Moulded Case Circuit Breaker (MCCB)

1 Comprehensive range : 25A - 1600A in different frame sizes

2 Compact dimension - space economy

3 Identical front plate cut out - lends uniformity

4 Interchangeable line & load connection -Offers flexibility of mounting


Moulded Case Circuit Breaker (MCCB)

The STANDARD range of Moulded Case Circuit Breakers (MCCBs) circuit elements. They are designed for use in Switchboards, Control
are designed for circuit protection of low voltage distribution system. Panels, Combination Starters, in separate enclosures and meet the
They are suitable for application as main breakers and for protection requirements of lighting, distribution and power circuits.
of branch and feeder circuit & connected equipments / load.
Standard offers a comprehensive range of MCCBs employing world
These MCCBs provide overload and short circuit protection for all class technology and fully conform to the latest IS / IEC-60947-2.

Features

Comprehensive range : 25A - 1600A in different frame sizes. Suitable for use as Switch Disconnectors / Isolators.
Compact dimension - space economy. Trip Free Mechanism - The breaker trips internally in case of fault,
Identical front plate cut out - lends uniformity. even if the knob is in the ON position.
Interchangeable line & load connection -Offers flexibility of mounting. Mounting possible in vertical or horizontal position or 15 in
Adjustable / front accessible thermal and magnetic setting. (Thermal vertical plane.
setting for overload adjustable from 70% - 100% of the rated current Complete range of accessories. (Under Voltage Release, Shunt
& magnetic setting for short circuit adjustable 4-10 times / 5-10 times). Trip, Auxiliary Switches, Rotary Handles, Extended Terminals, Back
Available in Single pole, 3 pole and 4 pole with switched neutral Studs, Phase Barriers, Terminal Shrouds, Enclosures and Earth
version. Leakage Relay).

Electrical & mechanical life

Rated Current (A) Mechanical Life Electrical Life


In < 100 8500 1500
100 < In 315 7000 1000
315 < In 630 4000 1000
630 < In 800 2500 500

30
Moulded Case Circuit Breaker (MCCB)

Construction

The MCCB comprises of switching mechanism, contact system, arc The insulated enclosure with high withstand capacity against thermal
extinguishing device and tripping unit all contained in a compact and mechanical stresses.
Moulded Case and Cover. Protection against secondary fire hazards.
The insulating case and cover are made of high strength, heat resistant, Increased safety of operating personnel.
flame retardant resin bonded thermo setting material which provides:-
Interphase insulation of a high dielectric strength, making the MCCB
considerably compact and light weight.

Switching mechanism

Control mechanism

Overload & short circuit adjustment


Push to trip

Trip bar

Instantaneous trip release

Instantaneous trip release

31
Moulded Case Circuit Breaker (MCCB)

SKB-1 & 2

MCCB Adjustable Type - Three Pole MCCB Adjustable Type - Four Pole (wSN)
Cat No. Cat No.
Rating (Amps.) Rating (Amps.)
SKB-1 SKB-2 SKB-1 SKB-2
25 ISLAST0025 ISLANT0025 25 ISLASF0025 ISLANF0025
32 ISLAST0032 ISLANT0032 32 ISLASF0032 ISLANF0032
50 ISLAST0050 ISLANT0050 50 ISLASF0050 ISLANF0050
63 ISLAST0063 ISLANT0063 63 ISLASF0063 ISLANF0063
80 ISLAST0080 ISLANT0080 80 ISLASF0080 ISLANF0080
100 ISLAST0100 ISLANT0100 100 ISLASF0100 ISLANF0100
125 ISLAST0125 ISLANT0125 125 ISLASF0125 ISLANF0125
160 ISLAST0160 ISLANT0160 160 ISLASF0160 ISLANF0160
200 ISLAST0200 ISLANT0200 200 ISLASF0200 ISLANF0200
250 - ISLANT0250 250 - ISLANF0250

32
Moulded Case Circuit Breaker (MCCB)

Technical information - SKB1 & 2

Standard conformity : IEC 60947-2/IS:13947-2


Rated operational voltage : 500V AC
Rated Insulation Voltage : 750V AC
Type of release : Thermomagnetic
Utilisation Category : A
Rated frequency : 50/60 Hz
Ambient temp : 40oC (50oC on request)
Operating altitude : 2000 meters
Humidity : 0 - 90%
Rated impulse voltage : 8 KV

Frame SKB1 SKB2


No. of Poles 1P / 3P / 4PwSN 1P / 3P / 4PwSN
Standard current range / ratings (In) A 25-200* 25-250*
Thermal release setting (Adjustable) 70-100% of In 70-100% of In
Magnetic release setting for current rating :
25A - 63A 400A 400A
80A - 125A 800A 800A
160A - 250A 1600A 1600A
50A -125A AM Frame - -
160A -250A AM Frame - -
Rated short circuit making capacity (Peak) Icm KA 32 73.5 52.5
Rated ultimate short circuit breaking (160-200A) (25-125A) (25-250A)
capacity (Icu), KA 240V 25 50 40
(at different voltages) 415V 16 35 25
440V 16 35 25
500V 12 25 18
Ics = % Icu 100% 75% 75%
Weight SP (Single Pole) Kg 0.7 0.7
TP (Triple Pole) Kg 1.8 1.8
FPwSN (Four Pole Switched Neutral) Kg 2.4 2.4
Terminal capacity (Cable) Sq.mm 70 (upto 100A)/150 (125A-250A)
(Bus bar width) mm 25 (125A-250A)
Recommended Torque Nm 10 10
Internal Accessories
Auxiliary Switch (1 C/O or 2C/O)
Shunt Trip
Under Voltage Release
Alarm Switch (1 C/O) Factory Fitted
External Accessories
Earth Fault Relay
Rotary Handle
Back Studs
Extended Terminals (above 63A) + +
Dolly Extension - -
Phase Barriers + +
Terminal Shrouds
Dolly pad locking Device
* Current Ratings - 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A, 160A, 200A, 250A 1P - Single Pole
Available, - Not Available, + Supplied alongwith the MCCB above 63A.. 3P - Three Pole
4PwSN - Four Pole with Switched Neutral

33
Moulded Case Circuit Breaker (MCCB)

Accessories - SKB-1 & 2

Shunt trip
Voltage Cat No.
100-110Vac ISLLSTD110
220-240Vac ISLLSTD240
380-415Vac ISLLSTD415

Under Voltage Release


Voltage Cat No.
100-110Vac ISLUVRD110
220-240Vac ISLUVRD240
380-415Vac ISLUVRD440

Auxiliary contact (250Vac/250Vdc)


Accessories Cat No.
1-Changeover ISLLASD1CO
2-Changeover ISLLASD2CO

Rotary handle
Accessories Cat No.
Direct Mounting ISLLRRHD30

Back studs
Accessories Cat No.
ISLLBSA250

Extended terminals Trip alarm contact


Accessories Cat No. Accessories Cat No.
125A 3 Pole ISLAX0062 Factory fitted ISLLALA1C0
4 Pole ISLAX0059
160A - 250A 3 Pole ISLAX0061
4 Pole ISLAX0050

34
Moulded Case Circuit Breaker (MCCB)

Time current characteristics - SKB-1 & 2

SKB1/2 Frame MCCB 25 to 63 Amp. SKB1/2 Frame MCCB 80 to 250 Amp.


10000 10000

25A

80A
32A

100A
1000 1000

A
125
50A

0A
16
100 63A 100

0A
20

0A
25
10 10

Time (seconds)
Time (seconds)

1 1

0.1 0.1

0.01 0.01

0 0
10 100 1000 100 1000
RMS current (A) RMS current (A)

Dimensional details (in mm)

Scale-1.5
45 45.5 45.5
46 17 8
100
35 35 136
35 35 35
135
112

154
112
92

92
25

35 70
29
35

105 140
Dia. 6.0 (4 Off) Mounting Holes Dia. 6.0 (4 Off) Mounting Holes 12.5
91
83 25 25 25 DIA 10.0 HOLES
3P 4PwSN
3P With Extended Terminals

35
Moulded Case Circuit Breaker (MCCB)

SKB-3 & 4

MCCB Adjustable Type - Three Pole MCCB Adjustable Type - Four Pole (wSN)
Cat No. Cat No.
Rating (Amps.) Rating (Amps.)
SKB-3 SKB-4 SKB-3 SKB-4
160 ISLCNT0160 ISLCHT0160 160 ISLCNF0160 ISLCHF0160
200 ISLCNT0200 ISLCHT0200 200 ISLCNF0200 ISLCHF0200
250 ISLCNT0250 ISLCHT0250 250 ISLCNF0250 ISLCHF0250
315 ISLCNT0315 ISLCHT0315 315 ISLCNF0315 ISLCHF0315
400 ISLCNT0400 ISLCHT0400 400 ISLCNF0400 ISLCHF0400
500 ISLCNT0500 ISLCHT0500 500 ISLCNF0500 ISLCHF0500
630 ISLCNT0630 ISLCHT0630 630 ISLCNF0630 ISLCHF0630
800 ISLCNT0800 ISLCHT0800 800 ISLCNF0800 ISLCHF0800

36
Moulded Case Circuit Breaker (MCCB)

Technical information - SKB 3 & 4

Standard conformity : IEC 60947-2/IS:13947-2


Rated operational voltage : 500V AC
Rated Insulation Voltage : 690V AC
Type of release : Thermomagnetic
Utilisation Category : A
Rated frequency : 50/60 Hz
Ambient temp : 40oC (50oC on request)
Operating altitude : 2000 meters
Humidity : 0 - 90%
Rated impulse voltage : 8 KV

Frame SKB 3 SKB 4

No. of Poles 3P/4PwSN 3P/4PwSN


Standard current ratings (In) A 160-800* 160-800*
Thermal release setting (Adjustable) 70-100% of In 70-100% of In
Magnetic release setting Adjustable Adjustable
160 - 315A 5-10 times In 5-10 times In
400 - 800A 4-10 times In 4-10 times In

Rated short circuit making capacity (Peak) Icm KA 73.5 105


Rated ultimate short circuit breaking
capacity(Icu), KA 240V 50 70
(at different voltages) 380V 35 50
415V 35 50
500V 25 35
Ics = % Icu 75% 50%
Weight TP (Triple Pole) Kg 9.2 9.2
FPwSN (Four Pole with Switched Neutral) Kg 11.6 11.6
Terminal capacity (Cable) Sq.mm - -
(Busbar width) mm 40 40

Internal Accessories
Auxiliary Switch (1 C/O or 2 C/O)
Shunt Trip
Under Voltage Release
Alarm Switch (1 C/O) # Factory Filled

External Accessories
Earth Fault Relay
Rotary Handle
Back Studs -
Extended Terminals +
Dolly Extension
Phase Barriers + -
Terminal Shrouds - -
Dolly pad locking Device

* Current Ratings - 160A, 200A, 250A, 315A, 400A, 500A, 630A, 800A, 1000A, 1250A, 1600A. 3P - Three Pole
Available, - Not Available, + Supplied alongwith the MCCB as standard. 4PwSN - Four Pole with Switched Neutral
** Terminals at Front
# Terminals at back / rear

37
Moulded Case Circuit Breaker (MCCB)

Accessories - SKB-3 & 4

Shunt trip
Voltage Cat No.
18-30Vac,
ISLLSTC030
12-36Vdc
100-110Vac ISLLSTC110
220-240Vac ISLLSTC240
380-415Vac ISLLSTC415

Under Voltage Release


Voltage Cat No.
100-110Vac ISLUVRC110
220-240Vac ISLUVRC240
380-415Vac ISLUVRC440

Auxiliary contact (250Vac/250Vdc)


Accessories Cat No.
1-Changeover ISLLASC1CO
2-Changeover ISLLASC2CO

Rotary handle
Accessories Cat No.
Direct Mounting ISLLRRHC30

Back studs
Accessories Cat No.
ISLLBSC###

Extended terminals Trip alarm contact


Accessories Cat No. Accessories Cat No.
3 Pole ISLCX0019 Factory fitted ISLLALC1C0
250A
4 Pole ISLCX0023
3 Pole ISLCX0020
315A - 500A
4 Pole ISLCX0025
3 Pole ISLCX0027
630A - 800A
4 Pole ISLCX0028

38
Moulded Case Circuit Breaker (MCCB)

Time current characteristics - SKB-3 & 4

SKB3/4 Frame MCCB 250 to 800 Amp.


10000

250A
A
1000
1

315

A
500
100

0A
80
10
Time (seconds)

0.1

0.01

0
100 1000 10000
RMS current (A)

Dimensional details (in mm) - SKB-3 & 4

B B B Scale-1.10
54.5 A A
206 17.5
70 70
24.5 8
100

58.9
257.2
232

92

375

40 30
70 70 208 40
70 52 102 160-400A, A=40, B=30
208
500-800A, A=20, B=50
Fixing Hole
3P 4PwSN 3P With Extended Terminals

39
Moulded Case Circuit Breaker (MCCB)

SKB 5, 6 & 7

MCCB Fixed Type - Single Pole MCCB Fixed Type - Three Pole
Cat No. Rating Cat No.
Rating (Amps.)
SKB-6 (Amps.) SKB-5 SKB-6 SKB-7
25 ISLGNS0025 25 ISLGST0025 ISLGNT0025 ISLGHT0025
32 ISLGNS0032 32 ISLGST0032 ISLGNT0032 ISLGHT0032
50 ISLGNS0050 50 ISLGST0050 ISLGNT0050 ISLGHT0050
63 ISLGNS0063 63 ISLGST0063 ISLGNT0063 ISLGHT0063
80 ISLGNS0080 80 ISLGST0080 ISLGNT0080 ISLGHT0080
100 ISLGNS0100 100 ISLGST0100 ISLGNT0100 ISLGHT0100
125 ISLGNS0125 125 ISLGST0125 ISLGNT0125 -

MCCB Fixed Type - Four Pole (wSN)


Cat No.
Rating (Amps.)
SKB-5 SKB-6 SKB-7
25 ISLGSF0025 ISLGNF0025 ISLGHF0025
32 ISLGSF0032 ISLGNF0032 ISLGHF0032
50 ISLGSF0050 ISLGNF0050 ISLGHF0050
63 ISLGSF0063 ISLGNF0063 ISLGHF0063
80 ISLGSF0080 ISLGNF0080 ISLGHF0080
100 ISLGSF0100 ISLGNF0100 ISLGHF0100
125 - - -

40
Moulded Case Circuit Breaker (MCCB)

Technical information - SKB 5, 6 & 7

Standard conformity : IEC 60947-2/IS:13947-2


Rated operational voltage : 500V AC
Rated Insulation Voltage : 750V AC
Type of release : Thermomagnetic
Utilisation Category : A
Rated frequency : 50/60 Hz
Ambient temp : 40oC (50oC on request)
Operating altitude : 2000 meters
Humidity : 0 - 90%
Rated impulse voltage : 8 KV

Frame SKB-5 SKB-6 SKB-7


No. of Poles 1P / 3P / 4PwSN 1P / 3P / 4PwSN 3P / 4PwSN
Standard current range / rating (In)A 16-160* 16-160* 16-160*
Thermal release setting Fixed Fixed Fixed
Magnetic release setting for current rating :
16A - 32A A 350 350 350
40A - 50A A 500 500 500
63A - 80A A 800 800 800
100A - 160A A 1000 1000 1000
Rated short circuit making capacity
(Peak) Icm at 415V AC KA 17 32 52.5
Rated ultimate short circuit breaking
capacity (Icu), KA 240V 16 25 40
(at different voltages) 415V 10 16 25
440V 10 14 16
500V 7.5 10 12
Ics = % Icu 100% 75% 50%
Weight SP Kg 0.35 0.35 0.35
TP Kg 0.93 0.93 0.93
4PwSN Kg 1.2 1.2 1.2
Terminal capacity (cable) Sq.mm 70 70 70
Bus bar (width) mm 10 10 10
Recommended Torque Nm 2.5 2.5 2.5
Internal Accessories
Auxiliary Switch (1 C/O or 2C/O)
Shunt Trip
Under Voltage Release
External Accessories
Earth Fault Relay
Rotary Handle
Back Studs - - -
Extended Terminals (above 63A) + + +
Dolly Extension - - -
Phase Barriers + + +
Terminal Shrouds
Dolly pad locking Device
* Current Ratings - 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A, 150A, 160A 1P - Single Pole
Available, - Not Available, + Supplied alongwith the MCCB as standard. 3P - Three Pole
D Available in single pole 4PwSN - Four Pole with Switched Neutral
Available in 3P & 4P

41
Moulded Case Circuit Breaker (MCCB)

Accessories - SKB-5, 6 & 7

Shunt trip
Voltage Cat No.
18-30Vac,
ISLLSTG030
12-36Vdc
100-110Vac ISLLSTG110
220-240Vac ISLLSTG240

Under Voltage Release


Voltage Cat No.
100-110Vac ISLUVRG110
220-240Vac ISLUVRG240
380-415Vac ISLUVRG440

Auxiliary contact (250Vac/250Vdc)


Accessories Cat No.
1-Changeover ISLLASG1CO
2-Changeover ISLLASG2CO

Rotary handle
Accessories Cat No.
Direct Mounting ISLGD000
Direct Mounting ISLGRN30

Extended terminals Trip alarm contact


Accessories Cat No. Accessories Cat No.
16A - 160A 3 Pole ISLGX0012 Factory fitted ISLLALA1C0
4 Pole ISLGX0046

42
Moulded Case Circuit Breaker (MCCB)

Time current characteristics - SKB-5, 6 & 7

SKB5/6/7 Frame MCCB 25 to 125 Amp.


10000

25A
32A

50A
1000

63A
A
80
100

0A
10

5A
12
10
Time (seconds)

0.1

0.01

0
10 100 1000
RMS current (A)

Dimensional details (in mm) - SKB-5, 6 & 7 (1 Pole)

11.4
70.5
12
78.6
120
44

74

11.2
20 33.5
77.5
26.25
83.5
96

43
Moulded Case Circuit Breaker (MCCB)

Dimensional details (in mm) - SKB-5, 6 & 7 (3 Pole)

38 38
26.25

26.25
Fixing hole
94

15
26.26 12.5

78.50 83.5 18 18 18

D1A 10.0 HOLES 26

3P 3P with Extended Terminal

Dimensional details, in mm - SKB-5, 6 & 7 (3 Pole)

104.50 83.50
26.25 26.25 26.25 77.50
71

ON
120.00
102.00
94.00

Four Pole with Switched Neutral


OFF

26.25 97.00 2 nos. mounting holes for m4 screws

44
Moulded Case Circuit Breaker (MCCB)

SKB-8 & 9

MCCB Fixed Type - Three Pole MCCB Fixed Type - Four Pole (wSN)
Cat No. Cat No.
Rating (Amps.) Rating (Amps.)
SKB-8 SKB-9 SKB-8 SKB-9
25 ISLFNT0025 ISLFHT0025 25 ISLFNF0025 ISLFHF0025
32 ISLFNT0032 ISLFHT0032 32 ISLFNF0032 ISLFHF0032
50 ISLFNT0050 ISLFHT0050 50 ISLFNF0050 ISLFHF0050
63 ISLFNT0063 ISLFHT0063 63 ISLFNF0063 ISLFHF0063
80 ISLFNT0080 ISLFHT0080 80 ISLFNF0080 ISLFHF0080
100 ISLFNT0100 ISLFHT0100 100 ISLFNF0100 ISLFHF0100
125 ISLFNT0125 ISLFHT0125 125 ISLFNF0125 ISLFHF0125
160 ISLFNT0160 ISLFHT0160 200 ISLFNF0200 ISLFHF0200
200 ISLFNT0200 ISLFHT0200 250 ISLFNF0250 ISLFHF0250
250 ISLFNT0250 ISLFHT0250

45
Moulded Case Circuit Breaker (MCCB)

Technical information - SKB 8 & 9

Standard conformity : IEC 60947-2/IS:13947-2


Rated operational voltage : 500V AC
Rated Insulation Voltage : 750V AC
Type of release : Thermomagnetic
Utilisation Category : A
Rated frequency : 50/60 Hz
Ambient temp : 40oC (50oC on request)
Operating altitude : 2000 meters
Humidity : 0 - 90%
Rated impulse voltage : 8 KV

Frame SKB 8 SKB 9


No. of Poles 3P / 4PwSN 3P / 4PwSN
Standard Current ratings (In) A 25-250* 25-250*
Thermal release setting Fixed Fixed
Magnetic release setting for current rating Fixed Fixed
25A - 32A 500A 500A
40A - 80A 800A 800A
100A - 125A 1250A 1250A
160A - 250A 1600A 1600A
Rated short circuit making capacity (Peak) Icm kA 73.5 105
Rated ultimate short circuit breaking
capacity(Icu), kA 240V 50 70
(at different voltages) 380V 35 50
415V 35 50
500V 25 35
Ics = % Icu 100% 100%
Weight TP (Triple Pole) / FPwSN Kg 2.9 / 3.8 2.9 / 3.8
Terminal Type M8 M8
Terminal capacity (Cable) Sq.mm 185 185
(Bus bar width) mm 18 18
Internal Accessories
Auxiliary Switch (1 C/O or 2C/O)
Shunt Trip
Under Voltage Release
Alarm Switch (1 C/O) # (Factory Fitted)
External Accessories
Earth Fault Relay
Rotary Handle
Back Studs
Extended Terminals (above 63A) + +
Dolly Extension - -
Phase Barriers + +
Terminal Shrouds (only in 3P MCCB)
Dolly pad locking Device
* Current Ratings - 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A, 160A, 200A, 250A 3P - Three Pole
Available, - Not Available, + Supplied alongwith the MCCB above 63A. 4PwSN - Four Pole with Switched Neutral
# Factory Fitted

46
Moulded Case Circuit Breaker (MCCB)

Accessories - SKB-8 & 9

Shunt trip
Voltage Cat No.
18-30Vac,
ISLLSTF030
12-36Vdc
100-110Vac ISLLSTF110
220-240Vac ISLLSTF240
380-415Vac ISLLSTF415

Under Voltage Release


Voltage Cat No.
100-110Vac ISLUVRF110
220-240Vac ISLUVRF240
380-415Vac ISLUVRF440

Auxiliary contact (250Vac/250Vdc)


Accessories Cat No.
1-Changeover ISLLASF1CO
2-Changeover ISLLASF2CO

Rotary handle
Accessories Cat No.
Direct Mounting ISLLRRHF30

Extended terminals Trip alarm contact


Accessories Cat No. Accessories Cat No.
3 Pole ISLFX0048 Factory fitted ISLLALF1C0
160A
4 Pole ISLFX0045
3 Pole ISLFX0049
200A - 250A
4 Pole ISLFX0046

47
Moulded Case Circuit Breaker (MCCB)

Time current characteristics - SKB-8 & 9

SKB8/9 Frame MCCB 25 to 250 Amp.


10000

1000

100
Time (seconds)

10

250A

200A
1
80A/125A/160A

63A/100A

0.1 32A/50A

25A

0.01
0.005
0 1 10 100
RMS current (A)

Dimensional details, in mm - SKB-8 & 9

30 TERMINAL HIGHT

SUITABLE FOR M8 SCREWS TERMINALS SUITABLE FOR 22mm


WIDE STRIP OR 185mm2 CABLE
55

4 HOLES FOR MS SCREWS


170 FIXING CTRS.

190 FIXING CTRS.

78.6

35 FIXING CTRS. 94
100
35 35
114
135
104.5

T hree P ole

F our P ole with S witc h Neutral

48
Moulded Case Circuit Breaker (MCCB)

SKB 10 & 11

Adjustable thermal (80-100%) & fixed magnetic setting Adjustable thermal & adjustable magnetic setting
Cat No. Cat No.
Rating (Amps.) Rating (Amps.)
Three pole Four pole (wSN) Three pole Four pole (wSN)
SKB 10 - Icu 36kA SKB 10 - Icu 36kA
250 ISLLSEBT0250 ISLLSEBF0250 250 ISLLSECT0250 ISLLSECF0250
315 ISLLSEBT0315 ISLLSEBF0315 315 ISLLSECT0315 ISLLSECF0315
400 ISLLSEBT0400 ISLLSEBF0400 400 ISLLSECT0400 ISLLSECF0400
500 ISLLSEBT0500 ISLLSEBF0500 500 ISLLSECT0500 ISLLSECF0500
630 ISLLSEBT0630 ISLLSEBF0630 630 ISLLSECT0630 ISLLSECF0630
SKB 11 - Icu 50kA SKB 11 - Icu 50kA
250 ISLLNFBT0250 ISLLNEBF0250 250 ISLLNFCT0250 ISLLNECF0250
315 ISLLNFBT0315 ISLLNEBF0315 315 ISLLNFCT0315 ISLLNECF0315
400 ISLLNFBT0400 ISLLNEBF0400 400 ISLLNFCT0400 ISLLNECF0400
500 ISLLNFBT0500 ISLLNEBF0500 500 ISLLNFCT0500 ISLLNECF0500
630 ISLLNFBT0630 ISLLNEBF0630 630 ISLLNFCT0630 ISLLNECF0630

49
Moulded Case Circuit Breaker (MCCB)

Technical information - SKB 10 & 11

Standard conformity : IEC 60947-2/IS:13947-2


Rated operational voltage : 415V AC
Rated Insulation Voltage : 750V AC
Type of release : Thermomagnetic
Utilisation Category : A
Rated frequency : 50/60 Hz
Ambient temp : 40oC (50oC on request)
Operating altitude : 2000 meters
Humidity : 0 - 90%
Rated impulse voltage : 8 KV

Frame SKB 10 SKB 11


No. of Poles 3P/4P 3P/4P
Standard Current Ratings (In) A 250, 315, 400, 500 250, 315, 400, 500

Thermal release setting (Adjustable) 80-100% In 80-100% In

Magnetic release setting for current rating

250A - 400A 4000A 4000A


500A - 500A 6300A 6300A

Trip Unit
Adjustable Thermal & fixed magnetic setting =
=
Adjustable Thermal & adjustable magnetic setting =
=

Rated S.C. Making Capacity at 415V (Icm) kA 75.6 105

Rated Ultimate S.C breaking capacity (Icu) at 240V kA 50 65


415V kA 36 50

Rated Service S.C Breaking Capacity at 415V Ics = % Icu % 100 75

Weight Kg 6/7 6/7


Terminal capacity (Max.) Sq. mm 1x240 (250A-400A) 1x240 (250A-400A)
2x185 (500A) 2x185 (500A)
Bus bar width mm 30 30
Overall dimension (W X H X D) 140x254x109 140x254x109

Internal Accessories #
Auxillary Switch 1C/O or 2C/O = =
Shunt Trip (bulit-in auxillary contact) = =
Under Voltage release = =
Alarm Switch = =

External Accessories
Rotary Handle - Extended = =
Extended Terminals = =
Dolly Extension = =
Phase Barriers = =
Dolly pad locking device = =
Earth Fault Relay = =

Available
# Only 2 accessories at a time can be fitted in the MCCB

50
Moulded Case Circuit Breaker (MCCB)

Accessories - SKB-10 & 11

Alarm switch
Voltage Cat No. Rating Configuration
240Vac ISLLB000 1A 1NO + NC

Shunt trip with Auxilary switch Under Voltage Release


Voltage Cat No. Voltage Cat No.
110Vac ISLLS110 110Vac ISLLU110
240Vac ISLLS240 240Vac ISLLU240
415Vac ISLLS415 415Vac ISLLU440

Note: Shunt Trip release is provided with built-in auxiliary contact Note: The breaker trips if the supply voltage dips below 70%- 35% of the
rated voltage.
The breaker cannot be switched ON unless there is a supply to the UVR.
(NVNC feature).
Suplied with external mounting Electronic Power pack to operate on AC
supplies.

Auxiliary switch
Voltage Cat No. Current rating Configuration
(AC12)
250Vac ISLLA1CO 4A 1NO + 1NC
250Vac ISLLA2CO 4A 2(1NO + 1NC)

Rotary handle Dolly pad lock


Accessories Cat No. Voltage Cat No.
With door interloack Dolly extension ISCPSMLLX009
and 300mm remote ISLLRN30 Dolly pad locking device ISLLP000
shaft

Extended terminal with phase barrier


Cat No.
Extended terminals (250A - 400A) ISSLX0013
Extended terminals (500A - 630A) ISSLX0014
Phase barriers ISSLLX0004

51
Moulded Case Circuit Breaker (MCCB)

Time current characteristics - SKB-10 & 11, Three Pole

Mounting

Time current characteristics - SKB-10 & 11, Four Pole

40 18.75 58.75 58.75


15
35
75.7
102.5

254
354

43.75 43.75 43.75


186

52
Code logic

1 2 3 4 5 6 7 8 9 10 11 12

I H L L S E B T 0 2 5 0

Product ID Frame Ics = % of Icu Icu Type of Release No. of poles Breaker current Rating (A) = 250

3 rd Digit 5 th Digit 7 th Digit 9-12 th Digit


Product ID Thermal Magnetic / Electronic Breaker current Rating
Designation Ics as % versions
of Icu (A)
Thermal Adjustable
SKB 10 MCCBs B

53
S 100% Magnetic Fixed 0250 250A

N 75% 0315 315A


4 th Digit
H 50% 0400 400A
Frame
0500 500A
SKB 10
0630 630A
6 th Digit 8 th Digit
Icu Designation No. of poles
E 36kA T Three Pole
F 50kA

Example
Industrial MCCB SKB 10 Frame with Ics as
ISLLSEBT0250 100% Icu, Icu = 36KA, Release Type: Thermal
Adjustable, Magnetic Fixed, 3-Pole, 250A Current Rating
Moulded Case Circuit Breaker (MCCB)
Moulded Case Circuit Breaker (MCCB)

SKB-0

MCCB Adjustable Type - Three Pole MCCB Adjustable Type - Four Pole (wSN)
Rating (Amps.) SKB-0 Rating (Amps.) SKB-0
1000 ISLDNT1000 1000 ISLDNF1000
1250 ISLDNT1250 1250 ISLDNF1250
1600 ISLDNT1600 1600

54
Moulded Case Circuit Breaker (MCCB)

Technical information - SKB 0

Standard conformity : IEC 60947-2/IS:13947-2


Rated operational voltage : 500V AC
Rated Insulation Voltage : 690V AC
Type of release : Thermomagnetic
Utilisation Category : A
Rated frequency : 50/60 Hz
Ambient temp : 40oC (50oC on request)
Operating altitude : 2000 meters
Humidity : 0 - 90%
Rated impulse voltage : 8 KV

Frame SKB 0

No. of Poles 3P/4PwSN


Standard current ratings (In) A 1000-1600*
Thermal release setting (Adjustable) 70-100% of In
Magnetic release setting Adjustable
800 - 1600A 4000-10,000A
Rated short circuit making capacity (Peak) Icm KA 105
Rated ultimate short circuit breaking
capacity(Icu), KA 240V 70
(at different voltages) 380V 50
415V 50
500V 35
Ics = % Icu 75%
Weight TP (Triple Pole) Kg 17#/19**
FPwSN (Four Pole with Switched Neutral) Kg 22/25
Terminal capacity (Cable) Sq.mm -
(Busbar width) mm 45** upto 1000A
60** upto 1250A
65** upto 1600A
35.5# upto 1600A
Internal Accessories
Auxiliary Switch (1 C/O or 2 C/O)
Shunt Trip
Under Voltage Release
Alarm Switch (1 C/O) # Factory Filled
External Accessories
Earth Fault Relay
Rotary Handle
Back Studs
Extended Terminals
Dolly Extension
Phase Barriers
Terminal Shrouds -
Dolly pad locking Device

* Current Ratings - 160A, 200A, 250A, 315A, 400A, 500A, 630A, 800A, 1000A, 1250A, 1600A. 3P - Three Pole
Available, - Not Available, + Supplied alongwith the MCCB as standard. 4PwSN - Four Pole with Switched Neutral
** Terminals at Front
# Terminals at back / rear

55
Moulded Case Circuit Breaker (MCCB)

Accessories - SKB-0

Shunt trip
Voltage Cat No.
100-110Vac ISLLSTD110
220-240Vac ISLLSTD240
380-415Vac ISLLSTD415

Under Voltage Release


Voltage Cat No.
100-110Vac ISLUVRD110
220-240Vac ISLUVRD240
380-415Vac ISLUVRD440

Auxiliary contact (250Vac/250Vdc)


Accessories Cat No.
1-Changeover ISLLASD1CO
2-Changeover ISLLASD2CO

Rotary handle
Accessories Cat No.
Direct Mounting ISLLRRHD30

56
Moulded Case Circuit Breaker (MCCB)

Dimensional details (in mm) - SKB-0 (3 Pole)

57
Moulded Case Circuit Breaker (MCCB)

Dimensional details (in mm) - SKB-0 (4 Pole with switched neutral)

S. No. Rating A B T
1. 800A 70 45 6x2
2. 1000A 70 45 15
3. 1250A 82 60 15
4. 1600A 87 65 18

Time current characteristics - SKB-0

SKB 0 Frame MCCB 800 to 1600 Amp.


10000
800A

1000
0A
100

A
50
12
0A
100
0
16

10
Time (seconds)

0.1

0.01

0
1000 10000
RMS current (A)

58
Moulded Case Circuit Breaker (MCCB)

Earth fault relay

The earth fault detection system for use with STANDARD MCCBs
comprises of a core balance transformer (CT) coupled to an advanced
RCD relay. The relay may be used to trip a circuit breaker via a shunt
trip or an under voltage release in the event of an Earth Fault.
The relay and one of the four available CTs is all that is required for a
complete earth fault sensing system suitable for the control of a circuit
breaker in a circuit upto 800A fitted with either a shunt trip or an under
voltage release. The simple arrangement and a small number of inter-
connection necessary ensure that EFR is easily selected and installed.
The relay is suitable for 220-240V AC supply with the flexibility of
choosing the sensitivity between 300mA to 2A and time delay should
be selected by the DIP switches provided on the facia of the relay.

Features
No nuisance tripping
DIN rail mounting
Adjustable time delay
Choice of sensitivity from 300mA upto 2A
Trip indication LED(Red)
ON indication LED(Green)
Test push button
Reset push button

Other external accessories


Dolly Pad locking device
Phase Barriers
Back Studs
Extended terminals
Dolly Extension

59
Moulded Case Circuit Breaker (MCCB)

Technical data

Supply Voltage : 220V / 240V AC, 50 / 60Hz


Changeover contact : 5A-15A 240V AC
Sensitivity : 300mA, 500mA, 1A, 2A
Time delay (m.sec.) : 200, 500, 1000, 5000
The earth fault relay is supplied with the CT based on the current
rating. To operate the EFR a shunt trip or an under voltage release is
necessary which has to be ordered separately.

Coil Voltage Cat No.


25-100 ISEF1100
125-200 ISEF2200
250-400 ISEF3400
500-800 ISEF4800

Dimensional details (in mm) - Core balance current transformer

Size MCCB Current Rating Internal Dimension Shape


1 25-100A 60mm Circular
2 125-200A 95mm Circular
3 250-400A 145mm Circular
4 500-800A 300 x 80 mm Rectangular
5 1000-1600A On Request Rectangular

60
Moulded Case Circuit Breaker (MCCB)

General purpose enclosure

Enclosures made of special grade CRCA steel are available for housing SKB-1 to SKB-9 Frame MCCBs upto 800A. They are manufactured with
latest technology using CNC Punch and Brake presses to attain highest degree of perfection. The enclosures are painted with latest techniques
in powder coating using epoxy polyester and polyester resin based powder paints to ensure smooth, scratch resistant surface coatings. They
are suitable for wall mounting & adequate knockouts are provided for cable entry.

Description Cat. No.


SKB-5/6/7 Frame SP ISEGSP
SKB-5/6/7 Frame TP ISEGTP
SKB-5/6/7 Frame FP ISEGFP
SKB-1/2 Frame SP ISEASP
SKB-1/2 Frame TP ISEATP
SKB-1/2 Frame FP ISEAFP
SKB-8/9 Frame TP ISEFTP
SKB-8/9 Frame FP ISEFFP
SKB-3/4 Frame TP (400A) ISECTP
SKB-3/4 Frame FP (400A) ISECFP
SKB-3/4 Frame TP (800A) ISECTP
SKB-3/4 Frame FP (800A) ISECFP

Dimensional details (in mm)

Description W D h H AxB
SKB-5/6/7 Frame 190 81 300 310 160x360
SKB-1/2 Frame 260 108 560 570 160x480
SKB-8/9 Frame 260 122 560 570 160x480
SKB-3/4 Frame 440 122 960 975 280x802
upto 400 A
SKB-3/4 Frame 540 122 960 975 380x802
upto 800 A

h H
B

A D

61
Moulded Case Circuit Breaker (MCCB)

Ambient temperature compensation chart (SKB 1/2, SKB 3/4, SKB 5/6)
Compensation factor (% of current rating, i)

40C Ref SKB 0


40C Ref SKB 1/2
40C Ref SKB 8/9
40C Ref SKB 3/4
40C Ref SKB 5/6/7

Ambient tempera ture (C)

Ambient temperature compensation chart (SKB 1/2, SKB 3/4, SKB 5/6)

IS:13703 HBC Fuse - Upstream Device

Product Rating KA @ Current Rating of HBC Fuses


(A) 415V 80 100 125 160 200 250 315 400 500 630 800
SKB 1/2 25 25 1200 1400 1800 2400 3200 4500 5500 8000 12000 14000 23000
STANDARD MCCB DO WNSTREAM DEVICE (LOW SET)

32 25 1200 1400 1800 2400 3200 4500 5500 8000 12000 14000 23000
40 25 350 1400 1800 2400 3200 4500 5500 8000 12000 14000 23000
50 25 300 1400 1800 2400 3200 4500 5500 8000 12000 14000 23000
63 25 250 1400 1800 2400 3200 4500 5500 8000 12000 14000 23000
80 25 300 450 2400 3200 4500 5500 8000 12000 14000 23000
100 25 400 650 3200 4500 5500 8000 12000 14000 23000
125 25 550 3200 4500 5500 8000 12000 14000 23000
160 25 650 1300 5500 8000 12000 14000 23000
200 25 1200 1300 8000 12000 14000 23000
SKB 3/4 250 50 1000 8000 12000 14000 23000
315 50 2000 12000 14000 23000
400 50 2500 14000 23000
500 50 3500 23000
630 50 5500
SKB 0 800 50 6000

The above table gives fault currents in amperes till which level the downstream breakers shall act prior to the upstream fuse.

62
Moulded Case Circuit Breaker (MCCB)

Discrimination data standard MCCB upstream device instantaneous trip set at high

Product Rating kA@ SKB 1/2 SKB 3/4 SKB 0

(A) 415V 25 23 40 50 63 80 100 125 106 ALL 250 315 400 500 630 800 600 800 1000 1250 1600

SKB 1/2 63 25 800 800 800 1600 1600 2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200

80 25 1600 1600 2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200

100 25 1600 1600 2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200

SKB 3/4 125 25 1600 1600 2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200

160 25 2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200

200 25 2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200

315 50 4000 5000 6300 8000 7400 8300 9200 9200 9200

400 50 5000 6300 8000 7400 8300 9200 9200 9200

500 50 6300 8000 7400 8300 9200 9200 9200

630 50 8000 7400 8300 9200 9200 9200

800 50 7400 8300 9200 9200 9200

SKB 0 1000 50 9200 9200 9200

1250 50 9200 9200


1600 50 9200

The above table gives fault current in amperes till which level the downstream breakers shall act prior to the upstream breaker

Selection & application

Transformer Protection kVA 1000


Ie = Amps
Primary side
3 Ue
For the protection of transformer with a circuit breaker connected to the Ue is the Rated Voltage at the LT side
primary side (LT primary) the no load inrush current of the transformer
must be considered. The peak value of the first current wave often
reaches 10-15 times the rated current and may sometimes reach as The Breaking capacity of the breaker for protection can be calculated as :
high as 20-25 times. However, the transient decays very quickly (in a
few m.sec.). Thus the MCCB selected should have a magnetic setting Ie
which will not be actuated by the momentary inrush current. Ib = 10 3 Kiloamperes
Z%
Secondary side
Where Ib is the rated breaking capacity,
STANDARD MCCBs can be used for protection of transformer on the
LT side (secondary side) as an outgoing protective device. Ie the rated current

The rated current of the transformer is calculated as follows : Z% is the percentage impedance of transformer (specified
by the manufacturer)

63
Moulded Case Circuit Breaker (MCCB)

Selection table for transformer protection

Transformer MCCB Rating in Amperes


rating (KVA) SKB-5 10kA SKB-6 17kA SKB-7 25kA SKB-1 25kA SKB-2 35kA SKB-2 35kA SKB-3 35kA SKB-3 50kA SKB-0 50kA
16 25 25 25 25 25 25
25 40 40 40 40 40 40
63 100 100 100 100 100 100
100 160 160 160 160 160
160 250 250 250 250 250
200 315 315
250 400 400
315 500 500
400 630 630
500 800 800
630 1000
750 1200

Generator set protection Selection table for DG set protection


STANDARD MCCBs can be used for the effective protection and
control of Diesel Generating set against overload and short circuits.
The Current rating of MCCB to be selected is calculated as follows :
DG Set MCCB
kVA = 3 Ue Ie Rating Rating
(kVA) (Amps)
or 10 16
kVA 16 25
Ie =
3 Ue 25 40

63 100
10 160
Where,
16 250
kVA = Rating of the DG Set
Ue = Rated Voltage 20 315
Ie = Rated Current 25 400
31 500
The MCCB rating selected is greater than or equal to the rated current
value 40 630
63 1000
750 1200

Typical installation

1000 kVA
A transformer

10 meters
8sc 300 mm2 B
70 meters 4c 120 mm2

20 meters 2c 16 mm2

64
Moulded Case Circuit Breaker (MCCB)

Feeder/cable protection The selection of STANDARD MCCB for feeder /cable protection depends
on the total load to be protected and the prospective short-circuit
An estimation of the prospective short-circuit current (psc) in an
current (psc) at the point of installation.
installation is an important consideration in the selection of the
appropriate protective device.
The magnitude of the short-circuit current (rms value of the AC PSC at A Aapproximately 27kA
component) at a point in the installation will depend upon;
PSC at B
(A) Prospective short-circuit current at the origin of the installation.
(B) The amount of resistance in the circuit between the origin of the resistance A to B (a) 0.30mW = 25kA
installation and the point at which the short circuit occurs.
(C) The type of short-circuit, phase to phase or phase to earth or PSC at C
phase to neutral. +resistance A to B 0.30mW
It is possible to arrive at a maximum prospective short circuit value at +resistance B to C1 10.70mW
the origin by taking the transformer kVA rating and its impedance and 11.00mW = 12kA
calculating from the expression :

PSC at D
Transformer rating (kVA) 100 +resistance A to B 0.30mW
SCkA =
3 Secondary voltage % impedance of transformer +resistance B to C 10.70mW
+resistance C to D 46.00mW (b)
57.00mW = 3kA
To calculate the resistance in the LV circuit, obtain details of lengths
and sizes of cables between the source of supply and the point under
calculation. Using the table provided, determine the sum of cable (a) 2 cables per phase divided by 2
resistances and then simply read off the estimated fault current from (b) 2 core cable, multiplied by 2
the relevant transformer curve on the graph.
The above calculations have an inbuilt safety margin as they assume a
The values assume a symmetrical fault across the three phases. In a no impedance fault condition which would not be the case in practice.
single circuit, for line to neutral faults, take the cable resistance value
from the table and double it.

Estimating the prospective short circuit current

40 2000 kVA

1500 kVA

1250 kVA
30
1000 kVA
Fault Current (kA)

800 kVA

20

500 kVA

10 315 kVA

200 kVA

100 kVA

0
0.1 1.0 10 100

Total Circuit Resistance ( ohm)

65
Moulded Case Circuit Breaker (MCCB)

Maximum resistance of copper conductors at 20C (m ohm)

Nominal Cable length


Cross-sectional
Area (mm2) 5m 10m 15m 20m 30m 40m 50m 60m 70m 80m 90m 100m
1 90.50 181.00
1.5 60.50 121.00 182.00
2.5 37.10 37.10 74.1 0 111.00 148.00
4 23.10 46.1 0 69.2 0 92.2 0 138.00
6 15.40 30.8 0 46.2 0 61.6 0 92.40 123.00
10 9.1 5 18.3 0 27.50 36.6 0 54.9 0 73.2 0 91.50 110.00
16 5.75 11.50 17.30 23.00 34.5 0 46.00 57.20 69.00 80.5 0 103.5 0
25 3.6 4 7.27 10.9 0 14.5 0 21.8 0 29.1 0 36.40 43.6 0 50.9 0 58.2 0 65.40 72.7 0
35 2.6 2 5.24 7.86 10.4 8 15.7 0 21.00 26.2 0 31.40 36.70 41.9 0 47.20 52.40
50 1.94 3.8 7 5.81 7.74 11.6 0 15.5 0 19.40 23.2 0 27.10 31.00 34.8 0 38.7 0
70 1.34 2.6 8 4.0 2 5.3 6 8.04 10.7 0 13.40 16.1 0 18.8 0 21.40 24.10 26.8 0
95 0.9 6 1.93 2.1 0 3.8 6 5.7 9 7.72 9.6 5 11.6 0 13.6 0 15.40 17.40 19.3 0
120 0.7 7 1.53 2.3 0 3.0 6 4.5 9 6.12 7.65 9.18 10.70 12.2 0 13.8 0 15.3 0
150 0.6 2 1.24 1.86 2.4 8 3.7 2 4.96 6.2 0 7.44 8.6 8 9.9 2 11.20 12.40
185 0.4 9 1.00 1.49 1.98 2.9 7 3.96 4.96 5.96 6.9 4 7.93 8.9 2 9.9 1
240 0.3 4 0.75 1.13 1.51 2.26 3.0 2 3.7 7 4.5 2 5.28 6.0 3 6.79 7.54
300 0.3 0 0.63 0.9 0 1.20 1.8 0 2.8 0 3.00 3.61 4.21 4.81 5.41 6.0 1
400 0.2 3 0.4 7 0.7 0 0.9 4 1.41 1.88 2.35 2.8 5 3.29 3.76 4.2 3 4.7 0
500 0.1 8 0.37 0.55 0.7 3 1.10 1.46 1.83 2.2 0 2.56 2.9 3 3.29 3.6 6
630 0.14 0.28 0.4 2 0.5 7 0.8 5 1.13 1.42 1.78 2.15 2.51 2.8 8 3.2 5

Selection table for motor protection

Motor Apprx. Direct On Line MCCB Star/Delta MCCB


Rating Full Load Rating/Type Rating/Type
KW SKB-0
Current (A)
HP at 415V SKB-1 SKB-3/4 SKB-1 SKB-3/4
10 7.5 14 25 - 25 - -
12.5 9 17 25 - 25 - -
15 11 21 25 - 25 - -
20 15 28 32 - 32 - -
25 19 35 40 - 40 - -
30 22 41 50 - 50 - -
40 30 52 80 - 63 - -
50 37 69 100 - 80 - -
60 45 80 - - 100 - -
75 55 97 - - 125 - -
100 75 125 - - 160 - -
125 90 156 - 250 - - -
150 112 190 - 315 - 250 -
175 130 225 - 315 - 315 -
The figures shown are
200 149 255 - 315 - 315 - based on following motor
220 160 275 - 400 - 400 - starting conditions : -

250 186 320 - 400 - 500 600


Direct online 7 X full load
300 224 375 - 500 - 500 600 current for 5 seconds.
350 261 449 - 630 - 630 600
Star/Delta 4 X full load
400 298 505 - 630 - 630 600 current for 12 seconds.

66
Moulded Case Circuit Breaker (MCCB)

Motor Control Star-Delta Starting


STANDARD MCCBs can be used for motor protection. Selection of In Star Delta starting of motors, since there is a reduction in the starting
MCCBs has to be done taking into consideration the starting inrush current due to reduced voltage, the MCCBs do not have a problem
current, and the system fault levels. Further the selection is also based in the overload setting. But the transient currents can go upto 12
on type of starting, i.e. DOL or Star Delta. times the rated current during change over from star to delta which
will cause the instantaneous magnetic release to trip the breaker. So
DOL Starting proper selection of magnetic pickup level is important for prevention
of nuisance tripping during change over from Star to Delta.
Care is to be taken to avoid nuisance tripping during starting of Squirrel
Cage Motors since the inrush current will be in the order of 600 to It is always recommended to select an MCCB in co-ordination with
800% of the full load current of the motor. The overload setting is Contactor and Over Load Relay so as to have the best and optimum
chosen such that it does not trip during starting. benefit of all the devices.

Selection & application

Capcitor Control
When a capacitor circuit is opened, it exhibits characteristics distinctly 1200
differently from inductor loads due to the effects of residual electric 1000
charge in the capacitor. The recovery voltage appears across the
contacts immediately after the circuit is opened is equal to the difference 900
between the capacitor residual voltage and supply voltage. Therefore

Circuit breaker current (A)


800
half a cycle after the circuit opens, the voltage between the contacts
of the switch rises to twice the supply voltage or higher. 700
In a three phase circuit the recovery voltage appearing between the 600
contacts in the first interrupted phase could rise to as high as 2.5 times
the supply voltage. Unless the breaker contacts are fully open for at 500
least cycle after the capacitor current is interrupted, restrike of arc is 400
likely to occur. If the restrike arc is repeated, the voltage could continue
to rise to the dielectric breakdown point of the capacitor. Hence, fast 300
interrupting, quick make, quick-break circuit breakers should be used
200
for this type of circuit.
When a capacitor circuit is closed a condenser charge q = CU which 100
corresponds to the instantaneous value U of the supply voltage at
closing time, must be instantaneously supplied, causing a large inrush 50 100 150 200 250 300 350 400 450 500 550 600
current to flow through it. If the capacitor circuit is closed in the voltage Capacitor rating (KvAr)
phase at which the inrush current is maximum, the maximum value of
the inrush current is approximately, The AC rating of MCCBs is expressed as RMS value. The DC rating
is Average value. The RMS and average value can be related by a
C Form Factor which is 1.1.
Ip = U
L Hence, an AC MCCB can be assigned a 10% higher DC current rating.
The maximum time duration during which the maximum current flows But in practice the use of DC MCCB ratings are equal to AC ratings
is about 0.5 ms. Selection of a MCCB for capacitor circuit duty must and thereby, temperature rise is restricted within limits.
therefore consider the effects of higher short circuit and inrush currents. Overload Release & Overload Protection
This will affect the choice of instantaneous trip current rating. In practice,
an MCCB which satisfies the following equations should be chosen. The overload release are generally thermal type with a Bimetal-Heater
system. The heating effect which can be expressed by the factor integral
Ir > 1.5 Ic I 2t varies for AC and DC. The integral (I 2t) for AC will be 1.21 times
Ip integral (I2avt) for DC, thus an AC MCCB when used in DC circuit will
Iinst > trip slower. For example a 100A AC MCCB when used in DC circuit for
2 100A will sense a 20% overload only from 133A onwards.
Where : To retain the same Overload characteristics as AC, it is important to
I r = Rated current of MCCBs separately calibrate the MCCBs for DC ratings and overload tripping
I c = Rated current of capacitor characteristics need to be suitably modified.
Iinst = Short circuit pick up setting of the MCCB Short Circuit Release & Short Circuit Protection
Ip = Maximum capacitor inrush current The short circuit release is actuated by the peak value of the AC sine
It is therefore necessary to select a circuit breaker with current rating wave. Since no such peak exists in DC, DC tripping will be slower.
not less than 1.5 - 2.0 times the rated current of the capacitor. Hence to achieve the same short circuit pick up level in DC, the short
circuit release will be calibrated specially.
DC Control
Short Circuit Breaking Capacity
MCCBs though not separately designed for DC applications are suitably
modified to be able to operate on DC systems also upto 500V DC / In AC the breaking of the short circuit current usually occurs within the
250V DC. This is achieved by modifying for: first current zero, by the current limiting effect. No such current zero
exists in DC. Arc breaking and ultimate quenching of arc depends on
i) Current carrying capacity
the rapid dissipation of the inductive Energy Li2
ii) Over current and short circuit protection
iii) Short circuit breaking capacity (with L/R time constant limitations) This energy dissipation is dependent on L/R or time constant of the
circuit. The L/R values should be limited to 10-15 milli seconds to
Current Carrying Capacity achieve satisfactory performance. This is achieved usually by splitting
The continuous current carrying capacity is generally a function limited the DC arc voltage over 2 or 3 poles by connecting them in series,
by the temperature rise of various internal components of MCCBs. depending upon on the DC voltage.

67