You are on page 1of 44

Line distance protection IED Buyer's Guide

REL 670 Pre-configured


1MRK 506 264-BEN
Revision: G
Issued: February 2007
Data subject to change without notice

Page 1

Features Four configuration alternatives for single- or - Co-operation with synchrocheck function
multi-breaker arrangements available ready to
- Can be switched On-Off from remote through
connect
communication or with local switches through
For overhead lines and cables binary inputs
For single and/or three phase tripping Built-in data communication modules for station
bus IEC 61850-8-1
High impedance differential protection for
tee-feeders Data communication modules for station bus
IEC 60870-5-103, LON and SPA
Full scheme phase-to-phase and phase-to-earth
distance protection with up to five zones: Remote end communication function with capa-
bility for 192 binary signals
- All types of scheme communication
Integrated disturbance and event recorder for up
- Load encroachment feature to 40 analog and 96 binary signals
Four step directional and/or non-directional over-
Time synchronization over IEC 61850-8-1, LON,
current earth fault protection:
SPA, binary input or with optional GPS module
- Each step can be inverse or definite time
Analog measurements accuracy up to below
delayed
0.5% for power and 0.25% for current and volt-
- Each step can be blocked on second har- age and with site calibration to optimize total
monic component accuracy
Synchrocheck and dead-line check function for Versatile local human-machine interface
single- or multi-breaker arrangements:
Extensive self-supervision with internal event
- Selectable energizing direction recorder
- Two functions with built-in voltage selection Six independent groups of complete setting
- For automatic or manual synchrocheck and parameters with password protection
with different settings Powerful software PC tool for setting, distur-
Auto-reclosing function for single- two-, and/or bance evaluation and configuration
three-phase reclosing:
Remote end data communication modules for
- Two functions with priority circuits for C37.94 and G.703
multi-breaker arrangements

Application The REL 670 IED is used for the protection, con- The full scheme distance protection provides pro-
trol and monitoring of overhead lines and cables in tection of power lines with high sensitivity and
solidly earthed networks. The IED can be used up low requirement on remote end communication.
to the highest voltage levels. It is suitable for the The five zones have fully independent measuring
protection of heavily loaded lines and multi-termi- and setting which gives high flexibility for all
nal lines where the requirement for tripping types of lines.
is one, two-, and/or three pole. The IED is also
suitable as back-up protection on power transform- The auto-reclose for single-, two-, and/or three
ers, reactors etc. phase reclose includes priority circuits for
multi-breaker arrangements. It co-operates with
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 2

the synchrocheck function with high-speed or Four packages has been defined for following
delayed reclosing. applications:

High set instantaneous phase and earth overcur- Single-breaker (double or single bus) with
rent, four step directional or un-directional delayed three phase tripping (A31)
phase and earth overcurrent, thermal overload and
Single-breaker (double or single bus) with sin-
two step under and overvoltage functions are
examples of the available functions allowing the gle phase tripping (A32)
user to fulfill any application requirement. Multi-breaker (one-and a half or ring) with
three phase tripping (B31)
The distance and earth fault protection can com-
municate with remote end in any communication Multi-breaker (one-and a half or ring) with sin-
scheme. With the included remote communication, gle phase tripping (B32)
following the IEEE C37.94 standard, 6 x 32 chan-
nels for intertrip and binary signals is available in The packages are configured and set with basic
the communication between the IEDs. functions active to allow direct use. Optional func-
tions are not configured but a maximum configura-
The IED can also be provided with a full control tion with all optional functions are available as
and interlocking functionality including co-opera- template in the graphical configuration tool. Inter-
tion with the synchrocheck function to allow inte- face to analogue and binary IO are configurable
gration of the main or back-up control. from the Signal matrix tool without need of con-
figuration changes. Analogue and tripping IO has
The advanced logic capability, where the user been pre-defined for basic use on the, as standard
logic is prepared with a graphical tool, allows spe- supplied one binary input module and one binary
cial applications such as automatic opening of dis- output module. Add IO as required for your appli-
connectors in multi-breaker arrangements, closing cation at ordering. Other signals need to be applied
of breaker rings, load transfer logics etc. The as required for each application.
graphical configuration tool ensures simple and
fast testing and commissioning. For details on included basic functions refer to sec-
tion "Available functions".
Serial data communication is via optical connec-
tions to ensure immunity against disturbances. The applications are shown in figures 1 and 2 for
single resp. multi-breaker arrangement.
The wide application flexibility makes this product
an excellent choice for both new installations and
the refurbishment of existing installations.
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 3

BUS B

BUS A

TRIP BUSBAR

79 25
CLOSE
O->I SC/VC
94/86
TRIP
I->O

50BF
3I>

21
Z<
5
5

51/67
3I>
4
4
51N/67N
IN>
4
4
59
3U>
2
2
27
3U< en05000276.vsd
2
2

Figure 1: The single breaker packages for single- and three phase tripping typical arrangement for one
protection sub-system is shown here.
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 4

BUS A

TRIP BUSBAR & CB2

79 25
CLOSE
O->I SC/VC

94/86
CB1
TRIP
I->O 79 25

O->I SC/VC

50BF
21 3I>
50BF TRIP
Z<
5 3I> CB1/X
94/86
5
I->O

CLOSE
51/67

TRIP
59
3U> 3I>
2 4
2 4
27 51N/67N CB2
3U< IN>
2 4
2 4

en05000317.vsd

Figure 2: The multi breaker packages for single- and three phase tripping typical arrangement for one pro-
tection sub-system is shown here. Auto-reclose, Synchrocheck and Breaker failure functions
are included for each of the two breakers.
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 5

Available
functions
ANSI Function description Single breaker, Multi breaker, Single breaker, Multi breaker,
3-phase tripping 3-phase tripping 1-phase tripping 1-phase tripping
(A31) (B31) (A32) (B32)
Basic Option Basic Option Basic Option Basic Option
(Qty/ (Qty/ (Qty/ (Qty/
Option Option Option Option
design) design) design) design)

Differential protection
87 High impedance differential protection (PDIF) - 3/A02 - 3/A02 - 3/A02 - 3/A02

Distance protection
21 Distance protection zones (PDIS) 5 - 5 - 5 - 5 -
21 Phase selection with load enchroachment (PDIS) 1 - 1 - 1 - 1 -
Directional impedance (RDIR) 1 - 1 - 1 - 1 -
78 Power swing detection (RPSB) 1 - 1 - 1 - 1 -
Automatic switch onto fault logic (PSOF) 1 - 1 - 1 - 1 -

Current protection
50 Instantaneous phase overcurrent protection (PIOC) 1 - 1 - 1 - 1 -
51/67 Four step phase overcurrent protection (POCM) 1 - 1 - 1 - 1 -
50N Instantaneous residual overcurrent protection (PIOC) 1 - 1 - 1 - 1 -
51N/67N Four step residual overcurrent protection (PEFM) 1 - 1 - 1 - 1 -
26 Thermal overload protection, one time constant (PTTR) 1 - 1 - 1 - 1 -
50BF Breaker failure protection (RBRF) 1 - 2 - 1 - 2 -
50STB Stub protection (PTOC) - 1 - - 1 -
52PD Pole-discordance protection (RPLD) - - - - 1 - 2 -

Voltage protection
27 Two step undervoltage protection (PUVM) 1 - 1 - 1 - 1 -
59 Two step time delayed overvoltage protection (POVM) 1 - 1 - 1 - 1 -
59N Two step residual overvoltage protection (POVM) 1 - 1 - 1 - 1 -

Frequency protection
81 Underfrequency protection (PTUF) - 2/E02 - 2/E02 - 2/E02 - 2/E02
81 Overfrequency protection (PTOF) - 2/E02 - 2/E02 - 2/E02 - 2/E02
81 Rate-of-change frequency protection (PFRC) - 2/E02 - 2/E02 - 2/E02 - 2/E02

Multipurpose protection
General current and voltage protection (GAPC) - 4/F01 - 4/F01 - 4/F01 - 4/F01

Secondary system supervision


Current circuit supervision (RDIF) 1 - 2 - 1 - 2 -
Fuse failure supervision (RFUF) 3 - 3 - 3 - 3 -

Control
25 Synchrocheck and energizing check (RSYN) 1 - 2 - 1 - 2 -
79 Autorecloser (RREC) 1 - 2 - 1 - 2 -
Apparatus control for single bay, - 1/H07 - - - 1/H07 - -
max 8 apparatuses incl. interlocking (APC8)
Apparatus control for single bay, - - - 1/H08 - - - 1/H08
max 15 apparatuses (2CBs) incl. interlocking (APC15)

Scheme communication
85 Scheme communication logic for distance protection (PSCH) 1 - 1 - 1 - 1 -
85 Current reversal and weak-end infeed logic for 1 - 1 - 1 - 1 -
distance protection (PSCH)
Local acceleration logic (PLAL) 1 - 1 - 1 - 1 -
85 Scheme communication logic for 1 - 1 - 1 - 1 -
residual overcurrent protection (PSCH)
85 Current reversal and weak-end infeed logic for 1 - 1 - 1 - 1 -
residual overcurrent protection (PSCH)
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 6

ANSI Function description Single breaker, Multi breaker, Single breaker, Multi breaker,
3-phase tripping 3-phase tripping 1-phase tripping 1-phase tripping
(A31) (B31) (A32) (B32)
Basic Option Basic Option Basic Option Basic Option
(Qty/ (Qty/ (Qty/ (Qty/
Option Option Option Option
design) design) design) design)

Logic
94 Tripping logic (PTRC) 1 - 2 - 1 - 2 -
Trip matrix logic (GGIO) 12 - 12 - 12 - 12 -

Monitoring
Measurements (MMXU) 3/10/3 - 3/10/3 - 3/10/3 - 3/10/3 -
Event counter (GGIO) 5 - 5 - 5 - 5 -
Disturbance report (RDRE) 1 - 1 - 1 - 1 -
Fault locator (RFLO) 1 - 1 - 1 - 1 -

Metering
Pulse counter logic (GGIO) 16 - 16 - 16 - 16 -

Station communication
IEC61850-8-1 Communication 1 - 1 - 1 - 1 -
LON communication protocol 1 - 1 - 1 - 1 -
SPA communication protocol 1 - 1 - 1 - 1 -
IEC60870-5-103 communication protocol 1 - 1 - 1 - 1 -
Single command, 16 signals 3 - 3 - 3 - 3 -
Multiple command and transmit 60/10 - 60/10 - 60/10 - 60/10 -

Remote communication
Binary signal transfer 4 - 4 - 4 - 4 -

Functionality Differential protection


X
High impedance differential protection
(PDIF, 87)
Forward
The high impedance differential protection can be
operation
used when the involved CT cores have same turn
ratio and similar magnetizing characteristic. It uti-
lizes an external summation of the phases and neu-
tral current and a series resistor and a voltage
dependent resistor externally to the relay.
R

Distance protection
Reverse
operation
Distance protection zones (PDIS, 21)
The line distance protection is a five zone full
scheme protection with three fault loops for phase
to phase faults and three fault loops for phase to
en05000034.vsd
earth fault for each of the independent zones. Indi-
vidual settings for each zone resistive and reactive Figure 3: Typical distance protection zone with
reach gives flexibility for use on overhead lines load encroachment function activated
and cables of different types and lengths.

The function has a functionality for load encroach- The independent measurement of impedance for
ment which increases the possibility to detect high each fault loop together with a sensitive and reli-
resistive faults on heavily loaded lines (see able built in phase selection makes the function
figure 3). suitable in applications with single phase
auto-reclosing.

Built-in adaptive load compensation algorithm


prevents overreaching of zone1 at load exporting

end at phase-to-earth faults on heavily loaded power lines.


Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 7

The distance protection zones can operate, inde- Four step residual overcurrent
pendent of each other, in directional (forward or protection (PEFM, 51N/67N)
reverse) or non-directional mode. This makes them The four step single input overcurrent function has
suitable, together with different communication an inverse or definite time delay independent for
schemes, for the protection of power lines and each step separately.
cables in complex network configurations, such as
parallel lines, multi-terminal lines etc. All IEC and ANSI time delayed characteristics are
available together with an optional user defined
Power swing detection (RPSB, 78) characteristic.
Power swings may occur after disconnection of
The function can be set to be directional, forward,
heavy loads or trip of big generation plants.
reverse or non-directional independently for each
Power swing detection function is used to detect of the steps.
power swings and initiate block of selected dis-
A second harmonic blocking can be set individu-
tance protection zones. Occurrence of earth fault
ally for each step.
currents during a power swing can block the power
swing detection function to allow fault clearance. The function can be used as main protection for
phase to earth faults.
Automatic switch onto fault logic (PSOF)
Automatic switch onto fault logic is a function that The function can be used to provide a system
gives an instantaneous trip at closing of breaker back-up e.g. in the case of the primary protection
onto a fault. A dead line detection check is pro- being out of service due to communication or volt-
vided to activate the function when the line is age transformer circuit failure.
dead.
Directional operation can be combined together
with corresponding communication blocks into
Current protection permissive or blocking teleprotection scheme.
Current reversal and weak-end infeed functionality
Instantaneous phase overcurrent are available as well.
protection (PIOC, 50)
The instantaneous three phase overcurrent function The function can be configured to measure the
has a low transient overreach and short tripping residual current from the three phase current inputs
time to allow use as a high set short-circuit protec- or the current from a separate current input.
tion function, with the reach limited to less than
typical eighty percent of the power line at mini- Thermal overload protection, one time
mum source impedance. constant (PTTR, 26)
The increasing utilizing of the power system closer
Four step phase overcurrent to the thermal limits have generated a need of a
protection (POCM, 51_67) thermal overload function also for power lines.
The four step phase overcurrent function has an
A thermal overload will often not be detected by
inverse or definite time delay independent for each
other protection functions and the introduction of
step separately.
the thermal overload function can allow the pro-
All IEC and ANSI time delayed characteristics are tected circuit to operate closer to the thermal lim-
available together with an optional user defined its.
time characteristic.
The three phase current measuring function has an
The function can be set to be directional or I2t characteristic with settable time constant and a
non-directional independently for each of the thermal memory.
steps.
An alarm level gives early warning to allow opera-
tors to take action well before the line will be
Instantaneous residual overcurrent tripped.
protection (PIOC, 50N)
The single input overcurrent function has a low
Breaker failure protection (RBRF, 50BF)
transient overreach and short tripping times to
The circuit breaker failure function ensures fast
allow use as a high set short circuit protection
back-up tripping of surrounding breakers. The
function, with the reach limited to less than typical
breaker failure protection operation can be current
eighty percent of the power line at minimum
based, contact based or adaptive combination
source impedance. The function can be configured
between these two principles.
to measure the residual current from the three
phase current inputs or the current from a separate A current check with extremely short reset time is
current input. used as a check criteria to achieve a high security
against unnecessary operation.

The breaker failure protection can be single- or


three-phase started to allow use with single phase
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 8

tripping applications. For the three-phase version The function can be used as open line end detector,
of the breaker failure protection the current criteria normally then combined with directional reactive
can be set to operate only if two out of four e.g. over-power function or as system voltage supervi-
two phases or one phase plus the residual current sion, normally then giving alarm only or switching
starts. This gives a higher security to the back-up in reactors or switch out capacitor banks to control
trip command. the voltage.

The function can be programmed to give a single- The function has two voltage steps, each of them
or three phase re-trip of the own breaker to avoid with inverse or definite time delayed.
unnecessary tripping of surrounding breakers at an
incorrect starting due to mistakes during testing. The overvoltage function has an extremely high
reset ratio to allow setting close to system service
Stub protection (PTOC, 50STB) voltage.
When a power line is taken out of service for
maintenance and the line disconnector is opened in Two step residual overvoltage
multi-breaker arrangements the voltage transform- protection (POVM, 59N)
ers will mostly be outside on the disconnected part. Residual voltages will occur in the power system
The primary line distance protection will thus not during earth faults.
be able to operate and must be blocked.
The function can be configured to calculate the
The stub protection covers the zone between the residual voltage from the three phase voltage input
current transformers and the open disconnector. transformers or from a single phase voltage input
The three phase instantaneous overcurrent function transformer fed from an open delta or neutral point
is released from a NO (b) auxiliary contact on the voltage transformer.
line disconnector.
The function has two voltage steps, each with
inverse or definite time delayed.
Pole discordance protection (RPLD, 52PD)
Single pole operated circuit breakers can due to
electrical or mechanical failures end up with the Frequency protection
different poles in different positions (close-open).
This can cause negative and zero sequence cur- Underfrequency protection (PTUF, 81)
rents which gives thermal stress on rotating Underfrequency occurs as a result of lack of gener-
machines and can cause unwanted operation of ation in the network.
zero sequence current functions.
The function can be used for load shedding sys-
Normally the own breaker is tripped to correct the tems, remedial action schemes, gas turbine start-up
positions. If the situation consists the remote end etc.
can be intertripped to clear the unsymmetrical load
situation. The function is provided with an undervoltage
blocking. The operation may be based on single
The pole discordance function operates based on phase, phase-to-phase or positive sequence voltage
information from auxiliary contacts of the circuit measurement.
breaker for the three phases with additional criteria
from unsymmetrical phase current when required. Up to two independent under frequency function
instances are available.
Voltage protection Overfrequency protection (PTOF, 81)
Overfrequency will occur at sudden load drops or
Two step undervoltage shunt faults in the power network. In some cases
protection (PUVM, 27) close to generating part governor problems can
Undervoltages can occur in the power system dur- also cause overfrequency.
ing faults or abnormal conditions. The function
can be used to open circuit breakers to prepare for The function can be used for generation shedding,
system restoration at power outages or as remedial action schemes etc. It can also be used as
long-time delayed back-up to primary protection. a sub-nominal frequency stage initiating load
restoring.
The function has two voltage steps, each with
inverse or definite time delay. The function is provided with an undervoltage
blocking. The operation may be based on single
Two step overvoltage phase, phase-to-phase or positive sequence voltage
protection (POVM, 59) measurement.
Overvoltages will occur in the power system dur-
ing abnormal conditions such as sudden power Up to two independent over frequency function
loss, tap changer regulating failures, open line instances are available.
ends on long lines.
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 9

Rate-of-change frequency tance protection, undervoltage protection, neutral


protection (PFRC, 81) point voltage protection, energizing function (syn-
Rate of change of frequency function gives an chrocheck) etc. The fuse failure supervision func-
early indication of a main disturbance in the sys- tion prevents such unwanted operations.
tem.
There are three methods to detect fuse failures.
The function can be used for generation shedding,
load shedding, remedial action schemes etc. The method based on detection of zero sequence
voltage without any zero sequence current. This is
The function is provided with an undervoltage a useful principle in a directly earthed system and
blocking. The operation may be based on single can detect one or two phase fuse failures.
phase, phase-to-phase or positive sequence voltage
measurement. The method based on detection of negative
sequence voltage without any negative sequence
Each step can discriminate between positive or current. This is a useful principle in a non-directly
negative change of frequency. earthed system and can detect one or two phase
fuse failures.
Up to two independent rate-of-change frequency
function instances are available. The method based on detection of du/dt-di/dt
where a change of the voltage is compared to a
change in the current. Only voltage changes means
Multipurpose protection a voltage transformer fault. This principle can
detect one, two or three phase fuse failures.
General current and voltage
protection (GAPC)
The function can be utilized as a negative Control
sequence current protection detecting unsymmetri-
cal conditions such as open phase or unsymmetri- Synchrocheck and energizing check
cal faults. (RSYN, 25)
The synchrocheck function checks that the volt-
The function can also be used to improve phase ages on both sides of the circuit breaker are in syn-
selection for high resistive earth faults, outside the chronism, or with at least one side dead to ensure
distance protection reach, for the transmission line. that closing can be done safely.
Three functions are used which measures the neu-
tral current and each of the three phase voltages. The function includes a built-in voltage selection
This will give an independence from load currents scheme for double bus and one- and a half or ring
and this phase selection will be used in conjunc- busbar arrangements.
tion with the detection of the earth fault from the
directional earth fault protection function. Manual closing as well as automatic reclosing can
be checked by the function and can have different
settings, e.g. the allowed frequency difference can
Secondary system supervision be set to allow wider limits for the auto-reclose
attempt than for the manual closing.
Current circuit supervision (RDIF)
Open or short circuited current transformer cores Autorecloser (RREC, 79)
can cause unwanted operation of many protection The autoreclosing function provides high-speed
functions such as differential, earth fault current and/or delayed auto-reclosing for single or
and negative sequence current functions. multi-breaker applications.

It must be remembered that a blocking of protec- Up to five reclosing attempts can be programmed.
tion functions at an occurring open CT circuit will The first attempt can be single-, two and/or three
mean that the situation will remain and extremely phase for single phase or multi-phase faults
high voltages will stress the secondary circuit. respectively.

The current circuit supervision function compares Multiple autoreclosing functions are provided for
the residual current from a three phase set of cur- multi-breaker arrangements. A priority circuit
rent transformer cores with the neutral point cur- allows one circuit breaker to close first and the
rent on a separate input taken from another set of second will only close if the fault proved to be
cores on the current transformer. transient.

A detection of a difference indicates a fault in the Each autoreclosing function can be configured to
circuit and is used as alarm or to block protection co-operate with a synchrocheck function.
functions expected to give unwanted tripping.
Apparatus control (APC)
Fuse failure supervision (RFUF) The apparatus control is a function for control and
Failures in the secondary circuits of the voltage supervision of circuit breakers, disconnectors and
transformer can cause unwanted operation of dis- earthing switches within a bay. Permission to oper-
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 10

ate is given after evaluation of conditions from together with local under voltage criteria and no
other functions such as interlocking, synchro- reverse zone operation gives an instantaneous trip.
check, operator place selection and external or The received signal is also echoed back to acceler-
internal blockings. ate the sending end.

Interlocking Local acceleration logic (PLAL)


The interlocking function blocks the possibility to To achieve fast clearing of faults on the whole line,
operate primary switching devices, for instance when no communication channel is available, local
when a disconnector is under load, in order to pre- acceleration logic (ZCLC) can be used. This logic
vent material damage and/or accidental human enables fast fault clearing during certain condi-
injury. tions, but naturally, it can not fully replace a com-
munication channel.
Each apparatus control function has interlocking
modules included for different switchyard arrange- The logic can be controlled either by the auto
ments, where each function handles interlocking of re-closer (zone extension) or by the loss of load
one bay. The interlocking function is distributed to current (loss-of-load acceleration).
each IED and is not dependent on any central func-
tion. For the station-wide interlocking, the IEDs
communicate via the system-wide interbay bus Logic
(IEC 61850-8-1) or by using hard wired binary
inputs/outputs. The interlocking conditions depend Tripping logic (PTRC, 94)
on the circuit configuration and apparatus position A function block for protection tripping is pro-
status at any given time. vided for each circuit breaker involved in the trip-
ping of the fault. It provides the pulse prolongation
For easy and safe implementation of the interlock- to ensure a trip pulse of sufficient length, as well as
ing function, the IED is delivered with standard- all functionality necessary for correct co-operation
ized and tested software interlocking modules with autoreclosing functions.
containing logic for the interlocking conditions.
The interlocking conditions can be altered, to meet The trip function block includes functionality for
the customers specific requirements, by adding evolving faults and breaker lock-out.
configurable logic by means of the graphical con-
figuration tool. Trip matrix logic (GGIO, 94X)
Twelve trip matrix logic blocks are included in the
IED. The function blocks are used in the configu-
Scheme communication ration of the IED to route trip signals and/or other
logical output signals to the different output relays.
Scheme communication logic for
distance protection and directional The matrix and the physical outputs will be seen in
residual overcurrent protection (PSCH, 85) the PCM 600 engineering tool and this allows the
To achieve instantaneous fault clearance for all user to adapt the signals to the physical tripping
line faults, a scheme communication logic is pro- outputs according to the specific application needs.
vided. All types of communication schemes e.g.
permissive underreach, permissive overreach, Configurable logic blocks
blocking, intertrip etc. are available. The built-in A high number of logic blocks and timers are
communication module (LDCM) can be used for available for user to adapt the configuration to the
scheme communication signalling when included. specific application needs.

Logic for loss of load and/or local acceleration in Fixed signal function block
co-operation with autoreclose function is also pro- The fixed signals function block generates a num-
vided for application where no communication ber of pre-set (fixed) signals that can be used in the
channel is available. configuration of an IED, either for forcing the
unused inputs in the other function blocks to a cer-
Current reversal and weak-end infeed logic tain level/value, or for creating a certain logic.
for distance protection and directional
residual overcurrent protection (PSCH, 85)
The current reversal function is used to prevent Monitoring
unwanted operations due to current reversal when
using permissive overreach protection schemes in Measurements (MMXU)
application with parallel lines when the overreach The service value function is used to get on-line
from the two ends overlaps on the parallel line. information from the IED. These service values
makes it possible to display on-line information on
The weak-end infeed logic is used in cases where the local HMI and on the Substation automation
the apparent power behind the protection can be system about:
too low to activate the distance protection func-
tion. When activated, received carrier signal
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 11

measured voltages, currents, frequency, active, The function is characterized by great flexibility
reactive and apparent power and power factor, regarding configuration, starting conditions,
recording times and large storage capacity.
the primary and secondary phasors,
differential currents, bias currents, A disturbance is defined as an activation of an
input in the DRAx or DRBy function blocks which
positive, negative and zero sequence currents
is set to trigger the disturbance recorder. All sig-
and voltages, nals from start of pre-fault time to the end of
mA, post-fault time, will be included in the recording.
pulse counters, Every disturbance report recording is saved in the
measured values and other information of the IED in the standard Comtrade format. The same
different parameters for included functions, applies to all events, which are continuously saved
in a ring-buffer. The Local Human Machine Inter-
logical values of all binary in- and outputs and
face (LHMI) is used to get information about the
general IED information. recordings, but the disturbance report files may be
uploaded to the PCM 600 (Protection and Control
Supervision of mA input signals (MVGGIO) IED Manager) and further analysis using the dis-
The main purpose of the function is to measure turbance handling tool.
and process signals from different measuring
transducers. Many devices used in process control Event list (RDRE)
represent various parameters such as frequency, Continuous event-logging is useful for monitoring
temperature and DC battery voltage as low current of the system from an overview perspective and is
values, usually in the range 4-20 mA or 0-20 mA. a complement to specific disturbance recorder
functions.
Alarm limits can be set and used as triggers, e.g. to
generate trip or alarm signals. The event list logs all binary input signals con-
nected to the Disturbance report function. The list
The function requires that the IED is equipped may contain of up to 1000 time-tagged events
with the mA input module. stored in a ring-buffer.

Event counter (GGIO) Indications (RDRE)


The function consists of six counters which are To get fast, condensed and reliable information
used for storing the number of times each counter about disturbances in the primary and/or in the
has been activated. It is also provided with a com- secondary system it is important to know e.g.
mon blocking function for all six counters, to be binary signals that have changed status during a
used for example at testing. Every counter can sep- disturbance. This information is used in the short
arately be set on or off by a parameter setting. perspective to get information via the LHMI in a
straightforward way.
Disturbance report (RDRE)
Complete and reliable information about distur- There are three LEDs on the LHMI (green, yellow
bances in the primary and/or in the secondary sys- and red), which will display status information
tem together with continuous event-logging is about the IED and the Disturbance Report function
accomplished by the disturbance report functional- (trigged).
ity.
The Indication list function shows all selected
The disturbance report, always included in the binary input signals connected to the Disturbance
IED, acquires sampled data of all selected ana- Report function that have changed status during a
logue input and binary signals connected to the disturbance.
function block i.e. maximum 40 analogue and 96
binary signals. Event recorder (RDRE)
Quick, complete and reliable information about
The disturbance report functionality is a common disturbances in the primary and/or in the second-
name for several functions: ary system is vital e.g. time tagged events logged
during disturbances. This information is used for
Event List (EL) different purposes in the short term (e.g. corrective
Indications (IND) actions) and in the long term (e.g. Functional
Event recorder (ER) Analysis).

Trip Value recorder (TVR) The event recorder logs all selected binary input
Disturbance recorder (DR) signals connected to the Disturbance Report func-
tion. Each recording can contain up to 150
Fault Locator (FL) time-tagged events.

The event recorder information is available for the


disturbances locally in the IED.
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 12

The event recording information is an integrated The built-in fault locator is an impedance measur-
part of the disturbance record (Comtrade file). ing function giving the distance to the fault in per-
cent, km or miles. The main advantage is the high
Trip value recorder (RDRE) accuracy achieved by compensating for load cur-
Information about the pre-fault and fault values for rent and for the mutual zero sequence effect on
currents and voltages are vital for the disturbance double circuit lines.
evaluation.
The compensation includes setting of the remote
The Trip value recorder calculates the values of all and local sources and calculation of the distribu-
selected analogue input signals connected to the tion of fault currents from each side. This distribu-
Disturbance report function. The result is magni- tion of fault current, together with recorded load
tude and phase angle before and during the fault (pre-fault) currents, is used to exactly calculate the
for each analogue input signal. fault position. The fault can be recalculated with
new source data at the actual fault to further
The trip value recorder information is available for increase the accuracy.
the disturbances locally in the IED.
Specially on heavily loaded long lines (where the
The trip value recorder information is an inte- fault locator is most important) where the source
grated part of the disturbance record (Comtrade voltage angles can be up to 35-40 degrees apart the
file). accuracy can be still maintained with the advanced
compensation included in fault locator.
Disturbance recorder (RDRE)
The Disturbance Recorder function supplies fast,
complete and reliable information about distur- Metering
bances in the power system. It facilitates under-
standing system behavior and related primary and Pulse counter logic (GGIO)
secondary equipment during and after a distur- The pulse counter logic function counts externally
bance. Recorded information is used for different generated binary pulses, for instance pulses com-
purposes in the short perspective (e.g. corrective ing from an external energy meter, for calculation
actions) and long perspective (e.g. Functional of energy consumption values. The pulses are cap-
Analysis). tured by the binary input module and then read by
the pulse counter function. A scaled service value
The Disturbance Recorder acquires sampled data is available over the station bus. The special
from all selected analogue input and binary signals Binary input module with enhanced pulse counting
connected to the Disturbance Report function capabilities must be ordered to achieve this func-
(maximum 40 analog and 96 binary signals). The tionality.
binary signals are the same signals as available
under the event recorder function.
Basic IED functions
The function is characterized by great flexibility
and is not dependent on the operation of protection Time synchronization
functions. It can record disturbances not detected Use the time synchronization source selector to
by protection functions. select a common source of absolute time for the
IED when it is a part of a protection system. This
The disturbance recorder information for the last makes comparison of events and disturbance data
100 disturbances are saved in the IED and the between all IEDs in a SA system possible.
Local Human Machine Interface (LHMI) is used
to view the list of recordings.
Human machine interface
Event function (EV) The local human machine interface is available in
When using a Substation Automation system with a small, and a medium sized model. The principle
LON or SPA communication, time-tagged events difference between the two is the size of the LCD.
can be sent at change or cyclically from the IED to The small size LCD can display seven line of text
the station level. These events are created from any and the medium size LCD can display the single
available signal in the IED that is connected to the line diagram with up to 15 objects on each page.
Event function block. The event function block is
used for LON and SPA communication. Six SLD pages can be defined.

Analog and double indication values are also The local human machine interface is equipped
transferred through the event block. with an LCD that can display the single line dia-
gram with up to 15 objects.
Fault locator (RFLO)
The accurate fault locator is an essential compo- The local human-machine interface is simple and
nent to minimize the outages after a persistent fault easy to understand the whole front plate is
and/or to pin-point a weak spot on the line. divided into zones, each of them with a
well-defined functionality:
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 13

Status indication LEDs


Alarm indication LEDs which consists of 15
LEDs (6 red and 9 yellow) with user printable
label. All LEDs are configurable from the
PCM 600 tool
Liquid crystal display (LCD)
Keypad with push buttons for control and nav-
igation purposes, switch for selection between
local and remote control and reset
An isolated RJ45 communication port

Figure 5: Medium graphic HMI, 15 controllable


objects

Station communication
Overview
Each IED is provided with a communication inter-
face, enabling it to connect to one or many substa-
tion level systems or equipment, either on the
Substation Automation (SA) bus or Substation
Monitoring (SM) bus.

Figure 4: Small graphic HMI Following communication protocols are available:

IEC 61850-8-1 communication protocol


LON communication protocol
SPA or IEC 60870-5-103 communication pro-
tocol

Theoretically, several protocols can be combined


in the same IED.

IEC 61850-8-1 communication protocol


Single or double optical Ethernet ports for the new
substation communication standard IEC61850-8-1
for the station bus are provided. IEC61850-8-1
allows intelligent devices (IEDs) from different
vendors to exchange information and simplifies
SA engineering. Peer- to peer communication
according to GOOSE is part of the standard. Dis-
turbance files uploading is provided.

Serial communication, LON


Existing stations with ABB station bus LON can
be extended with use of the optical LON interface.
This allows full SA functionality including
peer-to-peer messaging and cooperation between
existing ABB IED's and the new IED 670.
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 14

SPA communication protocol Remote communication


A single glass or plastic port is provided for the
ABB SPA protocol. This allows extensions of sim- Binary signal transfer to remote end,
ple substation automation systems but the main 6 x 32 signals
use is for Substation Monitoring Systems SMS. Each of the six binary signal transfer function
blocks can be used for sending and receiving of 32
IEC 60870-5-103 communication protocol signals, transfer trip and/or other binary signals
A single glass or plastic port is provided for the between local and/or remote IEDs. An IED can
IEC60870-5-103 standard. This allows design of communicate with up to IEDs by means of the
simple substation automation systems including data communication module (LDCM).
equipment from different vendors. Disturbance
files uploading is provided. Line data communication module, short,
medium and long range (LDCM)
Single command, 16 signals The line data communication module (LDCM) is
The IEDs can receive commands either from a used for communication between the IEDs situated
substation automation system or from the local at distances <150 km or from the IED to optical to
human-machine interface, LHMI. The command electrical converter with G.703 or G.703E1 inter-
function block has outputs that can be used, for face located on a distances <3 km away. The
example, to control high voltage apparatuses or for LDCM module sends and receives data, to and
other user defined functionality. from another LDCM module. The IEEE/ANSI
C37.94 standard format is used.
Multiple command and transmit
When 670 IED's are used in Substation Automa- The line data communication module is used for
tion systems with LON, SPA or IEC60870-5-103 binary signal transfer. The module has one optical
communication protocols the Event and Multiple port with ST connectors.
Command function blocks are used as the commu-
nication interface for vertical communication to Galvanic interface G.703
station HMI and gateway and as interface for hori- The external galvanic data communication con-
zontal peer-to-peer communication (over LON verter G.703 makes an optical-to-galvanic conver-
only). sion for connection to a multiplexer. These units
are designed for 64 kbit/s operation. The converter
is delivered with 19 rack mounting accessories.

Hardware Hardware modules put or any signalling purpose. The two high speed
signal output channels are used for applications
description where short operating time is essential. Eight opti-
Power supply module (PSM)
The power supply module is used to provide the cally isolated binary inputs cater for required
correct internal voltages and full isolation between binary input information.
the terminal and the battery system. An internal
fail alarm output is available. mA input module (MIM)
The milli-ampere input module is used to interface
Binary input module (BIM) transducer signals in the 20 to +20 mA range
The binary input module has 16 optically isolated from for example OLTC position, temperature or
inputs and is available in two versions, one stan- pressure transducers.The module has six indepen-
dard and one with enhanced pulse counting capa- dent, galvanically separated channels.
bilities on the inputs to be used with the pulse
counter function. The binary inputs are freely pro- Optical ethernet module (OEM)
grammable and can be used for the input of logical The optical fast-ethernet module is used to connect
signals to any of the functions. They can also be an IED to the communication buses (like the sta-
included in the disturbance recording and tion bus) that use the IEC 61850-8-1 protocol. The
event-recording functions. This enables extensive module has one or two optical ports with ST con-
monitoring and evaluation of operation of the IED nectors.
and for all associated electrical circuits.
Serial SPA/IEC 60870-5-103 and LON
Binary output modules (BOM) communication module (SLM)
The binary output module has 24 independent out- The optical serial channel and LON channel mod-
put relays and is used for trip output or any signal- ule is used to connect an IED to the communica-
ling purpose. tion that use SPA, LON, or IEC608705103. The
module has two optical ports for plastic/plastic,
Binary input/output module (IOM) plastic/glass, or glass/glass.
The binary input/output module is used when only
a few input and output channels are needed. The Line data communication module (LDCM)
ten standard output channels are used for trip out- The line data communication module is used for
binary signal transfer. Each module has one optical
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 15

port, one for each remote end to which the IED transformers. The module has twelve inputs in dif-
communicates. ferent combinations.

Alternative cards for Short range (900 nm multi High impedance resistor unit
mode) are available. The high impedance resistor unit, with resistors for
pick-up value setting and a voltage dependent
Transformer input module (TRM) resistor, is available in a single phase unit and a
The transformer input module is used to galvani- three phase unit. Both are mounted on a 1/1 19
cally separate and transform the secondary cur- inch apparatus plate with compression type term-
rents and voltages generated by the measuring nals.

Layout and dimensions


Dimensions

B C
D

xx05000003.vsd
xx05000004.vsd

Figure 6: 1/2 x 19 case with rear cover Figure 7: Side-by-side mounting

Case size A B C D E F
6U, 1/2 x 19 265.9 223.7 201.1 242.1 252.9 205.7
6U, 3/4 x 19 265.9 336.0 201.1 242.1 252.9 318.0
6U, 1/1 x 19 265.9 448.1 201.1 242.1 252.9 430.3
(mm)

Mounting alternatives Wall mounting kit


Following mounting alternatives (IP40 protection
from the front) are available: See ordering for details about available mounting
alternatives.
19 rack mounting kit
Flush mounting kit with cut-out dimensions:
- 1/2 case size (h) 254.3 mm (w) 210.1 mm
- 3/4 case size (h) 254.3 mm (w) 322.4mm
- 1/1 case size (h) 254.3 mm (w) 434.7mm
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 16

Connection Table 1: Designations for 1/2 x 19 casing with 1 TRM slot


diagrams
Module Rear Positions
PSM X11
BIM, BOM or IOM X31 and X32 etc. to X51 and X52
GSM X51
SLM X301:A, B, C, D
OEM X311:A, B, C, D
LDCM X312:A, B
LDCM X313:A, B
TRM X401

Table 2: Designations for 3/4 x 19 casing with 2TRM slot

Module Rear Positions


PSM X11
BIM, BOM, IOM or MIM X31 and X32 etc. to X71 and X72
GSM X71
SLM X301:A, B, C, D
LDCM X302:A, B
LDCM X303:A, B
OEM X311:A, B, C, D
LDCM X312:A, B
LDCM X313:A, B
TRM X401, 411

Table 3: Designations for 1/1 x 19 casing with 2 TRM slots

Module Rear Positions


PSM X11
BIM, BOM or IOM X31 and X32 etc. to X131 and X132
MIM X31, X41, etc. or X131
GSM X131
SLM X301:A, B, C, D
OEM X311:A, B, C, D
LDCM X312:A, B
LDCM X313:A, B
TRM 1 X401
TRM 2 X411
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 17

CT/VT-input designation according to figure 8


Current/voltage AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12
configuration
(50/60 Hz)
9I and 3U, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 0-220V 0-220V 0-220V
9I and 3U, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 0-220V 0-220V 0-220V
5I, 1A and 4I, 5A 1A 1A 1A 1A 1A 5A 5A 5A 5A 0-220V 0-220V 0-220V
and 3U
6I and 6U, 1A 1A 1A 1A 1A 1A 1A 0-220V 0-220V 0-220V 0-220V 0-220V 0-220V
6I and 6U, 5A 5A 5A 5A 5A 5A 5A 0-220V 0-220V 0-220V 0-220V 0-220V 0-220V

Figure 8: Transformer input


module (TRM)

Figure 9: Binary input module (BIM). Input contacts named XA Figure 10: mA input module (MIM)
corresponds to rear position X31, X41, etc. and input
contacts named XB to rear position X32, X42, etc.
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 18

Figure 12: Communication interfaces (OEM,


LDCM, SLM and HMI)
Note to figure 12
1) Rear communication port IEC 61850, ST-connector
Figure 11: Binary in/out module (IOM). Input contacts named XA corresponds to rear 2) Rear communication port C37.94, ST-connector
position X31, X41, etc. and output contacts named XB to rear position X32, 3) Rear communication port SPA/ IEC 60870-5-103,
X42, etc. ST connector for glass alt. HFBR Snap-in connector
for plastic as ordered
4) Rear communication port LON, ST connector for
glass alt. HFBR Snap-in connector for plastic as
ordered
5) Front communication port, Ethernet, RJ45 connector

Figure 14: GPS time synchronization module


(GSM)

Figure 13: Power supply module (PSM)


Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 19

Figure 15: Binary output module (BOM). Output contacts named XA corresponds to rear position X31,
X41, etc. and output contacts named XB to rear position X32, X42, etc.
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 20

BUS A
BBP-TRIP BUS B
QB1-OPEN
ST BFP L1 *) QB1-CL
ST BFP L2 *) QB2-OPEN
ST BFP L3 *) QB2-CL -QB1
ST BFP 3PH -QB2

START AR
INHIBIT AR
TRM1:10
3PH TRIP *) MCB-OK

IN TEST
TRM1:11
MAN CLOSE MCB-OK

-QA1
CLOSE QA1 C
C
CLOSE Reinf
*) TRIP QA1 L1,L2,L3 REL/RED 3 Phase T
C
*) TRIP Reinf MAIN 2 TRIP T
QA1-OPEN C

QA1-CL
SIGNALLING

QA1-PD
FAULT

QA1-SPR UNCH

-BI1 P1
TRM1:1-3

Reserved for parallal line


TRM1:5
IN at mutual comp of FL

TO MAIN 2 RELAY

BUSBAR TRIP
PERMIT 1PH *) TO BUS PROT
TRIP MAIN 2
1PH AR IN PROG *)

CR Z<
CS Z<
TO/FROM PLC/MUX

QB9-OPEN
QB9-CL
CR DEF
CS DEF
-QB9

CR DIT
MCB OR
FUSE -BU1
CS DIT
TRM1:7-9
MCB-OK

X11 O NOTE! CB CLosed is


3 IRF X11 2 CB Closed L1&L2&L3
5 4
- + REMOTE END CB Open is CB Open
COMMUNICATION L1 OR L2 OR L3
*) is only valid for single phase tripping arrangements en05000261.vsd

Figure 16: Typical connection diagram for a single breaker arrangement with control integrated.
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 21

BUS A
BBP-TRIP
QB1-OPEN
ST BFP L1 *) QB1-CL -BU1
ST BFP L2 *) QB6-OPEN
-QB1
ST BFP L3 *) QB6-CL
ST BFP 3PH

START AR MCB OR
FUSE
INHIBIT AR
TRM1:11
3PH TRIP *) MCB-OK
=1-QA1
MAN CLOSE =1 CLOSE QA1 C
C
CLOSE Reinf
TRIP QA1 L1,L2,L3 REL/RED 3 Phase
*) T
C
*) TRIP Reinf MAIN 2 TRIP
T
QA1-OPEN
SIGNALLING

C
QA1-CL
FAULT

QA1-PD
QA1-SPR UNCH

-BI1 P1
TRM1:1-3
ST BFP L1 TO MAIN 2 RELAY
ST BFP L2
=2-QB9-OPEN
ST BFP L3 TO BUS PROT
=2-QB9-CL
ST BFP 3PH For Voltage
=2-QA1-OPEN
selection
START AR =2-QA1-CL
MCB OR -BU1 -QB6
INHIBIT AR FUSE
TRM1:7-9
3PH TRIP -QB9
MCB-OK

IN TEST QB9-OPEN
QB9-CL
-QB61
MAN CLOSE =3
TO MAIN 2 RELAY -BI1
BUSBAR TRIP
TRM2:1-3
TRIP =2-QA1 Reserved for parallal line IN P1
PERMIT 1PH TRIP TRM1:5 at mutual comp of FL =3-QA1
MAIN 2, =1 *) CLOSE QA1 C
C
PERMIT 1PH TRIP CLOSE Reinf
MAIN 2, =3 *) TRIP QA1 L1,L2,L3 T
C
1PH AR IN PROG *) TRIP Reinf MAIN 2 TRIP T
QA1-OPEN C
CR Z< QA1-CL
CS Z< QA1-PD
TO/FROM PLC/MUX

QA1-SPR
CR DEF UNCH
-QB62 -QB9
CS DEF MCB-OK
-BU1 -QB6
CR DIT TRM2:11
MCB OR
CS DIT
TRM1:12 FUSE
DIT2 Line 2 MCB OR =2-QA1 NOTE! CB CLosed is
MCB-OK FUSE
CB Closed L1&L2&L3
CB Open is CB Open
X11 O -BU1 L1 OR L2 OR L3
3 IRFX11 2
5 4
- + REMOTE END -QB2 BUS B
COMMUNICATION
*) is only valid for single phase tripping arrangements en05000267.vsd

Figure 17: Typical connection diagram for a multi breaker arrangement (1 1/2 CB) with control integrated.
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 22

Technical data General


Definitions

Reference value:
The specified value of an influencing factor to which are referred the characteristics of the equipment.
Nominal range:
The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements.
Operative range:
The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform
its intended functions according to the specified requirements.

Energizing quantities, rated values and limits


Analog inputs
Table 4: TRM - Energizing quantities, rated values and limits
Quantity Rated value Nominal range
Current Ir = 1 or 5 A (0.2-40) Ir
Operative range (0.02-100) x Ir
Permissive overload 4 Ir cont.
100 Ir for 1 s *)
Burden < 0.25 VA at Ir = 1 or 5 A
Ac voltage Ur = 110 V 0.5288 V
Operative range (0340) V
Permissive overload 420 V cont.
450 V 10 s
Burden < 0.2 VA at 220 V
< 0.1 VA at 110 V
Frequency fr = 50/60 Hz 5%
*)
max. 350 A for 1 s when COMBITEST test switch is included.

Table 5: MIM - mA input module


Quantity: Rated value: Nominal range:
Input range 5, 10, 20mA -
0-5, 0-10, 0-20, 4-20mA
Input resistance Rin = 194 Ohm -
Power consumption -
each mA-board 4W
each mA input 0.1 W

Auxiliary DC voltage
Table 6: PSM - Power supply module
Quantity Rated value Nominal range
Auxiliary dc voltage, EL (input) EL = (24 - 60) V EL 20%
EL = (90 - 250) V EL 20%
Power consumption 50 W typically -
Auxiliary DC power in-rush < 5 A during 0.1 s -

Binary inputs and outputs


Table 7: BIM - Binary input module
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL RL24 (24/40) V RL 20%
RL48 (48/60) V RL 20%
RL110 (110/125) V RL 20%
RL220 (220/250) V RL 20%
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 23

Quantity Rated value Nominal range


Power consumption
RL24 = (24/40) V max. 0.05 W/input -
RL48 = (48/60) V max. 0.1 W/input
RL110 = (110/125) V max. 0.2 W/input
RL220 = (220/250) V max. 0.4 W/input
Counter input frequency 10 pulses/s max -
Oscillating signal discriminator Blocking settable 140 Hz
Release settable 130 Hz

Table 8: BIM - Binary input module with enhanced pulse counting capabilities
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL RL24 (24/40) V RL 20%
RL48 (48/60) V RL 20%
RL110 (110/125) V RL 20%
RL220 (220/250) V RL 20%
Power consumption
RL24 = (24/40) V max. 0.05 W/input -
RL48 = (48/60) V max. 0.1 W/input
RL110 = (110/125) V max. 0.2 W/input
RL220 = (220/250) V max. 0.4 W/input
Counter input frequency 10 pulses/s max -
Balanced counter input frequency 40 pulses/s max -
Oscillating signal discriminator Blocking settable 140 Hz
Release settable 130 Hz

Table 9: IOM - Binary input/output module


Quantity Rated value Nominal range
Binary inputs 8 -
DC voltage, RL RL24 = (24/40) V RL 20%
RL48 = (48/60) V RL 20%
RL110 = (110/125) V RL 20%
RL220 = (220/250) V RL 20%
Power consumption -
RL24 = (24/40) V max. 0.05 W/input
RL48 = (48/60) V max. 0.1 W/input
RL110 = (110/125) V max. 0.2 W/input
RL220 = (220/250) V max. 0.4 W/input

Table 10: IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel reed relay)
Binary outputs 10 2
Max system voltage 250 V AC, DC 250 V AC, DC
Test voltage across open contact, 1 min 1000 V rms 800 V DC
Current carrying capacity
Continuous 8A 8A
1s 10 A 10 A
Making capacity at inductive load with
L/R>10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A
Breaking capacity for AC, cos > 0.4 250 V/8.0 A 250 V/8.0 A
Breaking capacity for DC with L/R < 40 48 V/1 A 48 V/1 A
ms 110 V/0.4 A 110 V/0.4 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Maximum capacitive load - 10 nF
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 24

Table 11: BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays
Binary outputs 24
Max system voltage 250 V AC, DC
Test voltage across open contact, 1 min 1000 V rms
Current carrying capacity
Continuous 8A
1s 10 A
Making capacity at inductive load with L/R>10 ms
0.2 s 30 A
1.0 s 10 A
Breaking capacity for AC, cos >0.4 250 V/8.0 A
Breaking capacity for DC with L/R < 40 ms 48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A

Influencing factors
Table 12: Temperature and humidity influence
Parameter Reference value Nominal range Influence
Ambient temperature, oper- +20 C -10 C to +55 C 0.02% /C
ate value
Relative humidity 10%-90% 10%-90% -
Operative range 0%-95%
Storage temperature -40 C to +70 C - -

Table 13: Auxiliary DC supply voltage influence on functionality during operation


Dependence on Reference value Within nominal range Influence
Ripple, in DC auxiliary voltage max. 2% 12% of EL 0.01% /%
Operative range Full wave rectified
Auxiliary voltage dependence, operate value 20% of EL 0.01% /%
Interrupted auxiliary DC voltage 24-60 V DC 20%
90-250 V DC 20%
Interruption interval
050 ms No restart
0 s Correct behaviour at
power down
Restart time <140 s

Table 14: Frequency influence (reference standard: IEC 602556)


Dependence on Within nominal range Influence
Frequency dependence, operate value fr 2.5 Hz for 50 Hz 1.0% / Hz
fr 3.0 Hz for 60 Hz
Harmonic frequency dependence (20% 2nd, 3rd and 5th harmonic of fr 1.0%
content)
Harmonic frequency dependence for 2nd, 3rd and 5th harmonic of fr 6.0%
distance protection (10% content)

Type tests according to standards


Table 15: Electromagnetic compatibility
Test Type test values Reference standards
1 MHz burst disturbance 2.5 kV IEC 60255-22-1, Class III
100 kHz disturbance 2.5 kV IEC 61000-4-12, Class III
Electrostatic discharge 15 kV air discharge IEC 60255-22-2, Class IV
Direct applicaton 8 kV contact discharge
Indirect application 8 kV contact discharge IEC 61000-4-2, Class IV
Fast transient disturbance 4 kV IEC 60255-22-4, Class A
Surge immunity test 1-2 kV, 1.2/50 s IEC 60255-22-5
high energy
Power frequency immunity test 150-300 V, IEC 60255-22-7, Class A
50 Hz
Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Class V
Radiated electromagnetic field disturbance 20 V/m, 80-1000 MHz IEC 60255-22-3
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 25

Test Type test values Reference standards


Radiated electromagnetic field disturbance 20 V/m, 80-2500 MHz EN 61000-4-3
Radiated electromagnetic field disturbance 35 V/m IEEE/ANSI C37.90.2
26-1000 MHz
Conducted electromagnetic field distur- 10 V, 0.15-80 MHz IEC 60255-22-6
bance
Radiated emission 30-1000 MHz IEC 60255-25
Conducted emission 0.15-30 MHz IEC 60255-25

Table 16: Insulation


Test Type test values Reference standard
Dielectric test 2.0 kV AC, 1 min. IEC 60255-5
Impulse voltage test 5 kV, 1.2/50 s, 0.5 J
Insulation resistance >100 M at 500 VDC

Table 17: Environmental tests


Test Type test value Reference standard
Cold test Test Ad for 16 h at -25C IEC 60068-2-1
Storage test Test Ad for 16 h at -40C IEC 60068-2-1
Dry heat test Test Bd for 16 h at +70C IEC 60068-2-2
Damp heat test, steady state Test Ca for 4 days at +40 C and humidity IEC 60068-2-3
93%
Damp heat test, cyclic Test Db for 6 cycles at +25 to +55 C and IEC 60068-2-30
humidity 93 to 95% (1 cycle = 24 hours)

Table 18: CE compliance


Test According to
Immunity EN 61000-6-2
Emissivity EN 61000-6-4
Low voltage directive EN 50178

Table 19: Mechanical tests


Test Type test values Reference standards
Vibration Class I IEC 60255-21-1
Shock and bump Class I IEC 60255-21-2
Seismic Class I IEC 60255-21-3

Differential protection
Table 20: High impedance differential protection (PDIF, 87)
Function Range or value Accuracy
Operate voltage (20-400) V 1.0% of Ur for U < Ur
1.0% of U for U > Ur
Reset ratio >95% -
Maximum continuous voltage U>Trip2/series resistor 200 W -
Operate time 10 ms typically at 0 to 10 x Ud -
Reset time 90 ms typically at 10 to 0 x Ud -
Critical impulse time 2 ms typically at 0 to 10 x Ud -

Distance protection
Table 21: Distance protection zones (PDIS, 21)
Function Range or value Accuracy
Number of zones 5 with selectable direction -
Minimum operate current (10-30)% of Ibase -
Positive sequence reactance (0.50-3000.00) /phase 2.0% static accuracy
Positive sequence resistance (0.10-1000.00) /phase 2.0 degrees static angular accuracy
Zero sequence reactance (0.50-9000.00) /phase Conditions:
Zero sequence resistance (0.50-3000.00) /phase Voltage range: (0.1-1.1) x Ur
Fault resistance, Ph-E (1.00-9000.00) /loop Current range: (0.5-30) x Ir
Fault resistance, Ph-Ph (1.00-3000.00) /loop Angle: at 0 degrees and 85 degrees
Dynamic overreach <5% at 85 degrees measured with -
CVTs and 0.5<SIR<30
Impedance zone timers (0.000-60.000) s 0.5% 10 ms
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 26

Function Range or value Accuracy


Operate time 24 ms typically -
Reset ratio 105% typically -
Reset time 30 ms typically -

Table 22: Phase selection with load encroachment (PDIS, 21)


Function Range or value Accuracy
Minimum operate current (5-30)% of Ibase 1.0% of Ir
Reactive reach, positive sequence, for- (0.503000.00) /phase 2.0% static accuracy
ward and reverse 2.0 degrees static angular accuracy
Resistive reach, positive sequence (0.101000.00) /phase
Conditions:
Reactive reach, zero sequence, forward (0.509000.00) /phase
Voltage range: (0.1-1.1) x Ur
and reverse
Current range: (0.5-30) x Ir
Resistive reach, zero sequence (0.503000.00) /phase
Fault resistance, phase-earth faults, for- (1.009000.00) /loop Angle: at 0 degrees and 85 degrees
ward and reverse
Fault resistance, phase-phase faults, (0.503000.00) /loop
forward and reverse
Load encroachment criteria:
Load resistance, forward and reverse (1.003000.00) /phase
Safety load impedance angle
(5-70) degrees
Reset ratio 105% typically -

Table 23: Power swing detection (RPSB, 78)


Function Range or value Accuracy
Reactive reach (0.10-3000.00) /phase 2.0% static accuracy
2.0 degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Resistive reach (0.101000.00) /loop Current range: (0.5-30) x Ir
Angle: at 0 degrees and 85 degrees
Timers (0.000-60.000) s 0.5% 10 ms

Table 24: Automatic switch onto fault logic (PSOF)


Parameter Range or value Accuracy
Operate voltage, detection of dead line (1100)% of Ubase 1.0% of Ur
Operate current, detection of dead line (1100)% of Ibase 1.0% of Ir
Delay following dead line detection input before SOTF function 200 ms 0.5% 10 ms
is automatically enabled
Time period after circuit breaker closure in which SOTF func- 1000 ms 0.5% 10 ms
tion is active

Current protection
Table 25: Instantaneous phase overcurrent protection (PIOC, 50)
Function Range or value Accuracy
Operate current (1-2500)% of lbase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio > 95% -
Operate time 25 ms typically at 0 to 2 x Iset -
Reset time 25 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Operate time 10 ms typically at 0 to 10 x Iset -
Reset time 35 ms typically at 10 to 0 x Iset -
Critical impulse time 2 ms typically at 0 to 10 x Iset -
Dynamic overreach < 5% at = 100 ms -

Table 26: Four step phase overcurrent protection (POCM, 51/67)


Function Setting range Accuracy
Operate current (1-2500)% of lbase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio > 95% -
Min. operating current (1-100)% of lbase 1.0% of Ir
Relay characteristic angle (RCA) (-70.0 -50.0) degrees 2.0 degrees
Maximum forward angle (40.070.0) degrees 2.0 degrees
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 27

Function Setting range Accuracy


Minimum forward angle (75.090.0) degrees 2.0 degrees
Second harmonic blocking (5100)% of fundamental 2.0% of Ir
Independent time delay (0.000-60.000) s 0.5% 10 ms
Minimum operate time (0.000-60.000) s 0.5% 10 ms
Inverse characteristics, see table 70 19 curve types See table 70 and table 71
and table 71
Operate time, start function 25 ms typically at 0 to 2 x Iset -
Reset time, start function 25 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Impulse margin time 15 ms typically -

Table 27: Instantaneous residual overcurrent protection (PIOC, 50N)


Function Range or value Accuracy
Operate current (1-2500)% of lbase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio > 95% -
Operate time 25 ms typically at 0 to 2 x Iset -
Reset time 25 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Operate time 10 ms typically at 0 to 10 x Iset -
Reset time 35 ms typically at 10 to 0 x Iset -
Critical impulse time 2 ms typically at 0 to 10 x Iset -
Dynamic overreach < 5% at = 100 ms -

Table 28: Four step residual overcurrent protection (PEFM, 51N/67N)


Function Range or value Accuracy
Operate current (1-2500)% of lbase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio > 95% -
Operate current for directional compari- (1100)% of lbase 1.0% of Ir
son
Timers (0.000-60.000) s 0.5% 10 ms
Inverse characteristics, see table 70 19 curve types See table 70 and table 71
and table 71
Second harmonic restrain operation (5100)% of fundamental 2.0% of Ir
Relay characteristic angle (-180 to 180) degrees 2.0 degrees
Minimum polarizing voltage (1100)% of Ubase 1.0% of Ur
Operate time, start function 25 ms typically at 0 to 2 x Iset -
Reset time, start function 25 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Impulse margin time 15 ms typically -

Table 29: Thermal overload protection, one time constant (PTTR, 26)
Function Range or value Accuracy
Reference current (0-400)% of Ibase 1.0% of Ir
Start temperature reference (0-400)C 1.0C
Operate time: Ip = load current before overload occurs IEC 60255-8, class 5 + 200 ms
Time constant = (01000) minutes

I 2 I p2
t = ln 2
I Ib 2

I = Imeasured
Alarm temperature (0-200)C 2.0% of heat content trip
Trip temperature (0-400)C 2.0% of heat content trip
Reset level temperature (0-400)C 2.0% of heat content trip
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 28

Table 30: Breaker failure protection (RBRF, 50BF)


Function Range or value Accuracy
Operate phase current (5-200)% of lbase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio, phase current > 95% -
Operate residual current (2-200)% of lbase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio, residual current > 95% -
Phase current level for blocking of con- (5-200)% of lbase 1.0% of Ir at I Ir
tact function 1.0% of I at I > Ir
Reset ratio > 95% -
Timers (0.000-60.000) s 0.5% 10 ms
Operate time for current detection 10 ms typically -
Reset time for current detection 15 ms maximum -

Table 31: Stub protection (PTOC, 50STB)


Function Range or value Accuracy
Operate current (1-2500)% of Ibase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio > 95% -
Definite time (0.000-60.000) s 0.5% 10 ms
Operate time, start function 25 ms typically at 0 to 2 x Iset -
Reset time, start function 25 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Impulse margin time 15 ms typically -

Table 32: Pole discordance protection (RPLD, 52PD)


Function Range or value Accuracy
Operate current (0100% of Ibase 1.0% of Ir
Time delay (0.000-60.000) s 0.5% 10 ms

Voltage protection
Table 33: Two step undervoltage protection (PUVM, 27)
Function Range or value Accuracy
Operate voltage, low and high step (1100)% of Ubase 1.0% of Ur
Absolute hysteresis (0100)% of Ubase 1.0% of Ur
Internal blocking level, low and high (1100)% of Ubase 1.0% of Ur
step
Inverse time characteristics for low - See table 72
and high step, see table 72
Definite time delays (0.000-60.000) s 0.5% 10 ms
Minimum operate time, inverse char- (0.00060.000) s 0.5% 10 ms
acteristics
Operate time, start function 25 ms typically at 2 to 0 x Uset -
Reset time, start function 25 ms typically at 0 to 2 x Uset -
Critical impulse time 10 ms typically at 2 to 0 x Uset -
Impulse margin time 15 ms typically -

Table 34: Two step overvoltage protection (POVM, 59)


Function Range or value Accuracy
Operate voltage, low and high step (1-200)% of Ubase 1.0% of Ur at U < Ur
1.0% of U at U > Ur
Absolute hysteresis (0100)% of Ubase 1.0% of Ur at U < Ur
1.0% of U at U > Ur
Inverse time characteristics for low - See table 73
and high step, see table 73
Definite time delays (0.000-60.000) s 0.5% 10 ms
Minimum operate time, Inverse char- (0.000-60.000) s 0.5% 10 ms
acteristics
Operate time, start function 25 ms typically at 0 to 2 x Uset -
Reset time, start function 25 ms typically at 2 to 0 x Uset -
Critical impulse time 10 ms typically at 0 to 2 x Uset -
Impulse margin time 15 ms typically -
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 29

Table 35: Two step residual overvoltage protection (POVM, 59N)


Function Range or value Accuracy
Operate voltage, low and high step (1-200)% of Ubase 1.0% of Ur at U < Ur 1.0% of U at U
> Ur
Absolute hysteresis (0100)% of Ubase 1.0% of Ur at U < Ur
1.0% of U at U > Ur
Inverse time characteristics for low - See table 74
and high step, see table 74
Definite time setting (0.00060.000) s 0.5% 10 ms
Minimum operate time (0.000-60.000) s 0.5% 10 ms
Operate time, start function 25 ms typically at 0 to 2 x Uset -
Reset time, start function 25 ms typically at 2 to 0 x Uset -
Critical impulse time 10 ms typically at 0 to 2 x Uset -
Impulse margin time 15 ms typically -

Frequency protection
Table 36: Underfrequency protection (PTUF, 81)
Function Range or value Accuracy
Operate value, start function (35.00-75.00) Hz 2.0 mHz
Operate time, start function 100 ms typically -
Reset time, start function 100 ms typically -
Operate time, definite time function (0.000-60.000)s 0.5% + 10 ms
Reset time, definite time function (0.000-60.000)s 0.5% + 10 ms
Voltage dependent time delay Settings: Class 5 + 200 ms
UNom=(50-150)% of Ubase
UMin=(50-150)% of Ubase
Exponent
U UMin
t= ( tMax tMin ) + tMin Exponent=0.0-5.0
UNom UMin tMax=(0.001-60.000)s
tMin=(0.000-60.000)s
U=Umeasured

Table 37: Overfrequency protection (PTOF, 81)


Function Range or value Accuracy
Operate value, start function (35.00-75.00) Hz 2.0 mHz
Operate time, start function 100 ms typically -
Reset time, start function 100 ms typically -
Operate time, definite time function (0.000-60.000)s 0.5% + 10 ms
Reset time, definite time function (0.000-60.000)s 0.5% + 10 ms

Table 38: Rate-of-change frequency protection (PFRC, 81)


Function Range or value Accuracy
Operate value, start function (-10.00-10.00) Hz/s 10.0 mHz/s
Operate value, internal blocking level (0-100)% of Ubase 1.0% of Ur
Operate time, start function 100 ms typically -

Multipurpose protection
Table 39: General current and voltage protection (GAPC)
Function Range or value Accuracy
Measuring current input phase1, phase2, phase3, PosSeq, -
NegSeq, 3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2,
phase2-phase3, phase3-phase1,
MaxPh-Ph, MinPh-Ph, Unbalan-
cePh-Ph
Base current (1 - 99999) A -
Measuring voltage input phase1, phase2, phase3, PosSeq, -
-NegSeq, -3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2,
phase2-phase3, phase3-phase1,
MaxPh-Ph, MinPh-Ph, Unbalan-
cePh-Ph
Base voltage (0.05 - 2000.00) kV -
Start overcurrent, step 1 and 2 (2 - 5000)% of Ibase 1.0% of Ir for I<Ir
1.0% of I for I>Ir
Start undercurrent, step 1 and 2 (2 - 150)% of Ibase 1.0% of Ir for I<Ir
1.0% of I for I>Ir
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 30

Function Range or value Accuracy


Definite time delay (0.00 - 6000.00) s 0.5% 10 ms
Operate time start overcurrent 25 ms typically at 0 to 2 x Iset -
Reset time start overcurrent 25 ms typically at 2 to 0 x Iset -
Operate time start undercurrent 25 ms typically at 2 to 0 x Iset -
Reset time start undercurrent 25 ms typically at 0 to 2 x Iset -
See table 70 and table 71 Parameter ranges for customer See table 70 and table 71
defined characteristic no 17:
k: 0.05 - 999.00
A: 0.0000 - 999.0000
B: 0.0000 - 99.0000
C: 0.0000 - 1.0000
P: 0.0001 - 10.0000
PR: 0.005 - 3.000
TR: 0.005 - 600.000
CR: 0.1 - 10.0
Voltage level where voltage memory (0.0 - 5.0)% of Ubase 1.0% of Ur
takes over
Start overvoltage, step 1 and 2 (2.0 - 200.0)% of Ubase 1.0% of Ur for U<Ur
1.0% of U for U>Ur
Start undervoltage, step 1 and 2 (2.0 - 150.0)% of Ubase 1.0% of Ur for U<Ur
1.0% of U for U>Ur
Operate time, start overvoltage 25 ms typically at 0 to 2 x Uset -
Reset time, start overvoltage 25 ms typically at 2 to 0 x Uset -
Operate time start undervoltage 25 ms typically 2 to 0 x Uset -
Reset time start undervoltage 25 ms typically at 0 to 2 x Uset -
High and low voltage limit, voltage (1.0 - 200.0)% of Ubase 1.0% of Ur for U<Ur
dependent operation 1.0% of U for U>Ur
Directional function Settable: NonDir, forward and reverse -
Relay characteristic angle (-180 to +180) degrees 2.0 degrees
Relay operate angle (1 to 90) degrees 2.0 degrees
Reset ratio, overcurrent > 95% -
Reset ratio, undercurrent < 105% -
Reset ratio, overvoltage > 95% -
Reset ratio, undervoltage < 105% -
Overcurrent:
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Impulse margin time 15 ms typically -
Undercurrent:
Critical impulse time 10 ms typically at 2 to 0 x Iset -
Impulse margin time 15 ms typically -
Overvoltage:
Critical impulse time 10 ms typically at 0 to 2 x Uset -
Impulse margin time 15 ms typically -
Undervoltage:
Critical impulse time 10 ms typically at 2 to 0 x Uset -
Impulse margin time 15 ms typically -

Secondary system supervision


Table 40: Current circuit supervision (RDIF)
Function Range or value Accuracy
Operate current (5-200)% of Ir 10.0% of Ir at I Ir
10.0% of I at I > Ir
Block current (5-500)% of Ir 5.0% of Ir at I Ir
5.0% of I at I > Ir

Table 41: Fuse failure supervision (RFUF)


Function Range or value Accuracy
Operate voltage, zero sequence (1-100)% of Ubase 1.0% of Ur
Operate current, zero sequence (1100)% of Ibase 1.0% of Ir
Operate voltage, negative sequence (1100)% of Ubase 1.0% of Ur
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 31

Function Range or value Accuracy


Operate current, negative sequence (1100)% of Ibase 1.0% of Ir
Operate voltage change level (1100)% of Ubase 5.0% of Ur
Operate current change level (1100)% of Ibase 5.0% of Ir

Control
Table 42: Synchrocheck and energizing check (RSYN, 25)
Function Range or value Accuracy
Phase shift, line - bus (-180 to 180) degrees -
Voltage ratio, Ubus/Uline (0.20-5.00)% of Ubase -
Voltage high limit for synchrocheck (50.0-120.0)% of Ubase 1.0% of Ur at U Ur
1.0% of U at U > Ur
Reset ratio, synchrocheck > 95% -
Frequency difference limit between bus (0.003-1.000) Hz 2.0 mHz
and line
Phase angle difference limit between (5.0-90.0) degrees 2.0 degrees
bus and line
Voltage difference limit between bus (2.0-50.0)% of Ubase 1.0% of Ur
and line
Time delay output for synchrocheck (0.000-60.000) s 0.5% 10 ms
Voltage high limit for energizing check (50.0-120.0)% of Ubase 1.0% of Ur at U Ur
1.0% of U at U > Ur
Reset ratio, voltage high limit > 95% -
Voltage low limit for energizing check (10.0-80.0)% of Ubase 1.0% of Ur
Reset ratio, voltage low limit < 105% -
Maximum voltage for energizing (80.0-140.0)% of Ubase 1.0% of Ur at U Ur
1.0% of U at U > Ur
Time delay for energizing check (0.000-60.000) s 0.5% 10 ms
Operate time for synchrocheck function 160 ms typically -
Operate time for energizing function 80 ms typically -

Table 43: Autorecloser (RREC, 79)


Function Range or value Accuracy
Number of autoreclosing shots 1-5 -
Number of autoreclosing programs 8 -
Autoreclosing open time:
shot 1 - t1 1Ph (0.000-60.000) s 0.5% 10 ms
shot 1 - t1 2Ph
shot 1 - t1 3PhHS
shot 1 - t1 3PhDld
shot 2 - t2 (0.00-6000.00) s
shot 3 - t3
shot 4 - t4
shot 5 - t5
Extended autorecloser open time (0.000-60.000) s
Autorecloser maximum wait time for sync (0.00-6000.00) s
Maximum trip pulse duration (0.000-60.000) s
Inhibit reset time (0.000-60.000) s
Reclaim time (0.00-6000.00) s
Minimum time CB must be closed before AR (0.00-6000.00) s
becomes ready for autoreclosing cycle
Circuit breaker closing pulse length (0.000-60.000) s
CB check time before unsuccessful (0.00-6000.00) s
Wait for master release (0.00-6000.00) s
Wait time after close command before pro- (0.000-60.000) s
ceeding to next shot
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 32

Scheme communication
Table 44: Scheme communication logic for distance protection (PSCH, 85)
Function Range or value Accuracy
Scheme type Intertrip -
Permissive UR
Permissive OR
Blocking
Co-ordination time for blocking communica- (0.000-60.000) s 0.5% 10 ms
tion scheme
Minimum duration of a carrier send signal (0.000-60.000) s 0.5% 10 ms
Security timer for loss of carrier guard (0.000-60.000) s 0.5% 10 ms
detection
Operation mode of unblocking logic Off -
NoRestart
Restart

Table 45: Current reversal and weak-end infeed logic for distance protection (PSCH, 85)
Function Range or value Accuracy
Detection level phase to neutral voltage (10-90)% of Ubase 1.0% of Ur
Detection level phase to phase voltage (10-90)% of Ubase 1.0% of Ur
Reset ratio <105% -
Operate time for current reversal (0.000-60.000) s 0.5% 10 ms
Delay time for current reversal (0.000-60.000) s 0.5% 10 ms
Coordination time for weak-end infeed (0.000-60.000) s 0.5% 10 ms
logic

Table 46: Scheme communication logic for residual overcurrent protection (PSCH, 85)
Function Range or value Accuracy
Communication scheme coordination (0.000-60.000) s 0.5% 10 ms
time
Scheme type Permissive UR -
Permissive OR
Blocking

Table 47: Current reversal and weak-end infeed logic for residual overcurrent protection (PSCH, 85)
Function Range or value Accuracy
Operate voltage 3Uo for WEI trip (5-70)% of Ubase 1.0% of Ur
Reset ratio >95% -
Operate time for current reversal (0.000-60.000) s 0.5% 10 ms
Delay time for current reversal (0.000-60.000) s 0.5% 10 ms
Coordination time for weak-end infeed (0.00060.000) s 0.5% 10 ms
logic

Logic
Table 48: Tripping logic (PTRC, 94)
Function Range or value Accuracy
Trip action 3-ph, 1/3-ph, 1/2/3-ph -
Minimum trip pulse length (0.000-60.000) s 0.5% 10 ms
Timers (0.000-60.000) s 0.5% 10 ms

Table 49: Configurable logic blocks


Logic block Quantity with update rate Range or value Accuracy
fast medium normal
LogicAND 60 60 160 - -
LogicOR 60 60 160 - -
LogicXOR 10 10 20 - -
LogicInverter 30 30 80 - -
LogicSRMemory 10 10 20 - -
LogicGate 10 10 20 - -
LogicTimer 10 10 20 (0.00090000.000) s 0.5% 10 ms
LogicPulseTimer 10 10 20 (0.00090000.000) s 0.5% 10 ms
LogicTimerSet 10 10 20 (0.00090000.000) s 0.5% 10 ms
LogicLoopDelay 10 10 20 (0.00090000.000) s 0.5% 10 ms
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 33

Monitoring
Table 50: Measurements (MMXU)
Function Range or value Accuracy
Frequency (0.95-1.05) fr 2.0 mHz
Voltage (0.1-1.5) Ur 0.5% of Ur at U Ur
0.5% of U at U > Ur
Connected current (0.2-4.0) Ir 0.5% of Ir at I Ir
0.5% of I at I > Ir
Active power, P 0.1 x Ur < U < 1.5 x Ur 1.0% of Sr at S Sr
0.2 x Ir < I < 4.0 x Ir 1.0% of S at S > Sr
Reactive power, Q 0.1 x Ur < U < 1.5 x Ur 1.0% of Sr at S Sr
0.2 x Ir < I < 4.0 x Ir 1.0% of S at S > Sr
Apparent power, S 0.1 x Ur < U < 1.5 x Ur 1.0% of Sr at S Sr
0.2 x Ir < I < 4.0 x Ir 1.0% of S at S > Sr
Power factor, cos () 0.1 x Ur < U < 1.5 x Ur 0.02
0.2 x Ir < I < 4.0 x Ir

Table 51: Supervision of mA input signals (MVGGIO)


Function Range or value Accuracy
mA measuring function 5, 10, 20 mA 0.1 % of set value 0.005 mA
0-5, 0-10, 0-20, 4-20 mA
Max current of transducer to input (-20.00 to +20.00) mA
Min current of transducer to input (-20.00 to +20.00) mA
Alarm level for input (-20.00 to +20.00) mA
Warning level for input (-20.00 to +20.00) mA
Alarm hysteresis for input (0.0-20.0) mA

Table 52: Event counter (GGIO)


Function Range or value Accuracy
Counter value 0-10000 -
Max. count up speed 10 pulses/s -

Table 53: Disturbance report (RDRE)


Function Range or value Accuracy
Pre-fault time (0.050.30) s -
Post-fault time (0.15.0) s -
Limit time (0.56.0) s -
Maximum number of recordings 100 -
Time tagging resolution 1 ms See Table 69: "Time synchronization,
time tagging".
Maximum number of analog inputs 30 + 10 (external + internally derived) -
Maximum number of binary inputs 96 -
Maximum number of phasors in the Trip 30 -
Value recorder per recording
Maximum number of indications in a 96 -
disturbance report
Maximum number of events in the 150 -
Event recording per recording
Maximum number of events in the 1000, first in - first out -
Event list
Maximum total recording time (3.4 s 340 seconds (100 recordings) at 50 Hz, -
recording time and maximum number of 280 seconds (80 recordings) at 60 Hz
channels, typical value)
Sampling rate 1 kHz at 50 Hz -
1.2 kHz at 60 Hz
Recording bandwidth (5-300) Hz -
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 34

Table 54: Fault locator (RFLO)


Function Value or range Accuracy
Reactive and resistive reach (0.001-1500.000) /phase 2.0% static accuracy
2.0% degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Phase selection According to input signals -
Maximum number of fault locations 100 -

Metering
Table 55: Pulse counter logic (GGIO)
Function Setting range Accuracy
Input frequency See Binary Input Module (BIM) -
Cycle time for report of counter value (03600) s -

Station communication
Table 56: IEC 61850-8-1 communication protocol
Function Value
Protocol IEC 61850-8-1
Communication speed for the IEDs 100BASE-FX

Table 57: LON communication protocol


Function Value
Protocol LON
Communication speed 1.25 Mbit/s

Table 58: SPA communication protocol


Function Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
Slave number 1 to 899

Table 59: IEC 60870-5-103 communication protocol


Function Value
Protocol IEC 60870-5-103
Communication speed 9600, 19200 Bd

Table 60: SLM LON port


Quantity Range or value
Optical connector Glass fibre: type ST
Plastic fibre: type HFBR snap-in
Fibre, optical budget Glass fibre: 11 dB (1000 m typically *)
Plastic fibre: 7 dB (10 m typically *)
Fibre diameter Glass fibre: 62.5/125 m
Plastic fibre: 1 mm
*) depending on optical budget calculation

Table 61: SLM SPA/IEC 60870-5-103 port


Quantity Range or value
Optical connector Glass fibre: type ST
Plastic fibre: type HFBR snap-in
Fibre, optical budget Glass fibre: 11 dB (1000 m typically *)
Plastic fibre: 7 dB (25 m typically *)
Fibre diameter Glass fibre: 62.5/125 m
Plastic fibre: 1 mm
*) depending on optical budget calculation
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 35

Remote communication
Table 62: Line data communication module (LDCM)
Quantity Range or value
Type of fibre Graded-index multimode 62.5/125 m or 50/125 m
Wave length 820 nm
Optical budget
Graded-index multimode 62.5/125 m 13 dB (typical distance 3 km *)
Graded-index multimode 50/125 m 9 dB (typical distance 2 km *)
Optical connector Type ST
Protocol C37.94
Data transmission Synchronous
Transmission rate 64 kbit/s
Clock source Internal or derived from received signal
*) depending on optical budget calculation

Hardware
IED
Table 63: Case
Material Steel sheet
Front plate Steel sheet profile with cut-out for HMI
Surface treatment Aluzink preplated steel
Finish Light grey (RAL 7035)

Table 64: Water and dust protection level according to IEC 60529
Front IP40 (IP54 with sealing strip)
Rear, sides, top and bottom IP20

Table 65: Weight


Case size Weight
6U, 1/2 x 19 10 kg
6U, 3/4 x 19 15 kg
6U, 1/1 x 19 18 kg

Connection system
Table 66: CT and VT circuit connectors
Connector type Rated voltage and current Maximum conductor area
Terminal blocks of feed through type 250 V AC, 20 A 4 mm2

Table 67: Binary I/O connection system


Connector type Rated voltage Maximum conductor area
Screw compression type 250 V AC 2.5 mm2
2 1 mm2

Basic IED functions


Table 68: Self supervision with internal event list
Data Value
Recording manner Continuous, event controlled
List size 1000 events, first in-first out

Table 69: Time synchronization, time tagging


Function Value
Time tagging resolution, Events and Sampled Measurement 1 ms
Values
Time tagging error with synchronization once/min (minute 1.0 ms typically
pulse synchronization), Events and Sampled Measurement
Values
Time tagging error with SNTP synchronization, Sampled 1.0 ms typically
Measurement Values
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 36

Inverse characteristics
Table 70: Inverse time characteristics ANSI
Function Range or value Accuracy
Operate characteristic: k = 0.05-999 in steps of 0.01 -
unless otherwise stated

A
t = P + B k
( I 1)

Reset characteristic:

tr
t = k
(I 2
)
1

I = Imeasured/Iset
ANSI Extremely Inverse no 1 A=28.2, B=0.1217, P=2.0, ANSI/IEEE C37.112, class 5 + 30 ms
tr=29.1
ANSI Very inverse no 2 A=19.61, B=0.491, P=2.0,
tr=21.6
ANSI Normal Inverse no 3 A=0.0086, B=0.0185, P=0.02,
tr=0.46
ANSI Moderately Inverse no 4 A=0.0515, B=0.1140, P=0.02,
tr=4.85
ANSI Long Time Extremely Inverse no 6 A=64.07, B=0.250, P=2.0, tr=30
ANSI Long Time Very Inverse no 7 A=28.55, B=0.712, P=2.0,
tr=13.46
ANSI Long Time Inverse no 8 k=(0.01-1.20) in steps of 0.01
A=0.086, B=0.185, P=0.02,
tr=4.6

Table 71: Inverse time characteristics IEC


Function Range or value Accuracy
Operate characteristic: k = (0.05-1.10) in steps of 0.01 -

A
t = P k
( I 1)

I = Imeasured/Iset
Time delay to reset, IEC inverse time (0.000-60.000) s 0.5% of set time 10 ms
IEC Normal Inverse no 9 A=0.14, P=0.02 IEC 60255-3, class 5 + 40 ms
IEC Very inverse no 10 A=13.5, P=1.0
IEC Inverse no 11 A=0.14, P=0.02
IEC Extremely inverse no 12 A=80.0, P=2.0
IEC Short-time inverse no 13 A=0.05, P=0.04
IEC Long-time inverse no 14 A=120, P=1.0
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 37

Function Range or value Accuracy


Customer defined characteristic no 17 k=0.5-999 in steps of 0.1 IEC 60255, class 5 + 40 ms
Operate characteristic: A=(0.005-200.000) in steps of
0.001
B=(0.00-20.00) in steps of 0.01
A
= + B k
C=(0.1-10.0) in steps of 0.1
(I P C )
t
P=(0.005-3.000) in steps of
0.001
Reset characteristic: TR=(0.005-100.000) in steps of
0.001
CR=(0.1-10.0) in steps of 0.1
TR
t = k
(I )
PR=(0.005-3.000) in steps of
PR
CR 0.001

I = Imeasured/Iset
RI inverse characteristic no 18 k=(0.05-999) in steps of 0.01 IEC 60255-3, class 5 + 40 ms

1
t = k
0.236
0.339
I
I = Imeasured/Iset
Logarithmic inverse characteristic no 19 k=(0.05-1.10) in steps of 0.01 IEC 60255-3, class 5 + 40 ms


t = 5.8 1.35 In
I

k
I = Imeasured/Iset

Table 72: Inverse time characteristics for Two step undervoltage protection (PUVM, 27)
Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of 0.01 Class 5 +40 ms

k
t =
U < U

U<
U< = Uset
U = Umeasured
Type B curve: k = (0.05-1.10) in steps of 0.01

k 480
t = + 0.055
32 U < U 0.5
2.0


U <
U< = Uset
U = Umeasured
Programmable curve: k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of
0.001
B = (0.50-100.00) in steps of
kA
0.01
t = +D C = (0.0-1.0) in steps of 0.1
U < U
P

B C D = (0.000-60.000) in steps of
U < 0.001
U< = Uset P = (0.000-3.000) in steps of
U = Umeasured 0.001
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 38

Table 73: Inverse time characteristics for Two step overvoltage protection (POVM, 59)
Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of 0.01 Class 5 +40 ms

k
t =
U U >

U>
U> = Uset
U = Umeasured
Type B curve: k = (0.05-1.10) in steps of 0.01

k 480
t =
32 U U > 0.5
2.0

0.035
U >
Type C curve: k = (0.05-1.10) in steps of 0.01

k 480
t =
32 U U > 0.5
3.0

0.035
U >
Programmable curve: k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of
0.001
kA
t = +D B = (0.50-100.00) in steps of
B U U >
P 0.01
C C = (0.0-1.0) in steps of 0.1
U >
D = (0.000-60.000) in steps of
0.001
P = (0.000-3.000) in steps of
0.001
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 39

Table 74: Inverse time characteristics for Two step residual overvoltage protection (POVM, 59N)
Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of 0.01 Class 5 +40 ms

k
t =
U U >

U>
U> = Uset
U = Umeasured
Type B curve: k = (0.05-1.10) in steps of 0.01

k 480
t =
32 U U > 0.5
2.0

0.035
U >
Type C curve: k = (0.05-1.10) in steps of 0.01

k 480
t =
32 U U > 0.5
3.0

0.035
U >
Programmable curve: k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of
0.001
kA
t = +D B = (0.50-100.00) in steps of
B U U >
P 0.01
C C = (0.0-1.0) in steps of 0.1
U >
D = (0.000-60.000) in steps of
0.001
P = (0.000-3.000) in steps of
0.001
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 40

Ordering REL 670, Line distance protection IED


Guidelines
Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the function matrix for included software functions given in
each software option package. Please observe that the character length of the software option section varies depending on the included options.
Enter option codes in the shaded spaces to complete the ordering number. To obtain the complete ordering code, please combined code from sheet 1 and sheet
2, as given in the example below. 1 BIM and 1 BOM is basic. Order futher I/O as required.

Sheet 1 Sheet 2
REL 670* - - - - - - -

SOFTWARE Notes and Rules


Version number
Latest version XX
Version No 1.0
Configuration alternatives
Single Breaker, 3-Phase A31
Tripping
Single Breaker, 1Phase A32
Tripping
Multi Breaker, 3-Phase Trip- B31
ping
Multi Breaker, 1Phase Trip- B32
ping
CAP configuration
ABB standard configuration X00
Software options All fields in the ordering form do not need to be filled in
No Option X00
High impedance differential protection A02
Frequency protections E02
General current and voltage protection F01
Apparatus control 8 objects H07 Note: Only one Apparatus control can be ordered
Apparatus control 15 objects H08 H07 only for A31/A32, H08 only for B31/B32
Additional HMI language
No second HMI language X0
German A1
Russian A2
French A3
Spanish A4
Italian A5
Polish A6
Hungarian A7
Czech A8
Swedish A9
Casing
1/2 19 case A
3/4 19 case 2TRM slots C
1/1 19 case 2TRM slots E
Mounting details with IP40 of protection from the front
19 rack mounting kit for 1/2 19 case or 2xRHGS6 or RHGS12 A
19 rack mounting kit for 3/4 19 case or 3xRHGS6 B
19 rack mounting kit for 1/1 19 case C
Wall mounting kit D
Flush mounting kit E
Flush mounting kit + IP54 mounting F
seal
Auxiliary power supply
24-60 VDC A
90-250 VDC B
Human machine interface
Small size - text only A
Medium size, 15 controllable objects B
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 41

Sheet 1 (Enter option codes from sheet 1 in spaces below) Sheet 2


REL 670* - - - - - - - - - * A - -

Analog system (First module X401, second module X411)


First TRM, 6I+6U 1A, 100/220V A6
First TRM, 6I+6U 5A, 100/220V A7
No second TRM included X0
Second TRM, 9I+3U 1A, 100/220V A3
Second TRM, 9I+3U 5A, 100/220V A4
Second TRM 5I, 1A+4I 5A+3U, 100/220V A5
Second TRM, 6I+6U 1A, 100/220V A6
Second TRM, 6I+6U 5A, 100/220V A7

Binary input and output, mA and time synchronizating boards. Note! Basic 1 BIM and 1 BOM included.
Slot position (rear view) Note! Max 3 positins in 1/2 - - -

X101

X121

X131
X111
rack and 5 in 3/4 rack with 2

X31

X41

X51

X61

X71

X81

X91
TRM and 11 in 1/1 rack wiht 2
TRM (=grey fields)
1/2 Case with 1 TRM (A31/32)
3/4 Case with 2 TRM
1/1 Case with 2 TRM
No board in this slot X X X X X X X X X
Binary output module 24 output relays Note! Maximum 4 (BOM + MIM) A A A A A A A A A A
(BOM) boards
BIM 16 inputs, RL24-30 VDC B B B B B B B B B B
BIM 16 inputs, 48-60 VDC C C C C C C C C C C
BIM 16 inputs, 110-125 VDC D D D D D D D D D D
BIM 16 inputs, 220-250 VDC E E E E E E E E E E
BIMp 16 inputs, 24-30 VDC for pulse F F F F F F F F F
counting
BIMp 16 inputs, 48-60 VDC for pulse G G G G G G G G G
counting
BIMp 16 inputs, 110-125 VDC for pulse H H H H H H H H H
counting
BIMp 16 inputs, 220-250 VDC for pulse K K K K K K K K K
counting
IOM 8 inputs, 10+2 output, 24-30 VDC L L L L L L L L L
IOM 8 inputs, 10+2 output, 48-60 VDC M M M M M M M M M
IOM 8 inputs, 10+2 output, 110-125 VDC N N N N N N N N N
IOM 8 inputs, 10+2 output, RL220-250 P P P P P P P P P
VDC
mA input module MIM 6 channels Note! Max 4 (BOM + MIM) board in R R R R R R R R
1/1 case. Max 1 MIM + 3 BOM in
3/4 case. No MIM board in 1/2 case
Serial communication unit for remote end communication
X312

Slot position (rear view)

No remote communication board included X


C37.94 single channel 3 km A
Serial communication unit for station communication
X301

X311

Slot position (rear view)

No first communication board included X


No second communication board included X
Serial SPA/IEC 60870-5-103 and LON com- A
munication module (plastic)
Serial SPA /IEC 60870-5-103 (plastic) and B
LON (glass) communication module
Serial SPA/IEC 60870-5-103 and LON com- C
munication module (glass)
Optical ethernet module, 1 channel glass D
Optical ethernet module, 2 channel glass E

Example:
REL 670*1.0-A31-A02E02F01-X0-A-A-B-A-A7X0-DAX-X-XD
Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 42

Accessories
Interface converter (for remote end data communication)
1 2
External interface converter from C37.94 to G703 including 1U 19
rack mounting accessories Quantity: 1MRK 002 245-AA

Test switch Single breaker/Single or Three Phase trip with


The test system COMBITEST intended for use external neutral on current circuits (ordering num-
with the IED670 products is described in 1MRK ber RK926 315-AC).
512 001-BEN and 1MRK 001024-CA. Please refer
to the website www.abb.com/substationautomation Multi-breaker/Single or Three Phase trip with
and ABB Product Guide > High Voltage Products internal neutral on current circuits (ordering num-
> Protection and Control > Modular Relay > Test ber RK926 315-BE).
Equipment for detailed information
Multi-breaker/Single or Three Phase trip with
Due to the high flexibility of our product and the external neutral on current circuit (ordering num-
wide variety of applications possible the test ber RK926 315-BV).
switches needs to be selected for each specific
application. The normally open "In test mode" contact 29-30
on the RTXP test switches should be connected to
Select your suitable test switch base on the avail- the input of the test function block to allow activa-
able contacts arrangements shown in the reference tion of functions individually during testing.
documentation.
Test switches type RTXP 24 are ordered sepa-
However our proposal for suitable variants are; rately. Please refer to Section "Related documents"
for reference to corresponding documents.
Single breaker/Single or Three Phase trip with
internal neutral on current circuits (ordering num- RHGS 6 Case or RHGS 12 Case with mounted
ber RK926 315-AK). RTXP 24 and the on/off switch for dc-supply are
ordered separately. Please refer to Section "Related
documents" for reference to corresponding docu-
ments.

Mounting details
19 rack mounting kit for one test switch

Quantity: 1MRK 002 420-BE


19 rack mounting kit for two test switches

Quantity: 1MRK 002 420-BB


19 rack mounting kit for three test switches

Quantity: 1MRK 002 420-BA

Protection cover
Protective cover for rear side of RHGS6, 6U, 1/4 x 19

Quantity: 1MRK 002 420-AE


Protective cover for rear side of IED, 6U, 1/2 x 19

Quantity: 1MRK 002 420-AC


Protective cover for rear side of IED, 6U, 3/4 x 19

Quantity: 1MRK 002 420-AB


Protective cover for rear side of IED, 6U, 1/1 x 19

Quantity: 1MRK 002 420-AA


Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 43

High impedance resistor unit 1-ph with resistor and voltage dependent
1 2 3
resistor 20-100V
Quantity: RK795101-MA
High impedance resistor unit 3-ph with resistor and voltage dependent
resistor 20-100V Quantity: RK795101-MB
High impedance resistor unit 1-ph with resistor and voltage dependent
1 2 3
resistor 100-400V
Quantity: RK795101-CB
High impedance resistor unit 3-ph with resistor and voltage dependent
resistor 100-400V Quantity: RK795101-DC

Combiflex
Key switch for lock-out of settings via LCD-HMI

Quantity: 1MRK 000 611-A


Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.

Side-by-side mounting kit

Quantity: 1MRK 002 420-Z

Configuration and monitoring tools


Front connection cable between LCD-HMI and PC

Quantity: 1MRK 001 665-CA

LED Label special paper A4, 1 pc

Quantity: 1MRK 002 038-CA


LED Label special paper Letter, 1 pc

Quantity: 1MRK 002 038-DA

Protection and control IED manager PCM 600


PCM 600 ver. 1.1, IED Manager

Quantity: 1MRK 003 395-AA


PCM 600 ver. 1.1, Engineering, IED Manager + CAP 531

Quantity: 1MRK 003 395-BA


PCM 600 ver. 1.1, Engineering Pro, IED Manager + CAP 531 + CCT
for IEC 61850-8-1 configuration of IED
Quantity: 1MRK 003 395-CA

Manuals
Note: One (1) IED Connect CD containing user documentation (Operators manual, Technical reference manual, Installa-
tion and commissioning manual, Application manual and Getting started guide), Connectivity packages and LED label tem-
plate is always included for each IED.

Rule: Specify additional quantity of IED Connect CD requested

Quantity: 1MRK 002 290-AA

Rule: Specify the number of printed manuals requested


Operators manual

Quantity: 1MRK 505 233-UEN


Technical reference manual

Quantity: 1MRK 506 232-UEN


Line distance protection IED REL 670 Buyer's Guide
Pre-configured
1MRK 506 264-BEN
Revision: G, Page 44

Installation and commissioning manual

Quantity: 1MRK 506 234-UEN


Application manual

Quantity: 1MRK 505 235-UEN


Engineering guide IED 670 products

Quantity: 1MRK 511 179-UEN

Reference information
For our reference and statistics we would be pleased to be provided with the following application data:

Country: End user:

Station name: Voltage level: kV

Related documents
Documents related to REL 670 Identity number
Operators manual 1MRK 505 233-UEN
Installation and commissioning manual 1MRK 506 234-UEN
Technical reference manual 1MRK 506 232-UEN
Application manual 1MRK 505 235-UEN
Buyers guide 1MRK 506 264-BEN
Connection diagram, Single breaker arr. Three phase tripping arr. 1MRK 002 801-BA
Connection diagram, Single breaker arr. Single phase tripping arr. 1MRK 002 801-CA
Connection diagram, Multi breaker arr. Three phase tripping arr. 1MRK 002 801-DA
Connection diagram, Multi breaker arr. Single phase tripping arr. 1MRK 002 801-EA
Configuration diagram A, Single breaker with single or double busbar 1MRK 004 500-86
Configuration diagram B, Single breaker with single or double busbar 1MRK 004 500-87
Configuration diagram C, Multi breaker such as 1 1/2 or ring busbar arr. 1MRK 004 500-88
Configuration diagram D, Multi breaker such as 1 1/2 or ring busbar arr. 1MRK 004 500-89
Setting example 1, 400 kV Long overhead power line with 1 1/2 CB arr. 1MRK 506 267-WEN
Setting example 2, 230 kV Extremely long overhead power line, double bus, single CB arr. 1MRK 506 268-WEN
Setting example 3, 132 kV Short overhead power line, double bus, single CB arr. 1MRK 506 269-WEN

Connection and Installation components 1MRK 013 003-BEN


Test system, COMBITEST 1MRK 512 001-BEN
Accessories for IED 670 1MRK 514 012-BEN
Getting started guide IED 670 1MRK 500 065-UEN
SPA and LON signal list for IED 670 1MRK 500 075-WEN
IEC 61850 Data objects list for IED 670 1MRK 500 077-WEN
Generic IEC 61850 IED Connectivity package 1KHA001027UEN
Protection and Control IED Manager PCM 600 Installation sheet 1MRS755552
Engineering guide IED 670 products 1MRK 511 179UEN

Latest versions of the described documentation can be found on www.abb.com/substationautomation

Manufacturer
ABB Power Technologies AB
Substation Automation Products
SE-721 59 Vsters
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
Internet: www.abb.com/substationautomation

You might also like