In its simple form, SVC is connected as Thyristor- The relevant Data of the PHCN network as obtained
Controlled-Reactor Fixed Capacitor (TCR-FC) from PHCN Control Centre, Oshogbo is as shown in Table
configuration as shown in Figure 1 with its equivalent I.
circuit in Figure 2. Its major components include coupling
A. SIMULINK Model of the Nigerian 28-Bus Power System
transformer, thyristor valves, reactors, and capacitors (for
under Study
harmonic filtering through tuning) [3].
Using Figure 3 and Table I, the SIMULINK model of
the single line diagram of the Nigerian 330kV, 28-bus
power system used for the study was obtained as shown in
Figure 4. Each generation station was modeled as a voltage
source and each transmission line represented by its
equivalent resistance and reactance.
In the model, measurement apparatus (voltmeter,
ammeter and wattmeter) and the modeled SVC were
incorporated.
B. Bus Voltage and Voltage drop Equations
Consider a transmission line between any two given
buses i and k extracted from the Nigerian 28-bus power
system of Figure 4 and represented as shown in Figure 5.
496
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 4, Issue 1, January 2014)
(8) From equation (9), it could be seen that by adjusting the
systems reactive power at bus k while keeping the voltage
From equation (8), at bus i constant, the voltage between buses i and k can be
regulated to minimizing the systems total voltage drop.
(9)
TABLE I
NETWORK DATA OF THE NIGERIAN 28-BUS POWER SYSTEM
497
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 4, Issue 1, January 2014)
498
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 4, Issue 1, January 2014)
By comparing equations (10) and (13) we have: By so doing, the bus voltage is being regulated near or at
the base voltage.
(14)
Assuming that the SVC is applied at bus k, then equation
Combining equations (11), (12) and (14), we have: (1) becomes;
( ) (15) (20)
Comparing equations (17) and (20) gives;
( ) (16)
(21)
. (17)
Equation (20) shows that if is kept constant, then by
The SVC controller was designed in such a way that the keeping the bus ( ) near or at the base voltage, the
TCR is switched off when the bus voltage becomes lower voltage drop is minimized and hence the systems voltage
than the reference voltage and vice-versa. As a result, at stabilized.
maximum var absorption the FC and the TCR are in
operation and as such; IV. SIMULATION RESULTS AND DISCUSSION
(18) Table 2 shows the bus voltages and the voltage drops
without/with SVC
And at minimum var absorption , so that;
A. Comparison Between the Voltage Drops without/with
(19) SVC
To appreciate the effect of SVC on the power systems
2) SIMULINK Model of the Static Var Compensator: voltage, the systems voltage drops without/with SVC were
The TCR-FC Static Var Compensator of Figure 1(a) was compared using the data from Table 2 as shown in Figure 6
modeled using SIMULINK blocks as shown in Figure 5, and 7.
where:
FC = Fixed Capacitor; L = Reactor; Tr1 = Step down
Transformer; Th = thyristor.
499
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 4, Issue 1, January 2014)
TABLE II
BUS VOLTAGES AND VOLTAGE DROPS OF THE 28-BUS POWER SYSTEM WITHOUT/WITH SVC
500
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 4, Issue 1, January 2014)
0.02
0.018
0.016 with SVC
0.012
0.01
0.008
0.006
0.004
0.002
0
12_14
15_21
10_17
11_12
13_14
16_19
17_18
17_23
17_21
19_20
20_22
20_23
23_25
12_26
19_26
26_27
4_5
5_28
1_3
1_5
2_8
2_7
5_8
5_9
6_8
5_10
7_24
8_14
8_10
8_24
9_10
V. CONCLUSION [2] Banga A. and Kaushik S. S. 2011. Modeling and Simulation of SVC
Controller for Enhancement of Power System Stability, International
In this paper, the basic structure and model of Thyristor- Journal of Advances in Engineering and Technology, Vol. 1,
Controlled-Reactor Fixed-Capacitor SVC were described. pp.79-84
A single line diagram of the Nigerian 28-bus, 330kv power, [3] Biswas M. M and Kamol K. D. 2011. Voltage Level Improving by
system used for the study was also modeled and simulated Using Static VAR Compensator, Global Journal of researches in
engineering, Volume 11,pp.12-18
without/with SVC. All the modeling and simulations were
[4] Conejo A. J., 2011, Load Flow Lecture, University of Castilla La
carried out in the SIMULINK/MALAB environment. From Mancha
the simulation results and the resulting graph and bar chart, [5] Nwohu M. N. 2009. Voltage Stability Improvement using Static Var
it was confirmed that SVC could be used to improve the Compensator in Power Systems, Leonardo Journal of Sciences,
voltage stability of power systems. Issue 14, pp. 167-17
[6] Pabla A. S. 2004. Electric Power Distribution, 5th edition, Tata
REFERENCES McGraw-Hill Publishing Company LTD, New Delhi
[1] Abido M. A. 2009. Power System Stability Enhancement Using [7] Tarik A. and Teleke S. 2006. Modeling and Comparison of
FACTS Controllers, The Arabian Journal for Science and Synchronous Condenser and SVC, Thesis presented for Master
Engineering, Volume 34, pp.153-172 Programme in Electric Power Engineering, Chalmers University of
Technology