Professional Documents
Culture Documents
PIX 36kV
with vacuum switchgear
Installation
Operation
Maintenance
Technical Instrucions
AREVA T&D
PIX 36kV
with vacuum switchgear
Only the specific written Technical AREVA T & D Belgium S.A. Route
Instructions suplied by AREVA with Zenobe Gramme, 33 Zoning des
the equipment must be used. Our Plenesses B-4821 Dison
products must only be Tel. : + 32 (0) 87 320 350
commissioned, operated, serviced, Fax : + 32 (0) 87 320 405
repaired or decommissioned in
accordance with Technical Instruction Great Britain :
which have been supplied with the
p ro d u c t i n q u e s t i o n b y t h e AREVA T & D UK Ltd. Services,
manufacturer. Frederick Road, Salford, M6 6QH,
England
This electronic version of the Tel. : + 44 (0) 161 745 9090
Technical instructions is provided to Fax : + 44 (0) 161 745 448
the customer for information
purposes only. The equipment must Switzerland :
not be commissioned, operated,
serviced, repaired or AREVA T & D
decommissioned on the basis of the Carl-Sprecher-Strasse
electronic version. Non-compliance 3 CH-5036 Oberentfelden
with this instruction may result in Tel. : + 41 (0) 62 737 33 33
serious damage to the product and Fax : + 41 (0) 62 737 31 80
its associated items, as well as a
health hazard or mortal danger. India
AREVA shall not be held liable for any
such consequences. AREVA T&D INDIA LIMITED
1, Taratala Road
1 AREVA AT YOUR SERVICE Kolkata-24
Tel. : + 91 (0) 33 24 50 72 69
Electrical equipment requires special Fax : + 91 (0) 33 24 69 35 11
attention and the compliance with
the provision stipulated in this manual. 2 WITH REGARDS TO
Operating procedures and THIS USER MANUAL
maintenance work must be
performed by qualified staff who are © - AREVA - 2005. AREVA, the
adequately skilled for their tasks. Your AREVA logo and any graphic version
local AREVA Service will be at your thereof are registered trademarks of
disposal at any time for support and AREVA.
advice.
The other trademarks mentioned in
Reminder : The mechanical lock-outs this document, whether registered or
must be designed according to the not, are the property of their individual
general safety provisions for electrical owners.
equipment and the specific provisions
for the network in question. 2.1 Warranty
1
AREVA cannot be held liable for the gases, steam and salts. measured over a period of one
possible consequences of : month, must not exceed 18 mbar.
Admissible air humidity Condensate may from in case of
• non-compliance with the sudden temperature fluctuations
provisions contained in this The average air humidity measured due to excessive ventilation,
m a n u a l , w h i c h re f e r t o over a period of 24 hours, must not increased air humidity or hot air.
inter national regulations. exceed 95%. Such condensate formation can be
avoided by a suitable arrangement
• non-compliance with the The average vapour pressure, of the room or the building (suitable
instructions of the suppliers of measured over a period of 24 hours, ventilation, air dehumidifier, heating
cables and connecting must not exceed 22 mbar. etc.)
a c c e s s o r i e s a s re g a rd s
application and installation. The average air humidity measured If the average air humidity exceeds
over a period of one month, must not 75%, we recommend that
• a n y a g g re s s i v e c l i m a t e exceed 90%. appropriate remedies are adopted.
conditions (humidity, pollution Support or an advice, please contact
etc.) prevailing in the immediate The average vapour pressure, the AREVA Service (see 1.1).
environment of switchgear not
suitable to this effect or not 2.4 Other technical manuals which may be consulted
protected accordingly.
AMT No. T023 General lubrication
This manual does not contain any instructions
instructions regarding the mechanical
lock-outs to be performed. The work No. MVI No. T 36-01 HVX Circuit breaker Installation and operating
described is performed on de- instructions
energized (on installation) or
No. MVI No. T 36-02 UTX & MTX Installation and operating
mechanically locked-out
instructions
(decommissioned) switchgear.
AMT No T053 DCX Presentation -
2.2 Eco-friendly design and
Commissioning - Operation
utilization of the materials
used
AMT No T054 DCX Parameter setting by PC
Instructions Mannual
The design and execution of our
packaging materials corresponds AMT No T069 DCX Modbus Communication
(in France) to the decree in
P 98-638 dated 20 July 1998 as 2.5 Tools and maintenance products (not supplied)
regards environmental compatibility. necessary for operations described in this instruction
manual
2.3 Normal to the operating
conditions (as provided by • Cutter
standard IEC 60694)
• Crow bar
Admissible ambient temperature
• Open-ended spanners size 8; 13; 16; 18
The ambient temperature must be in
the range of -5°C to +40°C. • Ratchet wrench with socket sizes 8; 13; 16; 18
The average value measured over a
period of 24 hours must not exceed • Allen keys for hexagonal screws size 8; 10; 12
35°C.
• Torque wrench with sockets size 13; 16; 18 and
Installation altitude sockets for hexagonal screws size 12
The ambient air must be free of dust, • Grease for electrical contacts Electrolube 2GX
smoke, corrosive or combustible from Comindus 22
2
2.6 Special instructions for operation and 3 PRESENTATION
any intervention with energized equipment
3.1 Description
When commissioning and operating switchgear equipment
under normal conditions, the general electrical safety The PIX-36 cabinet is made of :
instructions (gloves, insulating stool, etc.), as well as
operation handling instructions should be respected. • the front female connector which includes the
“switchgear” compartment (with withdrawable circuit
All manipulations must be completed once started. breaker), running up the low pressure box,
The length of time required for carrying out the operations • the rear female connector including, at the top, the
mentioned in the tables are given purely as an indication “busbar” compartment and at the bottom the “cable”
and depend upon conditions on-site. compartment.
Code of a product recommended and The circuit breaker compartment contains a withdrawable
06 marketed by AREVA truck with Vacuum Circuit Breaker or Bus PT Truck. The
breaker terminals are fitted with deflectors which are
Value of the tightening torque Example : 1.6 loose to turn freely.
16
daN.m
The withdrawable truck can be transferred between the
10 Mark corresponding to a legend service & test position behind closed doors using a hand
crank.
CAUTION ! Remain vigilant ! Precautions to
be taken in order to avoid any accident or Main earth bar with a small link for the connection houses
injury. in this compartment.
2.8 Tightening torques for standard The truck is locked against withdrawing and is earthed.
assemblies (bolt + nut)
The low voltage circuit is connected through the low
Threaded fasteners without grease : assembly with voltage plug connection.
ungreased washers.
3.1.1.2 Test Position
Threaded fasteners with grease : assembly with greased
A = LV Compartment
washers. B = CB Compartment
C = Bus Bar Compartment Bus bar support
Blow off cover
Use grease referenced 01 D = Cable Compartment
6
Bus Bar
Dimensions Ungreased zinc-plated Greased Chamber
7 C
steel threaded stainless A Spouts
LV Chamber 2
fasteners (daN.m) steel fasteners 1
Earth
(daN.m) 12
Switch
Live Line
Class 6.8 Class 8.8 A2-70 Indication
8
Breaker
Chamber
3 D 9
M6 7 9 7 B 4
11
LV Cable entry 13
10
M8 16 21 16
Current Transformer
Cable Entry CT & Cable Chamber
M 10 32 43 32
M 12 50 66 50 Fig (1)
M 20 262 350 262 In the test position, the truck with the breaker is withdrawn
so far between busbars & outgoing cables that there is
an isolating distance. The truck is locked against moving.
3
LV equipment
Feeder label
description
Rating plate
OFF
ON
Manual spring
charging Door Lock
Viewing
window
End cover
Apperture
for racking
Door opening lever
Fig (2)
The low voltage circuit is connected through low voltage • Support Insulator.
plug connection. Also metallic shutters drop down and
cover spouts which contain mating contacts. The circuit The main busbars are mounted on cast resin insulators.
breaker truck is earthed via earthing fingers scraping
against the fixed bar fitted on the base sheet. The circuit
breaker can be earthing tested for all functions.
3.1.3 Cable and CT compartment (D) (ref
3.1.1.3 Disconnected Position (Isolated Fig. 1)
Position)
The Cable compartment contains :
The position of withdrawable truck in which an isolating
distance or segragation is established in both primary • Spouts with the mating contacts for the lower
and secondary circuits of the withdrawable truck, whereas contact arms of the withdrawable part.
the truck remaining mechanically attached to the
enclosure. • Cable termination pieces
The position of withdrawable truck when it is outside LV compartment contains all the low voltage devices
the panel & electrically as well as mechanically (protective relays, MCBs, terminals, etc.) Indicators and
separated from it. Ramps are provided separately with re l a y s a re a c c o m m o d a t e d i n d o o r c u t o u t s .
the panel to withdraw the truck out of the panel
smoothly.
3.1.5 Accessories
The earthing fingers at the bottom of the breaker scrap
against the fixed earthing bar fitted on the base sheet Following accessories are supplied with the
of C.B. compartment ensuring the earthing of the truck switchgear :
in service, test, disconnected & transit position.
• Hand crank for charging the closing spring of the
3.1.2 Busbar Compartment (c) vacuum circuit breaker when in service
position.
The busbar compartment contains :
• Hand crank for truck movement between service
• The busbars and test position.
• Spouts with the mating contacts for the upper • Key for CB & LV compartment lock.
contact arms.
4
Contact Front
4) Incoming/Outgoing + 2 CTs/phase + earth switch
cover
5) Incoming/Outgoing + 2 CTs/phase + earth switch
+ Isolatable PT
On
Rod for
closing &
tripping the 6) Link connection + 1 CT/phase + earth switch
breaker
Spring
charging 7) Link connection + 1 CT/phase + earth switch +
opening Fixed PT
• Earthing switch handle (Optional). 11) Bus sectionaliser with current transformer
General :
11 12 13 14 15
3.1.6.1 Feeder Panels
3) Incoming/Outgoing + 1 CT/phase + earth switch + Basically metering panels are of the same construction
Isolatable PT as the standard outgoing panels. The metering truck with
5
voltage transformers & HRC fuses in series is equipped packaging]
with three upper isolating contacts & three other isolating
contacts which are not installed. In the cubicle the cutouts Functional Approximate Width Height Depth
for spouts are blanked. unit weight
With circuit
3.1.6.4 Panel with I/C & O/G Connections breaker (mm) (m) (mm)
(kg)
These panels are comprising of Incoming & Outgoing
Cables in the same panel. “Bus-riser” 1000 1200 2950 2550
• C.T.s are mounted on stationary part in the cable • Packaging for road and rail transport : functional
chamber. There are easily detachable individually. unit on wooden pallets and wrapped under plastic
film.
• Line P.T.s are available with an arrangement of
drawout fuses.
4.2 Reception
3.3 Dimensions and weights of the
functional units with no circuit breaker [with On reception, ensure that the switchgear is complete.
6
Carry out a visual examination of the functional of units
and moving parts.
• It is imperative that the forks of the truck are fully • Never handle the circuit breaker by its connecting
engaged throughout the entire width of the crate. plates.
7
• Packaging for road and rail transport : using two
slings supporting 1500 kg each and a lifting device.
8
4.6 Intervention levels 5. Unpacking and assembling the
equipment
Definition Level
5.1 Civil engineering characteristics
Operations carried out by the client 1
The installation of a switchboard necessitates a sufficiently
Operations requiring training and which flat civil engineering surface.
can be performed by an approved
third party 2 Levelling off by the use of a finishing cement layer must
be used to eliminate any asperities or declivities greater
Work, which can only be carried out then 2mm per metre.
by AREVA 3
A layout on iron supports truly levelled is ideal since it
4.7 Special Instructions for a storage period also acts as a guide for the adjustment of the layer of
between 0 and 6 months finishing cement.
• The minimum threshold (85% of Un) 5.3 Unpacking of the functional units
of the coil electrical operation should
be tested. – X X The functional unit should only be unpacked on the
installation site.
4.8 Special instructions for a storage period
between 6 and 12 months
4.9 Special instructions for a storage period • Carefully extract the cubicle using crane & put it on
between 12 and 24 months the floor.
Wrapped under heat sealing cloth with • Rack out the breaker using proper handle to test
inspection doors to change the desiccant bags 1 2 3 position as directed on the door.
9
• Unlock the door of the cubicle by the key provided
on the front door itself.
• Open the low voltage plug from the breaker & park
it beneath the low voltage chamber.
Front facing
Minimum rear
passage
Minimum front
passage
V.T.
“cable”
housing
10
Functional Minimum Minimum Minimum Minimum 6.4 Inter-functional unit earthing circuit
Unit front rear rear height connection
passage (mm) passage under
(mm) with voltage ceiling
Main Earth Bar of Cubicle
transformer (mm)
cables (mm)
6 Installation - Connections
Viewed from
the side
To connect two functional units together :
9 coupling
points :
1 Unscrew the bolt M8 x 35 (13 mm spanner) retaining
• 9H M 10x20 Viewed
screws from the busbar link.
• 9H M10 the rear
nuts
2 Slide this link through the functional units flange.
• 0H M10
unit
• 14 C10 • In the adjacent functional unit :
washers
Unscrew the fixing screw.
11
• Connect the earthing circuit linking all of the • Unscrew the bolt fixing the MS pipe to the support
functional units to the room’s earthing bar (Threaded insulator.
fasteners and earthing cables not supplied).
• Do both the above steps in adjacent panel as well.
The fresh plate shall be projected out of end cover as
shown in the diagram. • Replace the steel pipe with proper busbar.
6.6 Connecting the busbar • Loosely screw the busbar while still holding the
other end ensuring the packer piece is in the place
When connecting the different elements of the busbar : as shown in the diagram.
• respect the mounting directions of all the parts, • Replace the steel pipe of adjacent cubicle of same
phase by other end of the busbar.
• use the screws found in the accessories pack
• Loosely screw the busbar and that ensure the packer
• use the screw tightening torques recommended by piece is in place as shown in the diagram.
AREVA
• Put back the top support of busbar on both the
Make sure that the contact surfaces are clean. No ends.
other preparation is necessary to connect the copper
on copper, plated aluminium on plated aluminium and • Loosely screw the top support.
plated aluminium on copper connections.
• Tighten all the screws using appropriate torque as
Blow off covers to be
opened for busbar access mentioned earlier.
Top support
of Busbar Top support
of busbar
Bottom
support of
busbar
End cap of
busbars
Fixing Screw
M12
Packer piece
12
6.7 Preparation of the cable connection
• maximum cross-section :
630 mm2 with a maximum of 5 cables per phase,
13
- For cables>400 mm2, four M8 screws, 8.8 Rigorously observe the locking-out operations and tests
class, tightening torque : 1.6 daN.m. under the operating conditions on site.
Operational manoeuvres
of the moving parts
- Plugging-in and
un-plugging operations.
- LV plug connection.
• Connect the 3 earthing braids to the earthing circuit
(M8 x 25 screw, 13 mm spanner). - Arming, closing, tripping.
14
Details of the checks Date Notes Signature
Electrical tests
- Verification of the earthing
circuit continuity
- Checking the connections
of the LV links.
- Operational test of all of
the LV equipment.
- Recording of the relay
parameter settings after
having checked that the
switchboard is operating
correctly.
7 Operation
15
• Dis-engageable plugging-in and withdrawing
crank handle for the circuit breaker’s moving
part.
16
8.2 Unplugging operation for the moving part
(Compulsory before opening the door)
17
• Closing 9.4 Closing and tripping the circuit breaker
Fit the rod into the right-hand opening, through the by push button [door closed]
door, and push it home.
• Tripping
Fit the rod into the left-hand opening, thorugh the
• 2 To close the breaker, press the (black) button
door, and push it home.
on the right.
• The circuit breaker trips.
• The mimic diagram through the view port confirms • 3 To trip the breaker, press the (red) button on
the “closed” position. the left.
18
7.6 Electrical operations on the circuit 3- Press to open: the animated mimic diagram
breaker by DCX command control indicates “tripped” (turns green).
• Closing the circuit breaker : 2 Press to plug-in: the animated mimic diagram
indicates “plugged-in” (turns red) at the end
1- Preselect by pressing once: the indicator light of the manoeuvre.
flashes for 5 sec, the time to give the desired
order.
1- Preselect by pressing once: the indicator light 3 Press to unplug (withdraw): the animated
flashes for 5 sec, the time to give the desired mimic diagram indicates “withdrawn” (turns
order. green) at the end of the manoeuvre.
19
8 STANDARD LOCKING OUT AND INTERLOCKING PROCEDURES
The PIX functional units are equipped with mechanical function interlocks, intended to avoid any kind of operational
error.
• Between the plugging-in of the • The plugging-in of the moving part is • The racking handle can not be
moving part and the installation impossible if the low voltage plug is inserted to desired position.
of the low voltage plug. not connected.
• Between the plugging-in of the • Plugging-in of the moving part is • Earthing interlock lever prohibits
moving part and the earthing impossible if the earthing switch is VCB movement.
switch “closed”. closed.
• Between the closure of the • Closure of the earthing switch is • Earthing interlock lever prohibits
earthing switch and the position impossible as soon as the moving “ON” movement.
of the moving part. part is in the course of being
plugged in or is “plugged-in”.
• Between the plugging-in and the • Plugging-in of the moving part is • Interlock lever prohibits insertion
closed state of the moving part. impossible if the latter is closed. of the crank handle.
• Between the closing of the moving • Closing of the moving part is • Electrical and manual command
part and plugging-in. impossible outside of the controls of the moving part are
“Plugged-in” or “Test” positions. impossible.
• The rear cover opening & • Opening of rear cover is impossible • The interlock lever prohibits the
earthing switch closure. if the eathing switch is in “OFF” rear cover movement.
condition.
• Cubicle front door opening • Opening of the front door is • The interlock lever prohibits the
& moving part in plugged-in impossible if the moving part front cover movement.
condition. is plugged-in.
• Between Low voltage plug & • Opening of the LV plug is • The interlock lever prohibits the
position of moving part in impossible if the moving part LV plug opening.
plugged-in condition. is plugged-in.
8.3 Interlocks using keylocks • If several padlocks are used in one location, an
accessory (not included in scope of supplies) is
• 1 Locking the earthing switch in the closed used.
20
9 COMMISSIONING - Aming, closing and
tripping.
9.1 Importance Notice
Tests and trials Date Remarks Signature
Prior to dispatch, PIX functional units are mechanically
and electrically tested. Dielectric tests
If the material has been stored in a damp location, it is - Whilst taking all
recommended that the room must be heated and the precautions necessary,
heating coils must be energized for a period of 24 hous carry out a dielectric
prior to installation. test on the HV
equipment and LV
Also check to leaking devices in the room, the cable cabling.
troughs, ventilation etc. NB: These tests must be
carried out prior to electrical
9.2 Inventory of tools and accessories on testing.
completion of work on site
Electrical tests
Recover, draw up an inventory and tidy away all assembly
tools and objects not required in the switchboard. - Check the continuity
of the earthing circuit.
Return the functional unit’s and circuit breaker’s operating
accessories to their respective storage positions. - Check the connections
on the LV links.
Post the technical Manual PIX in a clearly visible position.
- Test the correct
9.3 Principle pre-commissioning checks operation of the LV
switchgear.
Visual inspection Date Remarks Signature
- Record the relay
- Ensure there are no parameters.
foreign bodies within
the switchboard State of the switchgear Date Remarks Signature
- Connection of the Energize the busbar. To do this, plug-in and close the
LV socket. circuit breaker (ses § operation).
21
9.5 Voltage test [VPIS indicators] 9.8 Voltage presence testing [VDS
indicators]
The indication of a VPIS, by itself, is insufficient to enure 9.9 Check phase coincidence using a
that the system is de-energized; if the operating rules phase monitor [VDS indicators]
demand it, then the appropriate voltage detectors must
be used to that effect, in compliance with IEC 61243-5. Checking the phase monitor
22
Opening the door is only authorised for the
maintenance operations.
• Turn it in anti-clockwise direction to unlock the door. 10.3 Disconnection of low voltage plug
• Turn handle downwards as shown : the door lifts Isolate the low voltage auxiliaries before
up. d i s c o n n e c t i n g t h e m o v i n g p a r t ’s p l u g .
23
• Pull horizontally on the low voltage plug unlocking • Plug it into the moving part’s socket and lock it.
lever.
• Pull out the low voltage plug from its housing. • Ensure following :
24
11 MAINTENANCE
Definition Levels
All preventive and corrective maintenance, all renovation and reconstruction work
to be carried out by AREVA 3
25
Operations recommended at the functional unit level 3 years 6 years 1 2 3
26
11.4 Systematic preventive maintenance
A systematic check of all High Voltage connections In certain cases, it may be necessary to grease certain
tightening points may be requested by the customer screws (please refer to the assembly drawings).
Apply the General Safety Instructions for Greases : Duration : 2 hrs per functional unit
Electrical Applications and the particular see § 2.5
regulations for the network concerned
for the locking out procedures.
• Unusual noises Voltage presence box • “Faston” plug poorly • Check the connections
when energized, connected
cracking, Capacitive voltage divider • Defective voltage • Replace the defective
extinguishes divider capacitive voltage divider
Insulators • Polluted or degraded • Clean the parts or consult our
insulating parts After-Sales Service : see
address at the beginning of
the manual
• Voltage presence MV fuse on outgoing • Fuse blown • Replace all three fuses
indicator switch or contactor
gushed. Voltage presence box • Deterioration of a • Replace the box
component
• Abnormal efforts Earthing switch • Safety interlocking • Check the position of the
for mechanical control mechanisms
parts operations Plugging-in of the circuit • Safety interlocking • Check the positions of control
breaker mechanisms
moving parts
• Circuit breaker Line section switch or • Line section switch or • Check the closure of the switch
does not close LV circuit breaker LV circuit breaker open or the LV circuit breaker
Protection devices • Action by protection • Check the adjustments
devices
External connections • Poor connection • Check with wiring diagrams
Low voltage connector • Poor connection • Check the connections
of the circuit breaker
27
12 SPARE PARTS
12.1 Spare part
Designates an element which is These parts may only be
intended to replace an appropriate replaced by a skilled person
element in order to restore the who has been trained accordingly.
required original function.
1 2 3
These are wear parts which have been Fan (3 each) 30,000 hours energized X X X
developed for replacement once a spe-
cified utilization period has expired. Blocking coil 40,000 hours energized X X X
1 2 3
1 2 3
A list of the technical data of the switchgear must be enclosed with each order of spare parts.
The parts must be stored so that they are protected Some parts are fragile : preferably they should be
against dust, humidity and sun exposure. For convenience kept in their original packaging.
they must be identified with the AREVA item number.
28
13 END OF THE EQUIPMENT SERVICE
LIFE
The tables (§ 13.4) give information and figures for the • Optimising the valorization process.
types of materials, their quality and their methods of
valorization. • Evaluating the cost of valorization.
These enable the following : The indications given in tables (§ 13.3) facilitate co-
operation between users and companies specialised in
• Calculation to be made of the capacities for elimination to valorize the product at the end of the
valorization. product’s service life.
Thermosetting Steel
Parts
Copper +
Aluminium
Thermosetting
Thermosetting
Glass
Copper
Polyster + VI +
Copper
External
Connection Steel
(Not included in
the quantitative
break down
Polyster
Thermosetting
Do not dismantle the mechanical Do not open the poles. Do not dismantle the earthing
control mechanism springs switch’s springs without the
without the releasing device. releasing device.
Regarding decommissioning, • All electrical equipment (coils, • During disassembly, the materials
please consult AREVA drives etc.) must be removed. must be sorted and routed to the
appropriate recycling procedures.
13.4 Dividing up and recycling of the materials used for PIX (see § 13.1)
29
Material Weight (kg) % of Materials Recycling
PC 1
PTFE 0.025 Not recyclable
PVC 0.240
PBT 1
PA 3
Others (PMMA, PE, PET) 0, 1
Total thermoplastic content 4.36 0.25
• Rating Table
• Shipping details
Complete cubicle and breaker goes in it packing and not packed separately. the packing dimensions are as under.
30
www.areva-td.com
Fax : +91(0) 2469 9506
Tel.: +44 (0) 1785 250 070