Professional Documents
Culture Documents
GENERATOR PROTECTION
TYPICAL SCHEMES
L&T SOLUTIONS
R.SESHADRI
MPS Business Unit
Mysore Works
Generator Protection
Typical Schemes and L&T Solutions
1.0 With increasing complications in the power system, utility regulations , stress
on cost reduction and trend towards automation, Generator protection has
become a high focus area. State of the art , microcontroller based
protection schemes from L&T offer a range of solutions to customers to
address the basic protections and control requirements depending upon the size
and plant requirements.
E/F protection (51N) : This will protect the generator from hazardous
leakages and ensure operator safety. Many SEBs have already made E/F
protection as mandatory. L&T Relay for this is MC12A.
MCCB MC12A
r
51 51
N
G
Fig. 1 Protection of
Generators less than 300 kVA
b) By virtue of larger power level, any faults inside the stator or fault
between the neutral of the machine and the breaker terminals can reach
very high intensity.
2
-2-
c) Machines of this size are likely to have external controls for frequency
and excitation so that they can be run in parallel with other power
sources (other generators on the same bus or the local grid). This
necessitates voltage and frequency related protections as well. L&T
Relays UM30A is the best solution for this purpose. Alternately Relay
MV12A (4 Nos) can be used if frequency protection is built in the
engine.
MV12A /
UM30A
r
27/ 81
59
51 50N 51 51N
MC61A
Fig. 2 Protection of
Generators 300 kVA 1 MVA
-3-
..3
-3-
g) Under / Over Voltage (27 / 59 ) : This will protect the machine from
abnormal voltage levels, particularly during synchronization and load
throw off conditions.
h) Under / Over frequency (81) : This will protect the machine from
abnormal frequency levels, particularly during synchronization and load
throw off conditions. This will also help in load shedding schemes for
the generator.
j) Stator Earth fault (64S): L&T relay MC12A will do this job.
5
-5-
4.2 Rotor side protections : Generators of this size, will need rotor side
protections listed below :
c)) Diode failure Relay : Brushless excitation systems will have rotor
mounted diodes, which can become short or open during operation.
Diode Failure relay (RHS) will monitor the condition of these diodes ,
for both open circuit and short, and give alarm.
..6
-6-
For large generators above 10 MVA size, the philosophy of main protection
and back up protection has to be followed. In addition to the protections listed
in Section 4.0, following extra protections are to be considered:
a) 100% Earth Fault Protection : This will help in sensing earth faults
close to neutral.
d) Over Excitation : This will protect the generator from Over fluxing
conditions.
7
-7-
6.0 Generator connected in parallel to grid : Whenever generators are
running parallel to grid, a comprehensive Auto Synchronising & Grid
Islanding Scheme will be required. This scheme will help in synchronizing the
generator to the bus and opening the incomer breaker of the plant whenever
there is a severe grid disturbance, thus protecting the generator from ill effects
of disturbed grid. L&T Relays SPM21, UFD34 , MW33 and MRP11 are ideal
for this scheme. Please see Fig. 5.
..8
-8-
8.0 Summary : The sections above describe the actual requirements and various
options available from L&T towards protection and management of generators
of various sizes. For generators above 1 MVA size, it is also recommended to
have complete data acquisition & control through PC. L&T supplies MSCOM
software for this purpose. The relays like IM3GV, MG30, MD32T,UM30A
can all communicate to a PC and provide all management data.
---ooO&Ooo---