MOULDED CASE CIRCUIT BREAKERS

DS Page DTH..E Page DG Page

Fixed Overload & Fixed Short-circuit Fixed Overload & Fixed Short-circuit Adjustable Overload & Fixed Short-circuit

release with Normal Breaking Capacity release with High Breaking Capacity release with Normal Breaking Capacity

Technical Data 2/9,2/10 Technical Data 2/11 Technical Data 2/12

I-t Characteristic Curves 2/26 I-t Characteristic Curves 2/27 I-t Characteristic Curves 2/28

MCCB Ordering Data 2/36 MCCB Ordering Data 2/36 MCCB Ordering Data 2/37

Accessories Ordering Data 2/45 Accessories Ordering Data 2/46 Accessories Ordering Data 2/47

Overall Dimensions 2/56,2/57 Overall Dimensions 2/58 Overall Dimensions 2/59,2/60

DH Page DL Page DTH Page

Adjustable Overload & Fixed Adjustable Overload & Fixed Adjustable Overload & Fixed Short-circuit

Short-circuit release with Short-circuit release with release (Conventional MCCBs) with

Standard Breaking Capacity High Breaking Capacity High Breaking Capacity

Technical Data 2/13,2/14 Technical Data 2/15 Technical Data 2/16,2/17

I-t Characteristic Curves 2/29 I-t Characteristic Curves 2/30 I-t Characteristic Curves 2/31

MCCB Ordering Data 2/38 MCCB Ordering Data 2/39 MCCB Ordering Data 2/40

Accessories Ordering Data 2/48 Accessories Ordering Data 2/49 Accessories Ordering Data 2/50

Overall Dimensions 2/61,2/62 Overall Dimensions 2/63,2/64 Overall Dimensions 2/65,2/66


MOULDED CASE CIRCUIT BREAKERS

DX..S Page DX..H Page DM Page

Adjustable Overload & adjustable Short- Adjustable Overload & adjustable Short- Motor protection MCCBs

circuit with standard Breaking Capacity circuit with high Breaking Capacity 3 & 4
3 & 4 Pole Pole

Technical Data 2/18,2/19 Technical Data 2/20-2/22 Technical Data 2/23

I-t Characteristic Curves 2/32-2/34 I-t Characteristic Curves 2/32-2/35 MCCB Ordering Data 2/43

MCCB Ordering Data 2/41 MCCB Ordering Data 2/42 Accessories Ordering Data 2/54

Accessories Ordering Data 2/51,2/52 Accessories Ordering Data 2/51-2/53 Overall Dimensions 2/76,2/77

Overall Dimensions 2/67-2/71 Overall Dimensions 2/67-2/75 Type 2 Co-ordination Chart 2/83

DTH Instantaneous Page DF Page

Instantaneous MCCBs Fuse Monitoring device

Technical Data 2/24 Technical Data 2/25

MCCB Ordering Data 2/44 Ordering Data 2/44

Accessories Ordering Data 2/55 Accessories Ordering Data 2/55

Overall Dimensions 2/78 Overall Dimensions 2/79

Wiring Diagram 2/79


MOULDED CASE CIRCUIT BREAKERS

2 L&T was the first company to introduce Moulded case circuit Breakers (MCCBs) in India. Over the years, it has developed &
enhanced the products to growing requirements of market conditions.

L&T MCCBs use latest technologies for circuit interruption under faults. These MCCBs comply with standards IS 13947, IEC 60947
and EN 60947-2 and are certified at independent and approved test authorities.

L&T offers a wide range of MCCBs with current ratings from 0.63A to 1600A in 3-Pole & 4-Pole versions & breaking capacity from
6kA to 100kA. These MCCBs are available with Thermal-Magnetic as well as with Electronic release (above 125A in DX range).
These MCCBs are available in Fixed or Drawout versions. They are also available in utilisation category A or B.

L&T MCCBs are complemented with a wide variety of internal and external accessories.

APPLICATIONS

Distribution Feeders Ideally suited for incoming and outgoing feeder circuits on distribution boards.

Transformers Provide effective protection to distribution transformers as outgoing breakers on the LT side.

DG Sets Used for protection and control of diesel generating sets against overloads and short circuits.

APFC Systems Suitable for controlling LT capacitors for power factor corrections.

DC Loads Suitable for both AC as well as DC applications. Hence find application in protecting rectifier panels.

UPS Used for UPS & Electronic equipment protection.

Motors Specially designed MCCBs for Motor back-up protection provide Type-2 co-ordination (as per IEC 60947)
in conjunction with suitably rated contactors and relays.

Furnaces Suitable for high frequency systems upto 400Hz and can be used for control of high frequency furnaces.
Also used in induction furnaces along with semiconductor fuses.

WORKING PRINCIPLE

L&Ts new range of MCCBs operate on Current limiting principle. This


helps in very fast clearance (less than 10 mS) of short-circuit faults. This is
achieved by

1. Quick opening of main contacts.

2. Guiding the arc rapidly away from the contacts into the arcing chamber.

3. Quick quenching of arc by using effective arc quenching devices.

As a result peak short circuit current (Ip) is limited to cut-off current (I c).

Thus, I2t let through (proportional to the shaded area) is considerably


reduced, resulting in lower thermal stresses in downstream equipments
and connecting cables.

2/1
MOULDED CASE CIRCUIT BREAKERS

PRODUCT HIGHLIGHTS 2
1. Operating mechanism is quick-make, quick-break and trip free. It is independent of manual speed of operation. Contacts cannot be
teased into position, nor can the breaker be held closed under fault conditions.
2. Clear indication of ON, OFF & TRIP position.
3. Suitable for both AC & DC applications.
4. Terminals suitable for both copper & aluminium terminations.
5. Push to trip facility to verify healthiness of mechanism.
6. Wide range of site fittable accessories.
7. Low let through energy.
8. No load line bias in new range of MCCBs.
9. Rotary operating mechanism has door interlock facility with an option of defeating interlock by an authorized person.
10. Housing is made of heat resistant insulating material.
11. Silver alloy contacts have long electrical life. The mechanism is so designed there is no arcing on the current carrying part of the
contact. The strong wipe action of the contact system keeps the contact surface clear of oxide films.

MOUNTING POSITION
L&Ts new range of MCCBs can be mounted up to 900 in any direction.

MCCBs FOR MOTOR BACK-UP PROTECTION


MCCBs are increasingly being used in motor application as
a back- up protection device due to following advantages:
Low down time
Reduced running cost
No risking of single phasing
Availability of various accessories

TYPICAL MOTOR FEEDER


A typical motor protection scheme comprises a starter (contractor and thermal overload relay) and a short circuit protective device(SCPD)
e.g.MCCB.
Thermal overload relay provides close protection to the motor against single phasing and moderate overloads like stalling etc. Protection
against higher overcurrents, beyond capability of the starter including short circuit faults is offered by MCCB.
It is necessary to have proper discrimination between thermal overload relay and SCPD for any effective protection scheme. Type DM
MCCBS are hence designed with instantaneous release to ensure proper discrimination.

FUSE MONITORING DEVICE


L&Ts range of MCCBs also includes the Fuse Monitoring Device type DF, designed to monitor the operation of fuse.
In the motor feeders, where Switch Disconnector Fuse units are used for motor backup protection, there is every possibility of only one of
the three fuses blowing due to a fault, resulting in single phasing. This can be avoided by using Fuse Monitoring Device along with Switch
Disconnector Fuse units of any fuse ratings (refer page 2/79 for connection diagram).

2/2
ACCESSORIES

INTERNAL

2 SHUNT RELEASE
The shunt release provides remote tripping of the circuit breaker. The coil of
shunt release is designed for short time as well as continuous operation (DX
range).
The operation voltage is :
85% to 110% of the rated voltage in AC
75% to 125% of the rated voltage in DC
Shunt release coil is short time rated, micro-switch is provided in the release to
cut off the supply. Once the MCCB trips, this prevents burning of coil even if the
supply to shunt coil is continuously fed.

UNDER VOLTAGE RELEASE


The under voltage release is used for protecting the installation against low voltage
situation. The under voltage release is designed to operate when the voltage
drops below a tripping threshold. This can also be used for remote tripping &
electrical interlocking purpose.
The tripping threshold is :
35% to 70% of rated in AC
35% to 70% of rated in DC
Circuit breaker closing is possible only if the voltage exceeds 85% of the rated
voltage.

AUXILIARY CONTACT BLOCK


The auxiliary contact block is used for remote signaling and control purposes.
This consists of one or more than one potential free change-over contacts. It
indicates the circuit breaker status- whether open or closed.

TRIP ALARM CONTACT


The trip alarm contact gives tripping indication once the MCCB trips. The potential
free change- over contacts can be used for indication or for control circuit.

Note : For ordering information, refer pages 2/45 - 2/55


2/3
ACCESSORIES

EXTERNAL

FOR DX RANGE
2
ANNUNCIATION UNIT
Annunciation unit indicates the differential remote and local operating states
like
- Tripping by Overload release
- Tripping be Short-circuit release
- Early-alarm in the event that the Overload release setting is about to be
exceeded.
Annunciation unit has 1NO+1NC.
ELECTRICAL & MECHANICAL INTERLOCK
RESIDUAL CURRENT OPERATED RELAYS
These are factory fitted with adjustable rated fault current and delay time.

MECHANICAL INTERLOCK
For mechanical interlocking of Two or Three MCCBs with Toggle or Rotary
drive in the same distribution panel.

PARALLELING MECHANISM
For simultaneous operation of two MCCBs mounted side by side, using a
Rotary drive.

SIDE WALL OPERATOR


This is to be used for actuating the Breaker from the side of the control
panel or for changing the Rotary movement by 90o

WITHDRAWABLE UNIT
Three position Withdrawable units are available for 3 and 4 PoleMCCBs
(250A and above).

PLUG-IN ADAPTORS
PARALLELING MECHANISM 3 pole DX range of MCCBs (upto 250A) are also available with plug-in
adaptor modules.

ADAPTOR TERMINAL WITH SHROUD / SPREADER


LINKS WITH BARRIERS
Adaptor terminals / Spreader links can be connected to basic MCCBs to facilitate
termination of higher size of cables / links.
The barrier is made of material with high dielectric strength. It is used to ensure
the electrical clearance between breaker terminals. It also prevents troubles
caused by contact of conductive material to the terminals.
Shrouds are used on both the sides of MCCB to provide additional safety and
are made of superior insulating material with good mechanical & electrical
ADAPTOR TERMINAL
properties. The shrouds are designed for click-fit fixing & thus do not need any
fixing hardware. Shroud prevents accidental contact to bare terminals.

SHROUD

Note : For ordering information, refer pages 2/45 - 2/55


2/4
ACCESSORIES

EXTERNAL

2 ROTARY OPERATING MECHANISM


The circuit breaker has a toggle handle operating mechanism, which also serves
as swtiching position indicator ON, OFF, TRIP. But when the circuit breaker is
installed in switchgear cubicles or distribution boards, it requires to be operated
outside of the switchgear cubicles or distribution boards. The mechanism is
designed for direct attachment to the MCCB and transforms the toggle handle
movement into a rotation. It facilitates operation of MCCB when the panel door is
closed.

ITS FEATURES
Easy operation
Door interlock mechanism. It doesnt allow the circuit breaker to be ON
when the door of switchgear cubicles or distribution boards is open thus
prevents the operator from an unsafe condition.
Door interlock defeat facility. This enables only authorized personnel to open
the door with MCCB in ON condition for the purpose of inspection.

FOR DX RANGE

REMOTE OPERATOR (MOTORISED)


For remote ON and OFF of circuit breakers. Local switching by hand also
possible.

Note : For ordering information, refer pages 2/45 - 2/55


2/5
ACCESSORIES

EXTERNAL

EARTH FAULT MODULES (Type GF1, GF2, GF11) 2


Protection against earth faults
Built-in CBCT solid state design (GF11 to be used with external C.T.)
10 50% adjustable current setting
GF1
100 / 200 mS selectable trip time delay
Suitable for both 3 phase 3 wire & 3 phase 4 wire7 systems.
Built in test facility.
Potential free NO contact to trip MCCB through shunt trip.
Manual reset for positive fault acknowledgment
GF2
(for Technical / Dimensional Details, refer page 2/80 and 2/81)

GF11

S. S. ENCLOSURE
Enclosure is made of CRCA material with superior quality paint for better
adherence and to enhance weather resistance.
MCCB mounted in Enclosure is ideally suited to be used as fuseless mains.
Features of Enclosure
Isolable neutral
Earthing terminal
Positive indication of breaker position
Door lock and additional lock on enclosure prevents accidental switching of
MCCB.

(for Dimensional Details, refer page 2/82)

Note : For ordering information, refer pages 2/45 - 2/55


2/6
ACCESSORIES RANGE

2 DS DTH..E DG DH DL DTH DX..S DX..H DM DF

Auxiliary Contacts

Standard l l l l l l l l l l

Early make - - - - - - l l - -

General Trip alarm l l l l l l l l l l

Contact alarm - - - - - - l l - -

Separate contact alarm - - - - - - l l - -

Under voltage release

Non-delayed l l l l l l l l l -

Off-delayed - - - - - - l l - -

Shunt release

Without early make aux. Contact l l l l l l l l l l

With early make aux. Contact - - - - - - l l - -

Remote operator - - - - - - l l - -

Rotary operating mechanism l l l l l l l l l -

Paralleling mechanism - - - - - - l l - -

Mechanical interlock - - - - - - l l - -

Castell lock - - - - - - l l - -

Earth-fault module l l l l l l l l l -

Earth-leakage module - - - - - - l l - -

Plug-in module - - - - - - l l - -

Withdrawable module - - - - - - l l - -

Adaptor terminals - - - l l - - - l -

Spreader terminals l - l l l - - - l -

Enclosure l - l l - - - - - -

l Available; Not Available


Note : Accessories mounting / location as per page 2/45 to 2/55
2/7
ACCESSORIES FOR MCCB

UV RELEASE
TRIP ALARM
CONTACT

AUXILIARY CONTACT ROTARY OPERATING SHUNT RELEASE


BLOCK MECHANISM

Note : Except DX Range


2/8
TECHNICAL DATA - DS

2 Type Designation DS 100 DS 125 DS 160

Rated Uninterrupted current


at 40o C. - Ith (AC/DC) A 100 125 160

Rated impulse withstand voltage - Uimp kV 8 8 8

Rated operational voltage - Ue V AC 415 415 415

V DC 250 250 250

Frequency Hz 50/60 50/60 50/60

Rated insulation voltage - Ui V 690 690 690

Operating Temperature C -5 to +55 -5 to +55 -5 to +55

Overvoltage category / pollution degree III/3 III/3 III/3

Rated Short-circuit making capacity - Icm kA 17 17 32

Rated ultimate S.C. breaking capacity - Icu


at 415V ac kA 10 10 16

Rated Service S.C. breaking capacity - Ics


at 415V ac kA 50% 50% 50%

Utilisation category A A A

Mechanical life
As per standard IS 13947-2 / IEC 60947-2
Electrical life

Release Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic

Overload release setting Fixed Fixed Fixed

Short Circuit release setting (+/- 20%) 9*In 9*In 8*In

Weight kg 1.7 1.7 1.7

Terminal capacity Cables mm2 50 70 95

Links mm 16 22 22

Accessories

Auxiliary contacts (1NO+1NC) (1NO+1NC) (1NO+1NC)

Shunt release y y y

Under voltage release y y y

Trip alarm contacts y y y

Earth fault module y y y

Rotary operating mechanism y y y

2/9
TECHNICAL DATA - DS

Type Designation DS 200 DS 250 DS 400


2
Rated Uninterrupted current
at 40o C. - Ith (AC/DC) A 200 250 400

Rated impulse withstand voltage - Uimp kV 8 8 8

Rated operational voltage - Ue V AC 415 415 415

V DC 250 250 250

Frequency Hz 50/60 50/60 50/60

Rated insulation voltage - Ui V 690 690 690

Operating Temperature C -5 to +55 -5 to +55 -5 to +55

Overvoltage category / pollution degree III/3 III/3 III/3

Rated Short-circuit making capacity - Icm kA 32 52.5 52.5

Rated ultimate S.C. breaking capacity - Icu


at 415V ac kA 16 25 25

Rated Service S.C. breaking capacity - Ics


at 415V ac kA 50% 50% 50%

Utilisation category A A A

Mechanical life
As per standard IS 13947-2 / IEC 60947-2
Electrical life

Release Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic

Overload release setting Fixed Fixed Fixed

Short Circuit release setting (+/- 20%) 6*In 6*In 6*In

Weight kg 2.4 5 5

Terminal capacity Cables mm2 150 300 300

Links mm 30 40 40

Accessories

Auxiliary contacts (1NO+1NC) (2NO+2NC) (2NO+2NC)

Shunt release y y y

Under voltage release y y y

Trip alarm contacts y y y

Earth fault module y y y

Rotary operating mechanism y y y

2/10
TECHNICAL DATA - DTH...E

2 Type Designation DTH 200E DTH 250E DTH 400E DTH 630E DTH 800E

Rated Uninterrupted current


at 40o C. - Ith (AC/DC) A 200 250 400 630 800

Rated impulse withstand voltage - Uimp kV 8 8 8 8

Rated operational voltage - Ue V 415 415 415 415 415

V DC 250 250 250 250 250

Frequency Hz 50/60 50/60 50/60 50/60 50/60

Rated insulation voltage - Ui V 600 600 600 600 600

Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55 -5 to +55

Overvoltage category / pollution degree III/3 III/3 III/3 III/3 III/3

Rated Short-circuit making capacity - Icm kA 105 105 105 105

Rated ultimate S.C. breaking capacity - Icu


at 660V ac kA 10 10 10 10

at 550V ac kA 25 25 25 25

at 500V ac kA 35 35 35 35

at 415V ac kA 35 50 50 50 50

at 380V ac kA 50 50 50 50

at 240V ac kA 60 60 60 60

Rated Service S.C. breaking capacity - Ics


at 415V ac kA 50% 50% 50% 50%

DC Breaking capacity at 250 V, L/R <= 15mS kA 20 20 20 20 20

Capacitor rating at 415 V, 50 Hz kVAR 70 100 160 240 240

Utilisation category A A A A A

Mechanical life (As per standard) Ops. 8000 8000 8000 8000 8000

Electrical life (As per standard) Ops. 2000 2000 1200 1200 1200

Release Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic

Overload release setting Fixed Fixed Fixed Fixed Fixed

Short Circuit release setting (+/- 20%) 8*In 3-8*In 3-8*In 3-8*In 3-8*In

Weight kg 3 10 10 10 10

Terminal capacity Cables mm 2


185 2*240 2*240 2*240 2*240

Links mm 36 40 (Max. 15 thk.) 40 (Max. 15 thk.) 40 (Max. 15 thk.) 40 (Max. 15 thk.)

Accessories

Auxiliary contacts 1 NO + 1 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC

Shunt release y y y y y

Under voltage release y y y y y

Earth fault module y y y y y

Rotary operating mechanism y y y y y

2/11
TECHNICAL DATA - DG

Type Designation DG 125 DG 200 DG 250 DG 400


2
Rated Uninterrupted current
at 40o C. - Ith (AC/DC) A 125 200 250 400

Rated impulse withstand voltage - Uimp kV 8 8 8 8

Rated operational voltage - Ue V AC 415 415 415 415

V DC 250 250 250 250

Frequency Hz 50/60 50/60 50/60 50/60

Rated insulation voltage - Ui V 690 690 690 690

Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55

Overvoltage category / pollution degree III/3 III/3 III/3 III/3

Rated ultimate S.C. breaking capacity - Icu


at 415V ac kA 10 16 25 25

Rated Service S.C. breaking capacity - Ics


at 415V ac kA 75% 75% 75% 75%

Utilisation category A A A A

Mechanical life
As per standard IS 13947-2 / IEC 60947-2
Electrical life

Release Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic

Overload release setting 80-100% 80-100% 80-100% 80-100%

Short Circuit release setting (+/- 20%) 4*In 4*In 4*In 4*In

Weight kg 1.8 2.4 5 5

Terminal capacity Cables mm2 70 150 300 300

Links mm 22 30 40 40

Accessories

Auxiliary contacts (1NO+1NC) (1NO+1NC) (2NO+2NC) (2NO+2NC)

Shunt release y y y y

Under voltage release y y y y

Trip alarm contacts y y y y

Earth fault module y y y y

Rotary operating mechanism y y y y

2/12
TECHNICAL DATA - DH

2 Type Designation DH 100 DH 125 DH 160 DH 200

Rated Uninterrupted current


at 40o C. - Ith (AC/DC) A 100 125 160 200

Rated impulse withstand voltage - Uimp kV 8 8 8 8

Rated operational voltage - Ue V 415 415 415 415

V DC 250 250 250 250

Frequency Hz 50/60 50/60 50/60 50/60

Rated insulation voltage - Ui V 690 690 690 690

Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55

Overvoltage category / pollution degree III/3 III/3 III/3 III/3

Rated Short-circuit making capacity - Icm kA 52.5 73.5 73.5 73.5

Rated ultimate S.C. breaking capacity - Icu


at 660V ac kA 5 7 7 7

at 550V ac kA 12 18 18 18

at 500V ac kA 18 25 25 25

at 415V ac kA 25 35 35 35

at 380V ac kA 25 35 35 35

at 240V ac kA 50 60 60 60

Rated Service S.C. breaking capacity - Ics


at 415V ac kA 100% 75% 75% 50%

DC Breaking capacity at 250 V, L/R <= 15mS kA 10 10 10 10

Capacitor rating at 415 V, 50 Hz kVAR 35 50 70 70

Utilisation category A A A A

Mechanical life
As per standard IS 13947-2 / IEC 60947-2
Electrical life

Release Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic

Overload release setting 80-100% 80-100% 80-100% 80-100%

Short Circuit release setting (+/- 20%) 9*In 9*In 8*In 6*In

Weight kg 1.7 1.7 1.7 2.4

Terminal capacity Cables mm2 50 50 95 150

Links mm 16 16 22 30

Auxiliary contacts (1NO+1NC) (1NO+1NC) (1NO+1NC) (1NO+1NC)

Shunt release y y y y

Under voltage release y y y y

Trip alarm contacts y y y y

Earth fault module y y y y

Rotary operating mechanism y y y y

2/13
TECHNICAL DATA - DH

Type Designation DH 250 DH 400 DH 630


2
Rated Uninterrupted current
at 40o C. - Ith (AC/DC) A 250 400 630

Rated impulse withstand voltage - Uimp kV 8 8 8

Rated operational voltage - Ue V 415 415 415

V DC 250 250 250

Frequency Hz 50/60 50/60 50/60

Rated insulation voltage - Ui V 690 690 690

Operating Temperature C -5 to +55 -5 to +55 -5 to +55

Overvoltage category / pollution degree III/3 III/3 III/3

Rated Short-circuit making capacity - Icm kA 73.5 73.5 73.5

Rated ultimate S.C. breaking capacity - Icu


at 660V ac kA 7 7 7

at 550V ac kA 18 18 18

at 500V ac kA 25 25 25

at 415V ac kA 35 35 35

at 380V ac kA 35 35 35

at 240V ac kA 60 60 60

Rated Service S.C. breaking capacity - Ics


at 415V ac kA 75% 75% 75%

DC Breaking capacity at 250 V, L/R <= 15mS kA 20 20 20

Capacitor rating at 415 V, 50 Hz kVAR 100 160 160

Utilisation category A A A

Mechanical life
As per standard IS 13947-2 / IEC 60947-2
Electrical life

Release Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic

Overload release setting 80-100% 80-100% 80-100%

Short Circuit release setting (+/- 20%) 6*In 6*In 6*In

Weight kg 5.5 5.5 6.5

Terminal capacity Cables mm2 300 300 400

Links mm 40 40 2x40

Auxiliary contacts (2NO+2NC) (2NO+2NC) (2NO+2NC)

Shunt release y y y

Under voltage release y y y

Trip alarm contacts y y y

Earth fault module y y y

Rotary operating mechanism y y y

2/14
TECHNICAL DATA - DL

2 Type Designation DL 100 DL 160 DL 250 DL 400

Rated Uninterrupted current


at 40o C. - Ith (AC/DC) A 100 160 250 400

Rated impulse withstand voltage - Uimp kV 8 8 8 8

Rated operational voltage - Ue V 415 415 415 415

V DC 250 250 250

Frequency Hz 50/60 50/60 50/60 50/60

Rated insulation voltage - Ui V 690 690 690 690

Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55

Overvoltage category / pollution degree III/3 III/3 III/3 III/3

Rated Short-circuit making capacity - Icm kA 105 105 105 105

Rated ultimate S.C. breaking capacity - Icu


at 660V ac kA 10 10 10 10

at 550V ac kA 25 25 25 25

at 500V ac kA 35 35 35 35

at 415V ac kA 50 50 50 50

at 380V ac kA 50 50 50 50

at 240V ac kA 65 50 65 65

Rated Service S.C. breaking capacity - Ics


at 415V ac kA 100% 100% 100% 100%

DC Breaking capacity at 250 V, L/R <= 15mS kA 20 25 25 25

Capacitor rating at 415 V, 50 Hz kVAR 50 70 100 160

Utilisation category A A A A

Mechanical life Ops.


As per standard IS 13947-2 / IEC 60947-2
Electrical life

Release Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic

Overload release setting 80-100% 80-100% 80-100% 80-100%

Short Circuit release setting (+/- 20%) 9*In 8*In 6 In 6 In

Weight kg 1.7 1.8 5 5

Terminal capacity Cables mm 2


50 95 300 300

Links mm 16 22 40 40

Accessories

Auxiliary contacts (1NO+1NC) (1NO+1NC) (2NO+2NC) (2NO+2NC)

Shunt release y y y y

Under voltage release y y y y

Trip alarm contacts y y y y

Earth fault module y y y y

Rotary operating mechanism y y y y

2/15
TECHNICAL DATA - DTH

Type Designation DTH 100 DTH 200


2
Rated Uninterrupted current
at 40o C - Ith (AC/DC) A 100 200

Rated impulse withstand voltage - Uimp kV

Rated operational voltage - Ue V 415 415

V DC 250 250

Frequency Hz 50/60 50/60

Rated insulation voltage - Ui V 600 600

Operating Temperature C -5 to +55 -5 to +55

Overvoltage category / pollution degree III/3 III/3

Rated ultimate S.C. breaking capacity - P1


at 415V ac kA 10 35

DC Breaking capacity at 250 V, L/R <= 15mS kA 5 20

Capacitor rating at 415 V, 50 Hz kVAR 25 70

Mechanical life Ops. 30000 8000

Electrical life Ops. 4500 2000

Release Type Thermal-Magnetic Thermal-Magnetic

Overload release setting 70-100% 70-100%

Short Circuit release setting (+/- 20%) 700 A 8*In

Weight kg 1.35 3

Terminal capacity Cables mm2 70 185

Links mm 22.5 36

Accessories

Auxiliary contacts - 1 NO + 1 NC

Shunt release - y

Under voltage release - y

Trip alarm contacts - y

Earth fault module y y

Rotary operating mechanism y y

2/16
TECHNICAL DATA - DTH

2 Type Designation DTH 250 DTH 400 DTH 630 DTH 800

Rated Uninterrupted current


at 40o C. - Ith (AC/DC) A 250 400 630 800

Rated impulse withstand voltage - Uimp kV 8 8 8 8

Rated operational voltage - Ue V 415 415 415 415

V DC 250 250 250 250

Frequency Hz 50/60 50/60 50/60 50/60

Rated insulation voltage - Ui V 600 600 600 600

Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55

Overvoltage category / pollution degree III/3 III/3 III/3 III/3

Rated Short-circuit making capacity - Icm kA 105 105 105 105

Rated ultimate S.C. breaking capacity - Icu


at 660V ac kA 10 10 10 10

at 550V ac kA 25 25 25 25

at 500V ac kA 35 35 35 35

at 415V ac kA 50 50 50 50

at 380V ac kA 50 50 50 50

at 240V ac kA 60 60 60 60

Rated Service S.C. breaking capacity - Ics


at 415V ac kA 50% 50% 50% 50%

DC Breaking capacity at 250 V, L/R <= 15mS kA 20 20 20 20

Capacitor rating at 415 V, 50 Hz kVAR 100 160 240 240

Utilisation category A A A A

Mechanical life Ops. 8000 8000 8000 8000

Electrical life Ops. 1200 1200 1200 1200

Release Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic

Overload release setting 70-100% 70-100% 70-100% 70-100%

Short Circuit release setting (+/- 20%) 3-8*In 3-8*In 3-8*In 3-8*In

Weight kg 10 10 10 10

Terminal capacity Cables mm2 2*240 2*240 2*240 2*240

Links mm 40 (Max. 15 thk.) 40 (Max. 15 thk.) 40 (Max. 15 thk.) 40 (Max. 15 thk.)

Accessories

Auxiliary contacts 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC

Shunt release y y y y

Under voltage release y y y y

Trip alarm contacts y y y y

Earth fault module y y y y

Rotary operating mechanism y y y y

2/17
TECHNICAL DATA - DX..S (3/4 POLE)

Type Designation DX 100S DX 125S DX 160S DX 200S


2
Rated Uninterrupted current
at 40o C. - Ith (AC/DC) A 100 125 160 200
Rated impulse withstand voltage - Uimp kV 8 8 8 8
Rated operational voltage - Ue V 415 415 415 415
V DC 440 440 440 440
Frequency Hz 50/60 50/60 50/60 50/60
Rated insulation voltage - Ui V 690 690 690 690
Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree III/3 III/3 III/3 III/3
Rated Short-circuit making capacity - Icm kA 94.5 94.5 94.5 94.5
Rated ultimate S.C. breaking capacity - Icu
at 690V ac kA 6 6 6 6
at 500V ac kA 12 12 12 12
at 415V ac kA 35 35 35 35
at 230V ac kA 45 45 45 45
Rated Service S.C.
breaking capacity - Ics (of Icu) kA 100% 100% 100% 100%
DC Breaking capacity at 440 V kA 20 20 20 20
Utilisation category A A A A
Rated short-time withstand current Icw (1 Sec)kA - - - -
Mechanical life Ops. 20000 20000 20000 20000
Electrical life (AC3, 400V) Ops. 6000 6000 6000 3500
Release Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic
Overload release setting 80-100% 80-100% 80-100% 80-100%
Short Circuit release setting 6-12*In 6-12*In 6-12*In 6-12*In
Mechanical Shock resistance g 20 20 20 20
Weight (3 - Pole) kg 1.7 1.7 1.7 1.7
(4 - Pole) kg 1.7 1.7 1.7 1.7
Accessories
Auxiliary contacts y y y y
Shunt release y y y y
Under voltage release y y y y
Trip indicating auxiliary contacts y y y y
Earth fault module y y y y
Rotary operating mechanism y y y y
Residual-current protection module y y y y
Remote operator y y y y
Withdrawable unit - - - -
Plug-in module y y y y
Mechanical interlock y y y y
Paralleling mechanism y y y y
Load monitoring

2/18
TECHNICAL DATA - DX..S (3/4 POLE)

2 Type Designation DX 250S DX 400S DX 630S

Rated Uninterrupted current


at 40o C. - Ith (AC/DC) A 250 400 630
Rated impulse withstand voltage - Uimp kV 8 8 8
Rated operational voltage - Ue V 415 415 415
V DC 440
Frequency Hz 50/60 50/60 50/60
Rated insulation voltage - Ui V 690 690 690
OperatingTemperature C -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree III/3 III/3 III/3
Rated Short-circuit making capacity - Icm kA 94.5 220 220
Rated ultimate S.C. breaking capacity - Icu
at 690V ac kA 6 25 25
at 500V ac kA 12 42 42
at 415V ac kA 35 65 65
at 230V ac kA 45 100 100
Rated Service S.C.
breaking capacity - Ics (of Icu) kA 100% 50% 50%
DC Breaking capacity at 440 V kA 20 - -
Utilisation category A A/B A/B
Rated short-time withstand current Icw (1 Sec) kA - 8 8
Mechanical life Ops. 20000 20000 20000
Electrical life (AC3, 400V) Ops. 3500 1250 1250
Release Type Thermal-Magnetic Electronic Electronic
Overload release setting 80-100% 50-100% 50-100%
Short Circuit release setting 6-12*In 2-12*In 2-12*In
Mechanical Shock resistance g 20 20 20
Weight (3 - Pole) kg 1.7 9.1 9.1
(4 - Pole) kg 1.7 11.9 11.9
Accessories
Auxiliary contacts y y y
Shunt release y y y
Under voltage release y y y
Trip indicating auxiliary contacts y y y
Earth fault module y y y
Rotary operating mechanism y y y
Residual-current protection module y y y
Remote operator y y y
Withdrawable unit - y y
Mechanical interlock y y y
Paralleling mechanism y y y
Load monitoring

2/19
TECHNICAL DATA - DX..H (3/4 POLE)

Type Designation DX 100H DX 125H DX 160H DX 200H


2
Rated Uninterrupted current
at 40C. - Ith (AC/DC) A 100 125 160 200
Rated impulse withstand voltage - Uimp kV 8 8 8 8
Rated operational voltage - Ue V 415 415 415 415
V DC 440 440 440 440
Frequency Hz 50/60 50/60 50/60 50/60
Rated insulation voltage - Ui V 690 690 690 690
Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree III/3 III/3 III/3 III/3
Rated Short-circuit making capacity - Icm kA 220 550 220 220
Rated ultimate S.C. breaking capacity - Icu
at 690V ac kA 8 8 8 8
at 500V ac kA 20 20 20 20
at 415V ac kA 65 65 65 65
at 230V ac kA 100 100 100 100
Rated Service S.C.
breaking capacity - Ics (of Icu) kA 75% 75% 75% 75%
DC Breaking capacity at 440 V kA 25 25 25 25
Utilisation category A A A A
Rated short-time withstand current Icw (1 Sec) kA - - - -
Mechanical life Ops. 20000 20000 20000 20000
Electrical life (AC3, 400V) Ops. 6000 6000 6000 3500
Release Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic
Overload release setting 80-100% 80-100% 80-100% 80-100%
Short Circuit release setting 6-12*In 6-12*In 6-12*In 6-12*In
Mechanical Shock resistance g 20 20 20 20
Weight (3 - Pole) kg 1.7 1.7 1.7 1.7
(4 - Pole) kg 1.7 1.7 1.7 1.7
Accessories
Auxiliary contacts y y y y
Shunt release y y y y
Under voltage release y y y y
Trip indicating auxiliary contacts y y y y
Earth fault module y y y y
Rotary operating mechanism y y y y
Residual-current protection module y y y y
Remote operator y y y y
Withdrawable unit - - - -
Plug-in module y y y y
Mechanical interlock y y y y
Paralleling mechanism y y y y
Load monitoring

2/20
TECHNICAL DATA - DX..H (3/4 POLE)

2 Type Designation DX 250H DX 400H DX 630H DX 800H

Rated Uninterrupted current


at 40C. - Ith (AC/DC) A 250 400 630 800
Rated impulse withstand voltage - Uimp kV 8 8 8 8
Rated operational voltage - Ue V 415 415 415 415
V DC 440
Frequency Hz 50/60 50/60 50/60 50/60
Rated insulation voltage - Ui V 690 690 690 690
Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree III/3 III/3 III/3 III/3
Rated Short-circuit making capacity - Icm kA 220 440 440 275
Rated ultimate S.C. breaking capacity - Icu
at 690V ac kA 8 30 30 25
at 500V ac kA 20 65 65 45
at 415V ac kA 65 100 100 65
at 230V ac kA 100 200 200 100
Rated Service S.C.
breaking capacity - Ics (of Icu) kA 75% 50% 50% 75%
DC Breaking capacity at 440 V kA 25 - - -
Utilisation category A A/B A B
Rated short-time withstand current Icw (1 Sec) kA - 8 8 15 (0.3 S)
Mechanical life Ops. 20000 20000 20000 2500
Electrical life (AC3, 400V) Ops. 3500 5000 5000 500 (AC1)
Release Type Thermal-Magnetic Electronic Electronic Electronic
Overload release setting 80-100% 50-100% 50-100% 50-100%
Short Circuit release setting 6-12*In 2-12*In 2-12*In 2-12*In
Mechanical Shock resistance g 20 20 20 20
Weight (3 - Pole) kg 1.7 9.1 9.1 20.4
(4 - Pole) kg 1.7 11.9 11.9 26.4
Accessories
Auxiliary contacts y y y y
Shunt release y y y y
Under voltage release y y y y
Trip indicating auxiliary contacts y y y y
Earth fault module y y y y
Rotary operating mechanism y y y y
Residual-current protection module y y y -
Remote operator y y y y
Withdrawable unit - y y y
Mechanical interlock y y y y
Paralleling mechanism y y y -
Load monitoring y

2/21
TECHNICAL DATA - DX..H (3/4 POLE)

Type Designation DX 1000H DX 1250H DX 1600H


2
Rated Uninterrupted current
at 40C. - Ith (AC/DC) A 1000 1250 1600
Rated impulse withstand voltage - Uimp kV 8 8 8
Rated operational voltage - Ue V 415 415 415
Frequency Hz 50/60 50/60 50/60
Rated insulation voltage - Ui V 690 690 690
Operating Temperature C -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree III/3 III/3 III/3
Rated Short-circuit making capacity - Icm kA 275 275 275
Rated ultimate S.C. breaking capacity - Icu
at 690V ac kA 25 25 45
at 500V ac kA 45 45 65
at 415V ac kA 65 65 85
at 230V ac kA 100 100 125
Rated Service S.C.
breaking capacity - Ics (of Icu) kA 75% 75% 75%
Utilisation category B B B
Rated short-time withstand current Icw (1 Sec) kA 15 (0.3 S) 15 (0.3 S) 20 (0.3 S)
Mechanical life Ops. 2500 2500 2500
Electrical life (AC3, 400V) Ops. 500 (AC1) 500 (AC1) 500 (AC1)
Release Type Electronic Electronic Electronic
Overload release setting 50-100% 50-100% 50-100%
Short Circuit release setting 2-12*In 2-12*In 2-12*In
Mechanical Shock resistance g 20 20 20
Weight (3 - Pole) kg 20.4 20.4 20.4
(4 - Pole) kg 26.4 26.4 26.4
Accessories
Auxiliary contacts y y y
Shunt release y y y
Under voltage release y y y
Trip indicating auxiliary contacts y y y
Earth fault module y y y
Rotary operating mechanism y y y
Residual-current protection module - - -
Remote operator y y y
Withdrawable unit y y y
Side wall operator - - -
Mechanical interlock y y y
Load monitoring y y y

2/22
TECHNICAL DATA - DM

2 Type Designation DM 16 DM 100 DM 160 DM 250 DM 400

Rated Uninterrupted current


at 40o C. - Ith (AC/DC) A 16 70 160 250 400

Rated impulse withstand voltage - Uimp kV 8 8 8 8 8

Rated operational voltage - Ue V 415 415 415 415 415

Frequency Hz 50/60 50/60 50/60 50/60 50/60

Rated insulation voltage - Ui V 690 690 690 690 690

Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55 -5 to +55

Overvoltage category / pollution degree III/3 III/3 III/3 III/3 III/3

Rated Short-circuit making capacity - Icm kA 105 105 105 105 105

Rated ultimate S.C. breaking capacity - Icu


at 660V ac kA 10 10 10 10 10

at 550V ac kA 25 25 25 25 25

at 500V ac kA 35 35 35 35 35

at 415V ac kA 50 50 50 50 50

at 380V ac kA 50 50 50 50 50

at 240V ac kA 85 85 85 85 85

Rated Service S.C.


breaking capacity - Ics at 415V ac kA 100% 100% 100% 100% 100%

Utilisation category A A A A A

Mechanical life
As per standard IS 13947-2 / IEC 60947-2
Electrical life

Release Type Magnetic Magnetic Magnetic Magnetic Magnetic

Short Circuit release setting (+/- 20%) 12*In 12*In 12*In 12*In 12*In

Weight kg 1 1.65 4.8 5.5 5.5

Terminal capacity Cables mm2 10 50 185 300 300

Links mm - 16 36 40 40

Accessories

Auxiliary contacts 1 NO + 1 NC 1 NO + 1 NC 1 NO + 1 NC 2 NO + 2 NC 2 NO + 2 NC

Shunt release y y y y y

Under voltage release y y y y

Trip alarm contacts y y y y y

Rotary operating mechanism y y y y y

2/23
TECHNICAL DATA - DTH 800 INST.

Type Designation DTH 800 INST.


2
Rated Uninterrupted current
at 40o C. - Ith (AC/DC) A 800

Rated impulse withstand voltage - Uimp kV 8

Rated operational voltage - Ue V 415

Frequency Hz 50/60

Rated insulation voltage - Ui V 600

Operating Temperature C -5 to +55

Overvoltage category / pollution degree III/3

Rated ultimate S.C. breaking capacity - Icu


at 415V ac kA 50

Rated Service S.C. breaking capacity - Ics


at 415V ac (of Icu) kA 50%

Utilisation category A

Mechanical life Ops. 8000

Electrical life Ops. 1200

Release Type Magnetic

Short Circuit release setting (+/- 20%) 360A, 550A, 850A, 1050A

Weight kg 10

Terminal capacity Cables mm2 2*240

Links mm 40 (Max. 15 thk.)

Accessories

Auxiliary contacts y

Shunt release y

Under voltage release y

Trip alarm contacts y

Earth fault module y

Rotary operating mechanism y

2/24
TECHNICAL DATA - DF

2 Type Designation DF

Rated Uninterrupted current


at 40o C. - Ith (AC/DC) A 1

Rated impulse withstand voltage - Uimp kV 8

Rated operational voltage - Ue V 415

Frequency Hz 50/60

Rated insulation voltage - Ui V 600

Operating Temperature C -5 to +55

Overvoltage category / pollution degree III/3

Rated ultimate S.C. breaking capacity - Icu


at 415V ac kA 50

Magnetic Threshold A 2

Mechanical life Ops. 10000

Electrical life Ops. 6000

Overload release setting (Fixed) A 1

Weight kg 0.65

Terminal capacity Without lugs mm2 4

With lugs mm2 16

Accessories

Auxiliary contact 1 CO, 5A-250V

Shunt release y

Auxiliary contact y

Trip alarm contacts y

2/25
I-t CHARACTERISTIC CURVES

MCCB - TYPE DS

DS 100 DS 125/160

DS 200 DS 250/400

Note: Short Circuit tripping values indicated as multiple of rated current


2/26
I-t CHARACTERISTIC CURVES

MCCB - TYPE DTH...E

DTH 200E DTH 250E

DTH 400E DTH 630E DTH 800E

Note: Short Circuit tripping values indicated as multiple of rated current


2/27
I-t CHARACTERISTIC CURVES

MCCB - TYPE DG

DG 125 DG 160

DG 200 DG 250/400

Note: Short Circuit tripping values indicated as multiple of rated current


2/28
I-t CHARACTERISTIC CURVES

MCCB - TYPE DH

DH 100/125 DH 160

DH 200 DH 250/400/630

Note: Short Circuit tripping values indicated as multiple of rated current


2/29
I-t CHARACTERISTIC CURVES

MCCB - TYPE DL

DL 100 DL 160

DL 250/400

Note: Short Circuit tripping values indicated as multiple of rated current


2/30
I-t CHARACTERISTIC CURVES

MCCB - TYPE DTH

DTH 100 DTH 200 DTH 250

DTH 400 DTH 630 DTH 800

Note: Short Circuit tripping values indicated as multiple of rated current


2/31
I-t CHARACTERISTIC CURVES

DX 100-250 S/H (3/4 POLE)

Note: Short Circuit tripping values indicated as multiple of rated current


2/32
I-t CHARACTERISTIC CURVES

DX 400 S/H (3/4 POLE)

2
 # #

Note: Short Circuit tripping values indicated as multiple of rated current


2/33
I-t CHARACTERISTIC CURVES

DX 630 S/H (3/4 POLE)

Note: Short Circuit tripping values indicated as multiple of rated current


2/34
I-t CHARACTERISTIC CURVES

DX 800-1600 H (3/4 POLE)

DX 800 H DX 1000 H

DX 1250 H DX 1600 H

Note: Short Circuit tripping values indicated as multiple of rated current


2/35
ORDERING DATA - DS RANGE

MCCB Rating
(A)
Current
Rating (A)
Breaking
Capacity, Icu(kA)
Overload
Setting (A)
Short-Circuit
Setting
Std.
Pack
Catalogue No. Ordering
Suffix
2
DS 100 100 16 10 16 9*In 12 SL97917 OOOO

20 10 20 9*In 12 SL97918 OOOO

25 10 25 9*In 12 SL97919 OOOO

32 10 32 9*In 12 SL97920 OOOO

40 10 40 9*In 12 SL97921 OOOO

50 10 50 9*In 12 SL97922 OOOO

63 10 63 9*In 12 SL97923 OOOO

80 10 80 9*In 12 SL97924 OOOO

100 10 100 9*In 12 SL97925 OOOO

DS 125 125 125 10 125 9*In 12 SL97929 OOOO

DS 160 160 160 16 160 9*In 12 SL97930 OOOO

DS 200 200 200 16 200 6*In 12 SL97931 OOOO

DS 250 250 250 25 250 6*In 1 SL94541 OOOO

DS 400 320 320 25 320 6*In 1 SL94542 OOOO

400 400 25 400 6*In 1 SL94543 OOOO

ORDERING DATA - DTH...E RANGE

MCCB Rating Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Rating (A) Capacity, Icu(kA) Setting (A) Setting Pack Suffix

DTH 200E 200 200 35 200 8*In 1 ST 30513 OOOO

DTH 250E 250 250 50 250 3-8*In 1 ST 30543 OOOO

DTH 400E 400 400 50 400 3-8*In 1 ST 30545 OOOO

DTH 630E 630 630 50 630 3-8*In 1 ST 30514 OOOO

DTH 800E 800 800 50 800 3-8*In 1 ST 30546 OOOO

2/36
ORDERING DATA - DG RANGE

2 MCCB Rating
(A)
Current
Rating (A)
Breaking
Capacity, Icu(kA)
Overload
Setting (A)
Short-Circuit
Setting
Std.
Pack
Catalogue No. Ordering
Suffix

DG 125 125 16 10 12 - 16 6*In 1 SL97941 OOOO

20 10 16 - 20 6*In 1 SL97942 OOOO

25 10 20 - 25 6*In 1 SL97943 OOOO

32 10 25 - 32 6*In 1 SL97944 OOOO

40 10 32 - 40 6*In 1 SL97945 OOOO

50 10 40 - 50 6*In 1 SL97946 OOOO

63 10 50 - 63 4*In 1 SL97947 OOOO

80 10 63 - 80 4*In 1 SL97948 OOOO

100 10 80 - 100 4*In 1 SL97949 OOOO

125 10 100 - 125 4*In 1 SL97950 OOOO

DG 200 200 160 16 128 - 160 4*In 1 SL97951 OOOO

200 16 160 - 200 4*In 1 SL97953 OOOO

DG 250 250 250 25 200 - 250 4*In 1 SL97957 OOOO

DG 400 400 320 25 250 - 320 4*In 1 SL97958 OOOO

400 25 320 - 400 4*In 1 SL97959 OOOO

2/37
ORDERING DATA - DH RANGE

MCCB Rating
(A)
Current
Rating (A)
Breaking
Capacity, Icu(kA)
Overload
Setting (A)
Short-Circuit
Setting
Std.
Pack
Catalogue No. Ordering
Suffix
2
DH 100 100 16 25 12 - 16 9*In 1 SL 97201 OOOO

20 25 16 - 20 9*In 1 SL 97202 OOOO

25 25 20 - 25 9*In 1 SL 97203 OOOO

32 25 25 - 32 9*In 1 SL 97204 OOOO

40 25 32 - 40 9*In 1 SL 97205 OOOO

50 25 40 - 50 9*In 1 SL 97206 OOOO

63 25 50 - 63 9*In 1 SL 97207 OOOO

80 25 63 - 80 9*In 1 SL 97208 OOOO

100 25 80 - 100 9*In 1 SL 97209 OOOO

DH 125 125 16 35 12 - 16 9*In 1 SL 98556 OOOO

20 35 16 - 20 9*In 1 SL 98557 OOOO

25 35 20 - 25 9*In 1 SL 98558 OOOO

32 35 25 - 32 9*In 1 SL 98559 OOOO

40 35 32 - 40 9*In 1 SL 98560 OOOO

50 35 40 - 50 9*In 1 SL 98561 OOOO

63 35 50 - 63 9*In 1 SL 98562 OOOO

80 35 63 - 80 9*In 1 SL 98563 OOOO

100 35 80 - 100 9*In 1 SL 98564 OOOO

125 35 100 - 125 9*In 1 SL 98555 OOOO

DH 160 160 160 35 128 - 160 8*In 1 SL 98566 OOOO

DH 200 200 200 35 160 - 200 6*In 1 SL 97869 OOOO

DH 250 250 200 35 160 - 200 6*In 1 SL 97881 OOOO

250 35 200 - 250 6*In 1 SL 97882 OOOO

DH 400 400 320 35 250 - 320 6*In 1 SL 97883 OOOO

400 35 320 - 400 6*In 1 SL 97884 OOOO

DH 630 630 500 35 400 - 500 6*In 1 SL 94531 OOOO

630 35 500 - 630 6*In 1 SL 94532 OOOO

2/38
ORDERING DATA - DL RANGE

2 MCCB Rating
(A)
Current
Rating (A)
Breaking
Capacity, Icu(kA)
Overload
Setting (A)
Short-Circuit
Setting
Std.
Pack
Catalogue No. Ordering
Suffix

DL 100 100 16 50 12 - 16 9*In 1 SL 97801 OOOO

20 50 16 - 20 9*In 1 SL 97802 OOOO

25 50 20 - 25 9*In 1 SL 97803 OOOO

32 50 25 - 32 9*In 1 SL 97804 OOOO

40 50 32 - 40 9*In 1 SL 97805 OOOO

50 50 40 - 50 9*In 1 SL 97806 OOOO

63 50 50 - 63 9*In 1 SL 97807 OOOO

80 50 63 - 80 9*In 1 SL 97808 OOOO

100 50 80 - 100 9*In 1 SL 97809 OOOO

DL 160 160 100 50 80 - 100 8*In 1 SL97128 OOOO

125 50 100 - 125 8*In 1 SL 97129 OOOO

160 50 128 - 160 8*In 1 SL 97130 OOOO

DL 250 250 200 50 160 - 200 6*In 1 SL 97541 OOOO

250 50 200 - 250 6*In 1 SL 97542 OOOO

DL 400 400 320 50 250 - 320 6*In 1 SL 97543 OOOO

400 50 320 - 400 6*In 1 SL 97544 OOOO

2/39
ORDERING DATA - DTH RANGE

MCCB Rating
(A)
Current
Rating (A)
Breaking
Capacity, Icu(kA)
Overload
Setting (A)
Short-Circuit
Setting
Std.
Pack
Catalogue No. Ordering
Suffix
2
DTH 100 100 16 6 12 - 16 700 1 SL 94473 OOOO

20 6 16 - 20 700 1 SL 94474 OOOO

25 6 20 - 25 700 1 SL 94475 OOOO

32 6 25 - 32 700 1 SL 94476 OOOO

40 6 30 - 40 700 1 SL 94477 OOOO

50 6 38 - 50 700 1 SL 94478 OOOO

63 8 48 - 63 700 1 SL 94479 OOOO

80 10 60 - 80 700 1 SL 94480 OOOO

100 10 70 -100 700 1 SL 94481 OOOO

DTH 200 200 100 35 70 -100 8*In 1 SL 94512 OOOO

125 35 90 -125 8*In 1 SL 94513 OOOO

160 35 120 -160 8*In 1 SL 94514 OOOO

200 35 140 -200 8*In 1 SL 94515 OOOO

DTH 250 250 175 50 125 - 175 3-8*In 1 SL 94466 OOOO

250 50 175 - 250 3-8*In 1 SL 94467 OOOO

DTH 400 400 320 50 225 - 320 3-8*In 1 SL 94468 OOOO

400 50 280 - 400 3-8*In 1 SL 94469 OOOO

DTH 630 630 500 50 360 - 500 3-8*In 1 SL 94470 OOOO

630 50 460 - 630 3-8*In 1 SL 94471 OOOO

DTH 800 800 800 50 600 - 800 3-8*In 1 SL 94472 OOOO

ORDERING DATA - DTH 100 4-POLE


MCCB Rating Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Rating (A) Capacity, Icu(kA) Setting (A) Setting Pack Suffix

DTH 100 100 100 6 12 - 16 700 1 SL 94525 OOBO

100 6 16 - 20 700 1 SL 94525 OOCO

100 6 20 - 25 700 1 SL 94525 OODO

100 6 25 - 32 700 1 SL 94525 OOEO

100 6 30 - 40 700 1 SL 94525 OOFO

100 6 38 - 50 700 1 SL 94525 OOGO

100 8 48 - 63 700 1 SL 94525 OOHO

100 10 60 - 80 700 1 SL 94526 OOOO

100 10 70 -100 700 1 SL 94525 OOOO

2/40
ORDERING DATA - DX..S (3 POLE)

2 MCCB Rating
(A)
Utilisation
Category
Current Breaking
Rating (A) Capacity, Icu(kA)
Overload
Setting (A)
Short-Circuit
Setting
Std.
Pack
Catalogue No. Ordering
Suffix

DX 100S 100 A 40 35 25 - 40 9.5*In 1 ST 31038 OOOO

63 35 40 - 63 6-12*In 1 ST 31039 OOOO

80 35 63 - 80 6-12*In 1 ST 31040 OOOO

100 35 80 - 100 6-12*In 1 ST 31041 OOOO

DX 125S 125 A 125 35 80 - 125 6-12*In 1 ST 31042 OOOO

DX 160S 160 A 160 35 125 - 160 6-12*In 1 ST 31043 OOOO

DX 200S 200 A 200 35 160 - 200 6-12*In 1 ST 31044 OOOO

DX 250S 250 A 250 35 200 - 250 6-10*In 1 ST 31045 OOOO

DX 400S 400 A / B* 250 65 125 - 250 2-12*In 1 ST 31058 OOOO

A / B* 400 65 200 - 400 2-12*In 1 ST 31059 OOOO

DX 630S 630 A / B* 630 65 300 - 630 2-12*In 1 ST 31060 OOOO

ORDERING DATA - DX..S (4 POLE)

MCCB Rating Utilisation Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Category Rating (A) Capacity, Icu(kA) Setting (A) Setting Pack Suffix

DX 100S 100 A 40 35 25 - 40 9.5*In 1 ST 31001 OOOO

63 35 40 - 63 6-12*In 1 ST 31002 OOOO

80 35 63 - 80 6-12*In 1 ST 31003 OOOO

100 35 80 - 100 6-12*In 1 ST 31004 OOOO

DX 125S 125 A 125 35 80 - 125 6-12*In 1 ST 31005 OOOO

DX 160S 160 A 160 35 125 - 160 6-12*In 1 ST 31006 OOOO

DX 200S 200 A 200 35 160 - 200 6-12*In 1 ST 31007 OOOO

DX 250S 250 A 250 35 200 - 250 6-10*In 1 ST 31008 OOOO

DX 400S 400 A / B* 250 65 125 - 250 2-12*In 1 ST 31019 OOOO

A / B* 400 65 200 - 400 2-12*In 1 ST 31021 OOOO

DX 630S 630 A / B* 630 65 300 - 630 2-12*In 1 ST 31023 OOOO

* To be specified
2/41
ORDERING DATA - DX..H (3 POLE)

MCCB Rating
(A)
Utilisation
Category
Current Breaking
Rating (A) Capacity, Icu(kA)
Overload
Setting (A)
Short-Circuit
Setting
Std.
Pack
Catalogue No. Ordering
Suffix
2
DX 100H 100 A 40 65 25 - 40 9.5*In 1
63 65 40 - 63 6-12*In 1
80 65 63 - 80 6-12*In 1
100 65 80 - 100 6-12*In 1
DX 125H 125 A 125 65 80 - 125 6-12*In 1
DX 160H 160 A 160 65 125 - 160 6-12*In 1
DX 200H 200 A 200 65 160 - 200 6-12*In 1
DX 250H 250 A 250 65 200 - 250 6-10*In 1
DX 400H 400 A 250 100 125 - 250 2-12*In 1 ST 31046 OOOO
400 100 200 - 400 2-12*In 1 ST 31047 OOOO
DX 630H 630 A 630 100 300 - 630 2-12*In 1 ST 31048 OOOO
DX 800H 800 B 800 85 400 - 800 3-12*In 1 ST 31049 OOOO
DX 1000H 1000 B 1000 85 500 - 1000 3-12*In 1 ST 31050 OOOO
DX 1250H 1250 B 1250 85 630 - 1250 3-12*In 1 ST 31051 OOOO
DX 1600H 1600 B 1600 100 800 - 1600 3-12*In 1 ST 31052 OOOO

ORDERING DATA - DX..H (4 POLE)

MCCB Rating Utilisation Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Category Rating (A) Capacity, Icu(kA) Setting (A) Setting Pack Suffix

DX 100H 100 A 40 65 25 - 40 9.5*In 1 ST 31011 OOOO


63 65 40 - 63 6-12*In 1 ST 31012 OOOO
80 65 63 - 80 6-12*In 1 ST 31013 OOOO
100 65 80 - 100 6-12*In 1 ST 31014 OOOO
DX 125H 125 A 125 65 80 - 125 6-12*In 1 ST 31015 OOOO
DX 160H 160 A 160 65 125 - 160 6-12*In 1 ST 31016 OOOO
DX 200H 200 A 200 65 160 - 200 6-12*In 1 ST 31017 OOOO
DX 250H 250 A 250 65 200 - 250 6-10*In 1 ST 31018 OOOO
DX 400H 400 A 250 100 125 - 250 2-12*In 1 ST 31020 OOOO
400 100 200 - 400 2-12*In 1 ST 31022 OOOO
DX 630H 630 A 630 100 300 - 630 2-12*In 1 ST 31024 OOOO
DX 800H 800 B 800 85 400 - 800 3-12*In 1 ST 31025 OOOO
DX 1000H 1000 B 1000 85 500 - 1000 3-12*In 1 ST 31026 OOOO
DX 1250H 1250 B 1250 85 630 - 1250 3-12*In 1 ST 31027 OOOO
DX 1600H 1600 B 1600 100 800 - 1600 3-12*In 1 ST 31028 OOOO

2/42
ORDERING DATA - DM RANGE

2 MCCB Rating
(A)
Current
Rating (A)
Breaking
Capacity, Icu(kA)
Overload
Setting (A)
Short-Circuit
Setting
Std.
Pack
Catalogue No. Ordering
Suffix

DM 16 16 0.63 50 0.63 12*In 1 SL 97581 OOOO

1.0 50 1.0 12*In 1 SL 97582 OOOO

1.6 50 1.6 12*In 1 SL 97583 OOOO

2.5 50 2.5 12*In 1 SL 97584 OOOO

4.0 50 4.0 12*In 1 SL 97585 OOOO

5.0 50 5.0 12*In 1 SL 97586 OOOO

6.3 50 6.3 12*In 1 SL 97587 OOOO

7.5 50 7.5 12*In 1 SL 97588 OOOO

10 50 10 12*In 1 SL 97589 OOOO

12 50 12 12*In 1 SL 97590 OOOO

16 50 16 12*In 1 SL 97591 OOOO

DM 100 100 16 50 16 12*In 1 SL 97811 OOOO

25 50 25 12*In 1 SL 97812 OOOO

30 50 30 12*In 1 SL 97816 OOOO

35 50 35 12*In 1 SL 97813 OOOO

50 50 50 12*In 1 SL 97814 OOOO

60 50 60 12*In 1 SL 97817 OOOO

70 50 70 12*In 1 SL 97815 OOOO

DM 160 160 100 50 100 12*In 1 SL 97123 OOOO

120 50 120 12*In 1 SL 97703 OOOO

160 50 160 12*In 1 SL 97124 OOOO

DM 250 250 200 50 200 12*In 1 SL 97551 OOOO

230 50 230 12*In 1 SL 97552 OOOO

250 50 250 12*In 1 SL 97553 OOOO

DM 400 400 275 50 275 12*In 1 SL 97554 OOOO

325 50 325 12*In 1 SL 97555 OOOO

350 50 350 12*In 1 SL 97556 OOOO

400 50 400 12*In 1 SL 97557 OOOO

2/43
ORDERING DATA - DTH INST. RANGE

MCCB Rating
(A)
Current
Rating (A)
Breaking
Capacity, Icu(kA)
Overload
Setting (A)
Short-Circuit
Setting
Std.
Pack
Catalogue No. Ordering
Suffix
2
DTH 800 800 800 50 - 360 1 SB 95052 OOOO

800 50 - 550 1 SB 95053 OOOO

800 50 - 850 1 SB 95054 OOOO

800 50 - 1050 1 SB 95055 OOOO

ORDERING DATA - DF

FUSE MONITORING DEVICE

MCCB Thermal Rating Breaking Magnetic Threshold Std. Pack Catalogue No. Ordering
(A) Capacity, Icu(kA) (A) Suffix

DF 1 50 2 1 SL 97020 OOOO

2/44
ACCESSORIES - ORDERING DATA

TYPE DS

2 Accessory Coil Voltage /


Type
Location Std. Pack Catalogue No. Ordering
Suffix

DS 100/125/160/200

Shunt Release 110/240/415 V AC L 1 SL 97299 OMOO


24 V DC L 1 SL 97299 O4OO

Under Voltage Release 415 V AC L 1 SL 97610 OOOO


240 V AC L 1 SL 97611 OOOO

Auxiliary contact Block 1 NO + 1 NC R 1 SL 97296 OOOO


L 1 SL 97297 OOOO

Trip Alarm contact - R 1 SL 97298 OOOO

Rotary operating handle Ext. 1 SL 97301 OOOO

Earth Fault module2) GF1 Ext. 1 ST 27745 OOOO

S S Enclosure1) - Ext. 1 ST 29967 OOOO

DS 250/400

Shunt Release 415 V AC/220 V DC R/L 1 SL 97575 OOOO


240 V AC/110 V DC R/L 1 SL 97576 OOOO

Under Voltage Release 415 V AC L 1 SL 97579 OOOO


240 V AC L 1 SL 97580 OOOO

Auxiliary contact Block 2 NO + 2 NC L/R 1 SL 97573 OOOO

Trip Alarm contact - R 1 SL 97574 OOOO

Spreader Links with Barrier * - Ext. 1 Std. Kit

Rotary operating handle ROM Ext. 1 SL 97562 OOOO

Earth Fault module 2) GF2 Ext. 1 ST 27746 OOOO

Note : Any two internal accessories can be fitted simultaneously in a breaker


R To be mounted on right side
L To be mounted on left side
L/R Can be mounted on either side
Ext. External
* Along with DS400
1) Dimension on page 2/82
2) Dimension and wiring diagram on pages 2/80 & 2/81
2/45
ACCESSORIES - ORDERING DATA

TYPE DTH..E

Accessory Coil Voltage /


Type
Location Std. Pack Catalogue No. Ordering
Suffix
2
DTH 200E

Shunt Release 415 V AC/220 V DC R 1 SL 94331 ODOO

240 V AC/110 V DC 1 SL 94331 OBOO

110 V AC 1 SL 94331 OAOO

Under Voltage Release* 415 V AC L 1 SL 94332 DOOO

240 V AC 1 SL 94332 BOOO

110 V AC 1 SL 94332 AOOO

Auxiliary contact Block 1 NO + 1 NC R 1 SL 94330 OOOO

L 1 SL 94329 OOOO

Rotary operating mechanism ROM Ext. 1 SL 94336 OOOO

Earth Fault module1) GF2 Ext. 1 ST 27746 OOOO

DTH 250E / 400E / 630E / 800E

Shunt Release 110 V AC R 1 SL 98523 OOOO

415 V AC/220 V DC R 1 SL 98526 OOOO

24 V DC L 1 SL 98531 OOOO

240 V AC/110 V DC R 1 SL 98534 OOOO

Under Voltage Release 110 V AC L 1 SL 98543 OOOO

240 V AC L 1 SL 98545 OOOO

415 V AC L 1 SL 98548 OOOO

Auxiliary contact Block 1 NO + 1 NC L/R 1 SL 94217 OOOO

Rotary operating mechanism ROM 1 SL 94337 OOOO

Earth Fault module1) GF11 1 ST 28594 OOOO

Note : Any two internal accessories can be fitted simultaneously in a breaker


R To be mounted on right side
L To be mounted on left side
L/R Can be mounted on either side
Ext. External
* 24 V, 48 V, 110 V & 220 V DC are also available on request
1) Dimension and wiring diagram on pages 2/80 & 2/81
2/46
ACCESSORIES - ORDERING DATA

TYPE DG

2 Accessory Coil Voltage /


Type
Location Std. Pack Catalogue No. Ordering
Suffix

DG 125/200

Shunt Release 110/240/415 V AC L 1 SL 97299 OMOO


24 V DC L 1 SL 97299 O4OO

Under Voltage Release 415 V AC L 1 SL 97610 OOOO


240 V AC L 1 SL 97611 OOOO

Auxiliary contact Block 1 NO + 1 NC R 1 SL 97296 OOOO


L 1 SL 97297 OOOO

Trip Alarm contact - R 1 SL 97298 OOOO

Rotary operating handle Ext. 1 SL 97301 OOOO

Spreader Links with Barrier Ext. 1 Std. Kit

Earth Fault module 2) GF1 Ext. 1 ST 27745 OOOO

S S Enclosure 1) - Ext. 1 ST 29967 OOOO

DG 250/400

Shunt Release 415 V AC/220 V DC R/L 1 SL 97575 OOOO


240 V AC/110 V DC R/L 1 SL 97576 OOOO

Under Voltage Release 415 V AC L 1 SL 97579 OOOO


240 V AC L 1 SL 97580 OOOO

Auxiliary contact Block 2 NO + 2 NC L/R 1 SL 97573 OOOO

Trip Alarm contact - R 1 SL 97574 OOOO

Spreader Links with Barrier * - Ext. 1 Std. Kit

Rotary operating mechanism ROM Ext. 1 SL 97562 OOOO

Earth Fault module 2) GF2 Ext. 1 ST 27746 OOOO

Note : Any two internal accessories can be fitted simultaneously in a breaker


R To be mounted on right side
L To be mounted on left side
L/R Can be mounted on either side
Ext. External
* To be used with DS 125 & above
1) Dimension on page 2/82
2) Dimension and wiring diagram on pages 2/80 & 2/81
2/47
ACCESSORIES - ORDERING DATA

TYPE DH

Accessory Coil Voltage /


Type
Location Std. Pack Catalogue No. Ordering
Suffix
2
DH 100/125/160/200

Shunt Release 110/240/415 V AC L 1 SL 97299 OMOO


24 V DC L 1 SL 97299 O4OO

Under Voltage Release 415 V AC L 1 SL 97610 OOOO


240 V AC L 1 SL 97611 OOOO

Auxiliary contact Block 1 NO + 1 NC R 1 SL 97296 OOOO


L 1 SL 97297 OOOO

Trip Alarm contact - R 1 SL 97298 OOOO

Rotary operating mechanism ROM Ext. 1 SL 97301 OOOO

Adaptor terminal with shroud Ext. 1


Terminal shroud Ext. 1
Spreader Links with Barrier Ext. 1

Earth Fault module 2) GF1 Ext. 1 ST 27745 OOOO

S S Enclosure 1) - Ext. 1 ST 29967 OOOO

DH 250/400/630

Shunt Release 415 V AC/220 V DC R/L 1 SL 97575 OOOO


240 V AC/110 V DC R/L 1 SL 97576 OOOO

Under Voltage Release 415 V AC L 1 SL 97579 OOOO


240 V AC L 1 SL 97580 OOOO

Auxiliary contact Block 1 NO + 1 NC L/R 1 SL 97573 OOOO

Trip Alarm contact - R 1 SL 97574 OOOO

Adaptor terminal (3) with shroud (1) - 1 Set - Ext. 1 SL 97564 OOOO
Terminal shroud - Ext. 1 SL 97563 OOOO
Spreader Links with Barrier * - Ext. 1 Std. Kit

Rotary operating mechanism ROM Ext. 1 SL 97562 OOOO

Earth Fault module 2) GF2 Ext. 1 ST 27746 OOOO


GF11# Ext. 1 ST28594 OOOO

Note : Any two internal accessories can be fitted simultaneously in a breaker


R To be mounted on right side
L To be mounted on left side
L/R Can be mounted on either side
Ext. External
* To be used with DS 125 & above
# To be used with DH 630
1) Dimension on page 2/82
2) Dimension and wiring diagram on pages 2/80 & 2/81

2/48
ACCESSORIES - ORDERING DATA

TYPE DL

2 Accessory Coil Voltage /


Type
Location Std. Pack Catalogue No. Ordering
Suffix

DL 100
Shunt Release 110/240/415 V AC L 1 SL 97299 OMOO
24 V DC L 1 SL 97299 O4OO
Under Voltage Release 415 V AC L 1 SL 97610 OOOO
240 V AC L 1 SL 97611 OOOO
Auxiliary contact Block 1 NO + 1 NC R 1 SL 97296 OOOO
L 1 SL 97297 OOOO
Trip Alarm contact - R 1 SL 97298 OOOO
Rotary operating handle Ext. 1 SL 97301 OOOO
Earth Fault module 2) GF1 Ext. 1 ST 27745 OOOO
S S Enclosure 1) - Ext. 1 ST 29967 OOOO

DL 160
Shunt Release 415 V AC/220 V DC R 1 SL 94331 ODOO
240 V AC/110 V DC 1 SL 94331 OBOO
110 V AC 1 SL 94331 OAOO
Under Voltage Release* 415 V AC L 1 SL 94332 DOOO
240 V AC 1 SL 94332 BOOO
110 V AC 1 SL 94332 AOOO
Auxiliary contact Block 1 NO + 1 NC R 1 SL 94330 OOOO
L 1 SL 94329 OOOO
Trip Alarm contact # - R 1 Factory assembled
Rotary operating mechanism ROM Ext. 1 SL 94336 OOOO
Earth Fault module 2) GF2 Ext. 1 ST 27746 OOOO

DL 250/400
Shunt Release 415 V AC/220 V DC R/L 1 SL 97575 OOOO
240 V AC/110 V DC R/L 1 SL 97576 OOOO
Under Voltage Release 415 V AC L 1 SL 97579 OOOO
240 V AC L 1 SL 97580 OOOO
Auxiliary contact Block 1 NO + 1 NC L/R 1 SL 97573 OOOO
Trip Alarm contact - R 1 SL 97574 OOOO
Spreader Links with Barrier - Ext. 1 Std. Kit
Rotary operating mechanism ROM Ext. 1 SL 97562 OOOO
Earth Fault module 2) GF2 Ext. 1 ST 27746 OOOO

Note : Any two internal accessories can be fitted simultaneously in a breaker


R To be mounted on right side
L To be mounted on left side
L/R Can be mounted on either side
Ext. External
* 24 V, 48 V, 110 V & 220 V DC are also available on request
# On request
1) Dimension on page 2/82
2) Dimension and wiring diagram on pages 2/80 & 2/81

2/49
ACCESSORIES - ORDERING DATA

TYPE DTH

Accessory Coil Voltage /


Type
Location Std. Pack Catalogue No. Ordering
Suffix
2
DTH 100

Rotary operating handle - Ext. 1 SL 94286 OOOO

Earth Fault module 1) GF1 Ext. 1 ST 27745 OOOO

DTH 200

Shunt Release 415 V AC/220 V DC R 1 SL 94331 ODOO


240 V AC/110 V DC 1 SL 94331 OBOO
110 V AC 1 SL 94331 OAOO

Under Voltage Release* 415 V AC L 1 SL 94332 DOOO


240 V AC 1 SL 94332 BOOO
110 V AC 1 SL 94332 AOOO

Auxiliary contact Block 2 NO + 2 NC R 1 SL 94330 OOOO


L 1 SL 94329 OOOO

Trip Alarm contact # - R 1 Factory assembled

Rotary operating mechanism ROM Ext. 1 SL 94336 OOOO

Earth Fault module 1) GF2 Ext. 1 ST 27746 OOOO

DTH 250/400/630/800

Shunt Release 110 V AC R 1 SL 98523 OOOO


415 V AC/220 V DC R 1 SL 98526 OOOO
24 V DC L 1 SL 98531 OOOO
240 V AC/110 V DC R 1 SL 98534 OOOO

Under Voltage Release 110 V AC L 1 SL 98543 OOOO


240 V AC L 1 SL 98545 OOOO
415 V AC L 1 SL 98548 OOOO

Auxiliary contact Block 1 NO + 1 NC L/R 1 SL 94217 OOOO

Trip Alarm contact # - R 1 Factory assembled

Rotary operating mechanism ROM 1 SL 94337 OOOO

Earth Fault module 1) GF11 1 ST 28594 OOOO

Note : Any two internal accessories can be fitted simultaneously in a breaker


R To be mounted on right side
L To be mounted on left side
L/R Can be mounted on either side
Ext. External
* 24 V, 48 V, 110 V & 220 V DC are also available on request
# On request.
1) Dimension and wiring diagram on pages 2/80 & 2/81

2/50
ACCESSORIES - ORDERING DATA

TYPE DX (100/125/160/200/250)S / DX(100/125/160/200/250)H ... (3/4 POLE)

2 Accessory Type Std. Pack Catalgoue No. Ordering


Suffix

Shunt Release 415 V AC/DC 1 ST 33007 OOOO


240 V AC/DC 1 ST 33006 OOOO
110 V AC/DC 1 ST 33005 OOOO
48 V AC/DC 1 ST 33004 OOOO
24 V AC/DC 1 ST 33003 OOOO
With early-make auxiliary contacts 1

Under Voltage Release 440 V AC 1 ST 33010 OOOO


415 V AC 1 ST 33009 OOOO
240 V AC 1 ST 33008 OOOO
Off-delayed 1
With early-make auxiliary contacts 1

Auxiliary contact Block NO 1 ST 33001 OOOO


NC 1 ST 33002 OOOO
Early make 1
Trip indicating 1 ST 33021 OOOO

Door coupling rotary handle ROM 1 ST 33016 OOOO


Toggle to rotary convert 1 ST 33017 OOOO
Extension shaft 1 ST 33018 OOOO

Remote operator 240 V AC 1 ST 33013 OOOO

Residual-current protection module 1

Paralleling mechanism 1

Mechanical interlock 1

Plug-in adaptor 1

Side wall operator 1

Note: ROM consists of (Door coupling rotary handle + Toggle to rotary convert + Extension shaft)

2/51
ACCESSORIES - ORDERING DATA

TYPE DX (400/630)S / DX(400/630)H ... (3/4 POLE)

Accessory Type Std. Pack Catalgoue No. Ordering


Suffix
2
Time selectivity block 125-250A 1 ST 33053 OOOO
200-400A 1 ST 33054 OOOO
300-630A 1 ST 33055 OOOO
125-250A (1000-6000) 1 ST 33056 OOOO
200-400A (1000-9000) 1 ST 33057 OOOO
300-630A (1000-9000) 1 ST 33058 OOOO

Shunt Release 110 V AC/DC 1 ST 33034 OOOO


240 V AC / DC 1 ST 33035 OOOO
415 V AC / DC 1 ST 33036 OOOO

Under Voltage Release 240 V AC 1 ST 33037 OOOO


415 V AC 1 ST 33038 OOOO
440 V AC 1 ST 33039 OOOO
Off-delayed (AC) 1

Auxiliary contact Block 2NO + 2 NC 1 ST 33030 OOOO


Early make 1
General trip indicating 1

Annunciation unit - 1

Door coupling rotary handle ROM 1 ST 33045 OOOO


Toggle to rotary convert 1 ST 33046 OOOO
Extension shaft 1 ST 33047 OOOO

Rotary handle Used with Rotary drive 1 ST 33048 OOOO

Remote operator 240 V AC 1 ST 33042 OOOO


415 V AC 1 ST 33043 OOOO

Residual-current protection module 240 V AC 1


415 V AC 1

Paralleling mechanism 1

Mechanical interlock For 2 MCCBs 1 ST 33049 OOOO


For 2 MCCBs with Remote operator 1 ST 33050 OOOO
For 3 MCCBs 3 & 4 Pole with Toggle or Rotary drive 1 ST 33051 OOOO

Annunciation unit 1

Earth-fault Release (Fitted to Breaker) 3 Pole 1 ST 33031 OOOO


4 Pole 1

Residual-current operated relays (AC) 3 Pole (230 V) 1 ST 33040 OOOO


3 Pole (415 V) 1
4 Pole (230 V) 1
4 Pole (415 V) 1

Withdrawable unit 3 Pole 1 ST 33064 OOOO


4 Pole 1 ST 33063 OOOO
Withdrawable unit auxiliary contact For connection indication 1 ST 33061 OOOO
To connect Earth-fault release 1 ST 33062 OOOO

Toggle switch interlock For upto 3 Pad locks 1 ST 33044 OOOO


Note: ROM consists of (Door coupling rotary handle + Toggle to rotary convert + Extension shaft)
2/52
ACCESSORIES - ORDERING DATA

TYPE DX (800/1000/1250/1600)H ... (3/4 POLE)

2 Accessory Type Std. Pack Catalgoue No. Ordering


Suffix

Shunt Release 200 - 480 V AC 1


110 V AC 1

Under Voltage Release 200 - 480 V AC 1


110 V AC 1
Under Voltage Release Off-delayed (AC) 1

Auxiliary contact Block 2NO + 2 NC 1


Trip type indicator 240 V AC 1

Load monitoring 200 - 240 V AC 1

Door coupling rotary handle ROM 1


Toggle to rotary convert 1
Extension shaft 1

Remote operator 230 V AC 1

Mechanical interlock 1

Earth-fault Release (Fitted to Breaker) 1

Withdrawable unit 800 A 1


1250 A 1
1600 A 1

Note: ROM consists of (Door coupling rotary handle + Toggle to rotary convert + Extension shaft)

2/53
ACCESSORIES - ORDERING DATA

TYPE DM

Accessory Coil Voltage /


Type
Location Std. Pack Catalogue No. Ordering
Suffix
2
DM 16
Shunt Release 110/240/415 V AC L 1 SL 97042 OOOO
Auxiliary contact Block 1 NO + 1 NC R 1 SL 97023 OOOO
L 1 SL 97025 OOOO
Trip Alarm contact - R 1 SL 97037 OOOO
Rotary operating mechanism ROM Ext. 1 SL 97044 OOOO

DM 100
Shunt Release 110/240/415 V AC L 1 SL 97299 OMOO
24 V DC L 1 SL 97299 O4OO
Under Voltage Release 415 V AC L 1 SL 97610 OOOO
240 V AC L 1 SL 97611 OOOO
Auxiliary contact Block 1 NO + 1 NC R 1 SL 97296 OOOO
L 1 SL 97297 OOOO
Trip Alarm contact - R 1 SL 97298 OOOO
Rotary operating mechanism ROM Ext. 1 SL 97301 OOOO
Spreader Links with Barrier Ext. 1
Earth Fault module GF1 Ext. 1 ST 27745 OOOO

DM 160
Shunt Release 415 V AC/220 V DC R 1 SL 94331 ODOO
240 V AC/110 V DC 1 SL 94331 OBOO
110 V AC 1 SL 94331 OAOO
Under Voltage Release* 415 V AC L 1 SL 94332 DOOO
240 V AC 1 SL 94332 BOOO
110 V AC 1 SL 94332 AOOO
Auxiliary contact Block 1 NO + 1 NC R 1 SL 94330 OOOO
L 1 SL 94329 OOOO
Trip Alarm contact # - R 1 Factory assembled
Rotary operating handle ROH Ext. 1 SL 94336 OOOO
Earth Fault module GF2 Ext. 1 ST 27746 OOOO

DM 250/400
Shunt Release 415 V AC/220 V DC R/L 1 SL 97575 OOOO
240 V AC/110 V DC R/L 1 SL 97576 OOOO
Under Voltage Release 415 V AC L 1 SL 97579 OOOO
240 V AC L 1 SL 97580 OOOO
Auxiliary contact Block 1 NO + 1 NC L/R 1 SL 97573 OOOO
Trip Alarm contact - R 1 SL 97574 OOOO
Adaptor terminal (3) with shroud (1) - 1 Set - Ext. 1 SL 97564 OOOO
Terminal shroud - Ext. 1 SL 97563 OOOO
Spreader Links with Barrier - Ext. 1 Std. Kit
Rotary operating handle ROH Ext. 1 SL 97562 OOOO
Earth Fault module GF2 Ext. 1 ST 27746 OOOO

Note : Any two internal accessories can be fitted simultaneously in a breaker


R To be mounted on right side
L To be mounted on left side
L/R Can be mounted on either side
Ext. External
* 24 V, 48 V, 110 V & 220 V DC are also available on request
# On request.
2/54
ACCESSORIES - ORDERING DATA

TYPE DTH 800 INST.

2 Accessory Coil Voltage /


Type
Location Std. Pack Catalogue No. Ordering
Suffix

Shunt Release 110 V AC R 1 SL 98523 OOOO


415 V AC/220 V DC R 1 SL 98526 OOOO
24 V DC L 1 SL 98531 OOOO
240 V AC/110 V DC R 1 SL 98534 OOOO

Under Voltage Release * 110 V AC L 1 SL 98543 OOOO


240 V AC L 1 SL 98545 OOOO
415 V AC L 1 SL 98548 OOOO

Auxiliary contact Block 1 NO + 1 NC L/R 1 SL 94217 OOOO

Rotary operating mechanism ROM Ext. 1 SL 94337 OOOO

Note : Any two internal accessories can be fitted simultaneously in a breaker


R To be mounted on right side
L To be mounted on left side
L/R Can be mounted on either side
Ext. External
* 24 V, 48 V, 110 V & 220 V DC are also available on request

ACCESSORIES - ORDERING DATA

TYPE DF

Accessory Coil Voltage / Location Std. Pack Catalogue No. Ordering


Type Suffix

Shunt Release 110/240/415 V AC R 1 SL 97042 OOOO

Trip Alarm contact - R 1 SL 97037 OOOO

Auxiliary contact Block 1 NO + 1 NC R 1 SL 97023 OOOO

Note : Any one can be used.


R To be mounted on right side

2/55
OVERALL DIMENSIONS

MCCB - TYPE DS

MOUNTING AND MOUNTING AND


DOOR CUTOUT DETAILS DOOR CUTOUT DETAILS

DS 100 DS 125/160/200

MOUNTING AND
DOOR CUTOUT DETAILS

DS 250/400

Note: All dimensions are in mm.


2/56
OVERALL DIMENSIONS

DIMENSIONAL DETAILS OF ROTARY OPERATING MECHANISM - TYPE DS

DS 100/125/160/200

DS 250/400

Note: All dimensions are in mm.


2/57
OVERALL DIMENSIONS

MCCB - TYPE DTH..E

MOUNTING AND
DOOR CUTOUT DETAILS

DTH 200E DTH 250/400/630/800 E

ROTARY OPERATING MECHANISM FOR TYPE DTH..E

DTH 200E DTH 250/400/630/800 E

Note: All dimensions are in mm.


2/58
OVERALL DIMENSIONS

MCCB - TYPE DG

MOUNTING AND
DOOR CUTOUT DETAILS

DG 125/200

MOUNTING AND
DOOR CUTOUT DETAILS

DG 250/400

Note: All dimensions are in mm.


2/59
OVERALL DIMENSIONS

DIMENSIONAL DETAILS OF ROTARY OPERATING MECHANISM - TYPE DG

DG 125/200

DG 250/400

EXPLODED VIEW OF ROTARY OPERATING MECHANISM

Note: All dimensions are in mm.


2/60
OVERALL DIMENSIONS

MCCB - TYPE DH

MOUNTING AND MOUNTING AND


DOOR CUTOUT DETAILS DOOR CUTOUT DETAILS MOUNTING AND
DOOR CUTOUT DETAILS

DH 100 DH 125/160 DH 200

MOUNTING AND
DOOR CUTOUT DETAILS

DH 250 DH 400 DH 630

Note: All dimensions are in mm.


2/61
OVERALL DIMENSIONS

DIMENSIONAL DETAILS OF ROTARY OPERATING MECHANISM - TYPE DH

DH 100/125/160/200

DH 250/400

DH 630
Note: All dimensions are in mm.
2/62
OVERALL DIMENSIONS

MCCB - TYPE DL

DL 100 DL 160/200

DL 250/400

Note: All dimensions are in mm.


2/63
OVERALL DIMENSIONS

DIMENSIONAL DETAILS OF ROTARY OPERATING MECHANISM - TYPE DL

DL 100 DL 160

DL 250/400

Note: All dimensions are in mm.


2/64
OVERALL DIMENSIONS

MCCB - TYPE DTH

DTH 100 3 POLE / 4 POLE DTH 200

MOUNTING AND
DOOR CUTOUT DETAILS

DTH 250/400/630.800

Note: All dimensions are in mm.


2/65
OVERALL DIMENSIONS

ROTARY OPERATING MECHANISM FOR TYPE DTH

PANEL CUT OUT

DTH 100 DTH 200

DTH 250/400/630/800

Note: All dimensions are in mm.


2/66
OVERALL DIMENSIONS

DX 100-250 S/H ... 3/4 POLE

ROTARY DRIVE / ROTARY HANDLE FOR SURFACE MOUNTING BREAKERS

Note: All dimensions are in mm.


2/67
OVERALL DIMENSIONS

DX 100-250 S/H... 3/4 POLE

EXTENSION SHAFT

DOOR COUPLING ROTARY HANDLE FOR REAR MOUNTING SWITCHES

REMOTE OPERATOR

Note: All dimensions are in mm.


2/68
OVERALL DIMENSIONS

DX 160 S/H, DX 200-250 S/H

PLUG-IN ADAPTER

Note: All dimensions are in mm.


2/69
OVERALL DIMENSIONS

DX 400-630 S/H (3/4 POLE)

DIMENSIONAL DETAILS OF ROTARY OPERATING MECHANISM

ROTARY DRIVE

DOOR COUPLING ROTARY HANDLE

Note: All dimensions are in mm.


2/70
OVERALL DIMENSIONS

DX 400-630 S/H ... 3/4 POLE

REMOTE OPERATOR

PUSH-BUTTONS FOR REMOTE OPERATION ENCLOSED BREAKERS

WITHDRAWABLE UNIT

Note: All dimensions are in mm.


2/71
OVERALL DIMENSIONS

DX 800-1250 H ... 3/4 POLE

DX 1600 H ... 3/4 POLE

Note: All dimensions are in mm.


2/72
OVERALL DIMENSIONS

DX...H 800-1600 A (3/4 POLE)

MOUNTING BRACKETS REAR CONNECTION

Note: All dimensions are in mm.


2/73
OVERALL DIMENSIONS

DX 800-1600 H ... 3/4 POLE

ROTARY DRIVE

DOOR COUPLING ROTARY HANDLE

REMOTE OPERATOR

Note: All dimensions are in mm.


2/74
OVERALL DIMENSIONS

DX 800-1600 H ... 3/4 POLE

WITHDRAWABLE UNIT

Note: All dimensions are in mm.


2/75
OVERALL DIMENSIONS

MCCB - TYPE DM

MOUNTING AND
DOOR CUTOUT DETAILS
MOUNTING AND
DOOR CUTOUT DETAILS
DM 16 DM 100

MOUNTING AND
DOOR CUTOUT DETAILS
MOUNTING AND
DOOR CUTOUT
DETAILS
DM 160 DM 250/400

Note: All dimensions are in mm.


2/76
OVERALL DIMENSIONS

ROTARY OPERATING MECHANISM FOR MOTOR BACK-UP PROTECTION RANGE FOR TYPE DM

DM 16 DM 100

DM 160 DM 250/400

Note: All dimensions are in mm.


2/77
OVERALL DIMENSIONS

MCCB - TYPE DTH 800 INST.

ROTARY OPERATING MECHANISM FOR DTH 800 INST.

Note: All dimensions are in mm.


2/78
OVERALL DIMENSIONS & CONNECTION DIAGRAM

FUSE MONITORING DEVICE TYPE DF

Caution : Connect terminals of DF in parallel with the fuse links.

Note: All dimensions are in mm.


2/79
OVERALL DIMENSIONS

EARTH FAULT MODULES - GF1, GF2, GF11

GF1 GF2

GF11

Note: All dimensions are in mm.


2/80
WIRING DIAGRAM

EARTH FAULT MODULES - GF1, GF2, GF11

GF1 & GF2

GF11

2/81
OVERALL DIMENSIONS

SS ENCLOSURE

Note: All dimensions are in mm.


2/82