G19456 - DH-485 Cables used with SLC-500 processors and the 1747AIC
Network.
The link coupler provides 1500 VDC isolation between the communications cable and the
The following diagram shows a pictorial representation of the 1747-C10, 1747-C11, 1747-
C20 cables.
The cable distances are as follows:
1747-C10 -- 1.829 meters (6 feet)
http://domino.automation.rockwell.com/applications/kb/RAKB.nsf/0/F6315921381C164E8525... 6/29/2006
General Information Technote: DH-485 Cables used with SLC-500 processors and the 1747AIC Page 2 of 5
1747-C20 -- 6.096 meters (20 feet)
IMPORTANT NOTE:
The 1747-C13 Cable has the "DRAIN" (+24VDC) & "BROWN" (EARTH GROUND)
missing.
Therefore the cable is NOT capable of powering up the 1747-AIC Link coupler.
http://domino.automation.rockwell.com/applications/kb/RAKB.nsf/0/F6315921381C164E8525... 6/29/2006
General Information Technote: DH-485 Cables used with SLC-500 processors and the 1747AIC Page 3 of 5
CABLE PINOUTS:
Data Highway 485 (DH485) Communication Cables:
1747-C10/C11/C13/C20 CABLE PINOUT & CONNECTOR PART NUMBERS
P1 COLOR FUNCTION P2
These cables have only been tested at the 1ft, 6ft and 20ft length
http://domino.automation.rockwell.com/applications/kb/RAKB.nsf/0/F6315921381C164E8525... 6/29/2006
General Information Technote: DH-485 Cables used with SLC-500 processors and the 1747AIC Page 4 of 5
Drawing the power for the 1747-AIC module through the 1747-C20 cable from a SLC
QUESTION #2:
CAN I MAKE THIS CABLE LONGER THAN 20 FEET?
A-B does not recommend doing this.
Any device further away from the processor than 20 feet should be connected with a pair of
processor faults if you extend the C20 cable and do not use link couplers.
QUESTION #3:
CAN I USE THE 1747-C20 IN PLACE OF A 1747-C11 CABLE?
The 1747-C20 can be used to connect a SLC Processor to the 1747-AIC as long as the 1747-
For indepth information on the SLC 500 family of controllers please refer to
http://domino.automation.rockwell.com/applications/kb/RAKB.nsf/0/F6315921381C164E8525... 6/29/2006
General Information Technote: DH-485 Cables used with SLC-500 processors and the 1747AIC Page 5 of 5
Related Links:
DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of
such subjects. Accordingly, the information in this web site is not intended to constitute application, design, software or other professional engineering advice
or services. Before making any decision or taking any action, which might affect your equipment, you should consult a qualified professional advisor.
ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY OF THE DATA CONTAINED IN THIS
WEB SITE AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION
CONVEYED HEREBY IS PROVIDED TO USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING
DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON
THE POSSIBILITY OF SUCH DAMAGES.
ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF THE INFORMATION (INCLUDING
SOFTWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND
NON-INFRINGEMENT. Note that certain jurisdictions do not countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.
http://domino.automation.rockwell.com/applications/kb/RAKB.nsf/0/F6315921381C164E8525... 6/29/2006