For the purposes of this MANUAL, channel drop and energy dissipation
structures are classified into two groups. Channel drops are classified as
structures which shall only be used when the inflow channel flow is sub-critical
(Froude Number, F, < 0.86). Energy dissipators and stilling basins, are
classified as structures which may be used for either sub-critical (F, c 0.86) or
super-critical (F, > 1.13) inflow conditions.
Criteria and charts to aid in the design of these types of structures have been
developed based on many various hydraulic studies. Generalized standards
for each type of channel drop based on these hydraulic studies are provided
in the following sections.
The reader should refer to the standard channel drop and energy dissipation
design references to become familiar with the detailed information available on
Adopted August 12,1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1102
Section 1100 - Additional Hydraulic Structures
Presented in Table 1101 are the types of channel drop structures allowed in
the Clark County area. By definition, channel drop structures are to be used
only when the upstream channel flow is sub-critical. Presented in Figure 1101
are the generalized profiles and nomenclature for riprap drop structures. This
nomenclature is used throughout this section for discussion of specific
standards for each part of the structure. The nomenclature is also applicable
to gabion drop structures.
Presented in Table 1102 and Figure 1102 are the design standards and
details for sloping riprap drop structures. The design chart for sloping riprap
drop structures is based upon the unit discharge (q) of the approach channel,
the riprap classification and the slope of the drop structure, and is valid only
for sub-critical flow in the approach channel (i.e., Froude Number (F,) < 0.86).
The unit discharge is found by taking the average or normal channel velocity
(V,) for the loo-year discharge times the normal depth of the channel (Y ,).
The design chart is also based upon a prismatic channel section throughout,
from the upstream channel through the drop to the downstream channel. The
maximum (steepest) allowable side slope for the riprap lined channel within the
drop structure is 4:l. Flatter side slopes are allowable and encouraged when
available ROW permits.
The classification of riprap chosen for the sloping portion of the structure
should be used throughout the structure, including the upstream and
downstream aprons, the channel bottom and side slopes. See Section 700 for
riprap classification. The riprap should extend up the side slopes to a depth
equal to 1 foot above the normal major storm flow depth projected upstream
from the downstream channel, or 1 foot above the critical depth in the sloping
section, whichever is greater (see Figure 1102). The maximum fall allowed
at any one drop structure is 3 feet from the upper channel bottom to the lower
channel bottom, excluding the trickle channel.
1102.1.1.1 Criteria
Adopted August 12,1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1103
Section 1100 - Additional Hydraulic Structures
normal low water flows. The maximum normal depth, Y,, is 5 feet and
the maximum normal velocity, V,, is 7 fps.
b. Low Flow Channel: The low flow channel shown in this case is a
rectangular concrete channel. The concrete channel ends at the
upstream end of the upstream riprap apron. A combination cut-off wall
and foundation wall is provided to give the end of the low flow channel
additional support. The water is allowed to trickle through the
upstream apron and through the crest wall (discussed below). Riprap
low flow channels would simply feather into the upstream apron.
d. Crest Wall: The crest wall is a very important part of the drop structure,
and has several purposes, one of which is to provide a level rigid
boundary section and distribute the flow evenly over the entire width of
the structure. This is extremely important since the selection of the
riprap is based upon the unit discharge, and without the wall, flow
concentrations could result which would greatly exceed the design
discharge. The crest wall is also used to reduce or eliminate seepage
and piping along with the failures which can result from these problems.
The low flow channel is ended at the upstream end of the upstream
apron to prevent the low flow channel from concentrating additional
water at a point during high flows, thus exceeding the design unit
discharge. The apron and the crest wall combine to disperse the
concentrated flow. The low flows must be allowed through the crest
wall to prevent ponding. A series of notches in the wall will allow the
low flows to do this. The size and number of notches will depend on
the design discharge of the low flow channel. Note that they are offset
from the trickle channel to permit flow of water through the upstream
apron. The voids in the riprap below the notch inverts are expected to
silt in rapidly or they can be filled at the time of construction.
The two most common types of walls used will be reinforced concrete
or sheet pile. The design of the wall is a structural problem which will
not be addressed here. The depth of the wall should be at least to the
bottom of the bedding material and could be deeper if necessary for the
control of piping.
I The top of the crest wall should be placed a distance P above the
upstream channel bottom. This is done to create a higher water
Adopted August 12,1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1104
Section 1100 - Additional Hydraulic Structures
e. Chute Apron: The allowable size of riprap and chute slope for the
chute portion of the drop structure and the downstream apron are
obtained from Table 1102. The riprap size and chute slope are
determined from the table by first computing q = V,Y,. Next, enter the
table at the proper value of q in the left-hand column. Then, determine
the allowable slopes in the row for that q and select the best
combination of riprap classification and slope using site and cost
considerations.
The length of the downstream apron L, and the depth of the riprap D,
can also be obtained from Table 1102. The riprap must be placed on
bedding as shown in Figure 1102. The term bedding used in this
section (Section 1100) refers to 6-inch Type II Aggregate Base as
specified in the STANDARD SPECIFICATIONS. The 2 foot long filter
fabric cutoffs help prevent piping failures. The riprap should extend up
the side slopes a distance of Y, + 1 foot as projected from the
downstream channel or the critical depth plus 1 foot, whichever is
greater. The side slopes for the chute and downstream apron should
be the same as the crest wall and upstream channel with the exception
that a riprap slope as steep as 2:l can be used starting above the
height of the riprap lining required above. The thickness of the riprap
immediately downstream of the crest wall should be increased to D,,
as shown in Table 1102. This extra thickness is necessary to protect
the most critical area of the structure. The voids in the apron can be
filled during construction to reduce ponding of low flows in the apron
area.
Presented in Table 1103 and on Figure 1103 are the design standards and
details for vertical riprap drop structures.
Adopted August 12,1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1105
Section 1100 - Additional Hydraulic Structures
The design chart for the vertical channel drop structures is based upon the
height of the drop and the normal depth and velocity of the approach and exit
channels. The channel must be prismatic throughout, from the upstream
channel through the drop to the downstream channel.
The maximum (steepest) allowable side slope for the riprap stilling basin is
4:l. Flatter side slopes are allowable and encouraged when available ROW
permits. The riprap should extend up the side slopes to a depth equal to 1 foot
above the normal depth projected upstream from the downstream channel.
(See Figure 1103). The maximum fall allowed at any one drop structure is
3 feet from the upper channel bottom to the lower channel bottom, excluding
the low flow channel.
A detailed description of the drop structure and the design procedure from
upstream to downstream is given below and is presented on Figure 1103.
b. Low Flow Channel: The low flow channel shown in this case is a
rectangular concrete channel. The concrete channel ends at the
upstream end of the upstream riprap apron. A combination cut-off wall
and foundation wall, to give the end of the low flow channel additional
support, is provided. The water is allowed to trickle through the
upstream apron and through the vertical wall. Riprap low flow channels
would simply feather into the upstream apron.
d. Crest Wall: The vertical wall should have the same trapezoidal shape
as the approach channel. The wall distributes the flow evenly over the
entire width of the drop structure. This is important to prevent flow
concentrations which would adversely affect the riprap basin.
The low flow channel is ended at the upstream end of the upstream
apron to prevent the low flows from concentrating additional water at a
point during high flows, thus exceeding the design assumptions. The
apron and the vertical wall combine to disperse the flow concentrated
in the low flow channel. The low flows are allowed to trickle through the
, wall through a series of notches in order to prevent ponding. The voids
in the riprap below the notch inverts are expected to silt in rapidly, or
they can be filled at the time of construction.
Adopted August 12,1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1106
Section 1100 - Additional Hydraulic Structures
The wall must be designed as a structural retaining wall. The top of the
wall should be placed a distance P above the upstream channel
bottom. This is done to create a higher water surface elevation
upstream, thus reducing the drawdown effects normally caused by a
sudden drop. P can be determined from Table 1104.
e. Chute Apron: The riprap stilling basin is designed to force the hydraulic
jump to occur within the basin, and is designed for essentially zero
scour. The floor of the basin is depressed an amount B below the
downstream channel bottom, excluding the trickle channel. This is
done to create a deeper downstream sequent depth which helps keep
the hydraulic jump in the basin. This arrangement will cause ponding
in the basin. The trickle channel can, depending on the depth, relieve
all or some of the ponding. The riprap can also be buried and vegetated
to reduce the ponded area to a smaller size.
The riprap basin is sized using Table 1103. To use the table, the
designer must first determine the necessary height of the drop C, the
normal velocity of the approach channel V,, and the upstream and
downstream normal depths Y, and Y,. Both channels must have the
same geometry and Y, must be equal to Y,. Designs for drops when
Y, + Y, shall be discussed with the local entity and/or the CCRFCD
prior to design. Enter the row which contains the correct C, V,, Y,, and
Y, and select the riprap classification and necessary channel drop
dimensions from that row.
Adopted August 12,1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1107
Section 1100 - Additional Hydraulic Structures
Gabion drops are classified into three principal drop types according to the
slope of their downstream face:
a. Vertical type
b. Stepped type
C. Sloped type
Presented in Figures 1104 through 1106 are examples of these three types
of gabion drops.
In constructing gabion drops, either PVC coated wire mesh gabion baskets or
galvanized steel wire mesh gabion baskets are used. The designer shall
obtain soil corrosion data for the specific site to determine which type of
coating may be used or if the soil is too corrosive for either coating. The data
and coating recommendations shall be submitted to the local entity for review
and approval.
The manufacturer suppling the gabions should supply design guidelines and
criteria used in designing gabion drops. Specific reference is made in this
MANUAL to MACCAFERRI, 1987. This reference outlines typical step by step
procedures for design of gabion drops and thus typical procedures are not
repeated in this MANUAL. The naming of MACCAFERRI should not be
construed as an endorsement or acceptance of their products.
a) Vertical Drops
Adopted August 12,1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1108
Section 1100 - Additional Hydraulic Structures
W Stepped Drops
1. Stepped drops shall only be used with light bed loads and with
a maximum unit discharge of 35 cfs per foot.
C) Sloped Drop
1. Sloped drops are used where, due to the poor quality of the
foundation soil, a large foundation area and a fairly uniform
pressure distribution are required.
a. Where possible small drops in series would be more desired than one
large drop.
d. In heavy debris areas the gabion drop crest should be capped with
concrete to avoid debris blockage.
Adopted August 12,1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1109
Section 1100 - Additional Hydraulic Structures
Presented in Figure 1107 are the design details for a straight drop spillway. The
spillway produces a controlled overflow jet which is dissipated through impact on
the structure floor and baffle blocks. The jet energy is also dissipated in the
plunge pool created when impact blocks are used or through an hydraulic jump
using the typical baffle block arrangements from the USBR stilling basin designs.
The basin design is based on the drop distance, Y, and the unit discharge, q, as
related through the drop number, D, computed as follows:
D = q2 / gY3 (1101)
The impact block basin is applicable for low heads with a wide range of tailwater
depths. The hydraulic jump basin may be used as long as the design parameters
for the selected basin type are meet. The designer is referred to USBR, 1987,
for detailed design information, guidelines, and examples.
Presented on Figure 1108 is the baffled apron stilling basin. This structure
requires no initial tailwater to be effective, although when the tailwater forms a
pool into which the flow discharges, the channel bed scour is not as deep and is
less extensive. The chutes are constructed on an excavated slope, 2:1 or flatter,
extending to below the channel bottom. Backfill is placed over one or more rows
of baffles to restore the original streambed elevation. When scour or downstream
channel degradation occurs, successive rows of baffle piers are exposed to
prevent excessive acceleration of the flow entering the channel. If degradation
does not occur the scour creates a stilling pool at the downstream end of the
chute, stabilizing the scour pattern.
Presented in Table 1101 are the types of energy dissipation structures allowed
in the Clark County area. By definition, energy dissipation structures may be
Adopted August 12, 1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1110
Section 1100 - Additional Hydraulic Structures
used for both sub-critical and super-critical upstream channel (or pipe) flow
conditions. For sub-critical flow conditions, these structures are designed similar
to the channel drop structures discussed in the previous section. For super-
critical flow conditions, the upstream channel is tied directly into the stilling basin
floor (hydraulic rise) or the upstream channel is transitioned into the structure
through the use of a trajectory transition section. The hydraulic design of
trajectory transition sections is discussed in Section 1102.2.9.
The basis for design of all of the USBR stilling basins is analysis of the hydraulic
jump characteristics on horizontal and sloping aprons. The governing equation
for hydraulic jumps is based on pressure-momentum theory and may be written
as follows:
The results of the USBR analysis are presented in Figure 1109. In this figure Tw
is the tailwater depth necessary to create or assist in forming the hydraulic jump.
Generally, Tw is greater than D 2.
Adopted August 12, 1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1111
Section 1100 - Additional Hydraulic Structures
jump will also vary depending on the flow rate in the channel. Therefore, from a
structural and safety standpoint, horizontal and sloping apron stilling basins
should not be used as energy dissipation structures without the addition of
appurtenances (i.e., baffle blocks, end sills) to control the location of the hydraulic
jump. Standard designs for these types of structures are discussed in the
following sections.
Presented in Figure 1110 is the standard design for a Type lll stilling basin. The
chute blocks at the upstream end of a basin tend to corrugate the jet, lifting a
portion of it from the floor to create a greater number of energy dissipating
eddies. These eddies result in a shorter length of jump than would be possible
without them, and tend to stabilize the jump. The baffle piers act as an impact
dissipation device and the end sill is for scour control. The end sill has little or no
effect on the jump. The only purpose of the end sill in a stilling basin is to direct
the remaining bottom currents upward and away from the channel bed.
This type of basin is recommended at the outlet of a sloping channel drop when
there is adequate tailwater. For insufficient tailwater, a USBR Type Vl basin is
recommended.
Presented in Figure 1111 is the standard design of a low Froude number basin.
The basin is used instead of the USBR Type ll and Type lll basins in order to
achieve better jump characteristic at low Froude numbers (2.5 < Fr < 4.5). At
these low Froude numbers, excess waves are created because the jump is not
fully developed.
This basin minimizes the waves by directing jets from the tops of the baffle blocks
into the roller to strengthen and intensify it. In addition, the tail water depth (Tw)
should be at least 1.1 x D 2 (conjugate depth) to minimize the chance of the jump
sweeping out of the basin (See Figure 1109). The end sill has little or no effect
on the jump but rather directs the bottom currents upward and away from the
channel bed.
Adopted August 12, 1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1112
Section 1100 - Additional Hydraulic Structures
bottom and sides adjacent to the structure to avoid the tendency for scour of the
outlet channel downstream from the end sill when shallow tailwater exists. This
type of stilling basin is very effective at the outlet of storm drains or culverts where
there is little or no tailwater.
The three different stilling basin configurations can be divided into two
categories, basins for spillways or channels (Type lll or IV) and basins for pipe
outlets (Type Vl). A summary of the design data for all three basin types is
presented in Figure 1109. The reader is referred to PETERKA, 1978, for a
detailed discussion of the structural design requirements.
Riprap protection shall be provided downstream of the Type lll, IV, and Vl stilling
basins (except in fully concrete lined channels). This protection is necessary to
protect the downstream channel from erosion due to eddy currents and excess
velocities in the transition zone between the structure and the design channel
section.
For the Type lll and Type IV basin, a 2-foot layer of regular riprap shall be installed
from the end sill a distance of 4 times the design depth of flow in the downstream
channel.
For the Type Vl stilling basin, riprap protection shall extend downstream a
distance equal to the outlet width, W, of the basin. The minimum downstream
distance shall be 5 feet. A 2-foot layer of regular riprap shall be used for all basin
widths of 12 feet or less. For basin widths between 12 feet and 20 feet, a 3-foot
layer of heavy riprap shall be used. For basin widths greater than 20 feet, a 2-foot
layer of grouted riprap shall be used.
Adopted August 12, 1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1113
Section 1100 - Additional Hydraulic Structures
The safety factory, K, should be equal to or greater than 1.5 to assure positive
contact pressure.
The trajectory section should be connected to the stilling basin apron by a short,
steep chute section. This section should be at a slope between 1.5 horizontal to
1 vertical and 3 horizontal to 1 vertical with 2 horizontal to 1 vertical preferred. In
no case should the slope be flatter than 6 horizontal to 1 vertical.
The following example applications present typical design calculations for various
channel drop and energy dissipation structures. The reader is referred to
PETERKA, 1978, for additional design examples.
Problem: Design a sloping riprap drop for a channel with the following
characteristics:
Q = 1,600 cfs
Adopted August 12, 1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1114
Section 1100 - Additional Hydraulic Structures
Solution:
Step 2: Select the chute slope from Table 1102 for q = 25 cfs / ft
The best slope will depend on factors such as availability and cost
of the riprap bedding and filter cloth and ROW limitations. For this
example, a 7:1 slope was selected.
Problem: Design a vertical riprap drop for a channel with the following
characteristics:
Q = 1,600 cfs
Solution:
Step 1: From Table 1103, for C = 3.0 ft, V n = 6.0 fps and Yn and Y2 =
4.0 ft
Adopted August 12, 1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1115
Section 1100 - Additional Hydraulic Structures
Riprap - Heavy
B = 1.0 ft
A = 2.5 ft
LB = 20 ft
D = 5.0 ft
E = 4.0 ft
Problem: Design a vertical gabion drop structure for a channel with the
following characteristics:
Q = 1,600 cfs
Assume the drop is to be built with a lined stilling pool floor and
counter drop (weir).
Solution:
Adopted August 12, 1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1116
Section 1100 - Additional Hydraulic Structures
Z1 -fb = 1.25 ft
With Z1-fb = 1.25 ft and q = 29.6 and using dashed line in Figure 53
in MACCAFERRI, 1987
Z2 -fb = 5.8 ft
Lb = Lg1 + L12
Use L b = 48 ft
Adopted August 12, 1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1117
Section 1100 - Additional Hydraulic Structures
The total path L of seepage under and the structure must be L > C
) H (Equation 22, MACCAFERRI,1987)
Problem: Design an impact stilling basin (USBR Type Vl) for a 48-inch RCP
outlet with the following parameters:
Adopted August 12, 1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1118
Section 1100 - Additional Hydraulic Structures
Solution:
Step 1: Using the discharge (Q = 214 cfs) enter the discharge limits
portion of Figure 1109 and read the maximum and minimum basin
width.
Wmin = 12.5 ft
Wmin = 15.0 ft
Step 2: From the basic dimension portion of Figure 1109 and using the
discharge Q = 214 cfs, interpolate for the basin dimensions. Note
that the corresponding pipe size in the table is between a 54-inch
and 60-inch diameter, which is larger than the example pipe size
of 48 inches. The basin will therefore provide ample room for the
example pipe.
W = 12 ft - 4 in b = 10 ft - 6 in
H = 10 ft - 3 in c = 5 ft - 8 in
L = 18 ft - 2 in d = 2 ft - 4 in
A = 7 ft - 8 in g = 5 ft -1 in
Downstream length = W = 12 ft - 4 in
Use a downstream length of 13 in
Adopted August 12, 1999 HYDROLOGIC CRITERIA AND DRAINAGE DESIGN MANUAL 1119