Professional Documents
Culture Documents
Insulation Coordination Studies PDF
Insulation Coordination Studies PDF
TheSelectionofInsulationStrength
March25,2014
AdamSparacino
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
DefinitionofInsulationCoordination1
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
3
POWERSYSTEMENGINEERINGSERVICES
FourBasicConsiderations
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
4
POWERSYSTEMENGINEERINGSERVICES
DefinitionofOvervoltages
Overvoltage
Abnormal voltage between two points of a system that is greater than
the highest value appearing between the same two points under
normal service conditions.2
Overvoltages are the primary metric for measuring and
quantifying power system transients and thus insulation
stress.
(2) IEEE Std C62.221991 IEEE Guide for the Application of MetalOxide Surge Arresters for AlternatingCurrent
Systems, 1991.
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
5
POWERSYSTEMENGINEERINGSERVICES
VocabularyofVoltage
PeaklinegroundVoltage
RMSVoltagelineground=(Vpeak/2)
PeakVoltagelineground=VLL_rms2/3
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
6
POWERSYSTEMENGINEERINGSERVICES
IllustrationofOvervoltages
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
7
POWERSYSTEMENGINEERINGSERVICES
FourBasicConsiderations
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
8
POWERSYSTEMENGINEERINGSERVICES
ElectricalInsulation
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
9
POWERSYSTEMENGINEERINGSERVICES
InsulationStrength
TypicalVoltTimeCurveforInsulationWithstand
StrengthforLiquidFilledTransformers
Source: IEEE Std 62.22-1997, IEEE Guide for the Application of Metal-Oxide Surge Arresters for AC Systems
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
10
POWERSYSTEMENGINEERINGSERVICES
InsulationStrength
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
11
POWERSYSTEMENGINEERINGSERVICES
FrequencyofDifferentEvents
seconds milliseconds
10-20 minutes microseconds
Power
Frequency
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
12
POWERSYSTEMENGINEERINGSERVICES
FourBasicConsiderations
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
13
POWERSYSTEMENGINEERINGSERVICES
PotentialOvervoltageMitigation
1. Surge Arresters
Need to be sized and located properly to clip overvoltages.
2. PreInsertion Resistors/Inductors
Need to be sized according to equipment being switched (only help
during breaker operation) to prevent excessive overvoltages from
being initiated.
3. SynchronousClose/Open Control
Need to use independent pole operated (IPO) breakers and program
controller based on equipment being switched (only help during
breaker operation) to prevent excessive overvoltages from being
initiated.
4. Surge Capacitors
Need to be sized and located to slow the front of incoming surges
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
14
POWERSYSTEMENGINEERINGSERVICES
FourBasicConsiderations
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
15
POWERSYSTEMENGINEERINGSERVICES
InsulationCoordinationProcess
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
16
POWERSYSTEMENGINEERINGSERVICES
InsulationCoordinationStudies
1. Very Fast Transients (VFT) Analysis (nanoseconds time frame)
GIS disconnected switching.
Quantify the overvoltages throughout the substation.
Primary intent of determining location and number of surge arresters
within the substation.
2. Lightning Surge Analysis (microseconds time frame)
Quantify the overvoltages throughout the substation.
Primary intent of determining location and number of surge arresters
within the substation.
3. Switching Overvoltage Analysis (milliseconds time frame)
Quantify the overvoltages and surge arrester energy duties associated
with switching events and fault/clear operations.
Primary intent is to verify that transient overvoltage mitigating devices
(e.g., surge arresters, preinsertion resistors, synchronous close control)
are adequate to protect electrical equipment.
Capacitor, Shunt Reactor, Transformer, and Line Switching Studies.
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
17
POWERSYSTEMENGINEERINGSERVICES
InsulationCoordinationStudies(cont.)
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
18
POWERSYSTEMENGINEERINGSERVICES
EXAMPLEAPPLICATION
STUDYFORINSULATIONCOORDINATION
LIGHTNINGSURGEANALYSIS
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
19
POWERSYSTEMENGINEERINGSERVICES
Refer to Figure 2 for Refer to Figure 2 for
details of line details of line
terminations. terminations.
500 kV LINE BML00 BLU00
500 kV LINE
BML01
All lengths shown in meters. BLU01
la = 30.70
la = 21.19
lb = 25.66
lb = 20.74
lc = 21.76
lc = 23.64
la = 23.47 la = 23.47
lb = 22.56 lb = 22.56
lc = 21.64 lc = 20.64
WEST500kVBUS
GWB06
la = 9.518
lb = 8.603 la,b,c = 8.323
la,b,c = 8.323 la,b,c = 19.59 la,b,c = 5.634
lc = 7.689
CB CB CB CB CB CB CB CB CB
G752E G952E G762E G962E G772E G872E G972E
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
20
POWERSYSTEMENGINEERINGSERVICES
ExampleforLine/XFMRTermination
500 kV Line
Line Trap1
To Transformer
Gas-to- Surge
Air Arrester
Bushing
CCVT
To GIS
Gas-to-Air Bay #6
Bushing
550 kV GIS
Notes
To GIS
Bay (1) Line traps only on phase A and C for 500 kV lines. In
EMTP model, phase B has a 2.53 m section of
550 kV GIS conductor modeled in place of line trap.
350 MCM
Ground
Lead (38)
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
21
POWERSYSTEMENGINEERINGSERVICES
ApproachforEvaluationtheInsulationCoordinationof
the550kVGasInsulatedSubstation
Step 1: A severe voltage surge was injected into the substation for various
operating configurations to screen for maximum potential overvoltages.
ScreeningAnalysis
Step 2: The resulting overvoltages were compared to the Basic Lightning Impulse
Insulation Level (BIL) of the equipment and the protective margin1 for the
equipment was calculated.
Step 3: If overvoltages resulted in less than a 20% protective margin in the initial
DetailedAnalysis
screening analysis for cases with the full system in or N1 contingencies, a more
detailed analysis was performed to identify the protective margins resulting from a
reasonable upper bounds lightning surge based on the configuration of the
substation and connected transmission lines.
For the detailed analysis, specific details of the transmission lines such as conductor
characteristics, shielding design, ground resistivity, keraunic level, etc. are considered to
determine a reasonable upper bounds to place on the lightning surge impinging on the
substation.
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
22
POWERSYSTEMENGINEERINGSERVICES
LightningSurgeIncomingFrom500kVLine
PhasetoGroundVoltageofIncomingLightningSurge
MLFULL_halfSRC>MLSRCA(Type 1)
4000
3000
Voltage (kV)
2000
1000
0
0 5 10 15 20
Time (us)
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
23
POWERSYSTEMENGINEERINGSERVICES
LightningSurgeIncomingFrom500kVLine
HighestPhasetoGroundVoltageObservedinGIS
MLFULLB>G752WB(Type 1)
2000
1109 kV.
1000
500
0
0 5 10 15 20
Time (us)
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
24
POWERSYSTEMENGINEERINGSERVICES
EXAMPLEAPPLICATION
STUDYFORINSULATIONCOORDINATION
TRANSMISSIONLINESWITCHINGANALYSIS
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
25
POWERSYSTEMENGINEERINGSERVICES
TransmissionLineSwitchingAnalysis
PotentialEquipmentConcerns
ExcessiveTransientOvervoltagesand
thePossibilityofaFlashoverDuring
EnergizingorReClosing
OvervoltagesExceedingGuidelines
UsedtoDevelopLineClearances
Transmission line is energized
(normal energizing or re-closing).
Applicable Criteria
BasicSwitchingImpulseLevel(BSL)
ProbabilityofFlashovers
PotentialMitigationTechniques
SynchronousCloseControl
PreInsertionResistors/Inductors
SurgeArresters
ShuntReactors
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
26
POWERSYSTEMENGINEERINGSERVICES
StatisticalSwitchingMethodology
Source-Side Voltage
cycle window
Case simulated with
200-400 energizations
3 = cycle 2 = 2.08 ms
Tclose
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
27
POWERSYSTEMENGINEERINGSERVICES
ElectroGeometricLineModel
Example345kVTransmissionLine
ShieldWire:
Alumoweld7#8
14.5 14.5
Outsidediameter=0.385
RDC=2.40Ohm/mi
78
(63atmidpoint)
B C A
27 27 PhaseConductor:
ACSRLapwing
2/cBundle18spacing
Outsidediameter=1.504
RDC=0.059Ohm/mi
54 Thick/Diam=0.375
(24atmidpoint)
Center
Line
LineLength(total)=85mi
Untransposed
Groundresistivity=37Ohmm
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
28
POWERSYSTEMENGINEERINGSERVICES
StatisticalSwitchingOvervoltageStrengthCharacteristics
andSOVdensitiesoftheline
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
29
POWERSYSTEMENGINEERINGSERVICES
StatisticalDistr.OfOvervoltagesAlong500kVLinewith
NOSurgeArresters
StatisticalDistributionofOvervoltagesAlongLine
110%
Statistical
distributionbasedon
100%
thecasepeak
ProbabilitytoExceedOvervoltage(%)
Estimatedinsulation methodfromIEEE
90% Std1313.21999.
withstandforthe
80% transmissionline:CFO=3.53
p.u.,f/CFO =5%.
70%
SendingEnd
60% 1/4Point
98%oftheovervoltagesalong
50% thelineare2.62p.u.(1070 1/2Point
kV).
3/4Point
40%
Highestovervoltageatthe
RemoteEnd
remoteendoftheline=2.75
30% p.u.(1123kV). ExampleCFO
20% E2isthevalueinwhichthe
overvoltagesexceed2%ofthe
10% switchingoperations.
0%
1.00 1.50 2.00 2.50 3.00 3.50 4.00
PeakOvervoltage(PerUnitona500kVBase)
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
30
POWERSYSTEMENGINEERINGSERVICES
StatisticalDistr.OfOvervoltagesAlong500kVLinewith
LineEndSurgeArresters
StatisticalDistributionofOvervoltagesAlongLine
110%
Statistical
distributionbasedon
100%
thecasepeak
ProbabilitytoExceedOvervoltage(%)
Estimatedinsulation methodfromIEEE
90% Std1313.21999.
withstandforthe
80% transmissionline:CFO=3.53
p.u.,f/CFO =5%.
70%
SendingEnd
60% 1/4Point
98%oftheovervoltagesalong
50% thelineare2.16p.u.(882 1/2Point
kV). 3/4Point
40%
RemoteEnd
30%
ExampleCFO
20% Highestovervoltagealongthe E2isthevalueinwhichthe
line=2.21p.u.(902kV). overvoltagesexceed2%ofthe
10% switchingoperations.
0%
1.00 1.50 2.00 2.50 3.00 3.50 4.00
PeakOvervoltage(PerUnitona500kVBase)
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
31
POWERSYSTEMENGINEERINGSERVICES
EXAMPLEAPPLICATION
STUDYFORINSULATIONCOORDINATION
SHUNTCAPACITORSWITCHINGANALYSIS
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
32
POWERSYSTEMENGINEERINGSERVICES
ShuntCapacitorSwitchingAnalysis
PotentialEquipmentConcerns
ContactWearfromExcessiveInrush
CurrentDuty
ExcessiveTransientOvervoltages
InducedVoltagesandCurrentsin
Capacitor bank is energized and ControlCircuits
transient inrush currents flow
through capacitor bank breaker StepandTouchPotentialsDuring
and voltage surges propagate Switching
into the system.
ApplicableCriteria
ANSI/IEEEInrushCurrentLimits
BasicSwitchingImpulseLevel(BSL)
BreakerCapabilityBeyondStandards
IEEEStd 80forgrounding
PotentialMitigationTechniques
CurrentLimitingReactors
SynchronousCloseControl
PreInsertionResistors/Inductors
SurgeArresters
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
33
POWERSYSTEMENGINEERINGSERVICES
CapacitorBankReStrike
DuringDeEnergization
CurrentThroughSwitchingDevice VoltageonEachSideofSwitchingDevice
Voltageonsystem
sideofswitching
Firstrestrike
device
occursand
currentisre
established
Currentis
interrupted
Voltageoncapacitor
banksideof
switchingdevice(DC
trappedcharge)
Peakovervoltage
from2nd restrike
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
34
POWERSYSTEMENGINEERINGSERVICES
VoltageMagnification
1 1 2 2
Furthermore,whenC1>>C2,andL1<<L2 theconditioncanbe
exaggerated
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
35
POWERSYSTEMENGINEERINGSERVICES
VoltageMagnification(Cont.)
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
36
POWERSYSTEMENGINEERINGSERVICES
EXAMPLEAPPLICATION
STUDYFORINSULATIONCOORDINATION
SHUNTREACTORSWITCHINGANALYSIS
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
37
POWERSYSTEMENGINEERINGSERVICES
ShuntReactorSwitchingAnalysis
PotentialEquipmentConcerns
ExcessiveInrushCurrentsfrom
Energizing
TransientandTemporaryOvervoltages
fromResonanceConditions
Shunt reactor is energized and
inrush current flows through the GenerationofHarmonics
system and circuit breaker.
ResonancefromParallelLines
ApplicableCriteria
EquipmentInsulationLevels
VoltageSag/DipCriteria
HarmonicDistortion
PotentialMitigationTechniques
SynchronousCloseControl
SurgeArresters
AppropriateRelaySettings
OperationalLimitations
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
38
POWERSYSTEMENGINEERINGSERVICES
ResonanceOvervoltages
345kVSubstation 345kVSubstation
VoltageMeasuredonEnergizedLine
Lineinservice
(breakersclosed
atbothends)
Lineoutofservice
(breakersopenat
bothends)
345kVSubstation 345kVSubstation
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
39
POWERSYSTEMENGINEERINGSERVICES
ResonanceOvervoltages
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
40
POWERSYSTEMENGINEERINGSERVICES
Summary
Insulation Coordination is the selection of insulation strength.
Determine maximum insulation stress.
Determine the minimum insulation strength with margin taking into
account stress reducers (surge arresters, preinsertion resistors,
synchronous close control, etc.) that can withstand the maximum
stress.
Studies help in quantifying the maximum anticipated stress
and determining the rating/location of overvoltage mitigating
devices.
A key component of insulation coordination is pairing the
correct strength to the correct stress.
As a rule of thumb, the shorter the time the overvoltage is applied to
the insulation the greater the magnitude of overvoltage the insulation
can withstand before failure.
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
41
POWERSYSTEMENGINEERINGSERVICES
THANKYOUFORYOUATTENTION
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
42
POWERSYSTEMENGINEERINGSERVICES