PCS-902

Line Distance Relay

Optionally, the PCS-902 incorporates two sets of CT input for

Application dual-breaker application. The dual-breaker failure protection,


dual-breaker auto-reclosing and stub protection are integrated
for one-and-a-half breaker and ring breaker application.
To enhance accuracy of data sampling, frequency-tracking
function is used to trace the real-time current/voltage value.
The PCS-902 adopts the advanced UAPC multi-processor
platform which is fully complied with IEC 61850 station bus
& GOOSE process bus and supports both traditional electro-
magnetic CT/VT and electronic CT/VT.

Functions
The PCS-902 relay provides numerical line protection with
pilot distance protection, stepped distance protection, current
Protection and Control
protection, voltage protection, single and/or three pole tripping
and auto-reclosing functions. As a full-scheme device, it Pilot directional distance protection. (85)
integrates frequency protection, breaker failure protection Independent distance zone with PUTT, POTT, blocking and
and stub protection. The PCS-902 introduces an extensive DTT (Direct Transfer Tripping).
functional library, programmable logic and configurable I/O, Pilot zero sequence directional comparison protection.
PCS-902

intended for applications on overhead lines and underground (DEF)


cables of all voltage levels, including series compensated The relay includes zero sequence directional overcurrent
lines, double-circuit lines, heavily loaded lines, weak infeed elements for earth fault.
(WI), short lines and extremely long lines. The PCS-902
adopts a wide range of innovative patented technologies, DPFC distance protection. (21D)
such as DPFC (Deviation Power Frequency Component) Innovative Deviation of Power Frequency Component distance
distance protection and unique power swing blocking logic, to protection can quickly clear faults and is immune to the load
guarantee its accurate and reliable operation. current, weak-infeed and power swing.
Line Distance Relay

Four zones of full-scheme phase-to-phase distance


protection. (21P)
Four zones of phase-to-phase distance protection integrates
the memorized positive sequence voltage polarization,
reactance characteristic, direction characteristic, load blinder
and unique low-voltage distance element. The fourth zone can
be set as the reversal directional protection.

Four zones of full-scheme phase-to-ground distance


protection. (21G)
Four zones of phase-to-ground distance protection integrates
the memorized positive sequence voltage polarization,
reactance characteristic, direction characteristic, load blinder
and unique low-voltage distance element. The fourth zone can
be set as the reversal directional protection.

Four stages of directional phase overcurrent protection.


(67P, 50/51P)

Read more on the web


www.nari-relays.com
Overcurrent protection can be supervised by voltage element Frequency tracking.
and directional element. IDMT curves complied with IEC and Frequency tracking is provided to accommodate the frequency
ANSI standard are present for selection. shift in power system.

Four stages of directional zero sequence overcurrent Monitoring and Metering


protection. (67N, 50/51N) CT failure supervision.
Overcurrent protection can be supervised by voltage element VT failure supervision.
and directional element. IDMT curves complied with IEC and Line voltage failure supervision.
ANSI standard are present for selection. Tripping/Closing circuit supervision.
Breaker failure protection for one or two breakers (50BF) Self diagnostic test.
Breaker failure protection can be applied to one breaker and two Fault Recorder.
breakers applications. Fault Locator.
Total 1024 SOE, including tripping, alarm, binary input change
Two stages of under voltage protection and two stages of
and human operation reports.
over voltage protection (27/59)
Under/over phase voltage protection and under/over voltage User-configurable high resolution oscillography of last 24
protection are provided. (positive sequence, negative sequence oscillograms. (Compatible with COMTRADE format)
or zero sequence)
Communications
Four stages of frequency protection (81) Pilot communication schemes (PUTT, POTT, WI) with fiber,
Frequency is calculated reference to the positive sequence carrier or other channels.
voltage. The protection can be supervised by the df/dt element 2 Ethernet ports with IEC 61850 for station bus
and the undervoltage element. 2 optional GOOSE communication for process bus
2 RS-485 communication rear ports with IEC 60870-5-103
Stub protection for T-Zone in a 3/2 breaker application (50S)
protocol
Stub protection is introduced to protect T-zone in a one-and-a-
half breaker scheme or a ring breaker scheme. 1 RS-485 communication rear ports for clock synchronization
1 RS-232 communication rear ports for printer
Time overcurrent protection during VT failure. (51P VT) 1 faceplateRJ45 Ethernet port for testing and setting
Time overcurrent protection will be enabled if the phase-to- GPS clock synchronization.
phase distance protection is blocked by VT failure.

Time zero sequence overcurrent protection during VT failure.


(51N VT) Features
Time zero sequence overcurrent protection will be enabled if the
phase-to-ground distance protection is blocked by VT failure. The typical pickup time is 10 ms for a close-in fault, 15 ms for
a fault in the middle of a line, 25 ms for a remote fault.
Switch-onto-fault (SOTF) logic.
Switch-onto-fault logic is used to clear fault during manually- The relay is based on NRs well established and proven
closing and auto-reclosing. UAPC hardware platform with multi-processor architecture.
The multi CPU technology supports parallel operating

PCS-902
Unique power swing blocking logic. (68) simultaneously.
The power swing blocking logic can prevent mal-operation
during external fault in power swing and clear the internal fault The binary input can be used to initiate the power line carrier
quickly in power swing. transceiver and the optical fiber is optional instead of carriers
to realize the pilot scheme.
Thermal overload protection. (49)
The output of thermal overload protection can be set to tripping The sensitive DPFC distance protection is integrated to target
or alarm. on the quick clearance of internal fault without being affected
by power swing.
Pole discrepancy detection element.

Line Distance Relay


Pole discrepancy detection element is used to protect Each zone of phase-ground distance protection is provided
discrepancy between the pole positions of breaker with with independent zero-sequence compensation and mutual
independent gears. zero-sequence compensation.

Synchronism check. (25) The patented adaptive floating threshold is insensitive to


Synchronism check and dead bus or dead line check are both system imbalance and disturbance. The measuring element
provided for auto-reclosing. can achieve high security and high speed simultaneously.

Auto-reclosing (single and/or three-pole for one or two The unique built-in power swing blocking logic can properly
breakers). (79) supervise the distance protection during a power swing. The
The optional single/three pole auto-reclosing is applicable to one power swing blocking logic can prevent mal-operation for
or two breakers. Priority logic is integrated for use on one-and- an external fault and quickly clear the internal fault during a
a-half breaker application and ring breaker application. power swing.

Voltage and current drift auto adjustment. Single and/or three pole auto-reclosing with synchro-check
The relay continually and automatically traces the voltage and and dead line/bus check are provided for multi-breaker
current drifts and adjusts the zero point to the normal value. configuration. The priority logic of multi-breaker auto-reclosing
is integrated.

Read more on the web


www.nari-relays.com
The relay is insensitive to the power source change and can The two independent data acquisition paths can prevent any
be applied to the weak infeed condition. undesired trip caused by component failure. One works as a
fault detector and the other is designed for protection and its
Instantaneous, definite time and inverse time (IDMT)
logic. Tripping outputs are supervised by the fault detector to
characteristics are available in phase overcurrent protection
prevent a mal-operation.
and the zero sequence overcurrent protection which can
be controlled by directional protection and/or under voltage The connector type is optional, one is the plug in/out terminal
protection through logic setting. connector and the other is the screw terminal connector. The
unique plug in/out terminal connectors are used to connect the
Independent distance protection is designed for pilot scheme
rear panel to the terminal blocks on the rack or cabinet, making
to realize PUTT, POTT, Blocking and DTT application.
on-site commissioning and replacement much easier than using
Additional three zones of forward distance protection and
traditional screw terminals.
one zone of reverse distance protection are provided.
The relay provides GPS clock synchronization, including SNTP,
Users can select either Mho or quadrangle with Mho
binary input, and IRIG-B synchronization.
characteristics for distance protection. The load blinder
function is also integrated. The relay is compatible with multiple protocols- IEC61850 and
IEC 60870-5-103 for station level, GOOSE and IEC61850-9-2
The independent phase selection element can select the
for process level. It supports communication interfaces such as,
faulty phase and make a phase trip correctly, even for a high
RS485 and Ethernet.
resistance fault.