Professional Documents
Culture Documents
Ex
on
he says.
ati
cita
cit
tio
Ex
n
Regulating the Angle and Flow
Re
ing
Because power flow through a transmission
gu
lat
L3
S2
lati
gu
line is largely a function of the angle be-
Re
ng
tween two voltages, if the angle across the Excitation
line can be regulated, the power flow can
S3
L2
also be regulated. Power can be increased by
Figure 2Delta/hex configuration has two tap-changers
introducing a phase angle that is additive
(advance). Conversely, by introducing an
angle that is subtractive (retard), the power An Automated Control System
can be reduced. SEL engineers designed and installed the
first of the PST control systems within a few
PSTs typically inject a quadature voltage weeks of AEPs request. After testing the
into each phase between the source and the system with the AEP Protection and Control
load bushings to induce phase shifting. group, engineers from their Operations group
Traditional PST designs require two trans- added new specifications to take advantage
former cores to accomplish this task. How- of the PST overload capabilities without
ever, a new type of single-tank PST has undue risk of thermal damage.
emerged. This new design promises to
improve the economic viability of deploying In addition to the automated control system,
such devices on the transmission grid. Thompson explained, The design documen-
tation was an important deliverable in this
On the delta/hex PST, the three excitation project. We wrote a comprehensive instruc-
windings and three regulating windings are tion manual so others can understand how
connected in a delta/hex configuration. Two the tap-changer control works.
three-phase tap-changers are installed: one
for the source terminals and one for the load The primary PST control device is an
terminals. Each tap-changer mechanism SEL-451 connected to an SEL-2100 Logic
moves its terminals up and down the regu- Processor. The SEL-451 receives informa-
lating winding to create the phase shift tion on the open/close status of the bypass,
across the transformer. When the two tap- load, and source breakers via the communi-
changers pass each other, the transformer cations links through the logic processor.
shifts from advance to retard operation. The programming prevents invalid switch-
ing sequences that can result in a trip or
AEPs PST control system is based on the damage to the PST.
SEL-451 Protection, Automation, and Con-
trol System as the core for a transformer tap- For example, there are three different ways
changer control, Thompson explains. In for the control to check to see if the PST is
addition to controlling power flow, the tap- on neutral or not, Thompson explains. If
changer control provides automatic detec- you try to bypass a transformer that is not on
tion of improper tap operation sequences neutral, you are going to get some tremen-
Figure 4In addition to remote control via SCADA, the local user interface allows complete control and indication of PST functions