You are on page 1of 4

APPLICATION otes

N
Published for the Basler Electric Power Systems Group #125 August 1997

Synchronous motor controller prevents pole slip and


saves costs when operating brushless synchronous motors
Many brushless synchronous motors use a fixed dc transients, as
power supply for excitation, a low cost solution that well as provide
works reasonably well if motor loads and the power a reliable
supply voltage remain relatively constant. If motor load means for
varies widely, or if the power supply voltage is subject controlling the
to significant drops, such as those that occur when Var output or
other nearby motors are started, a constant excitation power factor of
source may be unable to maintain the motor in syn- the motor
chronism, resulting in pole slip and asynchronous during normal
operation. Pole slip events can seriously damage operation.
components of the motors brushless excitation system,
and asynchronous operation can quickly cause motors Var operation
to overheat. versus power
During pole slip events, large currents are induced factor control
in the field flow in opposition to the normal direction The use of
of excitation current, which creates voltage transients Var mode Figure 1: Synchronous Motor
that may exceed the peak inverse voltage rating of the versus power
power semiconductors on the rotating rectifier. If the factor operation is application dependent. For constant
semiconductors fail, the remaining semiconductors in loads, power factor operation is the preferred operating
the circuit must operate under overload conditions mode of the synchronous motor. Likewise for applica-
until the rotating bridge can be repaired. tions such as ball mill grinders or chipper motors, Var
Using a fixed source of excitation also eliminates control may be the favored control. The nature of these
the possibility of using the motors to provide local Var loads is cyclic, which produces momentary power load
support or to assist in controlling power factor on the surges in the system. Here, if the system operates in
supply bus. Poor power factor can cause excessive power factor mode, the power surges will be sensed and
loading on transformers and cabling and usually results cause the excitation system to produce cyclic surges of
in higher than necessary power bills. Proper operation field power in response to the load. This will result in
of synchronous machines can provide significant the power factor meter appearing unstable in response
savings in power cost for a relatively small investment to the nature of the load. For these applications, Var
in improved motor controls. (See Figure 3.) control provides the best solution . Here, the power
Both of these potential problems can be addressed component is not sensed by the controller, so the
by replacing fixed dc motor exciters with excitation system provides smooth, stable operation for the motor.
control systems that automatically maintain adequate
excitation to the motor to prevent pole slip during load
or power supply transients, while providing a means to
Motor protection
optimize Var production by the motor during normal The controller includes field over and under
operation. current and motor pullout protection and an adjustable
incomplete sequence timer that can be used to initiate
motor loading when the motor has been successfully
Basler synchronous motor controller synchronized.
The brushless synchronous motor control system The field current relay monitors excessive or
shown in Figure 2 provides the required automatic insufficient field current that can be caused by motor
control for brushless motors. The MVC (manual overload or too low a level of excitation current caused
voltage control) provides a reliable source of field by component failure or improper adjustment. (See
current interface with the SCP 250 Var/PF controller to Figure 4.)
provide the means to automatically respond to voltage
Notes:
1 Item not supplied by Basler.

Figure 2: Brushless Synchronous Motor Control Excitation System

Operation the Var/PF controller is enabled and will maintain either


The excitation system (See Figure 2.) is enabled via constant Vars or constant power factor.
the remote start/stop contact, which is generally closed S1 is used to calibrate the manual control to inter-
when the main motor breaker closes. Once enabled, the face with the Var/PF controller.
K1 on/off relay closes and applies power to the manual If excitation is not applied within time defined by
voltage control input. The manual control receives an K2 (incomplete sequence timer) while the motor is
input from the Var/PF controller to automatically adjust being started, an alarm output will provide annuncia-
field excitation to the motor. Placing the S2 switch in tion that the unit has not synchronized. Protective relays
the manual position provides constant field excitation, that include under and over field current monitor the
without automatic control. When placed in Var position, motor field current level and motor pullout. They are
used to determine if the machine is operating within loads. A power measuring energy management system
the acceptable limits of the design. Contacts for these can automatically vary the amount of Var flow via the
relays are wired out to a single alarm output. synchronous motor controller to optimize the plants
energy usage and reduce Var cost.
External Monitoring of
Brushless Exciter Diodes Applicable to dc Exciters
An optional exciter diode monitor can be added to Although most of the information described relates
the system to monitor the output of the brushless to the brushless exciter, the synchronous motor control-
exciter. The EDM200 is mounted in a location that is ler may also be used for dc exciters. Here, the brushless
external from the synchronous motor controller, and exciter is replaced with a dc exciter rotating having
monitors the field current for changes in ripple fre- commutators and brushes. The dc field breaker and
quency. When a diode failure occurs, the ripple fre- starting resistor (not shown) is used for starting the
quency will decrease, providing a unit alarm. synchronous motor. Once the motor speed reaches
synchronous speed, the excitation is applied.
Remote Var Management In some applications, the dc exciter is replaced with
The synchronous motor controller can be inter- a static exciter. The power for the main field is derived
faced with an RA-70 Reference Adjuster and a 4-20 ma from power semiconductors rated for its main field
input. The 4-20 ma input can be used in conjunction requirements. All control is static via silicon control
with an energy management system to optimize Var rectifiers.
flow from the synchronous motor to reduce energy cost For more information, consult the Basler factory at
within a plant. Reduced Var consumption can be 618/654-2341 or visit our web site at http://
realized by overexciting the synchronous motor to www.basler.com.
correct for magnetizing losses caused by inductive

Type of Conditions Motor Synchronous Affect on Economics


Excitation System Field Excitation Motor Operation System

Fixed dc supply - Low Bus Under excitation Lagging - Increase Costs


voltage power factor KVA
- Excessive loading on
load on plant
motor transformer
- Reduce
system
voltage
- Potential
pole slip

Automatic controller Automatic Leading - Decrease Saves


power factor power factor KVA
correction loading of
plant
transformer
- Improves
voltage
stability of
Bus

Figure 3: Synchronous Motor Operation, Lagging versus Leading due to Abnormal Operating Conditions
Models Field Current Field Voltage Sensing Input Var Control Power Factor
Amp. Voltage Current Range Range

SMC-36 0-36 Amp 32 120 Vac 3-5 Amps 0-100% Var .55 to 1.0 Lead
63
SMC-7 0-7 Amp 125 Lead or Lag .55 to 1.0 Lag

Incomplete Sequence Motor Pullout Field Undercurrent Field Overcurrent


Adjustment Range Range Time Range Time Delay Range Time Delay
Time

0 - 30 seconds .95 - .8 .25 - 1.5 40-100% 0 100-120% .4-10


PF lag Seconds Seconds Seconds

Figure 4: Synchronous Motor Controller Data Sheet

ROUTE 143, BOX 269, HIGHLAND, ILLINOIS U.S.A. 62249 P.A.E. Les Pins, 67319 Wasselonne Cedex FRANCE
PHONE 618-654-2341 FAX 618-654-2351 PHONE (33-3-88) 87-1010 FAX (33-3-88) 87-0808
http://www.basler.com, info@basler.com

APNOTE125 (8/97)

You might also like