Calibration Recommendation

Frequency of Calibration of OMICRON CMC Test


Equipment

Author
Reinhard Kuntner | reinhard.kuntner@omicron.at

Date
July 28, 2014

Related OMICRON Products


CMC Test Sets, FCS (Field Calibration Software)

OMICRON Page 1 of 7
Content

1 General remarks / Terms and Definitions ...........................................................................................3


2 Specifications ........................................................................................................................................3
2.1 CMC 156 .........................................................................................................................................3
2.2 CMC 156 EP ...................................................................................................................................3
2.3 CMC 256-6 .....................................................................................................................................3
2.4 CMC 256-6 EP ................................................................................................................................4
2.5 CMC 256plus ..................................................................................................................................4
2.6 CMC 356 and CMC 353 .................................................................................................................4
2.7 CMC 310 .........................................................................................................................................4
3 Drift .........................................................................................................................................................4
4 Recommended verification, calibration and re-adjustment intervals ..............................................5
5 Service Centers......................................................................................................................................5
Support..........................................................................................................................................................7

OMICRON 2014 Page 2 of 7


1 General remarks / Terms and Definitions
OMICRON specifies a typical and a guaranteed accuracy of its secondary test sets:

Typical accuracy: 95 % (2-Sigma deviation) of all devices of a production lot show the specified accuracy
immediately after a factory calibration.

Guaranteed accuracy: 100 % of all devices of a production lot remain within the specified accuracy for one
year after factory calibration (within 23C 5C in the frequency range from 10 to 100 Hz and after a warm-up
phase of more than 25 minutes).

Verification: conformation by examination and provision of objective evidence that specified requirements
have been fulfilled. (ISO 9000:2005). Verifications can be carried out by any user provided that required
reference devices and accessories are available. Verifications furthermore can be carried out at OMICRON
Service Centers and authorized Service Centers run by OMICRON distributors.

Calibration: a set of operations that establish, under specified conditions, the relationship between values of
quantities indicated by a measuring instrument, and the corresponding values realized by the standard
(reference device) Please note: a calibration does not include a re-adjustment

Re-adjustment: the act of adjusting something to match a standard. Calibrations including a re-adjustment are
exclusively carried out at the OMICRON Development Center in Klaus/Austria.

2 Specifications

2.1 CMC 156

Current Voltage Low level Phase angle Frequency


magnitude magnitude outputs (at 50/60 Hz) (10 1000 Hz)
0.03 % rd. + 0.03 % rd. + 0.015 % rd. + < 0.02
typical
0.01 % rg. 0.01 % rg. 0.005 % rg.
0.08 % rd. + 0.08 % rd. + 0.04 % rd. + < 0.1 0.5 ppm
guaranteed
0.02 % rg. 0.02 % rg. 0.01% rg. 1 ppm (drift)

2.2 CMC 156 EP

Current Voltage Low level Phase angle Frequency


magnitude magnitude outputs (at 50/60 Hz) (10 1000 Hz)
0.03 % rd. + 0.03 % rd. + 0.015 % rd. + < 0.02
typical
0.01 % rg. 0.01 % rg. 0.005 % rg.
0.08 % rd. + 0.08 % rd. + 0.04 % rd. + < 0.1 0.5 ppm
guaranteed
0.02 % rg. 0.02 % rg. 0.01% rg. 1 ppm (drift)

2.3 CMC 256-6

Current Voltage Low level Phase angle Frequency


magnitude magnitude outputs (at 50/60 Hz) (10 1000 Hz)
< 0.03 % < 0.025 % 0.025 % < 0.02
typical
(of range) (of range) (of range)
< 0.1 % < 0.1 % 0.07 % < 0.1 0.5 ppm
guaranteed
(of range) (of range) (of range) 1 ppm (drift)

OMICRON 2014 Page 3 of 7


2.4 CMC 256-6 EP

Current Voltage Low level Phase angle Frequency


magnitude magnitude outputs (at 50/60 Hz) (10 1000 Hz)
< 0.02 % < 0.02 % 0.025 % < 0.005
typical
(of range) (of range) (of range)
< 0.05 % < 0.05 % 0.07 % < 0.02 0.5 ppm
guaranteed
(of range) (of range) (of range) 1 ppm (drift)

2.5 CMC 256plus

Current Voltage Low level Phase angle Frequency


magnitude magnitude outputs (at 50/60 Hz) (10 1000 Hz)
0.015 % rd. + 0.015 % rd. + 0.015 % rd. + < 0.005
typical
0.005 % rg. 0.005 % rg. 0.005 % rg.
0.04 % rd. + 0.04 % rd. + 0.04 % rd. + < 0.02 0.5 ppm
guaranteed
0.01 % rg. 0.01 % rg. 0.01% rg. 1 ppm (drift)

2.6 CMC 356 and CMC 353

Current Voltage Low level Phase angle Frequency


magnitude magnitude outputs (at 50/60 Hz) (10 1000 Hz)
0.05 % rd. + 0.03 % rd. + 0.015 % rd. + voltage: 0.02
typical
0.02 % rg. 0.01 % rg. 0.005 % rg. current: 0.05
0.15 % rd. + 0.08 % rd. + 0.04 % rd. + voltage: 0.1 0.5 ppm
guaranteed 0.05 % rg. 0.02 % rg. 0.01% rg. current: 0.2 1 ppm (drift)

2.7 CMC 310


Current Voltage Low level Phase angle Frequency
magnitude magnitude outputs (at 50/60 Hz) (10 1000 Hz)
0.05 % rd. + 0.03 % rd. + n.a. voltage: 0.02
typical
0.05 % rg. 0.01 % rg. current: 0.05
0.15 % rd. + 0.08 % rd. + n.a. voltage: 0.1 0.5 ppm
guaranteed 0.15 % rg. 0.02 % rg. current: 0.2 1 ppm (drift)

3 Drift
Drift is the change of accuracy over time. The degree of drift depends on environmental conditions like
temperature, humidity, mechanical stress, frequency and hours of use.

Statistical evaluation of test sets show a drift of less than 200 ppm (0,02 %) per year in the vast majority of all
investigated devices. However, in rare cases drift effects could be verified up to 400 ppm per year.

OMICRON 2014 Page 4 of 7


4 Recommended verification, calibration and re-adjustment intervals
The precision requirements of a test set strongly depend on the applications it is used for. Protective relays
often measure the measurement quantities (V, I) in a quite inaccurate manner. Typical errors in magnitude
and phase angle are > 1 %. Relay testing thus can still be performed with a test set that does not meet its
initial accuracy specs. anymore. A magnitude error of 0.2 % for instance is still adequate in many applications.
In other cases where the test set is used for calibration of meters (class 0.2), transducers, PQ meters or
PMUs (Phasor Measurement Unit) the enhanced accuracy of a CMC 156 EP, CMC 256-6 EP or CMC 256plus
may be required and full attention has to be paid to regular accuracy checks (verifications) and re-calibrations
(including re-adjustments).

For relay testing applications it may be possible to extended calibration intervals to two or even three years. In
this case we recommend verifying the accuracy of the test equipment with on-site checks performed every 6
or 12 months to ensure that the equipment is still within the required tolerances. In addition we recommend a
factory re-calibration that always includes a re-adjustment at OMICRON Austria in regular intervals (i.e. every
three years).

For device calibrations of meters, transducers, PQ meters, PMUs or any other accurate measurement device
a re-calibration interval of one year is highly recommended. If national regulations call for shorter calibration
intervals additional on-site accuracy checks (verification) may be performed by the owner of the equipment
every 3 or 6 month.

On-site accuracy checks (verifications) and calibrations are supported by FCS. (Field Calibration Software)
FCS is integrated in the Test Universe software, for more details please consult the Test Universe software
help. Please note: FSC does not support CMC 310 and does not facilitate re-adjustments!

In case of increased verification or calibration intervals the user is responsible to ensure appropriate accuracy
of the test equipment by cross-referencing the accuracy with traceable reference equipment with appropriate
accuracy on a regular basis or prior to use. Typically the accuracy of the reference equipment should be 5
times better than the device to be verified or calibrated.

5 Service Centers
CMC users may carry out accuracy checks (verifications) by themselves. It must be pointed out that accurate
measurement equipment is required which is not available in many cases. More information on the required
equipment can be found in the TU software / FCS online help. As an alternative CMC test sets (and
amplifiers) can be sent to the nearest OMICRON Service Center or local Service Center run by an OMICRON
distributor. These Service Centers are fully equipped with the entire required reference measurement devices.

However, it must be re-emphasized that Calibrations including a Re-adjustment and calibrations of CMC 310
can exclusively be carried out at the OMICRON Development Center in Klaus/Austria.

OMICRON Service Centers


OMICRON electronics GmbH OMICRON electronics Corp. USA OMICRON Energy Solutions Private Ltd
Austria USA India
Oberes Ried 1 60 Hickory Drive Office No. 201E/A, 2nd Floor, D21 Corporate Park
A-6833 Klaus/Austria Waltham MA 02451 United States Near Dwarka Sector - 8 Metro Station
Phone: +43 59495 Phone: 1-800 OMICRON Sector 21, Dwarka,
support@omicron.at info@omicronusa.com New Delhi 110075
Phone: +91 11 301 57 935/936/937
support.india@omicron.at

OMICRON electronics Australia Pty Ltd OMICRON electronics Asia Limited OMICRON Power Technologies Cons. Co., Ltd.
Australia Hong Kong Unit No. 1110, Harbor Ring Plaza
Suite 21, 2 Enterprise Drive Unit 2812-19, 28/F, The Metropolis Tower No. 18 Xizang Road (M)
Bundoora VIC 3083 10 Metropolis Drive, Hung Hom, Shanghai 200001
Australia Kowloon, Hong Kong SAR of China China
Phone: +61 3 9466 7655 Phone: +852-3767-5500 Phone: +86 21 6886-9055
support.australia@omicron.at support.asia@omicron.at support.asia@omicron.at

OMICRON 2014 Page 5 of 7


OMICRON electronics Korea Inc. OMICRON Energy Solutions de Mxico
South Korea Paseo de las Palmas No. 731 Despacho 401
PoongLim I-want plus T-1306, Colonia Lomas de Barrilaco
255-1 Seo Hyun-Dong Delegacin Miguel Hidalgo
Bun Dang Goo, 11000 Mxico D.F.
Gyeong Gi Do 463-862 Mxico
South Korea Phone: +52 55 5046-6500
Phone: +82 31 708 1472 info.mexico@omicronusa.com
info.korea@omicron.at

Local Service Centers run by Distributors

Alectrix (Pty) Ltd. Marke Elektronik San. Tic. Ltd. Sti. Adimarco Representaes e Servios
South Africa Turkey Brazil
Unit C15, Mainstream Centre, Ataturk Mah. Alemdaroglu Sok. No. 10 Av. das Amricas,
Main Rd. 7806 Hout Bay 34758 Atasehir stanbul 500 - Bloco 10 - Sala 202
South Africa Turkey Barra da Tijuca
Phone: +27 21 790 1665 Phone: +90216 455 50 63/64/65 Rio de Janeiro 22640-100
alexander.dierks@alectrix.co.za info@markeelektronik.com
javascript:linkTo_UnCryptMailto('nbjmup+ojujonbibo3111Azbipp/dpn');
Phone: +55 21 2494 7140
adimarco@adimarco.com.br

EKRA Ltd Research and Production ENSYS S.A.C. ERASMUS


Russia Peru Colombia
428003 Cheboksary Jr. Alicante # 282 Centro Diagonal 40A No. 18-09
Chuvash Republic Russia Urb. Higuereta-Santiago de Surco Bogot
Phone: +7 8352 220110 Lima 12 Phone: +57 1 486 4030
soloviev_my@ekra.ru Phone: +51 1 652 3572 info@erasmus.com.co
acoronel@ensys.pe

IDUR S.A. Sunertech PT. Citra Wahana Sekar Buana


Argentina Philippines Indonesia
Av. Sucre 2074 1 piso - Of. 5 2F The Victoria Plaza Graha Arteri Mas Kav. 26
1643 Beccar, Prov. De Buenos Aires 41 Annapolis Street, Greenhills Arteri Jalan Panjang No. 68
Phone: 4719-5972 San Juan City 1502 11520 Jakarta
info@idur.com.ar Phone: +63 2 724 7203 Phone: +62 21 5800118
customersupport@sunertech.com sales@cwsb.co.id

OMICRON 2014 Page 6 of 7


Support

When you are working with our products we want to provide you with the greatest
possible benefits. If you need any support, we are here to assist you!

24/7 Technical Support Get Support


www.omicron.at/support
www.omicronusa.com/support

Offering our customers outstanding support is one of our top priorities. At our
technical support hotline, you can reach well-educated technicians for all of your
questions. Around the clock competent and free of charge.

Make use of our 24/7 international technical support hotline: +43 59495 4444.

Additionally, you can find our Service Center or Sales Partner closest to you at
www.omicron.at or www.omicronusa.com.

Customer Area Stay Informed


www.omicron.at/customer
www.omicronusa.com/customer

The customer area on our website is an international knowledge exchange platform.


Download the latest software updates for all products and share your own
experiences in our user forum.

Browse through the knowledge library and find application notes, conference papers,
articles about daily working experiences, user manuals and much more.

OMICRON Academy Learn More


www.omicron.at/academy
www.omicronusa.com/academy

Learn more about your product in one of the training courses offered by the
OMICRON Academy.

OMICRON July 2014


www.omicron.at | www.omicronusa.com Subject to change without notice.

You might also like