VAMPSET versions

Latest public revision 2.2.122 (For firmware V210)

Revision 2.2.1182.2.122 08.05.2013


minor fix for devices with smaller logic
left menu updating from device fixed
communication settings: com port list updating fixed
logic usage display has now three numbers, indicating inputs, memory and outputs
mouse wheel support added
help/homepage changed to www.schneider-electric.com

Revision 2.2.117 04.04.2013


reading protection stages could fail in time stamps
VEA tester removed
faster group refresh after writing settings to device
UL1y and UL1z scaling support added for virtual measurement

Revision 2.2.116 15.03.2013


GOOSE Subscriber network input bit index now can be updated using SCL files.

Revision 2.2.115 18.02.2013


ICD generation fix: BUG 571 - ICD-File Generation with Quick Connect (F11) and Connect
Device (F5)

Revision 2.2.1132.2.114 30.01.2013


ICD generation supports now edition 2 image
Fixed problem with updating RptId from SCD file

Revision 2.2.1112.2.112 18.12.2012


Fixes on closing password when disconnecting device
Auto com port selection added to communication settings. When USB com port is added,
Vampset selects it when user makes new connection. This can be used for VAMP5X and
VAMP3XX devices
Full group refreshing fixes

Revision 2.2.1082.2.110 14.12.2012


Full group refresh from device after changing parameter values, changing the visible group
and connecting to device
BUG 544: active signal names in matrix fixed
BUG 488: last window position is saved
BUG 511: Select group(s) text fixed
BUG 381: Boot pending text fixed
BUG 365: active signals now updating also in block matrix view
BUG 336: sublocation fixed
BUG 206: text box fixed for large font scaling
Reading available COM ports fixed

1 (11)
Revision 2.2.107 15.11.2012
IDE generation: variable array for harmonics and SDO->DO in datasets support

Revision 2.2.106 09.11.2012


ICD file generation changes: support for NARI SCADA

Revision 2.2.105 18.10.2012


Analog GOOSE values support added: creating ICD file updated

Revision 2.2.104 10.10.2012


EDS file reading: line feed bug fixed

Revision 2.2.103 8.10.2012


About & splash window fixed for Schneider version

Revision 2.2.102 27.9.2012


2.2.102 WIMO firmware update: DB data buffer is allocated only once, not again when db
data fails

Revision 2.2.101 27.9.2012


More fixes to WIMO sw updating via ethernet netport can be given via command line

Revision 2.2.99 25.9.2012


Update linked parameters when doing matrix connections from the logic editor, to prevent
duplicated OMC_ parameters with inconsistent values.
Avoid crash when trying to insert too many functions per block in the logic editor

Revision 2.2.98 14.9.2012


run-scripts: if device outputs multiple lines, all are added to log

Revision 2.2.97 5.9.2012


Supports logic output redirection. Logic output redirects are handled so that the logic outputs
will stay with the logic function they were connected to when editing the logic configuration.

Revision 2.2.96 4.9.2012


Wimo sw update via ethernet fixed
Language packet for G5 devices are generated using only translated lines to get smaller
filesize
Virtual meas: support added for U12y, U12z, U31

Revision 2.2.95 24.7.2012


Arc matrix support (32bits outputs)

Revision 2.2.94 31.5.2012


Since APPID in GOOSE Subscriber configuration is in Hex format configuration of NIs
according to SCD file needed to be corrected

Revision 2.2.93 19.4.2012


Dynamic datasets (persistent) can be created according to SCD file

Revision 2.2.92 26.3.2012


Dynamic datasets (persistent) are added to ICD file

2 (11)
Revision 2.2.91 14.3.2012
Fixed problem with ProfiBus/EthernetIP/DeviceNet views caused by change made for IEC
61850 in version 2.2.90

Revision 2.2.90 21.2.2012


Visualization of faultlog2 list modified: list can become shorter (used in IEC 61850 dynamic
datasets visualization)

Revision 2.2.89 10.2.2012


Support for 3XX

Revision 2.2.88 18.1.2012


Creation of ICD offline is supported

Revision 2.2.87 18.1.2012


Firmware updating fixes:
- BUG 321: db data buffer size increased
- BUG 298: support for manufacturer DeviceID
- "new/old method" text renamed

Revision 2.2.86 21.12.2011


BUG 311: speed changing fixed for firmware (USB file) updating for old devices, for example
VAMP40 5.75->6.88

Revision 2.2.85 1.12.2011


ICD generation: LLN0 elements in DS, 16 RCBs

Revision 2.2.802.2.84 24.11.2011


BUG 295: major fix for firmware updating of G5 devices. Older versions than 2.2.84 should
not be used for updating G5 firmwares (V10.xx). Updating firmwares V6.xx (or older) are not
affected. Only G5 devices are affected. Only small amount of G5 devices can have this
problem, but because of the risk, version 2.2.84 should be used only.
Fixed ICD file generation (no unused LN types, multipliers as text)
Added visualization of line differential diagram
LDP diagram changes
Fixed problem with updating time server IP from SCD file

Revision 2.2.772.2.79 17.6.2011


BUG 192: firmware update continues even if external flash is empty
BUG 195: harmonic display bars cannot go too high
BUG 196: waiting for boot message changed
BUG 203: fix for SpaM reading problem
BUG 204: closing com fixed
BUG 205: virtual meas is set off before booting device and closing com
BUG 207: protocol selections are written first and relay booted, before writing protocol
specific data
BUG 215: scandinavian characters in TestedBy fixed
BUG 209: fix for VAMP321 firmware updating
BUG 218: LCD contrast (and other items which are not sent by write all settings) are now
sent also by write current view, if they have changed (red values). In case not changed, they
are not sent.
BUG 219: Online meas display fixes
BUG 221: fix for using short device names (less than 3 characters)
Terminal com port closing fixed
Serial error dump file added
3 (11)
Revision 2.2.742.2.76 19.4.2011
BUG 179: fix for English.lan
BUG 180: device speed checking is run max three times when connecting to device
BUG 187: even buffer reading fix
20s timeout for opening com port
BUG 185: support for vector diagram with primary values
BUG 194: max virtual meas voltage 500kV
BUG 191: virtual meas view scrolling fixed with small resolutions

Revision 2.2.612.2.73 17.3.2011


BUG 102: EDS file creation fixed for Vista and Windows 7
BUG 130: default paths fixed (for SetPointPS)
BUG 132: changes log fixed
BUG 134136 Reading menus without fast reading mode fixed
BUG 164: virtual meas view scrolling fixed
Virtual meas: peak mode for Io and harmonics controls added, support for VAMP265
ICD file generation: INT128 support added for energy counters
Serial timeout is increased automatically for older devices

Revision 2.2.502.2.59 22.11.2010


BUG 71 fixed (Converting to UTF8 message caused problems with device library)
BUG 46 fixed (problem when changing from edit box to combo box without pressing enter)
BUG 79 fixed (Auto DR reading doesnt come over boot request dialog)
Wrong password message added to Device Setup window
New record trig buttons added
Vampset language selection changed. Now language can be selected from Program
Settings. New language becomes valid after rebooting Vampset.
Support added for new VAMP40 boot code (V5.11)

Revision 2.2.462.2.49 25.8.2010


BUG 18 fixed (problem with matrix signals, max signal count was too low)
BUG 47 fixed (NVRAM size is set to FFFFFFFF on boot code update)
BUG 69 fixed (problem with new FTDI driver 2.8.2, could not communicate with VAMP50)
ICD parser updated for firmware V10.58

Revision 2.2.422.2.45 10.6.2010


Font transfer function added (Chinese support)
Remove language packets function removes also font files
ICD parser: support for new control modes
Bug fix: get ICD/IID file function could crash in quick connect mode
Support for firmware updating in 9600 bps

Revision 2.2.392.2.41 24.3.2010


Writing IEC-61850 configuration fixed (problem with writing settings automatically)
Terminal changes and fixes, pressing CTRL+R runs last command again

4 (11)
Revision 2.2.322.2.38 10.3.2010
Supports V210 firmwares
Terminal works now like any terminal, showing also device boot messages
Online measurement display should not disappear any more
VAMP50 firmware updating uses always 187500 bps speed
Writing all settings fixed for VAMP 100-series (problems with writing voltage meas mode)
Communication error handling improvements
Writing IEC-103 configuration for 100-series fixed
Reading event codes from old devices (firmware < V5) fixed
SPBUS communication fixed, checksum added to all messages
Auto-disconnecting timer fixed
Fix for empty setting range problem
Event buffer supports now more than 200 events
Continuous updating reads maximum of 5 events at a time
Continuous updating started also if booting device was cancelled
Now continuous updating reads also values which were first changed by user, but refresh
from device later without writing to device (bug fix)
Communication error displaying in serial log fixed
Protection status display crashing fixed
Vector diagram display crashing fixed

Revision 2.2.232.2.31 16.2.2010


UTF-8 character conversion for non-G5 firmwares (< V10)
UTF-8 character conversion for older Vampset files
IEC-103 config fixed (UTF-8)
Reading disturbance recordings fixed for older devices (UTF-8 conversion)
Profibus DB data accepts max 8 bytes long items
Firmware update fixes
Restore device DB: default file name added, speed checking removed (for 2-button start)
Read all DB text from device: default file name added
Convert ASCII file to language packet: message texts fixed
Backup device DB always active, support for firmwares V510 added
Language setup fixed on connecting to device

Revision 2.2.162.2.22 4.2.2010


New info added to IID file
Buffer fixes for DeviceNet/EthernetIP config view
Firmware updating vie Ethernet fixed (WIMO & VEA3CG)
Document types changed when exe is not named Vampset
Continuous updating fixed for Network connection
ICD & SCD parsers updated
Better UTF-8 support

Revision 2.2.72.2.15 2.10.2009


SPABUS transmit delay added
Better UTF-8 support
Misc bug fixes

5 (11)
Revision 2.2.6.12.2.6.14 9.9.2009
UTF-8 character coding (only partial support)
Not fully compatible with older devices (until 2.2.38)
61850 updated

Revision 2.2.12.2.6 12.2.2009


Support for V10 firmware (new G5 platform)
Support for EDS & SCD files
New file selection window for language packet conversion
New timeout settings

Revision 2.1.332.1.40 29.7.2008


Event reading adds only unread events
61850: ICD file creation
Net port setting added
IP & port are resolved
PQ-diagram fix for VAMP210
Automatic menu & view update for new device firmware (6.49)
Matrix signals are read in fast mode also when quick connect is not used

Revision 2.1.122.1.32 21.4.2008


Communication changes for new device firmware (6.43)
Communication fix for external IO detection
Fix for modem initialization
Vamp257 FlexIO relay connections are also cleared with Clear Matrix
Option for reading disturbance records automatically

Revision 2.1.42.1.11 11.10.2007


Updates for new device firmware (6.23)
Updates for VAMP 257 (6.23)
Left menu fixes, grouping added
Protection stages: if both setting groups use inverse delay, definite time setting is not visible.
If both setting groups use definite delay, inverse time setting is not visible
Misc communication fixes
Public

Revision 2.1.22.1.3 3.5.2007


Cursor vectors added to disturbance recorder
Public

Revision 1.4.262.1.1 19.4.2007


Updates for new device firmware (6.x)
Writing old file (5.x) to relay running 6.x not allowed
Fixes for booting device via Ethernet connection
Clear all records menu command fixed
Table columns are bit wider

6 (11)
Revision 1.4.11.4.25 28.2.2007
Updates for new device firmware (5.53 5.74)
Several communication fixes
Writing current view works now in Block & AR matrixes
Parameter info box removed

Revision 1.3.19 24.4.2006


Public

Revision 1.3.6 12.12.2005


Disturbance recorder can open files with sample timestamps by forcing to fixed sampling
rate. A warning message is given.

Revision 1.3.5 8.12.2005


Writing logic group by Write Group command, writes also output matrix
(This is needed because matrix signals carry the logic input connections)
BUG FIX: matrix display reading fixed (affected also logic display)
BUG FIX: parameters with clear only access are not written when writing all settings
to device

Revision 1.3.4 7.12.2005


Communication settings layout fixed for longer (French) texts

Revision 1.3.3 5.12.2005


About menu: Version is visible only if Versions.pdf is found
About menu: Help is visible only if Vampset.hlp is found

Revision 1.3.2 7.11.2005


Support for VAMP 2xx firmware v5.32

Revision 1.3 17.10.2005


Logic editor displays input signal status (for VAMP 230/245/255 v5.21)
Logic editor layout updated
Spabus mode: slave address is requested when connecting to device
Reduced CPU usage
BUG FIX: instability problems with matrix displays fixed
BUG FIX: problems with COM port >= 10 fixed
BUG FIX: Scandinavian character fix for logic input & output selections

Revision 1.2.53 2.6.2005


BUG FIX: network connection problems with fast PCs fixed

Revision 1.2.50 27.5.2005


Online measurements display added (requires VAMP 230/245/255 v5.2). This can be enabled
on program settings. Display is active only when continuous updating is on and one or more
measured values are greater than zero.
7 (11)
Revision 1.2.47 4.5.2005
If modem doesnt respond to the first AT command, Vampset tries again with AT&F. This
sets on the modem echo, if initially disabled

Revision 1.2.46 21.4.2005


Fix for firmware updating: errors occuring while saving a tmp file doesnt stop the updating
process

Revision 1.2.44 4.4.2005


Table view type added (for VAMP 230/245/255 v5.2)
New matrix display type added (for VAMP 230/245/255 v5.2)
BUG FIX: clicking mouse above the first parameter on any screen doesnt cause illegal
operation any more

Revision 1.2.15 14.9.2004


New setting: inactive timeout. If communication has been inactive for set time, Vampset
closes the communication port. This is useful for Ethernet connection, thus other applications
can access the device after this timeout.
Browsing log-files on Program Settings: Open dialog is used instead of Write (no more
warnings about overwriting file)
BUG FIX: password is now treated as integer value (not string)
BUG FIX: check box items didnt update from the device correctly !

Revision 1.2.13 6.9.2004


BUG FIX (VAMP 265): selecting IL1..IL3 works now

Revision 1.2.12 31.8.2004


SPABUS slave address setting added to communication settings

Revision 1.2.11 27.8.2004


No need to open a document for using the Device Diagnostics function

Revision 1.2.9 13.8.2004


Quick fix for Finnish language. If the document is in Finnish, the device is forced to Finnish
when connecting to the device
Fix for empty strings.

Revision 1.2.6 10.6.2004


Device Setup dialog added: user can change language, application option, remote port
protocol etc when connecting to new device.

Revision 1.2.2 25.4.2004


BUG FIX: changes log works now correctly with automatic-writing

8 (11)
Revision 1.2 29.4.2004
Changes for VAMP 255 Motor option: blocking matrix supports now > 32 protections stages
Supports faster reading method found on VAMP 255 rev 4.39 (2004/04/05) and VAMP 260
rev 5.83 (2004/04/14)
XOR-function added to logic
BUG FIX: communication problems with Windows NT fixed
BUG FIX: mimic display was always sent to device after opening file and transmitting
changes, even if the mimic was not changed at all

Revision 1.1.70 19.1.2004


Boot window is not shown when Vampset is launched by clicking a file
Vampset rev 1.1.69 didnt show the boot window at all.
BUG FIX: If Vampset document is open, raw recordings could not be opened from
Disturbance Record/Open with the default file extension filter

Revision 1.1.69 7.1.2004


chanhes in "File/Open":
- can open also raw disturbance recordings
- "All VAMPSET Files" file extension filter added
changes in "Disturbance Recorder/Open":

- can open also raw disturbance recordings

- "All Record Files" file extension filter added


Time&Date button is not active on USER access level
If Vampset is not started with "-locked" argument, USER can change user level parameters

9 (11)
Revision 1.1.68 19.12.2003
*.dri files are associated to VAMPSET
(i.e. double clicking those files opens VAMPSET)
in disturbance recorder view, only channels that contain data (any of the samples differs from
zero) are displayed by default
BUG FIX:baud rates below 9600 bps work now

Revision 1.1.65 16.12.2003


support for raw distubance record files, that are read from VAMP relays via SPABUS
menu:"Disturbance Record/Open Raw" added for opening raw recordings
"Ignore Read Errors" setting added. Init reading doesn't stop in case of errors, if this
parameter has been checked
harmonics display added

Revision 1.1.62 3.12.2003


Response timeout setting for local port added

Revision 1.1.57 26.11.2003


SGS Fimko uses this version on EMC testing
BUG FIX: output matrix works now with new VAMP 230 firmware (version 4.x)

Revision 1.1.54 19.11.2003


Response timeout setting for network port added
BUG FIX: Removing communication cable if continous updating is on doesnt cause
illegal operation. (since version 1.1.44)

Revision 1.1.47 6.11.2003


Check box in the setting views is bigger now
BUG FIX: Closing Vampset doesnt cause illegal operation, if Ethernet port is still open
or serial port is open and the cable has been disconnected from the device
BUG FIX: Opening new document while communication port is still open doesnt cause
illegal operation
BUG FIX: Disturbance record reading didnt work on version 1.1.46

Revision 1.1.46 31.10.2003


Parity setting removed from communication settings, because it's never used. Local port (on
the device) works always in no parity mode, and SPABUS mode uses always EVEN parity.
No setting is needed.
Check box is used in setting views for Off/On and Disabled/Enabled type parameters

Revision 1.1.44 9.10.2003


Save Log button added to the communication display.
Homepage & Support added to the Help menu.
BUG FIX: Sync time & date from computer works now correctly if the device
language is finnish. Date was not changed if the date style was v-k-p or p.k.v

10 (11)
Revision 1.1.37 29.9.2003
simple SPABUS mode added. Communicates only with SPABUS slave number 1. This is
implemented only for testing Get/Set/Spa software on the devices and has no real use yet (no
slave address setting)
changes in log view of the progress & communication display
- Read all settings supported
- Boot dialog supported
- Stop & Close buttons added

Revision 1.1.34 18.9.2003


support for VAMP scripts (.run files)
support for SPABUS variable tables, Versions < 1.1.34 cause illegal operation
log view added to progress & communication display, supports the following functions:
- File/Open
- File/Save
- Communication/Run VAMP script
- Disrutbance Record reading
- Write All/Changed settings

Revision 1.1.33 5.9.2003


Public on www.vamp.fi/software

Revision 1.1.32 3.9.2003


Show only used matrix signals function added to View menu
State of this setting is saved within the document file
Changes in matrix printing: only signals, which have at least one connection are printed to
paper

Revision 1.1.26 10.7.2003


support for using Scandinavian characters in device strings
(like main & sub location in Device Info view)
Scandinavian character support in caption view & group view

Revision 1.1.16 13.6.2003


support for IEC-103 data configurations

Revision 1.1.10 27.5.2003


support for VAMP 255 fault logs
support for setting groups
changes in get/set & serial port handling
new colour look
CTRL + TAB can be used for switching between recorder and settings view
CTRL + R reads the oldest disturbance record from device