any one of the Device Servers
on-line and working. There are two basic methods used to log into the
Device Server and setup the IP address:
Network Port Login - Make a Telnet connection to the network port
(9999)
Serial Port Login Connect a terminal or a PC running a terminal
emulation program to the Device Servers first serial port (CH 1).
It is important to consider the following points before logging into and
configuring the Device Server:
The Device Servers IP address must be configured before a network
connect is available.
Only one person at a time may be logged into the network port. This
eliminates the possibility of several people simultaneously attempting to
configure the Device Server.
Network port logins can be disabled. The system manager will not be
able to access the unit. This port can also be password protected.
Only one terminal at a time can be connected to the serial port (In RS-
485 mode, the Device Server is capable of multidrop connections.)
Address and Port Number
The Ethernet address is also referred to as the hardware address or the MAC
address. The first three bytes of the Ethernet Address are fixed and read 00-
20-4A, identifying the unit as a Lantronix product. The fourth, fifth, and
sixth bytes are unique numbers assigned to each unit.

00-20-4A-74-05-52 OR 00:20:4A:74:05:52
Every device connected to an IP network must have a unique IP address.
This address is used to reference the specific unit.
A destination IP address and a port number define every TCP connection and
every UDP datagram. For example, a Telnet application commonly uses port
number 23. A port number is similar to an extension on a PBX system.
The units serial channel (port) can be associated with a specific TCP/UDP
port number. Port number 9999 is reserved for access to the units Setup
(Configuration) Mode window.
Setting the units IP address to 0.0.1.0 can disable AutoIP. This setting
enables DHCP but disables AutoIP.

Rec4251 Rev A 3 Used with P/N 084727


P/N 085719 Date 3/15/05
DeviceInstaller
You can manually assign the IP address using DeviceInstaller software. This
software can be downloaded from the Lantronix web site at:
http://www.lantronix.com/support/utils/dst/index.html
Once at the web site select Download the latest version of
DeviceInstaller. At the next screen, select Download Device Installer
v2.0 via FTP.
Appendix Figure 0-1: Lantronix Web Selections

A90875

A90876

Follow the download instructions and install the software on a personal


computer. Attach the personal computer to the network connected to the
Microtech Modbus/TCP Ethernet board. Please contact the Lantronix help
line for problems with the installation and operation of the DeviceInstaller
software.
Use the following procedure to assign an IP address and Network class.
1. Choose Start \Programs\Device Installer\Device Installer

Rec4251 Rev A 4 Used with P/N 084727


P/N 085719 Date 3/15/05
The following screen displays:
Appendix Figure 0-2: DeviceInstaller Main Screen

A90877

Click the IP icon. The assign IP address screen displays:


Appendix Figure 0-3: Assign IP Address

A90878

Rec4251 Rev A 5 Used with P/N 084727


P/N 085719 Date 3/15/05
In the Enter the Hardware or Ethernet Address field, enter the
Ethernet address (MAC address), which is listed on the label on the
bottom of the unit.
In the Enter IP Address to assign field, enter the units IP address in
XXX.XXX.XXX.XXX format.
In the PC Network Class section, select the class (subnet mask).
)Hint: Most users select Class C.
Click Set IP Address
Confirm the Successful message displays and click OK
Click Back and return to the DeviceInstaller main window
Test the IP Address
Use the follow steps to test the IP address setup:

2. Click the Ping icon. The Ping Device window displays.


Appendix Figure 0-4: Ping Device Window

A90879

Confirm the Reply received messages display in the window indicating the IP address has
been entered successfully.
Note: If you do not receive Reply received messages, make sure the unit is
properly attached to the network and that the IP address assigned is valid for
the particular network segment you are working with. If you are not sure,
check with your systems administrator.
Click Back to return to the DeviceInstaller main window.

Rec4251 Rev A 6 Used with P/N 084727


P/N 085719 Date 3/15/05
Add the Unit to the Manage List
After the network has been pinged and all things are working properly, use
the following steps to add the unit to the list of similar Lantronix devices on
the network.
3. At the DeviceInstaller main screen, click Search the network for

devices icon . The following screen displays:


Appendix Figure 0-5: Search the Network Screen

A90880

Select the PC Network Class (C is the default).


Click Start Search. A list of all active units displays.
Click Save. A confirmation message displays.
Click OK.
Click Back to return to the DeviceInstaller main window. The DeviceInstaller screen now
lists all of the devices in the group including the unit you are setting up. The hardware address
and firmware release number for the unit displays.
This procedure gives you the ability to manage (configure) the unit to
work with the serial device on the network.

Rec4251 Rev A 7 Used with P/N 084727


P/N 085719 Date 3/15/05
Status LEDs
The Cobox-Micro has four LEDs: channel 1 status, channel 2 status, diagnostics, and
network link status. See table for description.

Red Diagonstics
Green Channel 1 (blinks green when active)
3 1
2 4 Green Network Status (solid green)
Yellow Channel 2 (not used)

LED Description LED Function


1 Green Lights solid green to indicate channel 1 is idle. Blinks to
Channel 1 indicate Channel 1 is connected to the network and active.
status
2 Yellow Lights solid yellow to indicate channel 1 is idle. Blinks to
Channel 2 indicate Channel 1 is connected to the network and active.
status
3 Red Blinks or lights solid red in combination with the green
Diagnostics channel 1 LED to indicate diagnostics and error detection.
Red solid, green channel 1 blinking.
1x: EPROM checksum error
2x: Ram error
3x: Network controller error
4x: EEPROM checksum error
5x: Duplicate IP address on network *
6x: Software does not match hardware *

Red blinking, green channel 1 blinking


4x: Faulty network connection *
5x: No DHCP response received *
4 Green Lights solid green to indicate network port is connected to the
Network Link network.
Status
* Non-fatal error

Rec4251 Rev A 8 Used with P/N 084727


P/N 085719 Date 3/15/05