You are on page 1of 4

CASE STUDY

American Electric Power (AEP)South Texas, United States

Innovative Phase-Angle Control Helps AEP


Optimize Power Flow on Transmission Grid
AEP (American Electric Power) has desired one-pushbutton-in-service and
installed 138 kV, 150 MVA phase-shifting one-pushbutton-out-of-service capabilities.
transformers (PSTs) on the ERCOT (Electric AEP commissioned SEL to engineer, con-
Reliability Council of Texas) transmission figure, and program this control system.
grid. Three units went into service in 2006,
one in 2007, and at least one installation is
planned for 2008. These transformers were
selected to help optimize power flow from
existing transmission system assets until fu-
ture 345 kV line construction projects can be
completed. The delta/hex PSTs deployed in
South Texas are a new, single-tank design
that promises to be much more economical
than previous designs.

These specialized transformers require a


protection system that is redundant, sensi-
tive, and secure for all types of faults,
including turn-to-turn faults in the trans-
former and its surrounding buswork. In
addition, a flexible, automated PST control Figure 1First of several PSTs under assembly
is required. AEP selected a combination of
conventional protection concepts and a com- While SEL is perhaps best known for their
pletely new differential protection system prowess on the protection side of power
that compensates for the variable phase- systems, the company also provides innova-
angle shift introduced by operation of the tive products and services for the control
PST. Traditional percentage-restrained trans- side, including engineering, programming,
former differential protection could not be installation, and training. SEL developed the
used because of the continuously variable power flow regulating tap-changer control to
phase shift across a PST. The protection meet the AEP project requirements.
system incorporates a series of relays from
Schweitzer Engineering Laboratories (SEL), PSTs, also called phase shifters or PAR
Pullman, Washington. (phase-angle regulating) transformers, are
becoming more popular, says SELs
Initially, the original transformer manufac- Michael Thompson, because they are
turer was to provide the PST controls per considered FACTS devices, or flexible ac
AEP specifications. However, because auto- transmission system devices. There is a lot
mated controls were required, the customer of interest in getting more power down ex-
decided that a device with extensive pro- isting lines, which requires advanced power-
grammability was needed to provide the flow regulation.

Case StudyAEP South Texas Transmission Grid Page 1


Thompson adds that while PSTs are becom- and overload conditions. Included are alarms
ing a more common tool to optimize trans- and remedial action schemes that will alert
mission assets, until now the controls have key personnel and take proper actions if a
often been operated manually. SEL has problem occurs.
been able to automate the control technology
to enable the system operator to simply S1 L1
input a megawatt set point, allowing the tap-
changer control to automatically regulate
according to the operators requirements, Regulating

Ex
on
he says.

ati

cita
cit

tio
Ex

n
Regulating the Angle and Flow

Re

ing
Because power flow through a transmission

gu

lat
L3

S2
lati

gu
line is largely a function of the angle be-

Re
ng
tween two voltages, if the angle across the Excitation
line can be regulated, the power flow can

S3

L2
also be regulated. Power can be increased by
Figure 2Delta/hex configuration has two tap-changers
introducing a phase angle that is additive
(advance). Conversely, by introducing an
angle that is subtractive (retard), the power An Automated Control System
can be reduced. SEL engineers designed and installed the
first of the PST control systems within a few
PSTs typically inject a quadature voltage weeks of AEPs request. After testing the
into each phase between the source and the system with the AEP Protection and Control
load bushings to induce phase shifting. group, engineers from their Operations group
Traditional PST designs require two trans- added new specifications to take advantage
former cores to accomplish this task. How- of the PST overload capabilities without
ever, a new type of single-tank PST has undue risk of thermal damage.
emerged. This new design promises to
improve the economic viability of deploying In addition to the automated control system,
such devices on the transmission grid. Thompson explained, The design documen-
tation was an important deliverable in this
On the delta/hex PST, the three excitation project. We wrote a comprehensive instruc-
windings and three regulating windings are tion manual so others can understand how
connected in a delta/hex configuration. Two the tap-changer control works.
three-phase tap-changers are installed: one
for the source terminals and one for the load The primary PST control device is an
terminals. Each tap-changer mechanism SEL-451 connected to an SEL-2100 Logic
moves its terminals up and down the regu- Processor. The SEL-451 receives informa-
lating winding to create the phase shift tion on the open/close status of the bypass,
across the transformer. When the two tap- load, and source breakers via the communi-
changers pass each other, the transformer cations links through the logic processor.
shifts from advance to retard operation. The programming prevents invalid switch-
ing sequences that can result in a trip or
AEPs PST control system is based on the damage to the PST.
SEL-451 Protection, Automation, and Con-
trol System as the core for a transformer tap- For example, there are three different ways
changer control, Thompson explains. In for the control to check to see if the PST is
addition to controlling power flow, the tap- on neutral or not, Thompson explains. If
changer control provides automatic detec- you try to bypass a transformer that is not on
tion of improper tap operation sequences neutral, you are going to get some tremen-

Page 2 Case StudyAEP South Texas Transmission Grid


dously high circulating currents, so high it poor regulation around the desired set point.
would look like a fault. It is necessary to be The tap-changer control installed on the
absolutely sure that it is on neutral before AEP transformers includes a method for
you start any automatic procedures to put adapting bandwidth based on measured
the transformer in or out of service. power changes.

The control provides information through Source Side

AEPs SCADA system to the operations


center. Electronic information is available
inside the local area network at each of the
substations, so the control can automatically
make appropriate decisions as to when to
provide a bypass and when to place the unit MOD
in service. If the operator (dispatcher) starts
Tap Changer Position
to place the unit in service and it fails, a S1 S2 S3
Tap Change in Process PFR Tap-
routine check will send a warning, for exam- PST Lower Tap Changer
ple, if the dispatcher starts to put the unit in L1 L2 L3 Raise Tap
Control

service and it fails, the control returns a mes- IA


sage incomplete automatic sequence and
IB
aborts the process.
IC

Through the SEL-451, the control provides


automatic or manual control of tap-changer Load-Side
Circuit Breaker
Bypass
Circuit Breaker
position and gives operators complete
command of all tap-changer functions with
automatic safeguards to prevent overload
conditions, Thompson says. Programming VA
automatic sequences to run the tap-changer VB
position to neutral and open and close break- VC
ers and motor operated disconnect (MOD)
switches in the correct order enhances Load Side
safety.
Figure 3The tap-changer control measures real power flow
from source to load and controls the tap-changer to regulate
The tap-changer control maintains precise power flow when the bypass is open
regulation of system power flow. Automatic
control functions within the tap-changer The adaptive bandwidth function is one of
control include a power-flow dead-band the powerful innovations incorporated into
control with adaptive bandwidth. the SEL tap-changer control, Thompson
says. It stores the most recent eight tap
Adaptive Bandwidth Control changes in memory registers. So, in effect, it
learns with each step. From the operator
Thompson notes that one of the problems set point and bandwidth, the control calcu-
with automatic control of a discrete step de- lates the upper and lower band limits. To
vice such as the PST is hunting. Hunting prevent operation above the user-settable
occurs when a tap step results in a change in maximum automatic regulation set point, the
power that is near or greater than the total control also calculates band limits from the
bandwidth. For each tap step, the power MVA rating and the measured power factor
change can overshoot the band, and the of the load through the PST and uses the
regulator will soon attempt to step in the more restrictive of the two limits. Without
opposite direction. Selecting a high band- the adaptive bandwidth capability, the AEP
width will reduce the possibility of exces- controls would not have worked.
sive operations and hunting but result in

Case StudyAEP South Texas Transmission Grid Page 3


ENABLED ADJUST MW RAISE
TARGET SET POINT TAP/
RESET
TRIP SET POINT
INCOMPLETE
NEUTRAL
AUTOMATIC SEQ MANUAL LOWER
OK TO PUT OK TO REMOVE ENABLED TAP/
IN SERVICE FROM SERVICE
SET POINT
FLOW HIGH FLOW LOW
-OUT-OF-BAND -OUT-OF-BAND

-TIMING -TIMING AUTOMATIC PUT


ENABLED PST IN
-TIMED OUT -TIMED OUT SERVICE
-RESET -RESET

AUTO-TIMING MAN. CONTROL


REMOTE REMOVE
SUSPENDED CUTOUT ENABLED PST FROM
ADDITIONAL MAINT. L/R SW. SERVICE
ALARMS IN LOCAL

Figure 4In addition to remote control via SCADA, the local user interface allows complete control and indication of PST functions

About AEP About SEL


Headquartered in Columbus, Ohio, AEP is SEL has been making electric power safer,
one of the largest electric utilities in the more reliable, and more economical since
United States, delivering electricity to more 1984. This ISO 9001:2000-certified compa-
than 5 million customers in 11 states. AEP ny serves the electric power industry
ranks among the nations largest generators worldwide through the design, manufacture,
of electricity, owning nearly 38,000 mega- supply, and support of products and services
watts of generating capacity in the United for power system protection, control, and
States. AEP also owns the nations largest monitoring. For more information, visit
electricity transmission system, a nearly www.selinc.com, or contact SEL by phone:
39,000-mile network that includes more +1 (509) 332-1890; fax: +1 (509) 332-7990;
765 kilovolt extra-high voltage transmission or mail: 2350 NE Hopkins Court, Pullman,
lines than all other U.S. transmission sys- WA 99163, USA.
tems combined.

2008 by Schweitzer Engineering Laboratories, Inc. All rights


reserved.

All brand or product names appearing in this document are


the trademark or registered trademark of their respective
holders. No SEL trademarks may be used without written
permission.

SEL products appearing in this document may be covered by


US and Foreign patents. Date Code 20080317 *LCS0024*

Page 4 Case StudyAEP South Texas Transmission Grid

You might also like