Professional Documents
Culture Documents
TSguide 11 06 PDF
TSguide 11 06 PDF
Troubleshooting
Guide
Registered TradeMarks
Ceragon Networks is a registered trademark of Ceragon Networks Ltd.
FibeAir is a registered trademark of Ceragon Networks Ltd.
CeraView is a registered trademark of Ceragon Networks Ltd.
Other names mentioned in this publication are owned by their respective holders.
TradeMarks
CeraMapTM, PolyViewTM, EncryptAirTM, ConfigAirTM, CeraMonTM, EtherAirTM, and MicroWave
FiberTM, are trademarks of Ceragon Networks Ltd.
Other names mentioned in this publication are owned by their respective holders.
Statement of Conditions
The information contained in this document is subject to change without notice.
Ceragon Networks Ltd. shall not be liable for errors contained herein or for incidental or
consequential damage in connection with the furnishing, performance, or use of this
document or equipment supplied with it.
Information to User
Any changes or modifications of equipment not expressly approved by the manufacturer
could void the users authority to operate the equipment and the warranty for such equipment.
Copyright 2006 by Ceragon Networks Ltd. All rights reserved.
General .......................................................................................................... 1
Visual Inspection............................................................................................... 1
This guide explains the alarm indications of the FibeAir system, and contains procedures for troubleshooting
and fault isolation.
Maintenance Policy
To ensure simple and efficient system maintenance, the on-site technician will only replace IDU, ODU, or
RFU modules, and not repair them. Under no circumstance will the technician be permitted to open the
equipment in order to repair a module or circuit board. Opening equipment will terminate the Ceragon
warranty.
Maintenance procedures the technician can perform include visual inspection, cleaning, cable/connector
repair, link alignment/adjustment, and retorquing antenna mount bolts.
Visual Inspection
The following table lists the suggested preventive maintenance procedures, which include visual inspection of
the equipment and verification of operational parameters.
Corrective maintenance consists of the steps described in the following sections. The steps provide a logical,
sequential method for diagnosing and resolving system problems.
This step is generally peformed by the customer's field technician or supervisor. Examples of symptoms
include IDU alarm is red, complete loss of service, and excessive errors.
Symptoms may be constant or intermittent. Constant symptoms require immediate troubleshooting attention.
Intermittent symptoms may require circuit monitoring or robust test procedures prior to troubleshooting.
After you have a clear definition of the symptom, the malfunction can be isolated using diagnostics, loopback
testing, fault isolation tables/flow charts, test equipment, and manual procedures.
This step will identify the specific piece of equipment that is failing.
Although it may be difficult at times to immediately determine which part of a radio link is causing the fault,
the initial suspicion should be focused on one of the following near-end or far-end issues:
y Power supplies
y Fading (due to heavy rain, new obstacle in path, antenna misalignment)
y External equipment (SONET/SDH, ATM, FastEthernet, etc.)
y Indoor Unit (IDU)
y Outdoor Unit (ODU)or Radio Frequency Unit (RFU)
y RF cable between the ODU/RFU and IDU
y Exposure of equipment to severe conditions (high temperature, etc.)
y System configuration
Once the fault has been isolated, you will need to understand why the fault occurred and what is required to
correct it. Use the tables provided in the following sections to understand the problem, and for suggestions of
possible solutions.
Use the troubleshooting information in this guide to help solve the problem.
The following table lists the LEDs on the IDU panel and their functions.
Color
LED Description
Red Yello Green
w
For Hitless systems, the following table lists the LEDs and their indications:
If, after the radio link is installed, the payload is not received, there may be a problem either with the line
interface connection to FibeAir, or with external equipment.
Before you perform line interface troubleshooting, check the following items, which are common causes of
line interface failures:
y Both external equipment and FibeAir are using the same interface (single mode, multi-mode).
y For multi-mode interfaces, check that you are using multi-mode fibers to connect the unit. For single
mode interfaces, check that you are using single mode fibers.
If no problem is detected with any of the items above, proceed with the table below.
Insufficient system One of the system elements 1) Verify the existence of all IDMs
configuration for full does not support XPIC. and ODU, and verify their
XPIC Support Or, the system is missing connectivity.
one of the needed elements. 2) Open the unit Alarm Log (using
0
the element manager) and send to
customer support the code at the
end of the "XPIC Insufficient" event
text.
Synthesizer #1/2/3 One of the ODU synthisizers Replace ODU. (In XPIC
Unlocked is unlocked. configuration, the ODU may be
taking the sync from the mate
11
ODU. In that case, check if alarm
persists in non-XPIC
configuration.)
Tx Level Out of Range The ODU cannot transmit 1) Reduce TX power gradually.
12
the requested Tx power. 2) Replace ODU.
Rx Level Out of Range RSL is very low (typically 1) Check that the fault is not due to
below -80 dBm), link is rain/multipath fading or lack of
down. LOS.
13 2) Check link settings (TX
power,TX freq).
3) Check anttena alignment.
4) Replace local/remote ODU.
Power Input #2 is Down Subrack redundant power 1) Verify if the Power Input card
feed failure. exists in the subrack.
2) Check if Power Input connected
to -48 VDC supply.
3) Check -48 VDC supply to the
15
subrack.
4) Replace Power Input card if
problem still exists.
5) Disable Power Input if you do
not use redundant power feed.
Power Input #1 is Down Subrack redundant power 1) Verify if the Power Input card
feed failure. exists in the subrack.
2) Check if Power Input connected
to -48 VDC supply.
3) Check -48 VDC supply to the
15
subrack.
4) Replace Power Input card if
problem still exists.
5) Disable Power Input if you do
not use redundant power feed.
XPIC Cable Swap Left/Right cables swap in 1) Verify correct cable connection.
XPIC configuration. If
Drawer ID Mismatch (see Recommended connection is V to
above) alarm is identified in Right drawer and H to Left drawer
15
both drawers, the IF (coax)
cables between the drawers
and ODUs on one end are
swapped.
IDU 5/8/3.3/-5V Power Failure in an IDU power 1) Check -48 VDC supply to IDU.
15
Supply Failure supply. 2) Replace IDU
Wayside Channel Wayside Left Line loopback Disable Wayside line loopback
19
Loopback applied by user
Radio RS: LOF Radio RS: LOF (ADM) 1) Check that the fault is not due to
other alarms that can lead to LOF.
2) Check link settings (TX
power,TX freq).
22
3) Verify no interference.
4) Use loopbacks to identify
problem source.
5) Replace IDMs.
Link Group #1 N+1 N+1 Link Group protection 1) Check Protecting Radio module
Protection Fault: degraded due to Loss Of is powered on and operates
22 Protecting Radio Failure Frame or Loss Of Signal properly.
alarm on the radio port 2) Replace faulty module.
detected by XC board. 3) see Radio RS: LOF (SDH)
Radio RS: LOF (SDH) Loss Of Frame alarm on the 1) Check that the fault is not due to
Radio Section: LOF radio, link is down other alarms that can lead to LOF.
(Sonet) 2) Check link settings (TX
power,TX freq).
22
3) Verify no interference.
4) Use loopbacks to identify
problem source.
5) Replace IDMs/ODUs
Fiber RS: LOF (SDH) Loss Of Frame alarm on the 1) Check line input.
Fiber Section: LOF line input. 2) Check fibers/cables.
(Sonet) 3) Verify end equipment transmits
22 properly.
4) Use line loopbacks to confirm
input/IDU is ok.
5) Replace IDM.
Fiber RS: LOF (SDH) Loss Of Frame alarm on the 1) Check line input.
Fiber Section: LOF line input 2) Check fibers/cables.
(Sonet) 3) Verify end equipment transmits
22 properly.
4) Use line loopbacks to confirm
input/IDU is ok.
5) Replace IDU.
Fiber RS: LOF Fiber RS: LOF (ADM) 1) Check that the fault is not due to
other alarms that can lead to LOF.
2) Check link settings (TX
power,TX freq).
22
3) Verify no interference.
4) Use loopbacks to identify
problem source.
5) Replace IDMs
Fiber RS: LOS Loss Of Signal alarm on the 1) Check line input.
or?10;E1\T1\E3\DS3 #n line input 2) Check fibers/cables.
Loss of Signal?10;Fiber 3) Verify end equipment transmits
23 RS: LOS properly.
4) Use line loopbacks to confirm
input/IDU is ok.
5) Replace IDU.
Fast Eth. #01/02 Loss of Fast Ethernet Loss of 1) Check line input.
Carrier Carrier 2) Check cable.
23 3) Verify end equipment transmits
properly.
4) Replace IDU.
Trace Identifier Trace Identifier Mismatch Verify J0 settings in the IDU and in
24
Mismatch on Fiber #n alarm (J0 mismatch). the end equipment.
Excessive BER on Major radio Excessive BER 1) Check that the fault is not due to
Radio #n alarm other alarms that can lead to LOF.
2) Check link settings (TX
power,TX freq).
25
3) Verify no interference.
4) Use loopbacks to identify
problem source.
5) Replace IDMs/ODUs
E1\T1 Excessive BER Major Excessive BER alarm 1) Check line input.
on Port #n on E1/T1 port 2) Check cables.
3) Verify end equipment transmits
25 properly.
4) Use line loopbacks to confirm
input/IDM is ok.
5) Replace IDM.
Signal Degrade on Minor radio BER alarm 1) Check that the fault is not due to
Radio #n other alarms that can lead to LOF.
2) Check link settings (TX
power,TX freq).
26
3) Verify no interference.
4) Use loopbacks to identify
problem source.
5) Replace IDMs/ODUs
Signal Degrade on Fiber Minor line SD BER alarm 1) Check line input.
#n 2) Check fibers/cables.
3) Verify end equipment transmits
26 properly.
4) Use line loopbacks to confirm
that input/IDU is ok.
5) Replace IDM.
Fiber RS: Signal Minor line BER alarm 1) Check line input.
Degrade 2) Check fibers/cables.
3) Verify end equipment transmits
26 properly.
4) Use line loopbacks to confirm
input/IDU is ok.
5) Replace IDU.
E1\T1 Signal Degrade Minor BER alarm on E1/T1 1) Check line input.
on Port #n port 2) Check cables.
3) Verify end equipment transmits
26 properly.
4) Use line loopbacks to confirm
input/IDM is ok.
5) Replace IDM.
Fiber RS: Unexpected Unexpected signal on the 1) Enable line port or disconnect
28 ?10;E1\T1\E3\DS3 #n line input. Port disabled but line
Unexpected Signal line is connected.
Gigabit Ethernet GbE port is disabled but 1) Enable GbE port, disable GbE
28
Unexpected Signal GbE data is detected. port of source, or disconnect fiber.
General Hardware Fault Wrong card type detected in 1) Replace Subrack Auxiliary
42
#11 Subrack Auxiliary slot. module.
Wayside Firmware File Wayside firmware file is 1) Download Wayside firmware file
42
is Missing missing in the IDC. to the IDC and reset the IDC.
Auxiliary Card Fault #01 Subrack Auxiliary module 1) Check Subrack Auxiliary module
failed or extracted. is properly inserted.
42
2) Replace Subrack Auxiliary
module.
General Hardware Fault Subrack Auxiliary EEPROM 1) Extract and re-insert Subrack
#10 checksum failure. Auxiliary module.
42
2) Replace Subrack Auxiliary
module.
Link Group #1 N+1 N+1 Link Group protection 1) Check if XC module is powered
Protection Fault: degraded due to XC card on and no other alarm pertained
42
Protecting Radio Failure fault. to XC is active.
XC Card Fault 2) Replace XC module.
Link Group #1 N+1 N+1 Link Group protection 1) Verify Protection Radio link is up
Protection Fault: XC degraded due to peer XC and, no errors over the link.
Peer Communication communication fault. 2) Check that remote IDU is
Failure properly configured for N+1 Link
Group protection.
42 3) Check that remote IDU has
properly operational XC board.
4) Check that Protection Radio link
terminates over Protecting Radio
module (and not other Radio
module).
Link Group #1 N+1 N+1 Link Group protection 1) Check that remote IDU is
Protection Fault: Local- degraded due to Local- properly configured with N+1 Link
Remote Protection Remote Protection Group topology.
42
Mismatch Mismatch. 2) Check that remote IDU has all
relevant N+1 Link Group protection
line modules operational.
General Hardware Fault Upper IDM Board (MUX or 1) Try SW Reset affected module /
#9 XC) EEPROM inventory IDM.
42 information CRC error 2) Power cycle or re-insert affected
module / IDM.
3) Replace the module.
General Hardware Fault Upper IDM Board (MUX or 1) Try SW Reset affected module /
#8 XC) EEPROM read access IDM.
42 error 2) Power cycle or re-insert affected
module / IDM.
3) Replace the module.
General Hardware Fault Lower IDM Board (Modem 1) Try SW Reset affected module /
#11 or XC) EEPROM inventory IDM.
42 information CRC error 2) Power cycle or re-insert affected
module / IDM.
3) Replace the module.
General Hardware Fault Lower IDM Board (Modem 1) Try SW Reset affected module /
#10 or XC) EEPROM read IDM.
42 access error 2) Power cycle or re-insert affected
module / IDM.
3) Replace the module.
Line Card #n Powered Line module pertained to 1) Check if the card is inserted
Down Link Protection group is properly in the subrack.
powered down or extracted. 2) Check if own or redundant
42
power supply / Radio module
(in drawer #1) is powered on.
Replace module if faulty.
Line Card #1 Powered Line module in carrrier #1 of 1) Check if the card is inserted
Down the Link Protection group is properly in the subrack.
powered down or extracted. 2) Check if own or redundant
42
power supply / Radio module is
powered on.
3) Replace module if faulty.
Drawer Internal Power Internal Power failure. 1) Check that proper Subrack
Failure (Board #2) Auxiliary module inserted.
2) Extract and re-insert Subrack
42
Auxiliary module.
3) Replace Subrack Auxiliary
module.
XPIC Cable Swap Internal IDC to IDC 1) Check that IDC #n is power up
communication failure and finished initialization.
between modules requied 2) Check & configure both IDCs
for Link Group protection with proper system configuration:
service. System Type, Subrack#, Subrack
42 IP Base Address, Link Group
Topology.
3) Check for Hardware fault:
Subrack Auxiliary module, Ethernet
cable (if applicable), IDC modules.
Replace faulty module.
General Hardware Fault FPGA load failure - Subrack 1) Download correct Subrack
#7 Auxiliary board. Auxiliary FW file to 2-floor IDC, and
then extract and re-insert Subrack
42 Auxiliary board
2) Replace Subrack Auxiliary
module.
3) Replace 2-floor IDC.
MUX Firmware File is A Mux FW file is missing Load the required FW file, and
42
Missing from the system. reset system.
Modem Firmware File is A Modem FW file is missing Load the required FW file, and
42
Missing from the system. reset system.
Link ID Mismatch on Link ID is not identical on Set identical Link ID on both ends
46
Radio #n both ends of the link. of the link.
Auxiliary Channel User Incorrect Auxiliary channel 1) Check and correct configuration:
Configuration Mismatch configuration Use "Copy IDC to AUX" to copy
the Auxiliary channel configuration
46
to the IDC, or "Copy AUX to IDC"
to copy the Auxiliary channel
configuration to the AUX
Hitless Left/Right Left/Right receiver is used Not a real alarm since receiver
51 Receiver in Use for processing data switching is likely to happen during
multipath fading.
Unused Radio Receiver Hitless Self Radio Receiver 1) Check that the fault is not due to
LOF LOF other alarms that can lead to LOF.
2) Check link settings (TX
power,TX freq).
52
3) Verify no interference.
4) Use loopbacks to identify
problem source.
5) Replace IDMs/ODUs
Own Radio BBLOF on Hitless Self Radio Receiver 1) Check that the fault is not due to
Radio #n LOF other alarms that can lead to LOF.
2) Check link settings (TX
power,TX freq).
52
3) Verify no interference.
4) Use loopbacks to identify
problem source.
5) Replace IDMs/ODUs
In-Band Radio PPP Link In-band connection over the 1) Check the line connection.
Disconnect?10;In-Band line (STM-1/OC-3 or 2) Check in-band configuration.
57
Line PPP Link PPPoE) or over the radio
Disconnect was disconnected.
User Channel Ethernet User Right Channel Loss of 1) Check line input.
Loss of Carrier Carrier 2) Verify user-end Ethernet
equipment.
3) Check / replace connecting
58 cable.
4) Replace IDC module.
In case of N+1 Trunk Radio:
5) Replace Subrack Auxiliary
module.
User Channel Ethernet User Left Channel Loss of 1) Check line input.
Loss of Carrier Carrier 2) Verify user-end Ethernet
equipment.
3) Check / replace connecting
58 cable.
4) Replace IDC module.
In case of N+1 Trunk Radio:
5) Replace Subrack Auxiliary
module.
Wayside Channel Loss Wayside Left Channel Loss 1) Check line input.
of Signal/Carrier of Signal/Carrier 2) Verify user-end equipment.
3) Check / replace connecting
cable.
58
4) Replace IDC module.
In case of N+1 Trunk Radio:
5) Replace Subrack Auxiliary
module.
Protection Force Switch One of the system elements 1) Disable "Force Switch"
does not support XPIC.
61
Or, the system is missing
one of the needed elements.
RFU Power Failure (Vd) RFU Power Supply Failure 1) Reset IDM.
(Vd) 2) Check IF cable and connectors.
62
3) Replace ODU.
4) Replace IDM.
RFU Power Failure (6v RFU Power Supply Failure 1) Reset IDM.
pro) (6v pro) 2) Check IF cable and connectors.
62
3) Replace ODU.
4) Replace IDM.
RFU Power Failure (6v RFU Power Supply Failure 1) Reset IDM.
pro) (6v pro) 2) Check IF cable and connectors.
62
3) Replace ODU.
4) Replace IDM.
RFU Rx Level Path1 RSL of Main channel is very 1) Check that the fault is not due to
Out Of Range low (typically below -80 rain/multipath fading or lack of
dBm). LOS.
2) Check link settings (TX
63
power,TX freq).
3) Check anttena alignment.
4) Check antenna connections
5) Replace local/remote ODU.
RFU Rx Level Path2 RSL of Diversity channel is 1) Check that the fault is not due to
Out Of Range very low (typically below -80 rain/multipath fading or lack of
dBm). LOS.
2) Check link settings (TX
63
power,TX freq).
3) Check anttena alignment.
4) Check antenna connections
5) Replace local/remote ODU.
RFU Rx Level Path2 RSL of Diversity channel is 1) Check that the fault is not due to
Out Of Range very low (typically below - rain/multipath fading or lack of
80dBm). LOS.
2) Check link settings (TX
65
power,TX freq).
3) Check anttena alignment.
4)Check antenna connections
5)Replace local/remote ODU.
RFU Fan Failure Fan Failure was detected by 1) Check RFU connection to BP
RFU 2) Check that fans are connected
to PS
65 3) Replace RFU BP cable
4) Replace specific fan or fans
drawer
5) Replace RFU
RFU Fan Failure Fan Failure was detected by 1) Check RFU connection to BP
RFU 2) Check that fans are connected
to PS
65 3) Replace RFU BP cable
4) Replace specific fan or fans
drawer
5) Replace RFU
RFU Low Signal To RFU is detecting low signal 1) Check RFU IF cable connection
66 ODU from IDU 2) Reconnect the IF cable
3) Replace RFU
RFU XPIC Clock Failure No XPIC clock is received 1) Reconnect XPIC clock cables at
67 from Master RFU both RFUs
2) Replace XPIC cable
Gigabit Ethernet TX GbE port is enabled by the 1) Check the reason for the alarm
Mute Override user but the system (see the Probable Cause column)
overrides this and mutes the and correct it accordingly.
port.
This alarm may appear in
the following cases:
70
Radio LOF (local or remote),
Link ID mismatch (local or
remote), excessive BER
(local or remote), Signal
degrade (local or remote),
GbE LOS (remote)
Initial KEP Failed The first encryption key 1) Check link status.
73 exchange failed 2) Reset IDC.
3) Reset IDM.
Link Group #1 N+1 N+1 Link Group protection 1) Check if XC module is inserted
Protection Fault: XC degraded due to XC card and powered on and no other
81
Card is Down fault. alarm pertained to XC is active.
2) Replace XC module.
Link Group #1 N+1 N+1 Link Group protection 1) Verify Protection Radio link is up
Protection Fault: XC degraded due to peer XC and, no errors over the link.
Peer Communication communication fault. 2) Check that remote IDU is
Failure properly configured for N+1 Link
Group protection.
81 3) Check that remote IDU has
properly operational XC board.
4) Check that Protection Radio link
terminates over Protecting Radio
module (and not other Radio
module).
Link Group #1 N+1 N+1 Link Group protection 1) Check Protecting Radio module
Protection Fault: degraded due to Loss Of is powered on and operates
81 Protecting Radio Failure Frame or Loss Of Signal properly. Replace faulty module.
alarm on the radio port 2) see Radio RS: LOF (SDH)
detected by XC board.
Link Group #1 N+1 N+1 Link Group protection 1) Check that remote IDU is
Protection Fault: Local- degraded due to Local- properly configured with N+1 Link
Remote Group Remote Protection Group topology, and all protection
Topology Mismatch Mismatch. members are configured with the
same priority level (if extra traffic is
configured as revertive in one
subrack, it should also be
configured the same in the other
subrack).
81 2) Check that remote IDU has all
N+1 Link Group protection
pertained line modules operational.
3) Verify that remote subrack is not
configured to lockout or forced
switch mode.
4) Check that the extension cable
is connected properly in the remote
subrack (if extended mode is
used).
101101110
Loopback
FibeAir is capable of performing loopback testing at several points in the link. The test is run from the
CeraView management software, or via the SNMP protocol.
During the loopback test, an alarm indication will appear to remind you to cancel the test when you are done.
Local:
y Wayside Channel
Local IDU
101101110...
Local IDU Modem & to ODU
Equipment IF
Interfaces
101101110...
Local Loop
y Full IDU (all three inputs through the IDU, modulator, and looped in the IF).
y Wayside Channel
Local IDU
101101110...
Local IDU Modem &
Equipment IF
Interfaces
101101110...
Remote Loop
Full Radio Link Loopback (local external equipment through the radio link, to the remote line interface
module, back through the radio link, to the local external equipment).
155 MB/s
Line Interface
Loopback
Loop
The following steps will help you identify and correct such problems.
1. For Ethernet connection between FibeAir and a PC network card, use a cross cable.
For Ethernet connection between FibeAir and an Ethernet hub (for example, connecting to a LAN jack in
a wall) use a straight cable.
2. For serial connection between FibeAir and a PC serial port, use a straight cable.
Cable Connections
Ping FibeAir. If ping succeeds, the problem may be with the CeraView software installation, or the computer
TCP\IP stack. Check the read and write communities in FibeAir and in the management station configuration.
If ping fails, there may be a network connectivity problem.
A typical conflict may occur between the IDU configuration and the related CeraView parameter.
In addition, the Agent Address must be identical to the IDU IP address, and the source address must be
identical to the computers address.
The following figure shows a typical example of IP addresses and network configuration.