XXXXX Hfc134a Push PDF
XXXXX Hfc134a Push PDF
P134a
DuPont Suva
refrigerants
DuPont
HFC-134a
Properties, Uses,
Storage, and Handling
Table of Contents
Page
Introduction ................................................................................................................. 1
Background ................................................................................................................ 1
HFC-134aAn Environmentally Acceptable Alternative ........................................... 1
Uses .............................................................................................................................. 1
Safety ........................................................................................................................... 18
Inhalation Toxicity .....................................................................................................18
Cardiac Sensitization ................................................................................................. 18
Skin and Eye Contact ................................................................................................ 18
Spills or Leaks ........................................................................................................... 19
Combustibility of HFC-134a ........................................................................................ 19
Figure 1. Infrared Spectrum of HFC-134a Vapor at 400 mmHg Pressure (53.3 kPa) in a 10-cm Cell
MICRONS
2.5 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10 12 14 16 18 20 25 30 35 4050
100 100
80 80
TRANSMITTANCE (%)
TRANSMITTANCE (%)
60 60
40 40
20 20
0 0
4,000 3,500 3,000 2,500 2,000 1,800 1,600 1,400 1,200 1,000 800 600 400 200
-1
MICRONS WAVENUMBER (CM )
1
The thermodynamic and physical properties of saturated liquid and vapor in addition to heat
HFC-134a, coupled with its low toxicity, make it a capacity data and heat capacity ratios for both satu-
very efficient and safe replacement refrigerant for rated and superheated vapors. Thermodynamic
CFC-12 in many segments of the refrigeration in- tables in English and SI units are available in
dustry, most notably in automotive air conditioning, Bulletins T-134a-ENG and T-134a-SI. Liquid
appliances, small stationary equipment, medium- and vapor densities are included in the thermody-
temperature supermarket cases, and industrial and namic tables.
commercial chillers. Table 1 provides a comparison
Chemical/Thermal Stability
of the theoretical performance of CFC-12 and
HFC-134a at medium-temperature conditions.
Thermal Decomposition
Table 1
HFC-134a vapors will decompose when exposed
Theoretical Cycle Comparison of CFC-12 to high temperatures from flames or electric resist-
and HFC-134a* ance heaters. Decomposition may produce toxic
and irritating compounds, such as hydrogen fluoride.
CFC-12 HFC-134a The pungent odors released will irritate the nose and
Capacity (as % CFC-12) 100 99.7
throat and generally force people to evacuate the
area. Therefore, it is important to prevent decompo-
Coefficient of Performance (COP) 3.55 3.43
sition by avoiding exposure to high temperatures.
Compressor
Exit Temperature, C (F) 86.8 (188.2) 83.1 (181.5)
Exit Pressure, kPa (psia) 1349 (195.6) 1473 (213.7)
Stability with Metals and
Refrigeration Lubricants
Compression Ratio 4.1 4.7
Stability tests for refrigerants with metals are typi-
* Temperatures were as follows: Condenser, 54.4C cally performed in the presence of refrigeration oils.
(130.0F); Evaporator, 1.7C (35.0F); Compressor Suction,
26.7C (80.0F); Expansion Device, 51.7C (125.0F). The results of sealed tube stability tests are avail-
able for CFC-12/mineral oil combinations, which
HFC-134a can be used to replace CFC-11, CFC-12, have shown long-term stability in contact with cop-
and HCFC-142b in many thermoplastic foam ap- per, steel, and aluminum in actual refrigeration sys-
plications. HFC-134a can be used as a replacement tems. Polyalkylene glycol (PAG) and polyol ester
for CFC-12 and HCFC-141b in thermoset foams. (POE) lubricants are used with HFC-134a. Sealed
HFC-134a features properties that are advanta- tube tests were run to determine the relative long-
geous for high value-in-use products and meets the term stability of HFC-134a/metals in the presence
requirements of safety/environmental issues. of these lubricants.
HFC-134a is nonflammable, has negligible photo- The method followed was generally the same as
chemical reactivity, and low vapor thermal ASHRAE 97 with several minor modifications. A
conductivity. 3-mL volume of refrigerant/lubricant solution was
HFC-134a is also being developed for use in phar- heated in the presence of copper, steel, and alumi-
maceutical inhalers because of its low toxicity and num strips in an oven for 14 days at 175C (347F).
nonflammability. Other aerosol applications may use Both the neat lubricant and a mixture of lubricant
HFC-134a where these properties are critical. See and refrigerant (50/50 volume ratio) were tested.
DuPont Dymel Bulletin ATB-30 for additional Visual ratings were obtained on both the liquid solu-
information on aerosol applications of HFC-134a. tions and the metal coupons after the designated
exposure time. The visual ratings ranged from 0 to
5, with 0 being the best.
Physical Properties
After the visual ratings were obtained, sample tubes
Physical properties of HFC-134a are given in
were opened and the lubricant and refrigerant (if
Table 2 and Figures 2 through 8. Additional physi-
present) were analyzed. The lubricant was typically
cal property data may be found in other DuPont
checked for halide content and viscosity, while the
publications. Bulletin ART-1 contains viscosity,
refrigerant was examined for the presence of de-
thermal conductivity, and heat capacity data for
2
Table 2
Physical Properties of HFC-134a
Physical Properties Unit HFC-134a
3
composition products. Table 3 summarizes typical Figure 2. Solubility of Water in HFC-134a
data for both HFC-134a and CFC-12. Visual ratings Temperature, C
are listed for the neat lubricant, the lubricant/ 0 40 20 0 20 40 60 80 100
refrigerant solution and the three metals that
were present in the lubricant/refrigerant solutions. 3,500
Viscosity was determined on the unused lubricant,
the tested neat lubricant, and the lubricant tested in
the presence of refrigerant. A percent change was 3,000
calculated for the two tested lubricants. The decom-
0
50 0 50 100 150 200
Temperature, F
Table 3
Stability of HFC-134a with Metals and Lubricating Oils
Mobil Castrol
Mineral Mineral UCON EAL Icematic
Oil Oil Oil RO-W-6602* Arctic 32** SW 100**
Oil Viscosity, cSt at 40C (104F) 30.7 125 134 29.4 108.8
Refrigerant R-12 R-12 HFC-134a HFC-134a HFC-134a
Ratings
Neat Oil 0 0 0
Oil/Refrigerant 4 4 0 0 0
Copper 2 2 0 0 0
Iron 3 3 0 0 0
Aluminum 2 2 0 0 0
Viscosity Change
% Change Neat ND ND <1 3.1 4.3
% Change with Refrigerant ND ND 12.7 36.2 27.1
Decomposition Analysis
HFC-143a, ppm ND ND <7 <3 <0.3
Fluoride, ppm ND 420 <0.7 <7
4
Figure 3. Pressure vs. Temperature (SI Units)
10,000
1,000
Pressure, kPa
100
10
1
100 50 0 50 100 150
Temperature, C
1,000
100
Pressure, psia
10
0.1
150 100 50 0 50 100 150 200 250
Temperature, F
5
Figure 5. Vapor Thermal Conductivity of HFC-134a at Atmospheric Pressure (SI Units)
0.030
0.028
m C
Watts
0.026
Vapor Thermal Conductivity,
0.024
0.022
0.020
0.018
0.016
0.014
0.012
0.010
0 20 40 60 80 100 120 140
Temperature, C
0.016
0.015
hr ft F
Btu
0.014
Vapor Thermal Conductivity,
0.013
0.012
0.011
0.010
0.009
0.008
0.007
0.006
0 40 80 120 160 200 240 280
Temperature, F
6
Stability with Foam Chemicals Materials Compatibility
As with other alternative blowing agents, the Because HFC-134a is used in many applications, it
stability of HFC-134a in foam chemicals (B-side is important to review materials of construction for
systems) is being studied. The first tests evaluated compatibility when designing new equipment, retro-
HFC-134a stability in a sucrose-amine polyether fitting existing equipment, or preparing storage and
polyol with either an amine catalyst, a potassium handling facilities.
catalyst, a tin catalyst, or an amine catalyst neutral-
ized with an organic acid. The initial tests, which Plastics
included analysis of the volatile components, Customary industry screening tests, in which 23
showed no degradation of HFC-134a in any of the typical plastic materials were exposed to liquid
systems, even at elevated temperatures. The results HFC-134a in sealed glass tubes at room tempera-
are summarized in Table 4. ture, are summarized in Table 5. Observations of
weight gain and physical change were used to sepa-
Table 4 rate materials meriting further laboratory and/or
Stability of HFC-134a with Foam Chemicals field testing from materials that appeared unaccept-
Catalyst Degradation, % able. Users of this bulletin should confirm compat-
ibility in their own system designs.
Amine <0.001
Table 5
Potassium <0.001 Plastics Compatibility of HFC-134a
Tin <0.001
Chemical Type Trade Name
Neutralized Amine <0.001
Test Conditions Plastic materials meriting further testing:
Six weeks at 60C (140F). ABS Kralastic (Uniroyal Chem.)
25% (wt.) HFC-134a. Acetal Delrin
Two parts catalyst per 100 parts polyol by weight. Epoxy
One part water per 100 parts polyol by weight. Fluorocarbons
Type 1010 steel test coupon. PTFE Teflon
ETFE Tefzel
PVDF
Compatibility Concerns if HFC-134a Ionomer Surlyn
and CFC-12 Are Mixed Polyamide
HFC-134a and CFC-12 are chemically compatible 6/6 Nylon Zytel
with each other; this means that they do NOT react Polyarylate Arylon
Polycarbonate Tuffak (Rohm & Haas Co.)
with each other to form other compounds. However, Polyester
when the two materials are mixed together, they form PBT Valox (General Electric)
what is known as an azeotrope. An azeotrope is a PET Rynite
mixture of two components that acts like a single Polyetherimide Ultem (General Electric)
compound, but has physical and chemical properties Polyethylene-HD Alathon
different from either of the two components. An Polyphenylene Oxide Noryl (General Electric)
example of this is Freon 502, which is an azeotrope Polyphenylene Sulfide Ryton (Phillips Chem. Co.)
of HCFC-22 and CFC-115. When HFC-134a and Polypropylene
CFC-12 are mixed in certain concentrations, they Polystyrene Styron (Dow Chem. Co.)
form a high-pressure (low boiling) azeotrope. This Polysulfone Polysulfone
Polyvinyl Chloride
means that the vapor pressure of the azeotrope is
PVC
higher than that of either of the two components by CPVC
themselves. At 752 kPa absolute (109 psia) the
Plastic materials exhibiting unacceptable change:
azeotrope contains 46 wt% HFC-134a. In general,
Acrylic Lucite
compressor discharge pressures will be undesirably Cellulosic Ethocel (Dow Chem. Co.)
high if refrigeration equipment is operated with
a mixture of HFC-134a and CFC-12. Test Conditions: Plastic specimens exposed to liquid
HFC-134a (no lubricant) in sealed glass tubes for two weeks
Another characteristic of an azeotrope is that it is at room temperature.
very difficult to separate the components once they
Delrin, Teflon, Tefzel, Surlyn, Zytel, Arylon, Rynite, and
are mixed together. Therefore, a mixture of HFC- Lucite are registered trademarks of DuPont.
134a and CFC-12 cannot be separated in an on-site
recycle machine or in the typical facilities of an off- Because the performance of plastic materials is
site reclaimer. Mixtures of HFC-134a and CFC-12 affected by polymer variations, compounding
will usually have to be disposed of by incineration. agents, fillers, and molding processes, verifying
compatibility using actual fabricated parts under
end-use conditions is advised.
7
DuPont Fluorochemicals
HFC-134a
Pressure-Enthalpy Diagram
(SI Units)
8
Figure 7. Pressure-Enthalpy Diagram for HFC-134a (SI Units)
DuPont Fluorochemicals
HFC-134a
Pressure-Enthalpy Diagram
(English Units)
9
Figure 8. Pressure-Enthalpy Diagram for HFC-134a (English Units)
Elastomers The studies were run at 80C (176F) with an initial
Compatibility results for HFC-134a and CFC-12 are 80 vol % liquid loading of HFC-134a in 76-cm
compared for 11 typical elastomers in Tables 6 (30-in) lengths of 15.9-mm (5/8-in) inside diameter
through 17. It should be recognized, however, automotive air-conditioning hose. Hose construction
that effects on specific elastomers depend on the and permeation rates are summarized in Table 18.
nature of the polymer, the compounding formulation Based on these tests, hoses lined with nylon, as well
used, and the curing or vulcanizing conditions. as those made of Hypalon 48, appear to be suitable
Actual samples should be tested under end-use for use with HFC-134a. Note, however, that these
conditions before specifying elastomers for critical rate measurements provide a comparison of the
components. various hoses at a single temperature and should not
be used as an indication of actual permeation losses
Recommendations, based on the detailed data in from an operating system.
Tables 7 through 17, are given in Table 6. Data
on temporary elastomer swell and hardness changes Desiccants
were used as the prime determinants of compatibil- Driers filled with desiccant are typically used in
ity. The subsequent final data were used as a guide refrigeration systems and bulk storage facilities.
to indicate if the seals in a refrigeration system A common molecular sieve desiccant used with
should be replaced after equipment teardown. CFC-12, UOPs 4A-XH-5, is not compatible with
Most polymeric materials used in refrigeration HFC-134a. However, manufacturers have devel-
equipment are exposed to a mixture of refrigerant oped other molecular sieve desiccants that perform
and refrigeration oil. well with HFC-134a. UOPs XH-7 and XH-9 or
Graces MS 592 or MS 594 desiccants may be used
DuPont Films has measured the compatibility of in loose filled driers. Compacted bead dryers, in
Mylar polyester film with HFC-134a/polyol ester which the desiccant is compacted by mechanical
lubricant systems compared to CFC-12/mineral oil pressure, may use XH-6 in addition to the desic-
systems. Slot liners, wedges, and interphase insula- cants listed above.
tion of Mylar are widely used in hermetic com-
pressor motors for CFC-12 service. Studies indicate In molded core driers, the molecular sieve is dis-
that the life of Mylar in systems using HFC-134a persed within a solid core. Several manufacturers
will be comparable to film life in CFC-12 systems. offer molded core driers that are compatible with
In cases where polyester film fails in hermetic sys- HFC-134a. Consult the drier manufacturer for
tems, the cause is usually traced to unwanted mois- recommendations.
ture. Too much moisture causes polyester film to
hydrolyze and embrittle. Results indicate that the Refrigeration Lubricants
POE lubricants used with HFC-134a tend to pull Most compressors require a lubricant to protect
water from Mylar. This promotes a drier film, internal moving parts. The compressor manufac-
which should result in a longer motor insulation life. turer usually recommends the type of lubricant
Because polyester motor insulation is buried be- and viscosity that should be used to ensure proper
neath windings and can be difficult to dry, this water operation and equipment durability. Recommenda-
extraction capability of POE lubricants should be a tions are based on several criteria, such as lubricity,
valuable performance asset. Further information is compatibility with materials of construction, thermal
available from DuPont Films. stability, and refrigerant/oil miscibility. To ensure
efficient operation and long equipment life, it is im-
Additional materials compatibility data are being
portant to follow the manufacturers recommendations.
developed by equipment manufacturers.
Current lubricants used with CFC-12 are fully mis-
Hose Permeation cible over the range of expected operating condi-
Elastomeric hoses are used in mobile air-condition- tions, easing the problem of getting the lubricant to
ing systems and for transferring HFC-134a in other flow back to the compressor. Refrigeration systems
applications. The permeation rates of HFC-134a using CFC-12 take advantage of this full miscibility
and CFC-12 through several automotive A/C hoses when considering lubricant return. Refrigerants
were measured as a guide to hose selection. such as HFC-134a, with little or no chlorine, may
exhibit less solubility with many existing mineral oil
or alkylbenzene lubricants.
10
The search for lubricants for use with HFC-134a Although HFC-134a and CFC-12 are chemically
started with commercially available products. compatible with each other, such is not the case
Table 19 shows solubilities of various refrigerant/ with CFC-12 and PAG lubricants. Specifically, the
lubricant combinations. Current naphthenic, paraf- chlorine contained in CFC-12 or other chlorinated
finic, and alkylbenzene lubricants have very poor compounds can react with the PAG and cause
solubility with HFC-134a. PAGs with low viscosity lubricant degradation. Lubricant degradation can
show good solubility but, as viscosity increases, they result in poor lubrication and premature failure.
become less soluble. Polyol ester lubricants, of In addition, sludge will be formed, which can plug
which there are many types, generally show good orifice tubes and other small openings.
solubility with HFC-134a. When compared with
PAGs, ester lubricants are more compatible with
hermetic motor components and are less sensitive
to mineral oil and CFC-12 remaining in a refrigera-
tion system.
Table 6
Elastomer Compatibility of HFC-134a
Ratings
CFC-12 HFC-134a
25C 80C 141C 25C 80C 141C
(77F) (176F) (285F) (77F) (176F) (285F)
Adiprene L 1 5 2 5
Buna N 1* 0* 2* 1 0* 1
Buna S 3 4 3 2
Butyl Rubber 2 4 0 3
Hypalon 48 1 0 0 1* 0 0
Natural Rubber 4 5 0 2
Neoprene W 0* 1* 0 2
Nordel Elastomer 2* 2* 1 1
Silicone 5 5 2 2
Thiokol FA 1 1 1* 0
Viton A 5 5 5 5
*Recommend elastomer replacement after equipment teardown. Codes: 0 = No change.
Hypalon, Nordel and Viton are DuPont registered trademarks. 1= Acceptable change.
Adiprene is a Uniroyal registered trademark. 2= Borderline change.
Thiokol FA is a Morton Thiokol registered trademark. 3= Slightly unacceptable change.
4= Moderately unacceptable change.
5= Severely unacceptable change.
11
Table 7
Compatibility of Refrigerants with Adiprene L
25C (77F) 80C (176F)
CFC-12 HFC-134a CFC-12 HFC-134a
Length Change, %
Temporary 1.8 5.5 2.1 5.0
a
Final 0.3 0.1 0.5
Weight Change, %
Temporary 8.5 20 5.2 20
a
Final 1.2 0.3 0.5
Shore A Hardness
Original 60 61 60 63
a
Temporary, D SH 2 4 28
Final, D SH 0 1 19
Elasticity Rating
Temporary 0 0 5a 4b
Final 0 0 5a 5c
Visual Rating
Liquid 0 0 0 0
Polymer
Temporary 0 0 0 1d
Final 0 0 5a 2d
Test Conditions: 27 days immersion of the polymer at 25C (77F) and 80C (176F) in liquid (temporary) plus two
weeks drying in air at about 25C (77F) (final).
a c
Sample disintegrated Broke when stretched
b d
More elastic Sticky
Table 8
Compatibility of Refrigerants with Buna N
CFC-12 HFC-134a
25C 80C 141C 25C 80C 141C
(77F) (176F) (285F) (77F) (176F) (285F)
12
Table 9
Compatibility of Refrigerants with Buna S
25C (77F) 80C (176F)
CFC-12 HFC-134a CFC-12 HFC-134a
Length Change, %
Temporary 0.1 1.1 0.7 0.8
Final 2.5 <0.1 2.6 0.3
Weight Change, %
Temporary 2.8 1.9 2.9 2.5
Final 6.2 0.1 6.2 0.1
Shore A Hardness
Original 85 84 83 81
Temporary, D SH 12 12 16 9
Final, D SH 8 2 9 2
Elasticity Rating
Temporary 0 0 0 1a
Final 3b 1b 3b 0
Visual Rating
Liquid 0 0 0 0
Polymer
Temporary 0 0 0 0
Final 0 0 0 0
Test Conditions: 27 days immersion of the polymer at 25C (77F) and 80C (176F) in liquid (temporary) plus two
weeks drying in air at about 25C (77F) (final).
a
More elastic
b
Less elastic
Table 10
Compatibility of Refrigerants with Butyl Rubber
25C (77F) 80C (176F)
CFC-12 HFC-134a CFC-12 HFC-134a
Length Change, %
Temporary 6.3 0.2 7.6 1.3
Final 1.2 0 0.8 0.4
Weight Change, %
Temporary 34 2.0 36 3.7
Final 2.6 0.1 1.2 0.6
Shore A Hardness
Original 54 54 57 58
Temporary, D SH 8 1 14 4
Final, D SH 1 2 10 3
Elasticity Rating
Temporary 1a 1a 3a 0
Final 0 0 2a 0
Visual Rating
Liquid 0 0 3b 0
Polymer
Temporary 0 0 3c 4c
Final 0 0 1d 2d
Test Conditions: 27 days immersion of the polymer at 25C (77F) and 80C (176F) in liquid (temporary) plus two
weeks drying in air at about 25C (77F) (final).
a c
More elastic White deposit on elastomer
b d
White solids in liquid White film on elastomer
13
Table 11
Compatibility of Refrigerants with Hypalon 48
CFC-12 HFC-134a
25C 80C 141C 25C 80C 141C
(77F) (176F) (285F) (77F) (176F) (285F)
Table 12
Compatibility of Refrigerants with Natural Rubber
25C (77F) 80C (176F)
CFC-12 HFC-134a CFC-12 HFC-134a
Length Change, %
Temporary 14 1.3 14 2.0
Final 1.1 0.3 0.8 0.4
Weight Change, %
Temporary 51 4.5 55 5.8
Final 2.6 0.5 2.6 0.6
Shore A Hardness
Original 55 56 56 57
Temporary, D SH 9 1 17 8
Final, D SH 5 4 8 4
Elasticity Rating
Temporary 0 0 1* 1*
Final 0 0 2* 0
Visual Rating
Liquid 0 0 0 0
Polymer
Temporary 0 0 0 0
Final 0 0 0 0
Test Conditions: 27 days immersion of the polymer at 25C (77F) and 80C (176F) in liquid (temporary) plus two
weeks drying in air at about 25C (77F) (final).
* More elastic
14
Table 13
Compatibility of Refrigerants with Neoprene W
25C (77F) 80C (176F)
CFC-12 HFC-134a CFC-12 HFC-134a
Length Change, %
Temporary 0.2 0.7 0.9 1.4
Final 7.6 0.5 7.3 0.3
Weight Change, %
Temporary 6.6 2.3 6.8 2.9
Final 12 0.6 13 1.8
Shore A Hardness
Original 73 73 73 72
Temporary, D SH 1 0 5 7
Final, D SH 10 0 5 5
Elasticity Rating
Temporary 2a 0 1b 0
Final 2a 0 2b 0
Visual Rating
Liquid 1c 0 1d 0
Polymer
Temporary 0 0 1e 0
Final 0 0 0 0
Test Conditions: 27 days immersion of the polymer at 25C (77F) and 80C (176F) in liquid (temporary) plus two
weeks drying in air at about 25C (77F) (final).
a d
Less elastic Hazy
b e
More elastic White film
c
Clear, yellow
Table 14
Compatibility of Refrigerants with Nordel Elastomer
25C (77F) 80C (176F)
CFC-12 HFC-134a CFC-12 HFC-134a
Length Change, %
Temporary 0.6 0.5 0.4 0.7
Final 8.2 0.2 8.4 0.4
Weight Change, %
Temporary 5.5 2.8 6.1 4.4
Final 22 <0.1 22 0.2
Shore A Hardness
Original 66 66 65 63
Temporary, D SH 4 3 0 6
Final, D SH 19 4 20 0
Elasticity Rating
Temporary 2a 0 2b 1b
Final 2a 0 2b 0
Visual Rating
Liquid 0 0 0 1d
Polymer
Temporary 0 0 0 0
Final 0 0 1c 0
Test Conditions: 27 days immersion of the polymer at 25C (77F) and 80C (176F) in liquid (temporary) plus two
weeks drying in air at about 25C (77F) (final).
a c
Less elastic White film
b d
More elastic Hazy
15
Table 15
Compatibility of Refrigerants with Silicone
25C (77F) 80C (176F)
CFC-12 HFC-134a CFC-12 HFC-134a
Length Change, %
Temporary 41 6.1 44 5.5
Final 0.1 0.1 0.2 0.2
Weight Change, %
Temporary 173 20 187 20.3
Final 0.7 0.1 0.7 0.3
Shore A Hardness
Original 60 61 60 58
Temporary, D SH 13 8 15 6
Final, D SH 7 4 7 2
Elasticity Rating
Temporary 0 1a 1a 0
Final 0 0 0 0
Visual Rating
Liquid 0 0 0 0
Polymer
Temporary 5b 0 4b 0
Final 0 0 0 0
Test Conditions: 27 days immersion of the polymer at 25C (77F) and 80C (176F) in liquid (temporary) plus two
weeks drying in air at about 25C (77F) (final).
a
Less elastic
b
Swollen
Table 16
Compatibility of Refrigerants with Thiokol FA
25C (77F) 80C (176F)
CFC-12 HFC-134a CFC-12 HFC-134a
Length Change, %
Temporary 1.3 0.8 1.4 0.2
Final 0.5 0.2 0.5 0.9
Weight Change, %
Temporary 1.9 1.0 3.7 1.9
Final 0.2 0.1 0.8 0.8
Shore A Hardness
Original 70 69 74 74
Temporary, D SH 6 4 6 0
Final, D SH 5 6 1 0
Elasticity Rating
Temporary 1b 1b 0 1b
Final 0 0 1a 2a
Visual Rating
Liquid 0 0 0 0
Polymer
Temporary 0 0 0 0
Final 0 0 0 0
Test Conditions: 27 days immersion of the polymer at 25C (77F) and 80C (176F) in liquid (temporary) plus two
weeks drying in air at about 25C (77F) (final).
a
Less elastic
b
More elastic
16
Table 17
Compatibility of Refrigerants with Viton A
25C (77F) 80C (176F)
CFC-12 HFC-134a CFC-12 HFC-134a
Length Change, %
Temporary 5.5 13 4.9 12
Final 0.7 0.1 1.2 0.3
Weight Change, %
Temporary 19 48 20 49
Final 1.8 0.7 2.5 1.2
Shore A Hardness
Original 74 74 73 73
Temporary, D SH 19 30 23 31
Final, D SH 7 8 10 6
Elasticity Rating
Temporary 2b 2b 3a 3a
Final 0 0 0 0
Visual Rating
Liquid 0 0 0 0
Polymer
Temporary 0 1c 0 0
Final 0 1d 0 5e
Test Conditions: 27 days immersion of the polymer at 25C (77F) and 80C (176F) in liquid (temporary) plus two
weeks drying in air at about 25C (77F) (final).
a d
Less elastic Oily sheen
b e
More elastic Puffed mounds5% of surface
c
Very slightly tacky
Table 18
HFC-134a Permeation Through Elastomeric Hoses
Permeation Rate, gm/cmyr (lb/ftyr)
17
Table 19
Solubilities of HFC-134a in Lubricants
Temperature Range: 50C to 93C (58F to 199F)
Percent Refrigerant in Mixture
18
Spills or Leaks In general, HFC-134a should not be allowed to exist
If a large release of vapor occurs, such as from a with air above atmospheric pressure or at high tem-
large spill or leak, the vapors may concentrate near peratures; or in an oxygen enriched environment.
the floor or low spots and displace the oxygen avail- For example HFC-134a should NOT be mixed
able for breathing, causing suffocation. with air under pressure for leak testing or
other purposes.
Evacuate everyone until the area has been venti-
lated. Use blowers or fans to circulate the air at Refrigerants should not be exposed to open flames
floor level. Do not reenter the affected area unless or electrical heating elements. High temperatures
you are equipped with a self-contained breathing and flames can cause the refrigerants to decom-
apparatus or unless an area monitor indicates that pose, releasing toxic and irritating fumes. In addi-
the concentration of HFC-134a vapors in the area tion, a torch flame can become dramatically larger
is below the AEL. or change color if used in high concentrations of
many refrigerants including R-500 or R-22, as
Always use self-contained breathing apparatus or well as many alternative refrigerants. This flame
an air-line mask when entering tanks or other areas enhancement can cause surprise or even injury.
where vapors might exist. Use the buddy system Always recover refrigerants, evacuate equipment,
and a lifeline. Refer to the MSDS for HFC-134a and ventilate work areas properly before using any
for more information. open flames.
HFC-134a vapors have a slightly sweet odor that Test results and calculations have shown:
can be difficult to detect. Therefore, frequent leak
checks and the installation of permanent area At ambient temperature, all concentrations of
monitors are necessary in enclosed spaces. Refer HFC-134a in air are nonflammable at pressures
to American Society of Heating, Refrigerating, and below 205 kPa absolute (15 psig).
Air Conditioning Engineers (ASHRAE) Standards Combustible mixtures of air and HFC-134a will
15-94 and 34 for refrigeration machinery rooms. not form when liquid HFC-134a is pumped into a
To ensure safety when working with HFC-134a in closed vessel if the initial air pressure in the vessel
enclosed areas: is limited to 1 atm absolute and the final pressure
1. Route relief and purge vent piping (if present) is limited to 2,170 kPa absolute (300 psig). If the
outdoors, away from air intakes. initial air pressure is greater than 1 atm, combus-
tible mixtures may form as the tank is filled.
2. Make certain the area is well ventilated, using
auxiliary ventilation, if necessary, to move Based on the above information, the following oper-
vapors. ating practices are recommended.
3. Make sure the area is clear of vapors prior to Do Not Mix With Air For Leak Testing
beginning work. Equipment should never be leak tested with
4. Install air monitoring equipment to detect leaks. a pressurized mixture of HFC-134a and air.
(Monitors are discussed in the next section, Pressurized mixtures of dry nitrogen and
Monitors and Leak Detection.) HFC-134a can be used for leak testing.
Bulk Delivery and Storage
Combustibility of HFC-134a
HFC-134a is not flammable in air at temperatures Tanks should normally be evacuated at the start
up to 100C (212F) at atmospheric pressure. How- of filling, and should never be filled while under
ever, mixtures of HFC-134a with high concentra- positive air pressure.
tions of air at elevated pressure and/or temperature Tank pressure should never be allowed to
can become combustible in the presence of an igni- exceed the tank manufacturers maximum
tion source. HFC-134a can also become combus- allowable working pressure when filling with
tible in an oxygen enriched environment (oxygen HFC-134a. Relief devices on either the tanks or
concentrations greater than that in air). Whether a the HFC-134a supply system should be present
mixture containing HFC-134a and air, or HFC-134a and in good operating condition.
in an oxygen enriched atmosphere become combus- Tank pressures should be monitored routinely.
tible depends on the inter-relationship of 1) the tem-
perature 2) the pressure, and 3) the proportion of Air lines should never be connected to storage
oxygen in the mixture. tanks.
19
Filling and Charging Operations as the specificity of the monitor increases, so
Before evacuating cylinders or refrigeration does the complexity and cost. Another method
equipment, any remaining refrigerant should be used to find leaks is to add fluorescent dyes to
removed by a recovery system. the system.
Vacuum pump discharge lines should be free A detailed discussion of leak detection, along with a
of restrictions that could increase discharge list of manufacturers of leak detection equipment, is
pressures and result in the formation of com- given in Bulletin ARTD-27.
bustible mixtures.
Nonselective Detectors
Cylinders or refrigeration equipment should be Nonselective detectors are those that will detect
evacuated at the start of filling, and should any type of emission or vapor present, regardless
never be filled while under positive air pressure. of its chemical composition. These detectors are
Filled cylinders should periodically be analyzed typically quite simple to use, very rugged, inexpen-
for air (nonabsorbable gas or NAG). sive, and almost always portable. However, their
Refrigerant Recovery Systems inability to be calibrated, long-term drift, lack of
selectivity, and lack of sensitivity limit their use
Efficient recovery of refrigerant from equipment for area monitoring.
or containers requires evacuation at the end of
the recovery cycle. Suction lines to a recovery Some nonselective detectors designed for use with
compressor should be periodically checked for CFC-12 may have a much lower sensitivity when
leaks to prevent compressing air into the recovery used with HFC-134a. However, newly designed
cylinder during evacuation. In addition, the detectors with good HFC-134a sensitivity are now
recovery cylinder pressure should be monitored, available. Be sure to consult with the manufacturer
and evacuation stopped in the event of a rapid before selecting or using a nonselective detector
pressure rise indicating the presence of air. The with HFC-134a.
recovery cylinder contents should then be ana- Halogen-Selective Detectors
lyzed for NAG, and the recovery system leak Halogen-selective detectors use a specialized sen-
checked if air is present. Do not continue to sor that allows the monitor to detect compounds
evacuate a refrigeration system that has a containing fluorine, chlorine, bromine, and iodine
major leak. without interference from other species. The major
Combustibility with Chlorine advantage of such a detector is a reduction in
Experimental data have also been reported which the number of nuisance alarmsfalse alarms
indicate combustibility of HFC-134a in the presence caused by the presence of some compound in the
of chlorine. area other than the target compound.
These detectors are typically easy to use, feature
Monitors and Leak Detection higher sensitivity than the nonselective detectors
Service personnel have used leak detection equip- (detection limits are typically <5 ppm when used as
ment for years when servicing equipment. Leak an area monitor and <1.4 gm/yr [<0.05 oz/yr] when
detectors exist not only for pinpointing specific used as a leak pinpointer), and are very durable. In
leaks, but also for monitoring an entire room on a addition, due to the partial specificity of the detector,
continual basis. There are several reasons for leak these instruments can be calibrated easily.
pinpointing or area monitoring, including: conserva- Compound-Specific Detectors
tion of HFCs, protection of valuable equipment, The most complex detectors, which are also the
reduction of fugitive emissions and protection of most expensive, are compound-specific detectors.
employees. ASHRAE Standard 15-94 requires These units are typically capable of detecting the
area monitors in refrigeration machinery rooms as presence of a single compound without interference
defined in the standard. from other compounds.
Leak detectors can be placed into two broad cat- Fluorescent Dyes
egories: leak pinpointers and area monitors. Before Fluorescent dyes have been used in refrigeration
purchasing a monitor or pinpointer, several instru- systems for several years. These dyes, invisible
mental criteria should be considered, including under ordinary lighting, but visible under ultraviolet
sensitivity, detection limits, and selectivity. (UV) light, are used to pinpoint leaks in systems.
The dyes are typically placed into the refrigeration
Types of Detectors lubricant when the system is serviced. Leaks are
Using selectivity as a criterion, leak detectors can detected by using a UV light to search for dye that
be placed into one of three categories: nonselective, has escaped from the system.
halogen-selective, or compound-specific. In general,
20
Recent innovations in dye technology have allowed same outlet fittings as cylinders of CFC-12. How-
fluorescent dyes to be used with HFC-134a. How- ever, when used for Suva 134a (Auto) for the
ever, before adding dyes to a system, the compat- automotive industry, these cylinders have a CGA-
ibility of the specific dye with the lubricant and 167 valve outlet. This fitting was specified by the
refrigerant should be tested. Society of Automotive Engineers (SAE) to avoid
mixing CFC-12 and HFC-134a when servicing
Storage and Handling
mobile air-conditioning systems. Additional unique
fittings used with HFC-134a in automotive service
Shipping Containers in the U.S. applications are discussed in Bulletin ART-27.
HFC-134a is a liquefied compressed gas. According
The 123-lb cylinders are equipped with a nonrefill-
to the U.S. Department of Transportation (DOT), a
able liquid vapor CGA-660 valve. With this two-
nonflammable compressed gas is defined as a non-
way valve, HFC-134a can be removed from the
flammable material having an absolute pressure
cylinder as either a vapor or as a liquid, without
greater than 40 psi at 21C (70F) and/or an abso-
inverting the cylinder. The vapor handwheel is
lute pressure greater than 104 psi at 54C (130F).
located on the top. The liquid wheel is on the side
The appropriate DOT designations are as follows: of the valve and attached to a dip tube extending to
Proper shipping name: Liquefied Gas, N.O.S. the bottom of the cylinder. Each is clearly identified
(Tetrafluoroethane) as vapor or liquid.
Hazard class: 2.2 The 4,400-gal cylinder is known as an ISO tank.
The dimensions referenced in Table 20 represent
UN No.: 3159
the frame in which the container is shipped. The
A list of the different types of containers that can tank itself has the same length of 20 ft and an out-
be used to ship HFC-134a in the United States, side diameter of approximately 86 in. ISO tanks are
along with their water capacities, dimensions, DOT used for export shipments of HFC-134a from the
specifications, and the net weights of HFC-134a, United States.
are provided in Table 20. All pressure relief de-
The general construction of a 1-ton returnable con-
vices used on the containers must be in compliance
tainer is shown in Figure 9. Notice that one end of
with the corresponding Compressed Gas Associa-
the container is fitted with two valves. When the
tion (CGA) Standards for compressed gas cylinders,
container is turned so that the valves are lined up
cargo, and portable tanks.
vertically, the top valve will discharge vapor and the
The 30-lb and 123-lb cylinders designed for refriger- bottom valve will discharge liquid. The valves are
ant applications are a light blue color with labels that protected by a dome cover.
bear the name of the product in light blue. The color
Ton containers are equipped with two fusible plugs
designation is Light Blue (Sky), PMS 2975.
in each end. The fusible metal in the plugs is
The 30-lb cylinder, known as a Dispos-A-Can designed to start melting at 69C (157F) and
(DAC), fits into a box that measures 10 in x 10 in completely melt at 74C (165F). Containers should
x 17 in. Dispos-A-Can is DuPonts registered never be heated to temperatures higher than 52C
trade name for this type of single-use container. (125F). One spring-loaded pressure relief valve
When used to ship Suva 134a for the stationary is also located in each end of the ton container.
refrigeration market, these 30-lb cylinders have the
Table 20
Specifications of Shipping Containers for HFC-134a
Water DOT Net Weight (lb)
Capacity Dimensions Specification HFC-134a
30-lb Dispos-A-Can 10 in x 10 in x 17 in (box) 39 30
123 lb 55 in H x 10 in OD 4BA300 125
1,682 lb 82 in L x 30 in OD 110A500W 1,750
5,000 gal Tank Truck MC-330 or -331 40,000
4,400 gal ISO 8 ft x 8.5 ft x 20 ft (frame) 51 30,865
170,000 lb Tank Rail Car 114A340W
21
Figure 9. One-Ton Returnable Container
A typical bulk storage system is shown in Figure 10. The above is a simplified outline of what is actually
a lengthy procedure. Your DuPont Marketing Rep-
Your DuPont Marketing Representative can resentative can assist in obtaining the equipment,
arrange for guidance on site selection, purchase, instrumentation, and technical assistance to safely
installation, start-up, and maintenance. and effectively make the conversion.
22
Figure 10. Typical Bulk Storage System
Internal Safety
Relief Valves
Pressure Manway
Gauge
Tank
Liquid Level
Gauge
1" Pipe
FEED System Flow Indicator
Pump Motor
In a fluorocarbon storage system, elastomers are Never refill returnable cylinders without DuPont
most commonly found in: consent. DOT regulations forbid transportation
Packing and seats of manual valves of returnable cylinders refilled without DuPonts
authorization.
Pressure-relief device seats
Flange and manway gaskets Never use a lifting magnet or sling (rope or chain)
when handling containers. A crane may be used
Mechanical pump seals when a safe cradle or platform is used to hold the
Wet-end pump gaskets and O-rings container.
Filter O-rings Never use containers as rollers, supports, or for
Sight-flow indicator gaskets any purpose other than to carry HFC-134a.
Back-pressure regulator diaphragms and O-rings Protect containers from any object that will result
in a cut or other abrasion in the surface of the
Handling Precautions for HFC-134a metal.
Shipping Containers
The following rules for handling HFC-134a contain- Never tamper with the safety devices in the
ers are strongly recommended: valves or containers.
Use personal protective equipment, such as side Never attempt to repair or alter containers or
shield glasses, gloves, and safety shoes when valves.
handling HFC-134a containers. Never force connections that do not fit. Make
Avoid skin contact with liquid HFC-134a sure the threads on the regulators or other
because it may cause frostbite. auxiliary equipment are the same as those on
the container valve outlets.
Never heat a container to a temperature higher
than 52C (125F). Keep valves tightly closed and valve caps and
hoods in place when the containers are not in use.
Never apply direct flame or live steam to a
container or valve. Store containers under a roof to protect them
from weather extremes.
Never refill disposable cylinders with anything.
The shipment of refilled disposable cylinders is Use a vapor recovery system to collect
prohibited by DOT regulations. HFC-134a vapors from lines after unloading.
23
Recovery, Reclamation, Recycle, Reclamation offers advantages over on-site refrig-
and Disposal erant recycling procedures because these systems
Responsible use of HFC-134a requires that the cannot guarantee complete removal of contami-
product be recovered for reuse or disposal when- nants. Putting refrigerants that do not meet new
ever possible. DuPont purchases used refrigerants product specifications back into expensive equip-
for reclamation through its distributor networks ment may cause damage.
in the United States, Canada, and Europe. In the
United States, used HFC-134a is accepted as part Recycle
of this program. Recovery and reuse of HFC-134a Refrigerant recycle refers to the reduction of used
makes sense from an environmental and economic refrigerant contaminants using devices that reduce
standpoint. In addition, the U.S. Clean Air Act oil, water, acidity, and particulates. Recycle is usu-
prohibits known venting of CFC, HCFC and HFC ally a field or shop procedure with no analytical
refrigerants during the maintenance, servicing, or testing of refrigerant. HFC-134a may be recycled
disposal of refrigeration equipment. using one of the devices now on the market. In the
United States, the EPA sets standards for these
Recovery devices. Recycle is becoming the accepted practice
Recovery refers to the removal of HFC-134a from in the United States mobile air-conditioning service
equipment and collection in an appropriate external industry. Consult with the manufacturer before
container. As defined by the Air Conditioning and specifying a recycle device for HFC-134a.
Refrigeration Institute (ARI), a U.S. organization,
recovery does not involve processing or analytical Disposal
testing. HFC-134a may be recovered from refrig- Disposal refers to the destruction of used HFC-
eration equipment using permanent on-site equip- 134a. Disposal may be necessary when HFC-134a
ment or one of the portable recovery devices now has become badly contaminated with other products
on the market. The portable devices contain a small and no longer meets the acceptance specifications
compressor and an air-cooled condenser, and may of DuPont or other reclaimers. Although DuPont
be used for vapor or liquid recovery. At the end of does not presently accept severely contaminated
the recovery cycle, the system is evacuated to re- refrigerants for disposal, licensed waste disposal
move vapors. In the United States, the Environmen- firms are available. Be sure to check the quali-
tal Protection Agency (EPA) sets standards for fications of any firm before sending them used
recovery equipment. Before purchasing a specific HFC-134a.
recovery unit, check with the manufacturer to be
sure that it contains elastomeric seals and a com-
pressor oil compatible with HFC-134a.
Reclamation
Reclamation refers to the reprocessing of used
HFC-134a to new product specifications. Quality
of reclaimed product is verified by chemical analy-
sis. In the United States, HFC-134a is included in
DuPonts refrigerant reclamation program. Contact
DuPont or one of its authorized distributors for fur-
ther information.
24
For Further Information:
DuPont Fluorochemicals
Wilmington, DE 19880-0711
(800) 235-SUVA
www.suva.dupont.com
The information contained herein is based on technical data and tests which we believe to be reliable and is intended for use by persons having
technical skill, at their own discretion and risk. Because conditions of use are outside of DuPont control, we can assume no liability for results
obtained or damages incurred through the application of the data presented.