You are on page 1of 14

1490 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO.

3, JULY 2009

Feasibility of Electronic Tap-Changing Stabilizers


for Medium Voltage LinesPrecedents and New
Configurations
Salvador Martnez Garca, Senior Member, IEEE, Juan Carlos Campo Rodrguez, Member, IEEE,
Jos Antonio Jardini, Fellow, IEEE, Joaqun Vaquero Lpez, Alfonso Ibarzbal Segura, and
Pedro Mara Martnez Cid

AbstractThyristor-based onload tap-changing ac voltage sta- 300 VA to 300 kVA. This replacement does not apply to the
bilizers are cheap and robust. They have replaced most mechanical mechanical tap-changers associated to feeding transformers of
tap-changers in low voltage applications from 300 VA to 300 kVA. long medium-voltage lines (typically 69 kV primary, 34.5 kV
Nevertheless, this replacement hardily applies to tap-changers as-
sociated to transformers feeding medium-voltage lines (typically 69 secondary, 10 MVA), usually housed in the transformer tank,
kV primary, 34.5 kV line, 10 MVA) which need periodical main- needing periodical renewal of switches and isolating oil [1].
tenance of contacts and oil. The Electric Power Research Insti- The EPRI [2], [3] and other research institutes have evaluated
tute (EPRI) has studied the feasibility of this replacement. It de- the feasibility of such a replacement, both in voltage stabilizers
tected economical problems derived from the need for series as- and phase regulators, concluding (see II.F.1) that, although
sociation of thyristors to manage the high voltages involved, and
from the current overload developed under line fault. The paper technically possible, the equipment derived from the simple
reviews the configurations used in that field and proposes new so- substitution of mechanical switches by their semiconductor
lutions, using a compensating transformer in the main circuit and counterparts is too expensive because of the amount of de-
multi-winding coils in the commutating circuit, with reduced over- vices in series association needed to obtain medium-voltage
load effect and no series association of thyristors, drastically de- switches, and because of the high over-current under line faults.
creasing their number and rating. The stabilizer can be installed
at any point of the line and the electronic circuit can be fixed to They recommend looking for modified topologies needing less
ground. Subsequent works study and synthesize several commu- semiconductors.
tating circuits in detail. The long-standing positive results [4][12] on solid-state
Index TermsAC voltage stabilizer, onload tap-changer tap-changers with commutating current limitation based on
(OLTC), power conditioning, power quality, voltage control. multi-winding coils inspired us to explore their abilities for
medium-voltage lines. This work studies the feasibility of a di-
rect structure (without compensating transformer) and a series-
I. INTRODUCTION compensated structure, both commutated by multi-winding
coil. The steady and commutating operations are analysed to
C voltage stabilizers based on thyristor-commutated
A onload tap-changers (OLTC) are reliable and have al-
most completely replaced mechanical switching equipment in
derive expressions for the electrical working conditions of
switches, transformers and coils, thus enabling their econom-
ical evaluation. The circuits exposed summarise the results
low-voltage applications, single- and three-phase, ranging from of an iterative analysis and synthesis cost comparative search
method applied in other research on power electronics [13],
Manuscript received May 02, 2008. Current version published June 24, 2009. [14], some of them bringing the tap-changers to the field of fast
This work was supported by IBERDROLA S. A., Spain, I+D program, ESTRAP voltage and phase regulators [15][17].
Project: Feasibility of Electronic Medium Voltage Line Stabilizers, 19941997.
Paper no. TPWRD-00322-2008.
The direct configuration here analyzed in IV.A is similar to
S. Martinez is with the Departamento de Ingeniera Elctrica, Electrnica those studied by EPRI. The results confirm its high cost and a
y de Control (DIEEC) de la Universidad Nacional de Educacin a Distancia strong cost reduction for the new series-compensating solutions
(UNED), Madrid 28040, Spain (e-mail: smartine@ieec.uned.es).
J. C. Campo is with the Departamento de Ingeniera Elctrica, Electrnica,
here proposed, accomplished by the synergic effect of the com-
Computacin y Sistemas de la Universidad de Oviedo, Gijn 33205, Asturias, pensating transformer, the multi-winding commutating coil and
Spain (e-mail: campo@ate.uniovi.es). a bypass fault switch.
J. A. Jardini is with the Departamento de Energia e Automao Electricas da
Escola Politcinca da Universidade de So Paulo, So Paulo 05508-900, Brazil
(e-mail: jardini@pea.usp.br).
II. ANTECEDENTS
J. Vaquero is with the Departamento de Tecnologa Electrnica de la Univer-
sidad Rey Juan Carlos, 28933 Madrid, Spain (e-mail: joaquin.vaquero@urjc.es). A. Electromechanical Stabilizers
A. Ibarzbal is is with the INCOESA, Bo Bidecoeche, Vedia 48390, Vizcaya,
Spain (e-mail: aibarzabal@incoesa.com).
The early generalization of ac voltage in the electric lines was
P. M. Martnez is with IBERDROLA S.A., Direccin de Innovacin, Calidad an obvious encouragement to take advantage of tap-changers
y Medio Ambiente, Bilbao 48008, Vizcaya, Spain (e-mail: pedro.mcid@iber- associated to the transformers involved in energy distribution
drola.es). to accomplish easy voltage stabilization. Taps were first se-
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. lected manually and then electromechanically. Variants made
Digital Object Identifier 10.1109/TPWRD.2009.2021032 from iron toroid core and brushed over a one-layered coil are
0885-8977/$25.00 2009 IEEE

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 10,2010 at 11:28:43 EST from IEEE Xplore. Restrictions apply.
MARTNEZ GARCA et al.: FEASIBILITY OF ELECTRONIC TAP-CHANGING STABILIZERS FOR MV LINES 1491

Fig. 1. Fac simile of a mechanical tap-changer German patent 474 613, 1926,
awarded to B. Jansen. The incoming tap closes before the outcoming tap opens,
thus avoiding output voltage interruptions. The internal overcurrent during
overlap is limited by resistors, shorcircuited after the operation. By courtesy of
Maschinenfabrik Reinhausen (MR), Regensburg, Germany.
Fig. 2. Medium-voltage line transformer 132 kV/21.5 kV, 50 MVA with the
covering tank removed. It contains an electromechanical onload tap-changer
(OLTC, upper left) made by MR. Courtesy of INCOESA, Vedia, Spain.
very common today in laboratories and industrial plants for
one-phase low-voltage regulators in the range of 100 VA to 15
kVA I . For voltage regulation and stabilization, from 30 kVA
to 300 kVA III , three-limb vertical core equipments with
brushes contolled by servomotor are still in use. Long-lasting
graphite materials used in the brushes give high reliability to
this classic, although inherently slow (about 1 s correcting
time), equipment.

B. Early Line-Voltage Correctors


Line breakers, load interrupters (both manual and automatic)
and other simple devices intended to help power management
have been used in medium-voltage lines since the twenties, lo-
cated at any point from head to end of the lay-out. Remote con- Fig. 3. Single-phase, 32-step on-load voltage stabilizer with inductive limita-
trol versions have been available since the seventies (Fig. 4, tion of internal short circuits. It operates as an autotransformer with a com-
(left)). pensating winding in series with the load. The polarity of this winding can be
reversed by a switch and the turns changed by an 8-positions tap-changer associ-
In Europe, most ac tap correctors are derived from patents ated to a bridging reactor. Courtesy of Cooper Power Systems [23], Waukesha,
such us the German 474 613 one for mechanical resistive WI.
changers, awarded to B. Jansen in 1926 (Fig. 1). This tech-
nology was acquired by the MR company and brought about
important improvements in 1973.
C. Present Electromechanical Line Voltage Correctors
Electromechanical changers are used today in connection
with transformers feeding long medium-voltage lines (11.9 kV
to 34.5 kV; 3.15 MVA to 40 MVA) from high-voltage lines (30
kV to 138 kV). The need for making the change before break
to avoid interruptions necessarily creates internal short circuits
requiring current limiting components, resistive or/and induc- Fig. 4. Outdoor equipment for medium-voltage line management. Left: Line
tive. Improvements are made on transformers and commutating breaker. Right: McGraw-Edison-type voltage stabilizer (see Fig. 3). By courtesy
circuits [18][22]. The switches are normally housed in the of IBERDROLA, Direccin de Innovacin y Calidad, Spain, Madrid area.
transformer tank [Fig. 2, (upper left corner)].
In the U.S., the Cooper Power Systems Co. has combined the
inventions of T. A. Edison with the innovations of the McGraw [19][23] and some pure electronic variants [24][33]. The
Co. (first tap-changing voltage correctors in 1959) and currently later are not able to replace mechanical solutions in high and
makes more refined variants with inductive short-circuit limita- medium-voltage lines yet.
tions [Figs. 3 and 4 (right)]. Although the frequency of operation imposed by the system
Stabilizers with no connection to the line feeding transformer, to tap-changers is very low (typically several commutations per
as showed in Figs. 3 and 4 on the right, are useful in long lines hour) and the minimum time between changes is limited by the
with loads connected all along, correcting most voltage prob- control circuit (to no less that several minutes), the wearing of
lems. switches and oil make periodical and expensive revisions neces-
Mechanical changers have been diversified by other Euro- sary, which is the main problem with mechanical tap-changers.
pean, American, Australian and, more recently, Asian compa- The aim of the work conducted is to replace mechanical tap-
nies. There are variants with electronically-aided commutation changers by thyristor-based maintenance-free solutions.

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 10,2010 at 11:28:43 EST from IEEE Xplore. Restrictions apply.
1492 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 3, JULY 2009

Fig. 5. (a) Direct configuration tap-changing stabilizer using a multi-winding


coil to limit commutation over-current with 50 Hz transformer equivalent power
of 5% of the nominal power, typically. Optional short-circuit winding L and
switch S are explained in III.C.4. (b) Current in the outgoing (up) and the
6
incoming triac (bottom) in a ten-tap, shared load, 1 kVA, 230 V 15% input,
6 2:2% output, at nominal load. Worst case current peaks. Courtesy of Elec-
trnicas Boar, Madrid, Spain.

D. Electronic Tap-Changing Low-Voltage Stabilizers. Industry


and Office Applications
Low-cost plastic case thyristors and triacs up to 40 A, 800
V made it possible to replace most mechanical tap-changers by
their electronic counterparts in low-voltage applications under
10 kVA in the eighties. Both zero-crossing current commutation
and resistor- or inductor-aided commutation have been used to
reduce internal over-current at commutation [4][7], [24][33].
The multi-winding limiting coil with alternated corresponding
terminals [4][7] is especially useful in this respect, see Fig. 5.
It reduces the commutation over-current to a single impulse (8.3 Fig. 6. Configurations for electronic low-voltage tap-changing stabilizers. (a)
Direct configuration, suitable between 1 and 4 kVA. (b) Compensating series
ms or 10 ms) of about four times (seven times in the worst case) transformerthe single switch-comb configuration is suitable between 5 and
the repetitive peak with nominal load, while pure resistive lim- 50 kVA. The switch current is typically one third of the value in the direct con-
iters reduce it to no less than fifteen times, especially in equip- figuration. (c) Compensating series transformerdouble switch-comb config-
uration, suitable over 50 kVA. Switch current is typically one sixth of direct
ments over 10 kVA. configuration value. The multi-winding coil shown in Fig. 5 can be used in all
Since the nonrepetitive peak current allowed by triacs and al- configurations. In both compensating transformer configurations the taps can be
ternistors is about thirteen times its repetitive peak (four to nine associated to the primary or to the secondary of the main transformer.
times in an antiparallel thyristor pair) and assuming a security
coefficient of 0.333 in rms current [34], the multi-winding coil
in practice eliminates the need to oversize the semiconductors on multi-winding coil made by Electrnicas Boar in the 1980s
because of commutation over-current. In fact, for the worst case (later absorbed by Chloride) in the range of 0.3 to 300 kVA, sold
of the aforementioned numerical values (nonrepetitive peak cur- in more than 45 countries, drastically lowered failure frequency.
rent allowed by the semiconductor equal to four times its repet-
E. Advantages of the Series-Compensating Transformer
itive current peak), the switch can be able to withstand a non-
repetitive current peak of Another reason for the low-voltage electronic tap-changers
success is the series-compensating transformer configuration
% % (1) [Fig. 6(b) and (c)], replacing direct configuration [Figs. 5(a)
and 6(a)]. In a typical stabilizer with % input and %
of the repetitive peak under nominal load, while the output deviation, the current in the switches is divided by three
multi-winding coil demands no more than 700%. Since [Fig. 6(b)] or six [Fig. 6(c)], compared with the current in the
the equivalent 50 Hz power of that coil (power of the 50 Hz switches of the direct configuration [Fig. 6(a)]. The switches
transformer feasible with the same iron and cooper [13]) is voltage is not increased, thus making it possible to reduce their
about 3% to 11% of the nominal power of the stabilizer, the cost and to increase the power of practical equipment with
global cost is not significantly increased. no parallel thyristor association. The power handed by the
The coil allows for two main steady-state operation modes: compensating transformer is about 15% of the nominal power.
shared load by two adjacent taps and nonshared load. The first The series-compensating transformer and its economical
mode [4] (2nd and 3rd pat.), [5] yields in practice to very re- autotransformer variant [23] were used in very early electro-
liable equipments, as it performs rather well even with some mechanical voltage stabilizers. The scheme in Fig. 3 shows
switches (not adjacent ones) out of operation. Stabilizers based an example of it. It is also used in stabilizers not based on

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 10,2010 at 11:28:43 EST from IEEE Xplore. Restrictions apply.
MARTNEZ GARCA et al.: FEASIBILITY OF ELECTRONIC TAP-CHANGING STABILIZERS FOR MV LINES 1493

tap-changing, such as ferroresonant and phase-controlled re- breakthroughs could come by developing ways to avoid the
actor stabilizers. impact on device ratings of system short-circuit currents and
An added advantage of the compensating transformer is to re- transient voltages2.
duce high over-currents in the switches as those imposed by line 2) Tap-Changer Association With the Line Transformer: The
faults. In this abnormal condition the stabilization function of need to reduce slow voltage variations is common in medium-
the equipment is not mandatory, the tap switches are opened and voltage (13 kV to 34.5 kV) very long and/or undersized (poor)
the primary of the compensating transformer is short-circuited lines. The scalar line voltage drop reaches up to 10% of the
by means of an extra fault deviation switch (see Figs. 6 nominal voltage. Assuming an additional 9% scalar drop in a
and 11). The short-circuit impedance of the compensating trans- typical 69 kV/34.5 kV, 10 MVA feeding transformer, the drop
former appears between the mains and the load. Once the output rises to 19% from the high voltage feeding line to the end of
current comes down to normal values, opens and the tap- the medium-voltage line. Although the stability in the high-
switches are restored. voltage side is usually good and the legal variation allowed in the
The series-compensating transformer and the switches can medium-voltage inlets is about %, the aforementioned trans-
be connected before or after the main transformer of the sta- former-plus-line drop is usually compensated by a tap-changer
bilizer. In the first case [Fig. 6(b) and (c)], the main transformer associated with the line transformer [42], [43]. Since the actual
sees almost constant voltage, which means a very economical voltage at the end of the line is not known, a compound control
core design. In the second case, the switches are less exposed to criteria (input voltage plus load current) is used to select the tap
line over-voltages because of the isolation provided by the main [18], [42][44]. When the customers are connected all along the
transformer. medium-voltage line, it can be technically impossible to supply
a correct voltage to all of them by means of a single OLTC as-
F. Problems Found in Previous Studies and Solutions sociated to the feeding transformer. In these cases one or more
additional OLTC are installed in selected intermediate points of
1) EPRI Reports: Although modern monitoring and control the line (see Fig. 4, (right): two single-phase OLTCs connected
techniques improve the performance of both the mechanical and in V-configuration serving a three-wire line [23]).
the electronic versions [35][42], tap-changing ac voltage stabi- The following sections show that using an isolating series-
lizers and phase regulators show some common problems, when compensating transformer topology allows for the tap-changer
applied to medium- and high-voltage lines, on account of their to be installed in any point of the line. If connected at the output
discrete-regulation principle. of the line-feeding transformer, it can replace the associated
The 1988 and 1990 EPRI reports [2], [3] on improved OLTC, see Fig. 10. These options are not usually considered by
on-load-tap changers discussed the viability of electronic the studies on feasibility of electronic tap-changers, as [2], [3].
versions to reduce the high-cost maintenance of mechanical Besides the advantages in lowering the number and the current
solutions. The main conclusions were as follows. rate of the switches, seen in Section II-E, this topology makes it
1) Electronic stabilizers derived by simple substitution of possible to fix them to ground-voltage level.
switches in the mechanical equipment are not possible due
to the high number of semiconductors needed and their G. Antecedents on Live Line Installation and Maintenance
cost. The stabilizer solution to be proposed in this paper can be
2) New topologies minimizing the number of switches needed connected (and disconnected for maintenance purposes) to a live
to obtain a given number of voltage changes would help. medium-voltage line. Live working in overhead lines is a mature
3) Even with less switches, the need to associate the semicon- and reliable activity today regulated by very precise protocols
ductors in series to support high steady-state and transient from the electric companies [45] and governments [46][48].
voltage raises their number and complicates protection.
4) A no less important problem is the very high over-current III. ON CONFIGURATIONS, OPERATION
in medium-voltage lines developed as a consequence of MODES AND COMMUTATION
phase-to-phase and phase-to-ground faults. They reach up
to 1 200% the nominal current and last up to 100 ms, the A. Iterative Analysis and Synthesis Cost Comparative Search
opening time of the ordinary line over-current protectors. The method applied to explore the power circuit configura-
These over-currents are well supported by mechanical taps tions has been described in [13] and [14], when applied to the
providing that changes are inhibited in the meantime, but active filters search. Applications to tap changers can be seen in
in electronic versions they make oversizing the thyristors [8], [10], [11], [15][17]. It consists of the following steps: anal-
necessary, as their over-current rate1 for 100 ms is about ysis of new circuits; synthesis of component rates as a function
200% of the nominal current, far from the 1 200% needed. of equipment specifications; study of circuit variants; derivation
EPRI concludes that major breakthroughs are required of component cost by transformation to standard components;
before LTC equipment using solid-state devices can become technical and economical comparison of solutions.
economically attractive for ordinary power transformers. Such This paper compares the advantages of the general config-
1High current thyristors allow during 100 ms about 200% of the nominal
urations of stabilizers and introduces the commutation circuits.
current. Even taking into account the 0.333 current security coefficient men- Other solutions are studied in subsequent works. All of them are
tioned in II-D [34] (and loosing it during faults), only 600% of the nominal load based on natural zero-current commutation aided by the multi-
could be supported with thyristors not oversized by this reason, thus still under
1 200%. 2EPRI Perspective in the Technical Portofolio corresponding to [2].

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 10,2010 at 11:28:43 EST from IEEE Xplore. Restrictions apply.
1494 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 3, JULY 2009

TABLE I
STATES FROM A GIVEN NUMBER OF TAPS. IN
BRACKETS TOTAL TAPS FOR THE EXAMPLE

winding coil seen in II-D and their variants [4][7] because of


the low overcurrent and overvoltage developed in the thyristors
during the changes and the good practical results in low-voltage
Fig. 7. Shared load mode. Steady state with taps 1 and 2 activated. Ideal
applications. They can be referred to as thyristor-based, slow- switches and coil with perfect coupling. Load power factor 0.8 inductive.
commutated tap-changers, acting once in a half-cycle or at a
lower rate (supercyclic commutation).
is added or subtracted under the extreme condition. For the pre-
B. Configurations Comparison vious numerical example of the nominal. This
Irrespective of the circuit configuration, the number of means that the maximum power managed by the compensating
voltage state changes needed by a line stabilizer is a function transformer is 14.5% of the nominal power.
of the input high-voltage deviation to be compensated ( , As shown in Section II-E, in both structures the taps can be
positive and negative per unit deviation, respectively) and the in the primary or in the secondary of the main transformer. In
allowed output voltage deviations . The voltage drops the direct structure with taps on the primary side, the semicon-
with nominal load in the mains transformer and in the ductors can be used to open the circuit in case of a line fault,
line also have to be compensated. As most mechanical but they must be sized to support the fault current reflected to
tap-changing line stabilizers, the electronic counterpart must the primary and the inrush current when connecting the trans-
offer the ability to add or detract an optional per-unit output former. Using autotransformers in the compensating structure
deviation . By neglecting the voltage drops in the internal brings about an important reduction in their size and very eco-
transformers and coils and in the switches, the number of nomical equipments (Fig. 3). If the isolation transformers are
changes needed is maintained the electronic switch combs [Fig. 6(b) and (c)] can
be fixed to ground, which simplifies the isolation components
and maintenance, as shown at the end of II-F-2.
(2)
C. Operation Modes Comparison. Tap Commutation
where accounts for errors in voltage-sensing and In all solutions considered here, the multi-winding coil seen
control management. As an example, for in II-D, Fig. 5(a), is used to reduce the internal short-circuit cur-
(legal rent during commutation. This coil enables four steady state op-
maximum 0.07), and , the result eration modes, each one associated to a tap commutating pro-
is (eight in practice). Obviously, the number of cedure. They shall be studied here with the minimum extension
required voltage states is needed to make a technical-economical comparison in part IV.
1) Shared Load:
(3) a) Steady State Operation: The alternated corresponding
terminals of the multi-winding coil easily lend themselves to
The taps needed to obtain a given number of states depends sharing the load by two consecutive taps [4] (2nd pat.), [5][7].
on the operation mode (shared, nonshared and mixed load, see Both operating windings make a 1:2 ratio autotransformer that
III-C) [5], [6] and the configuration (Fig. 6) resulting in expres- distributes the load in a 1:1 proportion between the selected taps
sions (4)(9) in Table I. (taps 1 and 2 in Fig. 7). The output voltage must be the mean
Expressions (7)(9) also apply to the direct configuration value of both active taps voltage. A magnetizing current circu-
with double-comb (not contemplated in Fig. 6), sometimes lates in both equalizing windings , where
used for low power with the second comb working as a voltage is the voltage between consecutive taps and the induc-
vernier. tance of a single winding. In practice modifies the scalar
The configurations to be studied here belong to the direct tap currents and to about 0.4 and 0.6 times the nominal
[Fig. 6(a)] and the compensating transformer [Fig. 6(b) and (c)] current. The power rating of the stabilizer feasible with a given
structures. The secondary of this transformer adds or subtracts semiconductor is then multiplied by (1/0.6).
to the line the voltage needed to keep the load voltage within b) Commutating Process: Fig. 8 shows the equivalent cir-
limits. In an optimal design, the same scalar value cuits and the relevant variables evolution for the change from
taps 12 to taps 23.
(10) Turning off the outcoming switch. Interval to .

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 10,2010 at 11:28:43 EST from IEEE Xplore. Restrictions apply.
MARTNEZ GARCA et al.: FEASIBILITY OF ELECTRONIC TAP-CHANGING STABILIZERS FOR MV LINES 1495

At time , the switch of the incoming branch is


turned on while branch remains conducting. The
time duration is chosen slightly over half a cycle to
ensure that extinguishes before . A new equalizing current
operates whose magnetizing effect is opposite the effect
of , due to the change of doted terminals. Nevertheless,
the process does not imply any step in the magnetizing current,
thus avoiding over-voltage in the load and switches.
In fact, when reaches zero at time
the load current is . Then, at time this
current flowing through one winding produces the same mag-
netizing effect that flowing through two windings. The
magnetization sign is also maintained as deduced after the dot
of the involved terminals.
Once is closed at time evolves in a few cycles
from to the new steady state value - .
2) Nonshared Load:
a) Steady State Operation: The circuit in Figs. 7, 8 can
also operate with a single active branch in each voltage state
[6], [7]. One winding and one switch support the nominal load
current and the overloads, a less advantageous condition that in
shared load for the coil and switches. The number of voltage
states equals the number of taps, see (5), one state more than
for shared load, see (4). The voltage drop in the coil
(90 in advance with respect to ) can be up to four times the
drop in the switch, not appreciably disturbing the load voltage.
b) Commutating Process: The commutation to a next tap
has two steps. First, the switch of the incoming branch is turned
on and starts operating in shared load with the outgoing branch,
as explained in III.C.1. After a few milliseconds, the outgoing
switch is de-excited with no regard to its current. It is effectively
turned off in the first current zero crossing, as seen in III-C-1.b
for . No steps are forced in the magnetizing current, nor is
voltage transient generated. Since this operation in shared load
lasts no more than one or two half-cycles, a higher value for the
equalizing current than in shared load is permitted and a low coil
Fig. 8. Commutating process for shared load. (a) Equivalent circuit before t : voltage drop in steady state is easily obtained. The equivalent
from t to t , the outcoming switch S is de-excited but still conducting. (b) power of the coil is also reduced.
Equivalent circuit from t on: the incoming switch S is turned on and shares the
load with the permanent switch S . (c) Relevant current and voltage waves. The
3) Mixed Load (Shared and Nonshared Load): By com-
equivalent circuit from t to t , with S on and S ; S off, is not represented. bining the above modes, a mixed operation is obtained. The
Note that i is I before t and goes towards -I after t . load can be fed in steady state either by one single branch or
by two consecutive branches [4] (1st and 3rd pat.), [6]. The
number of voltage states, see (6), is the sum of the states in
While the branches and , for instance, are both modes. The switches and the coil windings must be rated
turned on, each one producing , see Fig. 8(a), the out- for nonshared load. must be a compromise drawn from
coming switch is de-excited at time . It is effectively turned the recommended values for shared and nonshared load. In a
off after the first zero-crossing of its current change, the stabilizer passes from a given mode to the other
at time . The load is now fed by branch until one. Only the following changes are possible:
is turned on at time . The equivalent circuit for to is 1) Change from one operating branch, nonshared load, to two
not given in Fig. 8. This subinterval lasts less than half a cycle branches (incoming the next or the precedent tap) shared
and the peak value of is in practice 3 to 7 times its repetitive load.
peak during steady state operation with nominal load. 2) Change from two branches, shared load, to a single branch
The equivalent total magnetizing current (defined as (outgoing: either the superior or the inferior tap), non-
flowing through a single winding, entering in dotted terminal) shared load.
is until and from to . The peak value In any case the commutation follows one of the processes
of must not saturate the core to keep the limitation ability seen in III-C-1.b or III-C-2.b.
during the next interval. 4) Nonshared Load and Mixed Load With Coil Short-Circuit
Turning on the incoming switch . Winding: If the coil voltage drop in nonshared load is too high

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 10,2010 at 11:28:43 EST from IEEE Xplore. Restrictions apply.
1496 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 3, JULY 2009

(as in equipment with high values of the inter-tap voltage


which, in turn, happens when input and output voltage deviation
can be high), adding a short-circuit winding helps keep that
drop low. and do not operate during commutation.
After a change is shortened by means of an extra switch
[4] (1st and 3rd pat), Fig. 5(a). The inductive drop in the
tap winding is eliminated leaving the resistive drops and the
reflected value of the conducting drop. closes one cycle
after a tap change and opens one cycle before a new change.
The power managed in winding is the same as in a
one-tap winding since both operate assembled as a transformer. Fig. 9. Solution 1. Three-phase stabilizer, direct configuration, taps in the sec-
ondary. Only phase R is detailed. Values for a typical medium voltage line.
The current in is reduced by the turns ratio of with
respect to a main winding. If this ratio is chosen over ten, the
cost of becomes negligible.

D. Coil Magnetic Evolution. Equivalent 50 Hz Transformer


Power
If a commutation starts with no heed paid to the magnetic
state of the coil core, the induction can in practice reach a tran-
sient value up to 2.8 times the steady state value, [5], [6]. Then,
typically a steady induction of 0.5 T must be chosen to guarantee
no more than 1.4 T in transients which, in turn, results in a high
core section. The resulting worst half-cycle peak current during Fig. 10. Stabilizer, with series compensating transformer CT, connected at the
commutation found in equipment designed under this criteria, output of the line feeding transformer. Circuit variant with independent shunt
as mentioned in II.D, is less than 4 times the steady repetitive transformer ST feeding the tap changer. To calculate ST power, the single comb
is assumed. Only one phase is detailed.
peak current with nominal load for shared load, less than 6 times
for nonshared load and less than 7 times for mixed load (when
operating in single tap).
For stabilizers over 100 kVA it is economically advisable to
limit the maximum induction (thus reducing the security factor
from 2.8 to 1.3 or less) by choosing a convenient instant to start
commutation. This requires a delay of one cycle or less from the
tap change order of the control circuit. The delay has no practical
effects in slow acting (supercyclic) stabilizers. The equivalent
50 Hz transformer power of the coil is reduced in the same pro-
portion as the maximum induction. The commutation start time
can be chosen by monitoring the core induction, by voltage and
current phase criteria or by a mixed procedure.

IV. INITIAL ANALYSIS AN SYNTHESIS OF CONFIGURATIONS Fig. 11. Single-phase circuit of the stabilizer for solutions with compensating
transformer CT and fault deviation switch S . The tap topology chosen in the
Here the direct and the compensating transformer configu- figure is a single switch-comb of five taps (Fig. 6(b)). The shunt transformer ST
rations (see III-B) shall be briefly analyzed and synthesized to feeds CT through de tap comb and the limiting multiple winding coil L 0 L.
compare their pros and cons independently of the operation ST also adds a fixed voltage to the line to accomplish balanced operation of CT.
An optional medium voltage disconnecting switch MDS makes live installation
mode (shared, nonshared and mixed load, see III-C) applied. and removal possible.
As this study will show, the direct configuration (Solution 1)
is at a clear disadvantage, both technically and economically.
It is similar to the solutions studied by EPRI [2], [3]. The sta- rent rate. In electronic equipments this advantage is cancelled
bilizers derived from the compensating configuration here pro- by the need for more series-connected semiconductors.
posed (Solutions 2 to 5) can be installed in any point of the line Fig. 9 shows the general circuit with only one phase in detail
with no association to the line transformer, thanks to an auxil- for the sake of simplicity. Three-phase equipment is normally
iary feeding shunt transformer. made with three wye-connected single-phase circuits, although
other connections are sometimes preferred for specific applica-
A. Stabilizers With Direct Configuration (Solution 1) tions and control strategies [22].
The electronic switches are linked to the secondary of the 1) Thyristor Rating: The steady estate current in the switches
HV/MV transformer that feeds the medium voltage line. They (nonshared load; mixed load in the nonshared condition)
manage the complete line power and voltage. In many mechan- is the nominal line current . The maximum overload typi-
ical stabilizers the switches are in the primary to reduce the cur- cally previewed by line operators is 0.2 during 1 h every 8

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 10,2010 at 11:28:43 EST from IEEE Xplore. Restrictions apply.
MARTNEZ GARCA et al.: FEASIBILITY OF ELECTRONIC TAP-CHANGING STABILIZERS FOR MV LINES 1497

h and, under fault condition, 11.5 during 0.1 s. Normally, ) are needed for the equipment. Thyristors for the coil short-
all semiconductors are chosen so as to withstand the voltage of circuit switches seen in III-C-4, if any, have been ignored
the upper tap. The worst case voltage (maximum line voltage because of their low rating. This confirms the EPRI conclusion
condition) is derived taking into account that the transforming seen in II-F-1: the electronic upgrade of mechanical stabilizers
ratio between the secondary upper tap and the primary must by simple substitution of switches in the direct configuration is
guarantee the minimum allowed load voltage plus the optional possible but expensive.
output deviation , while compensating for 2) Mains Transformer Power: The effective power of the
the voltage drops and , under minimum input voltage mains transformer exceeds the nominal power [10 MVA in
. Then (for the numerical limits given in the ex- the example] due to the extra winding necessary to feed the ex-
ample in III-B, for the line of 34.5 kV and 10 MVA in Fig. 9, treme tap operating with minimum input voltage and maximum
and for the said 11.5 overload rating), each switch withstands load. The extra secondary voltage needed to compensate for the
negative input deviation and the line drop , in per unit of
the nominal voltage, is , so that the power
of the transformer rises in that proportion.
MVA kV In transformers cooled by oil, the typical transient line over-
load condition (20% during 1 h every 8 h, as shown in IV-A-1)
A rms during (11) for this equipment makes it necessary to overrate the power
A rms during s (12) following the average quadratic rule. Afterwards, the effective
power of the transformer for this configuration and the values
kV kV rms of the example is
repetitive peak kV kV (13)

Taking into account the usual security coefficients [34] such


MVA
as
for current; 0.83 supplementary for parallel asso- MVA (17)
ciation;
for voltage; 0.7 supplementary for series association; The per unit extra secondary voltage
the ratings for the series-parallel ensemble in each switch are has been calculated for nonshared load for the sake of simplicity.
For other operation modes similar values are obtained. The av-
A rms during h (14) erage quadratic factor 1.027 also would apply for a line trans-
former without taps.
A
3) Equivalent 50 Hz Transformer Power of the Multi-Winding
A repetitive peak during s (15) Coil: The mixed load mode is considered here because it gives
kV kV repetitive peak (16) the best economical results. Every winding withstand the nom-
inal current in nonshared load, although in shared load the cur-
An economical and easy option (March 2007), which is not rent is lower. The voltage handled by any winding is equal to
in the limit of the available current and voltage, could be the the output voltage change which, in turn, must not exceed the
thyristor Westcode K1947ZC450 (330 /unit) whose charac- allowed step of the output voltage . This value
teristics are can be affected in practice by 0.9 due to voltage drop in the con-
ducting thyristors. Pressumably, a 0.8 coefficient acounts for the
A RMS C and under rate of the windings section due to nonsimultaneous op-
for an antiparallel pair eration. Thus, the equivalent power becomes
A A rms
A av
A C and
for an antiparallel pair
MVA (18)
A A rms
A repetitive peak during ms where 6 is the number of windings (five main windings and one
A nonrepetitive peak ms short-circuit winding, see Sections III-B and III-C.4).
V repetitive peak 1.2 is the core section overrating if the commutating instant
is optimized (see III-D).
Subsequently, a series association of kV kV
steps is needed. Parallel association is not required. Thus, B. Stabilizers With Series Compensating Transformer and
for the three phases thyristors (59 400 ) Fault Current Deviation (Solutions 2 to 5)
per tap in one phase are needed. For the best case, mixed load They show the advantages listed in Sections II-E and III-B as
[five taps per phase, see expression (6)], 900 thyristors (297 000 follows.

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 10,2010 at 11:28:43 EST from IEEE Xplore. Restrictions apply.
1498 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 3, JULY 2009

The power managed electronically is, typically, 15% of the and the voltage added by the CT secondary in extreme condition
nominal. 1 (equal to the voltage subtracted in extreme condition 2) is
The series association of thyristors is replaced by parallel
association, which is more reliable and economical.
Overload in the switches due to line faults is practically
eliminated.
The switches achieve galvanic isolation so that the as-
sembly can be separated from the transformers and fixed
to ground voltage. Both thyristor isolation and live main- kV (22)
tenance become easier.
The stabilizer can be settled at any point of the line, with This is a very economical configuration if the voltage given
no connection to the feeding line transformer. by expression (22) is lower than 0.3 . The operation and
The general circuit for these solutions is given in Fig. 10. commutation modes seen in Section III-C also apply to this
As shown in Fig. 3, and in Section II-E, Fig. 6(b), (c), the sec- group of solutions.
ondary of the series compensating transformer CT adds or sub- Besides the stated reduction of the power managed by the
tracts the voltage required by the line at the settling site chosen. switches (reduced to 0.145 in the example, see (22)), CT
The voltage needed to feed the primary is obtained by means helps to drastically cut down their overcurrent due to line faults
of a shunt transformer ST and associated taps. The power man- by means of an extra fault deviation switch connected
aged by CT is proportional to the voltage added-subtracted to across the primary, see Fig. 11. Once the fault is detected, the
the line voltage, typically 15% of the nominal power as advised conducting main switches are inhibited turning off at the first
in Section II.E. This figure also shows the power managed by current zero crossing. One half-cycle later (to avoid internal
the switches. short-circuit) is turned on absorbing the line over-current
The optimum design (minimum managed power) seeks equal reflected into the CT primary until the ordinary line protection
voltages added and subtracted by the secondary of CT in the ex- switch opens (normally after 100 ms maximum). In this way
treme conditions. If the combination of required line input and the maximum line current (typically, 12.5 times the nominal)
output voltage limits, MT drop and line drop do not result in an reflected to CT primary is supported by the main switches
overall symmetrical voltage addition and subtraction, an extra during one or two half cycles, and by during no more than
balance winding in the ST primary, in series with CT primary, 100 ms. As the thyristors of are usually open, they do not
is needed to attain balanced operation of CT. The extra winding need cooling heatsinks. Under fault condition, the stabilizing
works as an autotransformer with the main primary winding and operation is inhibited and the equipment is seen by the line as
adds half the difference between the system adding and sub- a short-circuited CT in series with the balance winding of ST.
tracting voltages. For the example in Section III-B, the extreme The rising effect of ST in the line fault current is compensated
conditions are: approximately by the short-circuit impedance of CT.
Extreme condition 1: Minimum input voltage, nominal 1) Single Switch-Comb Circuit: The single-comb configura-
load. The maximum phase-neutral voltage to be added by tion, Fig. 11, shall be first studied in detail for the sake of con-
the stabilizer is (numerical values for the example given ceptual and circuit simplicity.
in III-B) a) Thyristor Rating: Tap thyristors: The line current re-
flected in the CT primary is the steady state current in any con-
ducting tap switch for the nonshared load, and the maximum
value of this current for mixed load. For single-comb, Figs. 6(b)
kV (19) and 11, the voltage seen by the extreme tap switches is the sec-
ondary voltage of ST, which must be chosen to take maximum
Extreme condition 2: Maximum input voltage, no load. advantage of available medium voltage thyristors without se-
The maximum phase-neutral voltage to be subtracted is ries association. For using thyristors of 4 500 V repetitive peak
, for instance, the secondary rms voltage of ST
must be 4 500 V V. Following the example
in Section III-B, the balanced configuration in Figs. 10, 11, and
supposing, for the sake of simplicity, that the common tap is in
kV (20) the middle of ST secondary, the sec./prim. ratio of CT (ignoring
voltage drop in switches and ohmic drop in coils), according to
The phase-neutral voltage added by the balance winding be- (22), is
comes

V
V
kV (21) (23)

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 10,2010 at 11:28:43 EST from IEEE Xplore. Restrictions apply.
MARTNEZ GARCA et al.: FEASIBILITY OF ELECTRONIC TAP-CHANGING STABILIZERS FOR MV LINES 1499

where is the voltage drop in CT for nominal load change with respect to a standard nontap transformer of the
in per unit of its own voltage. nominal power (10 MVA in the example).
Extending to every tap switch the voltage requirements for c) Effective Power of the Compensating Transformer CT:
the extreme taps, each switch withstands To guarantee independent voltage stabilization of the phases,
three single-phase compensating transformers are needed. The
power managed by one CT in the extreme condition 1 (see IV-B)
MVA kV is the product of the added phase voltage, expressed in (22), by
the nominal line current . Taking into account the 1 h overload
A rms during (24)
as in (17), the CT effective power becomes

A nonrepetitive ms peak (25)


V repetitive peak (26)

Introducing the security coefficients seen in Section IV-A-1,


the nominal ratings for every tap semiconductor ensemble be-
come MVA (33)

A d) Effective Power of the Shunt Transformer ST: In ex-


A rms during h (27) treme condition 1, the single phase power given by the balance
winding is the product of the voltage expressed in (21) by the
A
nominal line current . The single-phase power given by the
A nonrep ms peak (28) upper half of the secondary to CT is given by (33) plus CT
V losses. The lower half manages similar power in the extreme
V repetitive peak as ab initio (29) condition 2. A 1.4 factor is applied as the secondary halves
do not operate simultaneously. Approaching the sum of unitary
By using the thyristor Westcode K1974ZC450 as in the di- losses in CT, the coils and the switches to four times the CT
rect configuration in Section IV-A-1, two units in parallel are voltage unitary drop under load , the equivalent
needed. After the ratings related in Section IV-A-1 for a single 50 Hz power of ST becomes
SCR, the ratings for the tap ensemble (four SCR: two paralleled
antiparallel pairs) become

A MVA (34)
C permanent (30)
e) Equivalent 50 Hz Transformer Power of the
A
Multi-Winding Coil: As for the direct configuration, the
A nonrepetitive ms peak (31) mixed load mode is considered. The value given in (18) is
V repetitive peak (32) also valid for the compensating configurations as, although the
winding voltage is now divided by , its current is multiplied
that surpasses the requirements given by (27) and (28). by the same ratio.
The final result is four individual thyristors per tap, which, for 2) Double Switch-Comb Circuit: In the double-comb config-
three-phase equipment, means 12 thyristors (3 960 ) per uration [Fig. 6(c)]more suitable than the single-comb for high
tap in one phase. For the best case (mixed load) of the proposed power, as in the example (10 MVA)we take (as in IV-B-1-a) 1
example (5 taps per phase), this gives 60 thyristors (19 800 ) 273 V again for the complete ST secondary. The voltage stress
for the equipment. Coil short-circuit switches are ignored as in of the switches does not change. The ratio and the current
IV-A-1. in the taps are divided by two, as the voltage in CT primary for
Fault deviation thyristors: Switch withstands the fault the extreme conditions is twice the value for single-comb. For
line current reflected to the primary of CT and, for the single- the example, shared load, 6 taps per comb result, see (9). Fol-
comb circuit (Fig. 11), supports half the voltage seen by the lowing the calculus procedure of IV-B-1 for the single-comb,
tap switches, as one side of the CT primary is connected to the the results are:
common tap. After the security coefficients seen in IV-A-1, the a) Thyristor Rating: Tap thyristors: The current demand
repetitive peak current rating for is expressed in (25) ex- per tap is given by (27) and (28) divided by two. The repetitive
tended to 100 ms. The voltage is half the value expressed in peak voltage is given by (29). By using the same K1974ZC450,
(26). Three switches can be made, for unification, with 12 a single antiparallel pair per tap (no parallel or series associa-
units K1947ZD450 (two paralleled antiparallel pairs per phase) tion needed) results. For mixed load ( taps per phase) 36
used for the taps, although underused in voltage. This represents thyristors (11 880 ) for the equipment are needed.
an additional 3 960 to the cost of the equipment. In both the single and the double-comb circuit, the cost of the
b) Mains Transformer Power: The equipment is indepen- small switch (see III-C-4) to shorcircuit the coil, if any, has
dent of the mains feeding transformer which does not need to not been considered.

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 10,2010 at 11:28:43 EST from IEEE Xplore. Restrictions apply.
1500 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 3, JULY 2009

Fault deviation thyristors: Switch withstands twice the TABLE II


voltage (4 500 V repetitive peak) and half the current (expres- THYRISTORS AND MAGNETIC COMPONENTS IN DIRECT AND COMPENSATING
CONFIGURATIONS FOR THE 10 MVA STABILIZER EXAMPLE INTRODUCED IN
sion (25) divided by two: 6 774 A repetitive peak during 100 III-B (CHOOSEN THYRISTOR: WESTCODE K1947ZC450 (330 C
=/UNIT, MARCH,
ms) needed with the single-comb. For the example, six units 2007) COMPARED TO THE CLASSICAL ELECTROMECHANICAL SOLUTION
(one antiparallel pair per phase) of the aforementioned thyristor
are needed, adding 1 980 to the cost of the equipment.
Comparison of the thyristor rating with direct configuration:
The results in IV-B-1.a and IV-B-2.a for the assembly of tap
and fault deviation thyristors show that the compensating trans-
former configuration improves the poor expectations of early
economical studies carried out excluding this configuration [2],
[3]. Although both the single and the double switch-comb dras-
tically reduce the number of thyristors, the double-comb has a
clear advantage.
b) Mains Transformer and Compensating Transformer
Power: The same considerations than for single-comb apply magnetic components have to be considered for a more com-
to the mains transformer. The compensating transformer has plete comparison. In the first column, the three-phase direct me-
the same secondary than in the single comb. The primary has chanical configuration (as appears in Fig. 6(a) for single-phase)
half the current and twice the voltage so that the same effective is given. The thyristors cost of the compensating transformer,
power (33) applies. The ratio is half the value given in double-comb, configuration is lower than the cost of the electro-
(20). mechanical switch assembly (Fig. 2, upper, left).
c) Effective Power of the Shunt Transformer ST: The
working conditions of the balance winding are the same as that
for single-comb. Only one secondary is needed with 1 273 V V. LIVE WORKING INSTALLATION AND REPAIR
rms to have the same nominal repetitive peak voltage rate in
As a consequence of their independence from the line feeding
the switches than for single-comb (4 500 V). The ratio is
transformer, the stabilizers derived from the compensating con-
half the value given in (23). Equation (34) for the equivalent 50
figuration proposed in IV-B can be connected to any point of the
Hz power of ST with a single-comb, becomes the following for
line to regulate the downstream voltage or to adjust the voltage
the double-comb:
of a derived line.
The stabilizer (in the single-phase equivalent circuit) is seen
by the line as a dipole (see Fig. 11) similar to the medium voltage
disconnecting switches used to isolate parts of a complex net
MVA (35)
[49], [50]. Subsequently, the stabilizer can be connected and
removed by using the same live working installation procedure
d) Equivalent 50 Hz Transformer Power of the
[45][47] developed by the electric companies for such switches
Multi-Winding Coils: For the proposed example, mixed
without service interruption, see Fig. 12 and Table III.
load, double comb, two multi-winding coils per phase with
Since the power-electronic assembly is at ground potential,
three tap coils (plus one short circuit coil) are needed. The
some maintenance operations can be performed in live status.
voltage winding is twice and the current is half the respective
values for single comb. By modifying expression (18), the
equivalent power of each coil becomes VI. AUTOREMOVAL
In case of stabilizer internal malfunction, the tap switches and
associated circuits can be functionally eliminated by following
the removal sequence in Table III up to point 3, keeping in co-
ordination the OLTC control and the MDS control. The line can
MVA (36) remain operative during the stabilizer reparation in situ or the re-
moval and reparation in a workshop, in this case following the
complete removal sequence.
C. Quick Economical Comparison of Direct and Compensating
Transformer Configurations VII. CONCLUSION
Table II compares the thyristors and the magnetic components The feasibility of voltage stabilizers for medium voltage lines
needed in the direct and the compensating configurations, mixed based on electronic tap changers has been reviewed drawing
load, to implement the 10 MVA stabilizer of the example in- from the advantages of using a multi-winding commutating coil,
troduced in III-B. The compensating configuration (both with largely proved in power distribution applications. This coil re-
single and double-comb) adds extra advantages as a free con- duces the commutation stress of the thyristors so that overrating
nection to any point of the line (see Section V). The costs of the is not necessary.

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 10,2010 at 11:28:43 EST from IEEE Xplore. Restrictions apply.
MARTNEZ GARCA et al.: FEASIBILITY OF ELECTRONIC TAP-CHANGING STABILIZERS FOR MV LINES 1501

TABLE III
LIVE WORKING INSTALLATION STEPS PLANNED FOR THE COMPENSATING
TRANSFORMER CONFIGURATION STABILIZER PROPOSED IN FIGS. 1012

The configuration proposed needs additional electromag-


netic components (multi-winding commutating coil, shunt
transformer and compensating transformer) whose power is
keep under reasonable limits (about 15% of the nominal power).
The advanatages of the proposed stabilizer are as follows.
Isolation of the electronic ensemble with respect to the line.
It can be connected to ground potential.
Series association of the thyristor is not needed. For power
of more than 10 MVA, an easy parallel association would
be needed.
The fault line current is derived from the tap thyristors to a
specific, not expensive, fault deviation thyristor switch.
Connection to any point in the line without any connection
to the head of the line feeding the transformer.
The configuration that is chosen facilitates eventual live
working installation and repair.

REFERENCES
[1] Transformers Committee of the IEEE Power Engineering Society, ,
IEEE Standard Requirements for Load Tap Changers. New York,
1995.
[2] P. Wood, V. Bapat, and R. P. Putkovich, Study of improved load-
tap-changing for transformers and phase-angle regulators, EPRI Rep.
EL-6079, Nov. 1988, p. 148.
[3] Study of improved load-tap-changing for transformers and
phase-angle regulators, Apr. 1990, p. 108, EPRI Staff, EPRI,
Fig. 12. (a) Single-phase conceptual scheme for the line connection of the com-
pensating configuration stabilizer proposed in Section IV-B. In parallel with the Rep. EL-6764.
[4] S. Martinez, E. BOAR, and S. A. , Perfeccionamientos en equipos
stabilizer there is a classic mechanical disconnecting switch (MDS). (b) Stabi-
lizer inhibited, MDS open, S closed. (c) Equivalent circuit for (b) status. Only electronicos para regulacin de tension alterna. . ., Spanish Patents
500.523, (Oct. 1981), 500.524 (Oct. 1981), 522.497 (Oct. 1984).
the short circuit impedance of CT remains in series with the line. (d) Possible
ground installation at a generic line point allowing a live working connection [5] S. Martinez, Estabilizadores de c.a. por pasos con carga compartida,
and removal. Single-phase representation after Fig. 1 of [49]. Aerial installation Mundo Electron., no. 166, pp. 127135, Oct. 1986.
[6] D. Gahigiro, M. A. Erro, and S. Martinez, AC tap changing stabi-
as in Fig. 4, right, is also possible.
lizers with limited commutating current, in Proc. IEEE 1st Power
Electronics Int. Congr., Cuernavaca, Mxico, Aug. 1992, pp. 195208.
[7] S. Martinez, Alimentacion Electronica de Equipos Informaticos y Otras
Cargas Criticas, ser. Electrotecnologias. Aravaca, Madrid: McGraw-
The study confirms the high costs of thyristors previewed Hill Interamericana, IBERDROLA, EVE), 1992.
[2], [3] if the classic direct configuration used in most mechan- [8] G. Villegas, J. Vaquero, R. Echevarria, S. Horta, M. A. Perez, and
ical tap changers is considered. Nevertheless, it also demon- S. Martinez, Quasi-resonant fast on-load tap changer stabilizer, pre-
sented at the IEEE-Cenidet, Morelia, Mexico, Oct. 1998.
strates drastic reductions and the possibility of adding tech- [9] J. Vaquero, J. C. Campo, S. Martinez, and M. A. Perez, Fast on-load
nical advantages by using compensating transformer configu- tap changers possibilities using new power devices, presented at the
rations, well-known in low- and medium-voltage low power Min, 10th Annu. Meeting EWG/IEEE/IAS/IPCC&PEDCC, Aveiro,
Portugal, Jun. 12, 1999.
applications. [10] J. Vaquero, AC on-load tap-changing fast voltage stabilizers for
This paper shows the feasibility of a 69 kV/34.5 kV, 10 MVA power quality improvement, Ph.D. dissertation, Universidad a Dis-
stabilizer for long medium voltage lines by using 42 standard tancia, Madrid, Spain, Apr. 2000.
[11] J. C. Campo, Functional and topological analysis of ultra-fast differ-
thyristors rated 1 847 A, 4 500 V, with no need of series, nor ential ac stabilizers, Ph.D. dissertation, Universidad de Oviedo, Gijn,
parallel, association. Spain, Oct. 2000.

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 10,2010 at 11:28:43 EST from IEEE Xplore. Restrictions apply.
1502 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 3, JULY 2009

[12] J. C. Campo, J. Vaquero, M. A. Perez, and S. Martinez, Fast two- [35] K. Imhof, F. Oesch, and I. Nordanly, Modelling of tap-changer trans-
taps changing AC stabilizer with seminatural switching, Elect. Power formers in an energy management system, IEEE Trans. Power Syst.,
Quality Utilization, vol. 6, no. 1, pp. 111114, Dec. 2000. vol. 11, no. 1, pp. 428434, Feb. 1996.
[13] F. Barrero, S. Martnez, F. Yeves, and P. M. Martinez, Active power [36] B. Kasztenny, E. Rosolowski, J. Izykowski, M. M. Saha, and B. Hill-
filters for line conditioning: A critical evaluation, IEEE Trans. Power strom, Fuzzy logic controller for on-load transformer tap changer,
Del., vol. 15, no. 1, pp. 319325, Jan. 2000. IEEE Trans. Power Del., vol. 13, no. 1, pp. 164170, Jan. 1997.
[14] F. Barrero, S. Martinez, F. Yeves, F. Mur, and P. M. Martinez, Uni- [37] M. Crape, L. Gertmar, A. Habck, W. Leonhard, and D. Povh, Eds.,
versal and reconfigurable to UPS active power filter for line condi- Power electronics and control by micoroelectronics in future energy
tioning, IEEE Trans. Power Del., vol. 18, no. 1, pp. 283290, Jan. systems, in Proc. Lausanne Conf. Rep., EPE J., Apr. 2000, vol. 10,
2003. no. 1, pp. 610, 4046.
[15] J. C. Campo, J. Vaquero, M. A. Perez, and S. Martinez, Dual-tap chop- [38] P. Kang and D. Birtwhistle, Condition assessment of power trans-
ping stabilizer with mixed seminatural switching. Analysis and syn- former on-load tap-changers using wavelet anaysis, IEEE Trans.
thesis, IEEE Trans. Power Del., vol. 20, no. 3, pp. 23152326, Jul. Power Del., vol. 16, no. 3, pp. 394400, Jul. 2001.
2005. [39] P. Kang and D. Birtwhistle, Condition monitoring of power trans-
[16] J. Vaquero, J. C. Campo, S. Monteso, S. Martinez, and M. A. Perez, former on-load tap-changers. Part 1: Automatic condition diagnostics,
Analysis of fast onload multitap-changing clamped-hard-switching Proc. Inst. Elect. Eng., Gen. Transm. Distrib., vol. 148, no. 4, pp.
AC stabilizers, IEEE Trans. Power Del., vol. 21, no. 2, pp. 852861, 301311, Jul. 2001.
Apr. 2006. [40] P. Kang and D. Birtwhistle, Condition assessment of power trans-
[17] J. Vaquero, J. C. Campo, S. Monteso, S. Martinez, and M. A. Perez, former onload tapchangers using wavelet anaysis and self-organizing
Synthesis of fast onload multitap-changing clamped-hard-switching map: Field evaluation, IEEE Trans. Power Del., vol. 18, no. 1, pp.
AC stabilizers, IEEE Trans. Power Del., vol. 21, no. 2, pp. 862872, 7884, Jan. 2003.
Apr. 2006. [41] M. M. Adibi, R. A. Polyak, I. A. Griva, L. Mili, and S. Ammari,
[18] G. Musgrave and D. OKelly, Improvement for Power System Trans- Optimal transformer tap selection using modified barrier-augmented
mission by Solid-State Techniques. London, U.K.: Inst. Elect. Eng. lagrangian method, IEEE Trans. Power Syst., vol. 18, no. 1, pp.
Conf. Publ., Dec. 1974, pp. 228233, no. 123. 251257, Feb. 2003.
[19] G. H. Cooke and K. T. Williams, New thyristor assisted diverter [42] G. N. Korres, P. J. Katsikas, and C. Contaxis, Transormer tap setting
switch for on load transformer tap changers, Proc. Inst. Elect. Eng. observability in state estimation, IEEE Trans. Power Syst., vol. 19, no.
B, vol. 139, no. 6, pp. 507511, Dec. 1974. 2, pp. 699706, May 2004.
[20] R. Shuttleworth, X. Tian, C. Fan, and A. Power, New tap changing [43] Consideraciones a la Regulacin de Tensin en ST a Los Niveles
scheme, Proc. Inst. Elect. Eng., Elect. Power Appl., vol. 143, no. 1, de MT. Bilbao, Spain, Sept. 1992, Personal DERED/PLANIFI-
pp. 108112, Jan. 1996. CACIN, Manual de Organizacin y Procedimientos, IBERDROLA
[21] A. Krmer and J. Ruff, Transformers for phase angle regulation con- S.A..
sidering the selection of on-load tap-changers, IEEE Trans. Power [44] F. S. Roesner and T. J. Sillers, Understanding voltage regulators,
Del., vol. 13, no. 2, pp. 518525, Apr. 1998. Elect. Power Int., p. 32, 58, Mar. 1995.
[22] M. T. Bishop, J. D. Foster, and D. A. Down, Single-phase voltage [45] Trabajos en Tensin, Mtodo a Distancia, Instalacin de rgano de
regulators and three-phase systems, IEEE Ind. Appl. Mag., vol. 2, no. Corte de Red, Simple Circuito, Aislamiento de Amarre. Bilbao,
4, pp. 3844, Jul./Aug. 1996. Spain, Sep. 1996, Personal Distribucin y Clientes, Manual Tcnico
[23] CPS staff, Cooper Power Systems, , Voltage regulators Bull. B225- de Distribucin y Clientes MTDYC 2.25.70, IBERDROLA-DIDYC.
97020, Jul. 2005. [46] Office of the Queensland Parliamentary Counsel, High voltage
[24] J. Arrillaga, A static alternative to the transformer on-load live line work, in Electric Safety Regulation 2002 (Division 3).
tap-changer, IEEE Trans. Power App. Syst., vol. PAS-99, no. 1, [Online]. Available: http://www.deir.qld.gov.au/electricalsafety/busi-
pp. 8691, Jan./Feb. 1980. ness/workers/live/safely/index.htm.
[25] R. M. Mathur and R. S. Basati, A thyristor controlled static phase- [47] Manual de Construo e Manuteno de Redes de Distribuo-Stan-
shifter for AC power transmission, IEEE Trans. Power App. Syst., vol. dard Operation Procedures for Live-Line Works in Spacer Cable,
PAS-100, no. 5, pp. 26502655, May 1981. CEMIG, Minas Gerais Brazil, 1998.
[26] E. C. Servetas and V. Vlachakis, A new AC voltage regulator using [48] Live Working, IEC/TC78, , Int. Elect. Committee., 2003.
thyristors, IEEE Trans. Ind. Electr. Control Inst., vol. IECI, no. 2, pp. [49] rgano de Corte en Red4a ed. May 2002, NORMA IBERDROLA, NI
140145, May 1981. 74.53.01.
[27] G. Gth, G. R. Baker, and P. Eglin, Static thyristor-controlled regu- [50] Fichas tcnicas de lineas aereas de media tensin 12/20 kV, Regu-
lating transformer for AC transmission, presented at the Inst. Elect. lador de Tensin Para Lineas de MT; LAM70 Organo de Corte en Red
Eng. Int. Conf. Thyristor and Variable Static Equipment for AC and de Intemperie (OCRI), Feb. 2003, IBERDROLA, DITEC-NOMAN,
DC Transmission, London, U.K., Nov./Dec. 1981. MT 2.03.96-II, 1a Ed.: LAM68.
[28] F. Q. Yousef-Zai and D. OKelly, Solid-state on-load transformer tap
changer, Proc. Inst. Elect. Eng., Electr. Power Appl., vol. 143, no. 6,
pp. 481491, Nov. 1996.
[29] O. Demirci, D. A. Torrey, R. C. Degeneff, F. K. Schaeffer, and R. H.
Frazer, A new approach to solid-state on load tap changing trans-
formers, IEEE Trans. Power Del., vol. 13, no. 3, pp. 952961, Jul.
1998.
[30] P. Bauer and S. W. H. de Haan, Electronic tap changer for 500 kVA/10
kVA distribution transformers: Design, experimental results and impact
in distribution networks, presented at the IEEE-IAS Annu. Meeting, Salvador Martnez Garca (M88SM90) was
St. Louis, MO, Oct. 1998. born in Spain in 1942. He received the M.Sc. and
[31] H. Jiang, R. Shuttleworth, B. A. T. Al Zahawi, X. Tian, and A. Power, Ph.D. degrees in electrical engineering from the
Fast response GTO assisted novel tap changer, IEEE Trans. Power Polytechnic University of Madrid, Madrid, Spain, in
Del., vol. 16, no. 1, pp. 111115, Jan. 2001. 1966 and 1969, respectively.
[32] J. Faiz and B. Siahkolah, New solid-state onload tap-changers He was Associate Professor at the Polytechnic
topology for distribution transformers, IEEE Trans. Power Del., vol. University of Madrid from 1975 to 1979 and at
18, no. 1, pp. 136141, Jan. 2003. the National Distance University of Spain, Madrid,
[33] J. Faiz and B. Siahkolah, Optimal configurations for taps of windings from 1979 to 1982, where he has been Full Pro-
and power electronic switches in electronic tap-changers, Proc. Inst. fessor since 1982. He was a Design Engineer of
Elect. Eng., Gen. Transm. Distrib., vol. 149, no. 5, pp. 517524, Jul. power-electronics equipment in several companies
2002. for eight years. His research interests are in integrated magnetics and power-line
[34] J. F. Ruiz-Garrido, Security coefficients for power thyristors in elec- conditioners.
tronic power converters SEPSA, Pinto, Madrid, Spain, Tech. Rep. 14, Prof. Garca was a member of the IEEE Industry Applications Society Indus-
Jun. 2000. trial Static Converter Committee EWG from 1990 to 1997.

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 10,2010 at 11:28:43 EST from IEEE Xplore. Restrictions apply.
MARTNEZ GARCA et al.: FEASIBILITY OF ELECTRONIC TAP-CHANGING STABILIZERS FOR MV LINES 1503

Juan Carlos Campo Rodrguez (M97) born in Alfonso Ibarzbal Segura was born in Spain in
Spain in 1970. He received the M.Sc. degree in 1945. He received the M.Sc. degree in electrical
electrical engineering from the Oviedo University, engineering from the Polytechnic University of
Asturias, Spain, in 1995 and the Ph.D. degree in Bilbao, Bilbao, Spain, in 1974.
electrical engineering in 2000. He is the Technical Director of INCOESA, ded-
Currently, he is an Associate Professor in the De- icated to the development and manufacture of dis-
partment of Electrical and Electronic Engineering at tribution power transformers, medium-voltage trans-
Oviedo University, where he has been since 1995. He formers, and onload tap changers.
has conducted research on a fast-tap changers for ac Mr. Segura is a member of the Standards
voltage control. His current research interests include Technical Committee of AENOR CTN207/GT 14,
power quality, line conditioners, and tap changers. Power Transformers.

Jos Antonio Jardini (M66SM78F90) was Pedro Mara Martnez Cid was born in Spain in
born in Brazil in 1941. He received the M.Sc. and 1956. He received the M.Sc. degree in electronic and
Ph.D. degrees from the Polytechnic School of So control engineering from the National Distance Uni-
Paulo University, EPUSP, So Paulo, Brazil, in 1971 versity of Spain, Madrid, in 1989.
and 1973, respectively. Since 1995, he has been a Lecturer with the
He was with Themag Eng. Ltd. for 25 years, National Distance University of Spain at the As-
where he conducted numerous studies on power sys- sociated Centre of Bilbao. In 1979, he joined the
tems and participated in many important Brazilian electrical company IBERDROLA S.A. where he has
projects, including Itaipu. Currently, he is a Pro- conducted research-and-development projects on
fessor in the Departamento de Energia e Automao flexible ac transmission systems (FACTS), including
Electricas da Escola Politcinca da Universidade de the ESTRAP Project among them. He is with the
So Paulo, So Paulo, Brazil, teaching power analysis and digital automation. Division for Innovation, Power Quality, and Ambient Studies.
He has conducted research work in power systems for many Brazilian utilities. Mr. Cid is a member of several international committees for the promotion
Prof. Jardini is a member of the CIGRE Working Group on HVDC transmis- of FACTS.
sion.

Joaqun Vaquero Lpez was born in Spain in 1968.


He received the M.Sc. degree in electrical engi-
neering from the Polytechnic University of Madrid,
Madrid, Spain, in 1994 and the Ph.D. degree from
the National Distance University of Spain, Madrid,
in 2000.
In 1995, he joined the Department of Electrical,
Electronic, and Control Engineering as Assistant Pro-
fessor at the Universidad Rey Juan Carlos. He was
a Design Engineer of power-electronics equipment
with SEPSA from 2000 to 2007. He joined the Elec-
tronics Technology Department at Rey Juan Carlos University of Madrid as an
Associate Professor with research interests in fast multi-tap changers and equip-
ment to improve power quality.

Authorized licensed use limited to: UNIVERSIDADE DE SAO PAULO. Downloaded on March 10,2010 at 11:28:43 EST from IEEE Xplore. Restrictions apply.

You might also like