You are on page 1of 22

SREX POWER INDIA PVT.

PRE-COMMISSIONING REPORT O
BREAKER

1.0 EQUIPMENT DETAILS:

MAKE :
TYPE :
HSV :
YEAR OF MFG :
SR. No. :
CURRENT RATING :
VOLTAGE RATING :
STC :
CONTROL VOLTAGE :
2.0 CHECK LIST

Sr. No. DES

1 EQUPIMENT IS CLEANED AND FREE FROM DU

2 EQUIPMENT IS FREE FROM ALL VISIBLE DE

3 SUPPORT STRUCTURES, MARSHALLING BOX

4 ALL NUTS AND BOLTS ARE TIGHTENED CORR

5 CHECK TIGHTNESS OF TERMINAL CONNECTO

6 LEVELLING AND ALIGNMENT OF STRUCTURE

Page 1 of 22
SREX POWER INDIA PVT. L

PRE-COMMISSIONING REPORT O
BREAKER

7 CONTROL BOX / MARSHALLING KIOSK IS FR

8 AUXILLARY CONTACTS AND RELAYS HAVE B

9 POWER CLOSING OPERATION AND OPENING D

10 CABLE TERMINATION AND TIGHTNESS CHE

ALL THE CABLE IDENTIFICATION TAGS PROV


11
IDENTIFICATION FERRULES AT M.B.
12 ELECTRICAL OPERATION IN TEST AND SERVIC
14 CLOSING AND OPENING COIL RESISTANCE CH

CHECK THAT ALL AUXILIARY CONTACTS ARE


15 OPEN IN OPEN CONDITION OF EQUIOMENT AN
OF EQUIPMENT

3.0 CIRCUITARY / OPEARTIONAL CHECKS :

SL NO CIRCUIT REFERENCE

A TRIPPING THROUGH TC
B CLOSING CIRCUIT
C BREAKER POSITION INDICATION
D HEATER IN CONTROL CUBICLE
E ILLUM. IN CONTROL CUBICLE

4.0 OPERATING TIME ( IN MILLI-SECONDS )

Page 2 of 22
SREX POWER INDIA PVT. L

PRE-COMMISSIONING REPORT O
BREAKER

PHASE
R - PH
Y - PH
B - PH

5.0 IR VALUE WITH BREAKER OPEN :


USING 5000 VOLT MEGGER

R - PHASE
>2000

6.0 IR VALUE WITH RESPECT TO EARTH WITH BREAKER CLOSED, EARTH S


USING 5000 VOLT MEGGER

BETWEEN
R - PHASE AND EARTH
Y - PHASE AND EARTH
B - PHASE AND EARTH

Page 3 of 22
SREX POWER INDIA PVT. L

PRE-COMMISSIONING REPORT O
BREAKER

7.0 IR VALUE WITH RESPECT TO EARTH WITH BREAKER CLOSED, EARTH S


USING 5000 VOLT MEGGER

BETWEEN
R - PHASE AND Y PHASE
Y - PHASE AND B PHASE
B- PHASE AND R PHASE

8.0 CONTACT RESISTANCE MEASUREMENT :

R-PH
22.5

9.0 TEST REPORT CIRCUIT BREAKER VI TESTING

10.0 REMARKS

TESTED BY
SIGNATURE :
NAME : UMAKANT
ORGANISATION : SREX POWER

Page 4 of 22
OWER INDIA PVT. LTD. DOC NO. :
PROJECT :
CUSTOMER
MISSIONING REPORT OF CIRCUIT CLIENT :
LOCATION :
EQUIPMENT IDENTIFICATION :
DATE OF TESTING :

SCHNEIDER
HVX-X
12 Kv
2015
V-7505142119-9
1600 A
11 KV
25 kA
110 V DC

STA
DESCRIPTION
YES

CLEANED AND FREE FROM DUST / DIRT FOREIGN MATERIALS ETC. YES

FREE FROM ALL VISIBLE DEFECTS ON PHYSICAL INSPECTION YES

CTURES, MARSHALLING BOX HAS BEEN PROVIDED WITH DOUBLE EARTH YES

BOLTS ARE TIGHTENED CORRECTLY AS PER SPECIFIED TORQUE YES

NESS OF TERMINAL CONNECTOR YES

ND ALIGNMENT OF STRUCTURE AND BASE FRAME IS CHECKED YES

Page 5 of 22
OWER INDIA PVT. LTD. DOC NO. :
PROJECT :
CUSTOMER
MISSIONING REPORT OF CIRCUIT CLIENT :
LOCATION :
EQUIPMENT IDENTIFICATION :
DATE OF TESTING :

/ MARSHALLING KIOSK IS FREE FROM ANY PHYSICAL DEFECTS YES

ONTACTS AND RELAYS HAVE BEEN CLEANED AND FREE FROM RUST / DAMAGE YES

NG OPERATION AND OPENING DONE YES

NATION AND TIGHTNESS CHECKED AND UNUSED HOLES SEALED YES

E IDENTIFICATION TAGS PROVIDED AND ALL CORES ARE PROVIDED WITH


YES
N FERRULES AT M.B.
PERATION IN TEST AND SERVICE CHECKED YES
OPENING COIL RESISTANCE CHECKED AND RECORDED YES

LL AUXILIARY CONTACTS ARE OPERATING PROPERLY (NC IS CLOSED AND NO IS


CONDITION OF EQUIOMENT AND ITS STATE IS CHANGING IN CLOSE CONDITION YES
T

CIRCUITARY CHECK OPERATIONA


RCUIT REFERENCE
TEST SERVICE TEST
OUGH TC Ok Ok Ok
UIT Ok Ok Ok
TION INDICATION Ok Ok Ok
NTROL CUBICLE Ok Ok Ok
TROL CUBICLE Ok Ok Ok

Page 6 of 22
OWER INDIA PVT. LTD. DOC NO. :
PROJECT :
CUSTOMER
MISSIONING REPORT OF CIRCUIT CLIENT :
LOCATION :
EQUIPMENT IDENTIFICATION :
DATE OF TESTING :

CLOSE TRI
38 39
38 38
37 38

MEASUREMENT VALUE (MOHM)


Y - PHASE
>2000

H BREAKER CLOSED, EARTH SWITCH AND ISOLATOR OPEN :


MINIMUM VALUE 1000 MOHM

BETWEEN MEASUR
>5000
>5000
>5000

Page 7 of 22
OWER INDIA PVT. LTD. DOC NO. :
PROJECT :
CUSTOMER
MISSIONING REPORT OF CIRCUIT CLIENT :
LOCATION :
EQUIPMENT IDENTIFICATION :
DATE OF TESTING :

H BREAKER CLOSED, EARTH SWITCH AND ISOLATOR OPEN :


MINIMUM VALUE 1000 MOHM

BETWEEN MEASUR
>5000
>5000
>5000

Y-PH
23.3

REAKER VI TESTING APPLY 16 KV DC

Page 8 of 22
66KV/11kV Substation
SMCC
Honda Motorcycle & Scooter India Ltd
VITHALAPUR GUJRAT
VCB INCOMER
9/10/2015

STATUS REMARK
NO RECORD DEFICIENCIES, IF ANY

Page 9 of 22
66KV/11kV Substation
SMCC
Honda Motorcycle & Scooter India Ltd
VITHALAPUR GUJRAT
VCB INCOMER
9/10/2015

PERATIONAL CHECK
SERVICE
Ok
Ok
Ok
Ok
Ok

Page 10 of 22
66KV/11kV Substation
SMCC
Honda Motorcycle & Scooter India Ltd
VITHALAPUR GUJRAT
VCB INCOMER
9/10/2015

TRIP CLOSE T R I P
39 49
38 49
38 49

B - PHASE
>2000

MEASUREMENT VALUE
MOHM
MOHM
MOHM

Page 11 of 22
66KV/11kV Substation
SMCC
Honda Motorcycle & Scooter India Ltd
VITHALAPUR GUJRAT
VCB INCOMER
9/10/2015

MEASUREMENT VALUE
MOHM
MOHM
MOHM

B-PH
29.7

KV DC FOUND OK

APPROVED BY
SIGNATURE :
NAME : JIMIT DESAI
ORGANISATION : HMSI

Page 12 of 22
SREX POWER INDIA PVT. LTD.

PRE-COMMISSIONING REPORT OF CURR


TRANSFORMER

1.0 EQUIPMENT DETAILS:

MAKE : SCHNEIDER ELECTRIC


TYPE /MODEL : WINDOW
RATING : 12 KV
HSV : 12 kV
STC : 25 kA/ 1 sec
YEAR OF MFG : 2016
CT SR. No. R - PHASE : 16/0400012
Y - PHASE : 16/0400011
B - PHASE : 16/0400010
2.0 SECONDARY DATA

CORE RATIO BURDEN


CORE-1 1200/600-1 A 15VA
CORE-2 1200/600-1 A 20VA

3.0 CHECK LIST BEFORE ELECTRICAL TESTING

Sr. No. DESCRIPTION


1 EQUPIMENT IS CLEANED AND FREE FROM DUST / DIRT FORE
2 EQUIPMENT IS FREE FROM ALL VISIBLE DEFECTS ON PH
3 CHECK TIGHTNESS OF TERMINAL CONNECTOR
4 ALL FITTINGS AS PER OUT LINE GENERAL ARRANGEMENT
5 CHECK PRIMARY POLARITY OF CT,S ERECTED AS PER RE
6 ALL THE CABLE IDENTIFICATION TAGS PROVIDED AND ALL
7 IDENTIFICATION FERRULES
WIRING CONTINUTI AT FROM
CHECKED M.B. ALL CT,S TO CT MB AN
4.0 PRIMARY INSULATION RESISTANCE MEASUREMENT

BETWEEN TERMINALS
PRIMARY TO EARTH
PRIMARY TO CORE-1
PRIMARY TO CORE-2
5.0 SECONDARY INSULATION RESISTANCE MEASUREMENT

BETWEEN TERMINALS
CORE-1 TO CORE-2

6.0 POLARITY TEST


USE 1.5V BATTERY ( P1 Positive and P2 Negative)
Check for Positive deflection in secondary

CORE BETWEEN
CORE-1 1S1 (+VE) 1S3 (-VE)
CORE-2 2S1 (+VE) 2S3 (-VE)

7.0 CURRENT RATIO TEST

PRIMARY INJECTION THROUGH PRIMARY INJECTION KIT AT PRIMARY TERMINAL


MEASURE CURRENT ON THE SECONDARY TERMINALS

CURRENT INJECTED IN RATIO/ TAPPING TERMINALS USED


PRIMARY (A)

1S1 TO 1S3
60 2S1 TO 2S3

1S1 TO 1S3
120 2S1 TO 2S3

TESTED BY
SIGNATURE :
NAME : UMAKANT
ORGANISATION : SREX POWER
DIA PVT. LTD. DOC NO. :
PROJECT :
PLANT/AREA :
ING REPORT OF CURRENT CLIENT :
ANSFORMER LOCATION :

EQUIPMENT IDENTIFICATION :
DATE OF TESTING :

CLASS KVp Ext. Amps


0.5
SP10

STATUS
DESCRIPTION
YES
FREE FROM DUST / DIRT FOREIGN MATERIALS ETC. YES
ALL VISIBLE DEFECTS ON PHYSICAL INSPECTION YES
NAL CONNECTOR YES
INE GENERAL ARRANGEMENT DRAWING YES
OF CT,S ERECTED AS PER RELEVANT DRAWING. YES
ON TAGS PROVIDED AND ALL CORES ARE PROVIDED WITH YES
T FROM
M.B. ALL CT,S TO CT MB AND UP CONTROL RELAY PANEL YES

VALUES MEASURED IN MEGA OHMS


R-PH Y-PH
1100 1100
1000 1100
1100 1100
VALUES MEASURED IN MEGA OHMS
R-PH Y-PH
>500 >500

R-PH Y-PH
OK OK
OK OK

KIT AT PRIMARY TERMINAL P1 - P2

CURRENT MEASURED IN SECONDARY (

R-PH Y-PH

0.050 0.049
0.049 0.050

0.100 0.099
0.099 0.100
66KV/11kV Substation
SMCC
Honda Motorcycle & Scooter India Ltd

VITHALAPUR GUJRAT

VCB BUS COUPLER


12/13/2016

RESISTANCE PURPOSE
METERING
PROTECTION

STATUS REMARK
NO RECORD DEFICIENCIES, IF ANY

ES MEASURED IN MEGA OHMS


Y-PH B-PH
1100 1050
1100 1050
1100 1100
ES MEASURED IN MEGA OHMS
Y-PH B-PH
>500 >500

Y-PH B-PH
OK OK
OK OK

T MEASURED IN SECONDARY (A)

Y-PH B-PH

0.049 0.049
0.050 0.048

0.099 0.099
0.100 0.100

Witnessed By
SIGNATURE :
NAME : JIMIT DESAI
ORGANISATION : HMSI
zs