MPPKVVCL

Group Metering System


Technical Specifications
Table of Content

Introduction of concept ............................................................................................................ 3


DIN Rail Meter .......................................................................................................................... 4
a. Rated Electrical Parameter ............................................................................................................................................ 5
b. Billing data...................................................................................................................................................................... 6
c. MD registration .............................................................................................................................................................. 6
d. TOD Metering................................................................................................................................................................. 7
e. Midnight Energy Stamp.................................................................................................................................................. 7
f. Display ............................................................................................................................................................................ 7
g. LED ................................................................................................................................................................................. 7
h. Tamper ........................................................................................................................................................................... 8
i. Load Survey .................................................................................................................................................................... 8

Remote Display Unit ................................................................................................................. 9


Low Power Radio .................................................................................................................... 10
Introduction of concept
Group Metering System is based on a powerful multiprocessor architecture enabling metrology and
communication functions.GMS is ready solution to enhance the HVDS systems functional efficiency .GMS
can be integrated with HVDS transformer for monitoring individual consumers electrical energy
consumption where majority of consumers are in cluster.One IGMS box is capable to record energy
consumption of maximum of 10 consumers.

GMS system comprises of:

1. Energy Meters - DIN rail type mounting 240Volts, 5-30Amp, Class 1.0, Single phase, Whole
Current, Energy meters confirming to IS: 13779 which are compatible to measure Energy
consumption and Demand (kW & kVA). Maximum 10 meters can be placed in a single system.

2. Data concentrator unit: This unit collects data from all individual meters (meter modules) on
a regular interval with wired serial communication.This communicates with remote energy display
unit (REDU) via RF technology (in ISM band).

3. Audit Meter: (optional) this is for energy auditing purpose and will measure HVDS Tr. Load.

4. RF Modem:RF modem enables communication between DCU and REDU & DCU and HHT (Hand
held device) when meter reading is done. This works on ISM band sub G-Hz frequency with point to
point RF communication technology.

5. REDU (Remote Meter Display Unit):This unit will be installed at consumer premises and
will have only displays of energy consumption and demand .This unit have RF chip and will
communicate with DCU through RF modem connected in main box to fetch the requireddisplay
information.
Data of all meters and of any one of selected meter can be downloaded through HHT using RF
technology.
DIN Rail Meter

a. Rated Electrical Parameter

S. No. Items Specified Operating Range

1. Connection type Single Phase 2 wire direct connected

2. Voltage 240volts P-N

+20% to -40% Vref

3. Current 05 - 30 A (Withstands 120% Imax),Starting current-0.2%Ib

4. Frequency 50Hz
5% (47.5 to 52.5)Hz

5. Power Factor Zero(lag)-Unity-Zero(Lead)

6. Accuracy 1.0

7 Withstand Voltage 440V up-to 5 minutes between Phase Phase

8. Burden Voltage 1W/8VA


Circuit

9. Burden Current <2VA


Circuit

10. Meter Constant 3200 imp/kwh

11. Measuring 1(on phase)


Element

b. Billing data

At billing date /time(Default last day of every month at 24:00hrs meter stores following details as billing
data:

Billing date and Time


Cumulative Active Energy
Cumulative TOD Energy
Maximum demand (KW)
Average Power Factor
Power on hours

Meter has the provision to store last 6 months billing data.All these data is accessible for
reading, recording by downloading through HHT (Hand Held Unit) on RF communication.

c. MD registration

The meter continuously monitors the demand (KW) and update the Maximum Demand for the month. The MD
will reset automatically at predefined Date & Time (Default last day of every month at 24:00hrs).

Meter stores MD in every 30 min. period along with date & time. At the end of every 30 min, new MD will be
computed & compared with previous MD and store whichever is higher and the same will be displayed. For MD
computation separate counter is used rather by difference of initial and final energy counter.
d. TOD Metering
Meter is capable of doing TOD metering for KWH, and MD in KW with 6 time zones (programmable on site
through CMRI).Two seasons summer and winter are configured in meter. Following are the default T&D time
zone.

st th st st
Tariff Timings 1 April-30 Sep 1 Oct- 31 Mar

1 00:00 to 6:00 Tnp Tnp

2 06:00 to 09:00 Tn Tn

3 09:00 to 15:00 Tn Tn

4 15:00 to 17:00 Tp Tn

5 17:00 to 23:00 Tp Tp

6 23:00 to 00:00 Tp Tnp

*Tnp TOD zone for non peak *Tn TOD zone for normal *Tp TOD zone for peak

e. Midnight Energy Stamp


Last 65 daysmidnight Kwh energy stamps are stored in meter.

f. Display
Following parameters will be displayed for 10 sec in auto mode.

1. LCD Check
2. Cumulative Kwh
3. MD(KW)
4. Date
5. Real Time
6. Instantaneous Voltage
7. Instantaneous Current
8. Instantaneous Load

g. LED
Two LEDs are provided on meter front

a. CAL LED: - For Calibration Pulse indication.


b. Phase LED :- If Phase and Neutral are present then it will glow, and If Meter is running at Neutral miss
then it will not glow
h. Tamper

1. TOP Cover open: - If meter top cover is opened then meter detect top cover open tamper with in
1sec & logged it.
2. Battery low: - If battery voltage is below 1.9V than meter detect it as battery low tamper & logged
it.
3. Over current tamper: -if load current is greater than 120%of Imax then over current tamper is
logged.
4. Low Voltage:- Event shall be logged in memory along with Occurrence and restoration event data.
Threshold should be below 180Volts.
5. Power on-off event: - Power on-off event will be logged in meter.
6. Low Power factor:-When Power factor is below then defined threshold limit then low power factor
event is logged.

Last 20 event of each type is stored in meter.

i. Load Survey

Last 65 days load survey for following parameters with 30 minute survey integration period is stored in
meter:

1. Voltage
2. Current
3. Demand(KW)
4. Power factor
5. Date/Time
Remote Display Unit(REDU)

The REDU is intended for Single Phase 2- wire Name Plate Details:-
System of rating 240V, 50Hz.
The various specifications are as follows:- The nameplate is fixed inside the REDU on the
topside of the front face and is visible through
the top cover. The arrangement is such that no
Rated Voltage : 240V A.C.
manipulation on the nameplate is possible
Frequency :50Hz
without opening the top cover. The nameplate
provides information on the following: -
RF Specifications:-
a. Type of REDU : 220V, 50Hz
Carrier frequency : 866 MHz b. Serial Number : Each REDU has unique
Data rate : 250 kbps serial no. and bar code printed on the name
Plate
c. Batch Code : To ensure traceability at
All parameters will be displayed for 4 secs in auto any stage, month/year has also been printed
mode. The down arrow segment () on LCD will along with the serial no. e.g. 04/12
show the type of parameter as written on name
plate. LEDs:
1.Status LED: For communication status.
SR.NO. Parameter AUTO MODE 2. Ph LED:For Supply indication

ALL SEGMENTS Besides above the nameplate contains


1 Display Check
GLOW (Manufacturer) name with logo

2 XXXXX.X Cumulative kWh

3 Load (KW)
Ld XX.XXX

4 MD (kW)
XX. XXX

Instantaneous Power
5
PF X.XXX Factor

Instantaneous
6 U XXX.XX
voltage

7 A XXX.XXX Instantaneous
current

8 HZ XX.X Supply Frequency

9 Date
d DD:MM:YY

10 Real time
t HH:MM:SS

Low Power Radio

LPR is working in ISM free RF band (866MHz) for wireless communication. RF is the wireless transmission
of data by digital radio signals at a particular frequency.

The various specifications are as follows:-

Rated Voltage : 3.3V dc


Carrier frequency : 866 MHz
Data rate : 250 kbps