JPL TAMNAR

Protocol for Load Shedding Relay (LSR) Commissioning Unit#2 Date:

S.No Voltage Injected Current Injected Load Throw off % Residual Load % Output
1 63.5 0 5--0 0
2 63.5 -120 5--0 -120 100% 50% OK
3 63.5 120 5--0 120

S.No Voltage Injected Current Injected Load Throw off % Residual Load % Output
1 63.5 0 5--2.4 0
2 63.5 -120 5--2.4 -120 50% 50% OK
3 63.5 120 5--2.4 120

S.No Voltage Injected Current Injected Load Throw off % Residual Load % Output
1 63.5 0 5-2.6 0
2 63.5 -120 5-2.6 -120 50% 50% NOT OK
3 63.5 120 5-2.6 120

S.No Voltage Injected Current Injected Load Throw off % Residual Load % Output
1 63.5 0 5--1.4 0
2 63.5 -120 5--1.4 -120 50% 30% OK
3 63.5 120 5--1.4 120

S.No Voltage Injected Current Injected Load Throw off % Residual Load % Output
1 63.5 0 5--1.6 0
2 63.5 -120 5--1.6 -120 50% 30% NOT OK
3 63.5 120 5--1.6 120

S.No Voltage Injected Current Injected Load Throw off % Residual Load % Output
1 63.5 0 5--0.9 0
2 63.5 -120 5--0.9 -120 50% 20% OK
3 63.5 120 5--0.9 120
Note: 1.The testing is performed through Omicron and Output of LSR is checked through 220V DC Bulb.
2.All CT and PT leads after testing are normalised and Output cable is connected.

BHEL JPL PROJECTS


L TAMNAR

12/8/2013

Output

OK

Output

OK

Output

NOT OK

Output

OK

Output

NOT OK

Output

OK
JPL PROJECTS
Testing of Check Sync Relay of Unit#1&2 ECP
Voltage Checking by keeping Frequency Constant

S.No Incoming Voltage Angle Running Voltage Angle Voltage Setting


1 106.9(PU) 0 109.1 0 2
106.8(DU)
2 111.8(PU) 0 109.1 0 2
111.9(DU)
3 105.0(PU) 0 109.1 0 4
104.8(DU)
4 103.7(PU) 0 99.2 0 4
104.0(DU)
5 93.3(PU) 0 99.2 0 6
93.1(DU)
6 105.8(PU) 0 99.2 0 6
106.0(DU)
7 91.3(PU) 0 99.2 0 8
91.1(DU)
8 108.0(PU) 0 99.2 0 8
108.3(DU)

Frequency checking by Keeping Voltage Constant

S.No Incoming Voltage frequency Running Voltage frequency Voltage Setting


1 110 49.82( Higher Side) 109 50 4
50.17( Lower Sde)
2 110 49.93( Higher Side) 109 50 4
50.06( Lower Sde)
3 110 49.96( Higher Side) 109 50 4
50.01( Lower Sde)
4 110 49.99( Higher Side) 109 50 4
50.02( Lower Sde)

Angle checking by Keeping Voltage and Frequency Constant

S.No Incoming Voltage frequency Running Voltage frequency Voltage Setting


1 110(0) 49.93 109(180) 50 4

2 110(0) 49.93 109(0) 50 4


Final Voltage setting and Frequency settings kept at 4V and With Slip 0.22.

BHEL PSWR SITE JPL PROJECTS


#1&2 ECP

Frequency Setting OutPut LED


0.22 OK

0.22 OK

0.22 OK

0.22 OK

0.22 OK

0.22 OK

0.22 OK

0.22 OK

Frequency Setting OutPut LED


0.45 OK

0.22 OK

0.15 OK

0.11 OK

Frequency Setting OutPut LED


0.22 NOT OK

0.22 OK
JPL PROJECTS
Testing of Unit#2 AUTO SYNCRONISER
Voltage Checking by keeping Frequency Constant

S.No Incoming Voltage Angle Running Voltage Angle Voltage Setting Frequency Setting Command Type Breaker cmd
1 108 0 110 0 2 0.25 Voltage Raise OK
49.99 50(Frequency)
2 110.3 0 110 0 2 0.25 Voltage Lower OK
49.99 50(Frequency)
3 106.3 0 110 0 5 0.25 Voltage Raise OK
49.99 50(Frequency)
4 112.1 0 110 0 5 0.25 Voltage Lower OK
49.99 50(Frequency)
5 98.5 0 110 0 15 0.25 Voltage Raise OK
49.99 50(Frequency)
6 112.1 0 100 0 15 0.25 Voltage Lower OK
49.99 50(Frequency)

Frequency checking by Keeping Voltage Constant

S.No Incoming Voltage frequency Running Voltage frequency Voltage Setting Frequency Setting Command Type OutPut LED
1 110.7 0 110 0 2 0.1 Frequency Raise OK
49.901 50(Frequency)
2 103.3 0 110 0 2 0.1 Frequency Lower OK
50.109 50(Frequency)
3 110.7 0 110 0 2 0.25 Frequency Raise OK
49.698 50(Frequency)
4 110.7 0 110 0 2 0.25 Frequency Lower OK
50.303 50(Frequency)

Final Voltage setting and Frequency settings kept at 2V and With Slip 0.1
BHEL PSWR SITE JPL PROJECTS
TESTING OF LOAD TRANSDUCER AT CJJ08 UNIT#2
A WATT TRANSDUCER U002
SERIAL NO:820/651 745/1-6
TYPE:P200-094-232

S.No Voltage Angle Current Angle Power Range


1 63.5 0 4.41 -31.78
2 63.5 120 4.41 88.22 600 MW 0-770
3 63.5 240 4.41 208.22
4 63.5 0 2.2 -31.78
5 63.5 120 2.2 88.22 300 MW 0-770
6 63.5 240 2.2 208.22
7 63.5 0 1.1 -31.78
8 63.5 120 1.1 88.22 150 MW 0-770
9 63.5 240 1.1 208.22

B WATT TRANSDUCER U003


SERIAL NO:820/651 743/1-8
TYPE:P200-094-232

S.No Voltage Angle Current Angle Power Range


1 63.5 0 4.41 -31.78
2 63.5 120 4.41 88.22 600 MW 0-770
3 63.5 240 4.41 208.22
4 63.5 0 2.2 -31.78
5 63.5 120 2.2 88.22 300 MW 0-770
6 63.5 240 2.2 208.22
7 63.5 0 1.1 -31.78
8 63.5 120 1.1 88.22 150 MW 0-770
9 63.5 240 1.1 208.22
C WATT TRANSDUCER U004
SERIAL NO:820/461 017/1-20
TYPE:P200-094-232

S.No Voltage Angle Current Angle Power Range


1 63.5 0 4.41 -31.78
2 63.5 120 4.41 88.22 600 MW 0-770
3 63.5 240 4.41 208.22
4 63.5 0 2.2 -31.78
5 63.5 120 2.2 88.22 300 MW 0-770
6 63.5 240 2.2 208.22
7 63.5 0 1.1 -31.78
8 63.5 120 1.1 88.22 150 MW 0-770
9 63.5 240 1.1 208.22

Note: 1.The testing is performed through Omicron and Output of LMU CHECKED AT DCS END.
2.All CT and PT leads after testing are normalised and Output cable is connected.

BHEL JPL PROJECTS


UNIT#2
TESTING OF TRANSDUCER OF CFA01 AND CFA02 DATE:01/09/2013

2MWT1 2MVART1 2PFT1


S.No Voltage Angle Current Angle
ECP DCS mA ECP DCS mA ECP DCS
1 63.5 0 4.41 -31.78
2 63.5 120 4.41 88.22 600 MW 600 MW 16.68 mA 450 MvAr 450 MvAr 16.68 mA 0.8 lag 0.8 lag
3 63.5 240 4.41 208.22
4 63.5 0 2.2 -31.78
5 63.5 120 2.2 88.22 300 MW 300 MW 12.68 mA 225 MvAr 225 MvAr 12.68 mA 0.8 lag 0.8 lag
6 63.5 240 2.2 208.22
7 63.5 0 1.1 -31.78
8 63.5 120 1.1 88.22 150 MW 150 MW 8.68 mA 112.5 MvAr112.5 MvAr 8.68 mA 0.8 lag 0.8 lag
9 63.5 240 1.1 208.22
2VT1/2VT2/2VT3 2HZT1
S.No Voltage Angle S.No Voltage FREQ
ECP DCS mA ECP DCS
1 63.5 0 21 KV 21 KV 16 mA 1 63.5 45 45 45
2 63.5 120 21 KV 21 KV 16 mA 2 63.5 45 45 45
3 63.5 240 21 KV 21 KV 16 mA 3 63.5 45 45 45
4 31.5 0 10.5 KV 10.5 KV 12 mA 4 63.5 50 50 50
5 31.5 120 10.5 KV 10.5 KV 12 mA 5 63.5 50 50 50
6 31.5 240 10.5 KV 10.5 KV 12 mA 6 63.5 50 50 50
7 15.75 0 5.25 KV 5.75 KV 8 mA 7 63.5 55 55 55
8 15.75 120 5.25 KV 5.75 KV 8 mA 8 63.5 55 55 55
9 15.75 240 5.25 KV 5.75 KV 8 mA 9 63.5 55 55 55

1VT4/1VT5/1VT6 400 KV BUS-1 1VT7/1VT8/1VT9 400 KV BUS-2


S.No Voltage Angle S.No Voltage Angle
ECP DCS mA ECP DCS
1 63.5 0 400 KV 400 KV 16 mA 1 63.5 0 400 KV 400 KV
2 63.5 120 400 KV 400 KV 16 mA 2 63.5 120 400 KV 400 KV
3 63.5 240 400 KV 400 KV 16 mA 3 63.5 240 400 KV 400 KV
4 31.5 0 200 KV 200 KV 12 mA 4 31.5 0 200 KV 200 KV
5 31.5 120 200 KV 200 KV 12 mA 5 31.5 120 200 KV 200 KV
6 31.5 240 200 KV 200 KV 12 mA 6 31.5 240 200 KV 200 KV
7 15.75 0 100 KV 100 KV 8 mA 7 15.75 0 100 KV 100 KV
8 15.75 120 100 KV 100 KV 8 mA 8 15.75 120 100 KV 100 KV
9 15.75 240 100 KV 100 KV 8 mA 9 15.75 240 100 KV 100 KV
1HZT2 400 KV BUS-1 1HZT3 400 KV BUS-1
S.No Voltage Frequency S.No Voltage Frequency
ECP DCS mA ECP DCS
1 63.5 45 45 45 11.78 mA 1 63.5 45 45 45
2 63.5 45 45 45 11.78 mA 2 63.5 45 45 45
3 63.5 45 45 45 11.78 mA 3 63.5 45 45 45
4 63.5 50 50 50 15.78 mA 4 31.5 50 50 50
5 63.5 50 50 50 15.78 mA 5 31.5 50 50 50
6 63.5 50 50 50 15.78 mA 6 31.5 50 50 50
7 63.5 55 55 55 19.78 mA 7 15.75 55 55 55
8 63.5 55 55 55 19.78 mA 8 15.75 55 55 55
9 63.5 55 55 55 19.78 mA 9 15.75 55 55 55

VT-IN HZT-IN VT-RUN HZT-RUN


S.No PHASE VOLTAGE VOLTAGE AT ECP FREQUENCY AT ECP
ECP(V) ECP(F) ECP(V) ECP(F)
1 IN 110 110 50
2 RUN 110 110 50
3 COMM 0
2PFT1 2AT1/2AT2/2AT3 2MWT2 2MVART2
mA ECP DCS mA ECP DCS mA ECP DCS mA

9.97 mA 19.4 KA 19.4 KA 17.25 Ma 600 MW 600 MW 16.68 mA 450 MvAr 450 MvAr 16.68 mA

9.97 mA 9.7 KA 9.7 KA 10.52 mA 300 MW 300 MW 12.68 mA 225 MvAr 225 MvAr 12.68 mA

9.97 mA 4.85 KA 4.85 KA 7.24 mA 150 MW 150 MW 8.68 mA 112.5 MvAr112.5 MvAr 8.68 mA
2HZT1
mA
11.78 mA
11.78 mA
11.78 mA
15.78 mA
15.78 mA
15.78 mA
19.78 mA
19.78 mA
19.78 mA

T8/1VT9 400 KV BUS-2


mA
16 mA
16 mA
16 mA
12 mA
12 mA
12 mA
8 mA
8 mA
8 mA
T3 400 KV BUS-1
mA
11.78 mA
11.78 mA
11.78 mA
15.78 mA
15.78 mA
15.78 mA
19.78 mA
19.78 mA
19.78 mA