Operators Manual
D I G I T A L C O NT R O L L E R 5 0 0 6H
CONTENTS
1. GENERAL SPECIFICATIONS
2. MOUNTING DETAIL
3. TERMINAL CONNECTION
5. CONFIGURATION MODE
6. RUN MODE
7. CALIBRATION MODE
9. COMMUNICATION PROTOCOL
1. GENERAL SPECIFICATION
Digital Zero and Span calibration
MODEL 5006H: using front panel keypad.
Two Set Point and Two Relay Zero adjustment automatically by
output rated for 2A@230VAC. software. (Except RTD input)
Four Operation Key SET1, SET2, CJC for T/C type input and 3-wire
INC and DEC. lead compensation for RTD sensor is
automatic.
DISPLAY:
TYPES OF SET POINT:
4 digit 0.8" Seven Segment Red
LEDs for Process Variable Set point types are configurable to
Individual discrete Red LEDs to energize relays for actual value
indicate relay status. below or above set point.
Hysteresis setting 0 to 100.
INPUT:
POWER SUPPLY:
RTD - PT100 3-wire
(Automatic three wire compensation) 110V/230V AC @ 50Hz
Thermo-couple types J, K, T, R, S (Factory set for any one),
(ANSI standard) 24V DC (+/- 10%) (optional)
4-20mA/1-5 V dc linear Ambient Temperature:
0-20mA/0-5 V dc linear 0 to 55 C
Humidity:
INPUT RANGE: Up to 95% RH non-condensing
Power consumption:
PT100 -199 to 850 C Less than 10 VA
PT100 (0.1C)-100.0 to 300.0 C
J -100 to 1200 C
K -100 to 1372 C
T -100 to 400 C
R 0 to 1768 C
S 0 to 1768 C
4-20 mA/1-5VDC
-1999 to 9999 (Field Scalable)
0-20mA/0-5VDC
-1999 to 9999 (Field Scalable)
ACCURACY:
(0.25% of FS + 1 count)
for T/C and RTD input.
(0.1% of FS + 1 count)
for mA and Voltage input
FRONT BEZEL: 48 x 96 mm
5. CONFIGURATION MODE
PANEL CUTOUT: 45 x 92 mm
DEPTH BEHIND THE PENAL: 163 mm Press Key together to enter
configuration mode.
3. TERMINAL CONNECTION
PASS WORD
Display Pass
Press 0
Press COnF
INTRODUCTION
The unit can be connected in RS-485 communication data link either in multi drop
or repeat mode. Each unit must have unique Serial Number. Entire range of addresses (1
to 255) may be used. Before starting any communication, choose a baud rate compatible
to the host computer. The serial protocol used is MODBUS RTU.
Protocol details:
The function codes used Read Write of parameters are:
03. READ HOLDING REGISTERS (REFERENCE - 4x).For Read operation
06. PRESET SINGLE REGISTER (REFERENCE - 4x).For Write operation
The error checking field contains a 16-bit value implemented as two eight-bit bytes. The
error check value is the result of a Cyclical Redundancy Check (CRC) calculation
performed on the message contents.
Note:
c) Decimal Position :
Type Value
L-on 0
h-on 1
Type Value
Set point - 1 0
Set point - 2 1
Type Value
UP 0
DN(down) 1
h) Baud Rate :
03 Illegal data value. A value contained in the query data field is not an allowable value for the
salve.
11. Maintenance:
Unit Resetting.
Check the proper input terminal connection.
If Input Range is 0-5V or 1-5V then maximum voltage should be less than
10V & minimum voltage should be greater than -3V.
Supply Voltage.
Supply voltage should be given through a good isolation transformer. This being a
microprocessor based instrument, a massive voltage spike can damage it. A good
isolation transformer shields the instrument from such voltage spikes and surges.
All supply connections to final control devices such as contactors, solenoids etc.
must be taken directly from the supply and not from the supply terminals of the
instrument.
This is an electronics instrument it may have problem not listed above, in case of
such fault while reporting to factory (masibus area office or head office), mention
exact nature of fault with sequence of events.