You are on page 1of 113

Instruction Manual

For Range of
Air Circuit Breakers
Larsen and Toubro is India’s largest
manufacturer of low tension switchgear,
offering the widest range of products
from push buttons to circuit breakers.

L&T invests continually in upgrading


its design, manufacturing and testing
facilities to ensure that the products
offer every feature and every advantage
that state-of-the-art technology can offer.

A proven performance record in tropical


conditions has established that L&T
switchgear is ideal for adverse conditions.

Switchgear Factory at Powai, Mumbai

The L&T switchgear Advantage


• Suitable for tropical climate
• Stands up the Indian summer
• Withstands wide voltage fluctuations
• Accommodates Aluminum terminations
• Easy to maintain
• Easy spares availability through a wide
network of authorised stockists

Switchgear Testing Laboratory (STL) at


Powai Works:

STL is NABL accredited laboratory, fully


equipped for all the type tests and routine
tests.

STL has dedicated 85 kA short- circuit testing


laboratory to ensure that the air circuit
breakers meet the high design standards of
quality and reliability.

Switchgear Testing Laboratories at Powai, Mumbai.


INTRODUCTION

L&T’s range of Air Circuit Breakers are manufactured and tested at one
of India’s most modern switchgear factories. Proper installation and maintenance
according to the instructions given in this manual will ensure that the breakers
render long years of trouble-free service.

These breakers are designed for normal industrial environment. It is important that
the circuit breakers subjected to hostile environment e.g. dust, caustic vapour,
corrosive gases etc. are appropriately enclosed.
CONTENTS

1 Storage............................................................................................................. 1-1

2 Unpacking........................................................................................................ 2-1

3 Handling........................................................................................................... 3-1

4 Identification..................................................................................................... 4-1

5 Operation....................................................................................................... 5-1

6 Racking............................................................................................................ 6-1

7 Installation........................................................................................................ 7-1

8 Protection......................................................................................................... 8-1

9 Accessories...................................................................................................... 9-1

10 Maintenance....................................................................................................10-1

11 Spare Parts......................................................................................................11-1

12 Overall dimensions..........................................................................................12-1

13 Wiring diagrams.............................................................................................. 13-1

14 Special applications........................................................................................ 14-1


1. STORAGE

TRIP

OFF

1. Do not store the breaker 2. If the ACB is not going to be


uncovered even for a short used for a long time then place
period. Always keep it covered the carton back on it.
with polyethylene bag.

3. Store the breaker in a cool and


well-ventilated place protected
from dusty, corrosive, salt laden
or wet atmosphere.

4. Please do not drop or roll the


ACB carton while storing or
transporting. Use proper
material handling equipment for
stacking of breakers.

5. Only same frame breakers should


be stacked one above another.
6. Do not stack more than four
breakers one above another.

Note: Storage Temperature: -5°C to 70°C 1-1


2. UNPACKING
FOR FIXED ACBs

Carton packing Nails


Nails Case packing
2. Lift the carton/wooden case. Cut and
remove any accessories taped to
1. Cut the straps and remove the nails. breaker or kept loose on the pallet.
(If any) Open the polyethylene bag.

Note: For identification ‘FIX (Arc chute holding bracket and padding)*
BREAKER’ written on green
colour sticker, is available on
packaging carton.

3. Remove breaker mounting hardware, arc-chute holding bracket,*


padding fixed to the breaker over arc chutes & lift the breaker.
*: For 3P/4P 3200D/4000C breaker, arc chute should be unpacked and mounted on the breaker.
FOR DRAWOUT ACBs (up to 3200A & except 4 pole version of 2000A / 2500A / 3200A)
1. Follow the first 2 steps of fixed ACB unpacking.

2. Remove the locking plate & Rack 3. Pull the breaker out. Remove breaker
out the breaker. mounting hardware & lift the breaker.

(Arc chute holding bracket


and padding)

4. Remove arc-chute holding bracket, 5. Remove cradle clamping hardware. Lift the cradle.
padding fixed to the breaker over arc-chute.
FOR DRAWOUT ACBS (4 pole version of 2000A / 2500A / 3200A & above)
There are separate packing cases for packing of breaker & cradle.
1. For breaker unpacking follow procedure mentioned for fixed ACB unpacking.
2. For cradle unpacking, follow 1 & 5 steps mentioned in drawout ACB unpacking. 2-1
3. HANDLING

1. Move the packing with fork lift. Do


not drop or roll the packing case.

2. Pictures showing attachment of ropes to breaker & cradle for handling.

Caution:
1. Before handling remove breaker from cradle (for drawout ACBS).
2. Do not lift / handle the breaker or cradle by holding its front facia / operating handle / breaker
or cradle terminal / jaw contacts.
3. Keep the breaker on a flat, firm surface in its normal position. Do not
keep it on sides or in up side down position.

Note : Refer the table as per clause 3.1 for weights of different ratings of breaker.

3-1
3.1 Weight of manually operated breaker (kg):
CN-CS...S1
Rating Breaker 3P Cradle 3P Breaker 4P Cradle 4P
400/630/800S1 50 38 54 44
1000/1250S1 50 38 54 44
1600S1 51 38 55 44
2000S1 62 38 71 44
2500S1 72 50 85 57
3200S1 73 50 86 57

CN-CS...C
Rating Breaker 3P Cradle 3P Breaker 4P Cradle 4P
800/1000C 50 38 54 44
1250/1600C 51 38 55 44
2000/2500C 72 50 77 65
5000/6300C 153 105 207 137

CN-CS...H
Rating Breaker 3P Cradle 3P Breaker 4P Cradle 4P
800/1000H 51 38 55 44
1250/1600H 51 38 55 44
2000/2500H 72 50 77 65
3200H1/3200H2 76 53 86 57
4000H/4000H2 76 53 86 57

CN-CS...HE
Rating Breaker 3P Cradle 3P Breaker 4P Cradle 4P
1250HE 51 38 55 44
2000HE 72 50 77 65
3200HE 76 53 86 57
5000HE 153 105 207 137

Special orders
Rating Breaker 3P Cradle 3P Breaker 4P Cradle 4P
3200C 73 50 86 57
3200D 113 75 154 101
4000C 115 75 156 101

CN-CS...G CN-CS...E
Rating Breaker 3P Rating Breaker 3P
400/630/800/1000/1250/1600G 50 400/630/800/1000/1250/1600E 40
2000G 51 2000E 41
For electrical breaker add 7 kg to the above mentioned breaker weight.
3-2
4. IDENTIFICATION
4.1 Identification for S1/C/D/H range breakers:

MAIN FACIA LABEL

LARSEN & TOUBRO MADE IN INDIA TYPE DESIGNATION ACB RATING

SERIAL NUMBER
RATED CURRENT
1 In : 2000
4000 A 8 IS/IEC 60947-2 11 LARSEN & TOUBRO MADE IN INDIA

6
2 Ue : 415 V ~ 50/60 Hz IEC 60947-2 SERIAL NUMBER
e

9
7 CN-CS 2000C
4000 H2
3 Icu : 55
75 kA Ics : 100 % I cu 10 BS EN 60947-2 RATED OPERATIONAL FR167177
Fr167177 SUITABILITY FOR ISOLATION
VOLTAGE In : 2000
4000 A Sr. No.
4 Icw : 55
75 kA for 1 s 415V~~50/60
U e : 415V 50/60Hz Hz
5 Utilization Category : B CN-CS 2000C
4000 H2 12 RATED ULTIMATE SHORT-
CIRCUIT BREAKING CAPACITY
Icu : 55
75 kA
Icw : 55
75kA
I cs : 100% I cu
kA for
for 11ss
RATED SERVICE SHORT-
CIRCUIT BREAKING CAPACITY
Utilization Category : B UTILIZATION CATEGORY

RATED SHORT TIME Standard : IS/IEC 60947-2, IEC 60947-2 APPLICABLE


RATED SHORT
CURRENT TIME
WITHSTAND STANDARDS
CURRENT WITHSTAND
CAPACITY
CAPACITY

METAL LABEL OF C-POWER

1 Rated current 7 Rated service short-circuit breaking capacity


2 Rated operational voltage 8 Standard compliance
3 Rated ultimate short-circuit breaking capacity 9 Standard compliance
4 Rated short time withstand capacity 10 Standard compliance
5 Utilization category 11 Suitability for isolation
6 Range of rated frequency 12 Type designation
13 marking

4-1
4.2 Identification for G-range breakers:

MAIN FACIA LABEL

LARSEN & TOUBRO MADE IN INDIA TYPE DESIGNATION ACB RATING

FOR DG SET 13
RATED CURRENT
1 In : 1600 A 8 IS/IEC 60947-2 11 LARSEN & TOUBRO MADE IN INDIA
FOR DG SET TYPE OF APPLICATION
6
2 Ue : 415 V ~ 50/60 Hz IEC 60947-2 SERIAL NUMBER
e

9
7 CN-CS 1600 G
3 Icu : 50 kA Ics : 100 % I cu 10 BS EN 60947-2 RATED OPERATIONAL FR167177
VOLTAGE In : 1600 A Sr. No. SUITABILITY FOR ISOLATION
4 Icw : 50 kA for 1 s U e : 415V ~ 50/60 Hz
5 Utilization Category : B CN-CS 1600 G 12 RATED ULTIMATE SHORT-
CIRCUIT BREAKING CAPACITY
Icu : 50 kA I cs : 100% I cu
Icw : 50 kA for 1 s
RATED SERVICE SHORT-
CIRCUIT BREAKING CAPACITY
Utilization Category : B UTILIZATION CATEGORY
Standard : IS/IEC 60947-2, IEC 60947-2 APPLICABLE
RATED SHORT TIME STANDARDS
CURRENT WITHSTAND
CAPACITY

METAL LABEL OF C-POWER G-RANGE BREAKER

1 Rated current 7 Rated service short-circuit breaking capacity


2 Rated operational voltage 8 Standard compliance
3 Rated ultimate short-circuit breaking capacity 9 Standard compliance
4 Rated short time withstand capacity 10 Standard compliance
5 Utilization category 11 Suitability for isolation
6 Range of rated frequency 12 Type designation
13 Type of application

4-2
4.3 Identification for HE range breakers: 4. IDENTIFICATION
4.1 Identification for S1/C/D/H range breakers:

MAIN FACIA LABEL

LARSEN & TOUBRO MADE


MADE IN
IN INDIA
INDIA TYPE DESIGNATION ACB RATING

ANTI CORROSIVE 13
SERIAL NUMBER
RATED CURRENT
1 In : 1250
4000 A 8 IS/IEC 60947-2 11 LARSEN & TOUBRO MADE
MADE IN
IN INDIA
INDIA
ANTI CORROSIVE TYPE OF APPLICATION
6
2 Ue : 415 V ~ 50/60 Hz IEC 60947-2 SERIAL NUMBER
e

9
7 CN-CS 1250
4000 HE
H2
3 Icu : 50
75 kA Ics : 100 % I cu 10 BS EN 60947-2 RATED OPERATIONAL FR167177 SUITABILITY FOR
SUITABILITY ISOLATION
FOR ISOLATION
VOLTAGE In : 1250
4000 A Sr. No.
4 Icw : 50
75 kA for 1 s U e : 415V
415V~~50/60
50/60Hz Hz
5 Utilization Category : B CN-CS 1250
4000 HE
H2 12 RATED ULTIMATE SHORT-
CIRCUIT BREAKING CAPACITY
Icu : 50
75 kA
Icw : 50
75kA
I cs : 100% I cu
kA for
for 11ss
RATED SERVICE SHORT-
CIRCUIT BREAKING CAPACITY
Utilization Category : B UTILIZATION CATEGORY
Standard : IS/IEC 60947-2, IEC 60947-2 APPLICABLE
RATED SHORT TIME STANDARDS
CURRENT WITHSTAND
CAPACITY

METAL LABEL OF C-POWER HE BREAKER

1 Rated current 7 Rated service short-circuit breaking capacity


2 Rated operational voltage 8 Standard compliance
3 Rated ultimate short-circuit breaking capacity 9 Standard compliance
4 Rated short time withstand capacity 10 Standard compliance
5 Utilization category 11 Suitability for isolation
6 Range of rated frequency 12 Type designation
13 Type of application

4-1
4-3
3 2 1

12
11

10

9
7
8

Fig. 4-1 FIXED ELECTRICAL ACB

1 Rating label 7 Spring ‘Charged / Discharged’ indication


2 Top cover 8 Mounting bracket
3 Arc chutes 9 Overcurrent release type DN1 *
4 Lifting lug ** 10 ‘Close’ push button
5 Operating handle 11 Sealable sliding shutters for push buttons
6 ‘ON / OFF’ indication 12 ‘Trip’ push button

** Should not be removed while removing ACB from packing case.


* Overcurrent releases type SR18/ SR18G/ SR18G with Display /SR18Gi with
Display/ SR21i/ SR71 etc.,when provided is mounted at the same location.

4-4
3 2 1

6 19
18
17

7 16

8 15
9
10

11 12 13 14
Fig. 4-2 DRAWOUT ELECTRICAL ACB

1 Rating label 11 Racking interlock


2 Top cover 12 Position indication
3 Arc chutes 13 Lock in - ‘Isolated’ position / ‘Any’ position
4 Lifting lug ** 14 Racking handle
5 Breaker (Draw-out part) 15 Bezel (to be mounted on panel door)
6 Cradle (Fixed part) 16 Overcurrent release type SR21i *
7 ‘ON / OFF’ indication 17 Sealable sliding shutters for push buttons
8 Spring ‘Charged / Discharged’ indication 18 ‘Close’ push button
9 Operating handle 19 ‘Trip’ push button
10 Door interlock

** Should not be removed while removing ACB from packing case.


* Overcurrent releases type DN1/ SR18/ SR18G/ SR18G with Display /SR18Gi
with Display / SR71 etc.,when provided is mounted at the same location.
4-4
4-5
Arc chute
clamps

Current Moving Secondary


transformer isolating contacts (SIC)
(for protection)
Scraping Mounting bracket
earth (moving)
Contact jaws

Voltmetric Door interlock pin


release termination

Fig. 4-3 DRAWOUT ACB - REAR VIEW

Note : Please do not place the breaker on its rear side.

Safety
shutter Fixed Secondary
isolating contacts (SIC)
Cradle
terminal
Microswitch
for position Earthing terminal
indication at rear
Scrapping
earth (fixed)
Racking
screw Telescopic rail

Interlock support
Door
interlock
Cradle facia
Racking
Lock in isolated /
interlock
any position
Racking
handle
Fig. 4-4 CRADLE - FRONT VIEW

4-6
Technical Data Sheet

Rating (A) 400 630 800 1000

Type Designation E S1 E S1 E S1 C H E S1 C H

Rated current (A) at 50°C In 400 630 800 1000


*
Rated operational voltage (V),50/60Hz U e 415 415 415 415

Rated insulation voltage (V),50/60Hz Ui 1000 1000 1000 1000

No. of poles 3 3/4 3 3/4 3 3/4 3 3/4

Rated ultimate short circuit breaking 380/415/500V 50 50 50 50 50 50 50 65 50 50 50 65


Icu
capacity 50/60Hz (kA rms)
690V - - - - - - 35 50 - - 35 50

Rated service short circuit breaking 380/415/500V 50 50 50 50 50 50 50 65 50 50 50 65


Ics
capacity 50/60Hz (kA rms) -
690V - - - - - 35 50 - - 35 50

0.5 sec 50 50 50 50 50 50 50 65 50 50 50 65
Rated short time
**
withstand capacity Icw 1 sec 50 50 50 50 50 50 50 65 50 50 50 65
50/60Hz (kA rms)
3 sec - 25 - 25 - 25 35 50 - 25 35 50

380/415/500V 105 105 105 105 105 105 105 143 105 105 105 143
Rated making capacity Icm
50/60Hz (kA peak) 690V - - - - - - 73.5 105 - - 73.5 105
Rated impulse withstand voltage Uimp 8 12 8 12 8 12 8 12
of main circuit (kV)
Rated impulse withstand voltage Uimp 4 4 4 4
of aux. circuit (kV)

Typical opening time (ms) 40 40 40 40

Typical closing time (ms) 60 60 60 60

Utilization category B B B B

Suitability for isolation ?? ? ?

Fixed ????????????

Draw out x ?x ?x ???x ???


Manual ????????????
Electrical x ?x ?x ???x ???

Electrical & Mechanical life (operating cycles) 15000 20000 15000 20000 15000 20000 15000 20000

Electrical life without maintenance 6000 8000 6000 8000 6000 8000 8000 8000 6000 8000 8000 8000

Dimensions (in mm) Fixed H 385 394 385 394 385 394 385 394

3 Pole 316 326 316 326 316 326 316 326


W
4 Pole - 414 - 414 - 414 - 414

D 449 443 449 443 449 443 431 449 443 431

Draw out H - 468 - 468 - 468 - 468

3 Pole - 399 - 399 - 399 - 399


W
4 Pole - 487 - 487 - 487 - 487

D - 587 - 587 - 587 - 587

* Please consult us for application at dc voltages & higher operational voltage upto 690V AC.
** Icw values are indicated based on thermal considerations. While selecting a breaker please ensure that Icw requirement for the application is not more than
Ics / Icu at the point of installation.

Electrical life = Mechanical life. However, arcing contacts need to be replaced depending upon wear & tear.

4-7
Technical Data Sheet

Rating (A) 1250 1600 2000


Type Designation E S1 C H E S1 C H E S1 C H
Rated current (A) at 50°C In 1250 1600 2000
*
Rated operational voltage (V), 50/60Hz Ue 415 415 415
Rated insulation voltage (V), 50/60Hz Ui 1000 1000 1000
No. of poles 3 3/4 3 3/4 3 3/4

Rated ultimate short circuit breaking 380/415/500V 50 50 50 65 50 50 50 65 50 50 55 75


Icu
capacity 50/60Hz (kA rms)
690V - - 35 50 - - 35 50 - - 40 65

Rated service short circuit breaking 380/415/500V 50 50 50 65 50 50 50 65 50 50 55 75


Ics
capacity 50/60Hz (kA rms)
690V - - 35 50 - - 35 50 - - 40 65
0.5 sec 50 50 50 65 50 50 50 65 50 50 55 75
Rated short time
**
withstand capacity Icw 1 sec 50 50 50 65 50 50 50 65 50 50 55 75
50/60Hz (kA rms)
3 sec - 25 35 50 - 35 35 50 - 45 50 65
380/415/500V 105 105 105 143 105 105 105 143 105 105 121 165
Rated making capacity Icm
50/60Hz (kA peak) 690V 143
- - 73.5 105 - - 73.5 105 - - 84
Rated impulse withstand voltage Uimp
of main circuit (kV) 8 12 8 12 8 12

Rated impulse withstand voltage Uimp


of aux. circuit (kV) 4 4 4

Typical opening time (ms) 40 40 40

Typical closing time (ms) 60 60 60

Utilization category B B B
Suitability for isolation ? ? ?
Fixed ?
? ???????x ??
Draw out x ???x ???x ???
Manual ?
? ??????????
Electrical x ???x ???x ???

Electrical & Mechanical life (operating cycles) 20000 20000 20000

Electrical life without maintenance 6000 7000 7000 7000 6000 7000 7000 7000 4500 6000 6000 6000

Dimensions (in mm) Fixed H 385 394 385 394 385 - 394

3 Pole 316 326 316 326 316 - 482


W
4 Pole 414 - 414 - - 628
D 449 443 431 437 431 437 - 431
Draw out H - 468 - 468 - 468 468

3 Pole - 399 - 399 - 399 555


W
4 Pole - 487 - 487 - 487 701
D 587 - 587 - 587 587

* Please consult us for application at dc voltages & higher operational voltage upto 690V AC.
** Icw values are indicated based on thermal considerations. While selecting a breaker please ensure that Icw requirement for the application is not more than
Ics / Icu at the point of installation.

Electrical life = Mechanical life. However, arcing contacts need to be replaced depending upon wear & tear.

4-8
Technical Data Sheet

Rating (A) 2500 3200 4000 5000 6300

Type Designation S1 C H S1 H2 H1 D H2 H C C C

Rated current (A) at 50°C In 2500 3200 4000 5000 6300


*
Rated operational voltage (V), 50/60Hz U e 415 415 415 415 415

Rated insulation voltage (V), 50/60Hz Ui 1000 1000 1000 1000 1000

No. of poles 3/4 3/4 3/4 3/4 3/4

Rated ultimate short circuit breaking 380/415/500V 60 60 75 60 75 100 70 75 100 70 95 95


Icu
capacity 50/60Hz (kA rms)
690V - 40 65 - 65 85 ? 65 85 ? ? ?

Rated service short circuit breaking 380/415/500V 60 60 75 60 75 100 70 75 100 70 95 95


Ics
capacity 50/60Hz (kA rms)
690V - 40 65 - 65 85 ? 65 85 ? ? ?

0.5 sec 60 60 75 60 75 100 70 75 100 70 95 95


Rated short time
**
withstand capacity Icw 1 sec 60 60 75 60 75 100 70 75 100 70 95 95
50/60Hz (kA rms)
3 sec 50 55 65 55 70 85 70 70 85 70 ? ?

380/415/500V 132 132 165 132 165 220 154 165 220 154 209 209
Rated making capacity Icm
50/60Hz (kA peak) 690V - 84 143 - 143 187 ?143 187 ? ? ?
Rated impulse withstand voltage Uimp 12 12 12 12 12
of main circuit (kV)
Rated impulse withstand voltage Uimp 4 4 4 4 4
of aux. circuit (kV)

Typical opening time (ms) 40 40 40 40 40

Typical closing time (ms) 60 60 60 60 60

Utilization category B B B B B

Suitability for isolation ? ? ? ??

Fixed x ??x x x ?x x ?x x

Draw out ????????????

Manual ????????????

Electrical ????????????

Electrical & Mechanical life (operating cycles) 20000 10000 5000 10000 5000 5000 5000

Electrical life without maintenance 5000 5000 5000 5000 5000 5000 2500 5000 5000 2500 2500 2500

Dimensions (in mm) Fixed H - 394 - ? 509 ? 509 - -

3 Pole - 482 - ? 636 ? 636 - -


W
4 Pole - 628 - ? 838 ? 838 - -

D - 431 - ? 518 ? 518 - -

Draw out H 468 468 468 583 468 583 583 583

3 Pole 555 555 701 711 701 711 913 913


W
4 Pole 701 701 909 913 909 913 1182 1182

D 587 612 607 652 607 678 691 691

* Please consult us for application at dc voltages & higher operational voltage upto 690V AC.
** Icw values are indicated based on thermal considerations. While selecting a breaker please ensure that Icw requirement for the application is not more than
Ics / Icu at the point of installation.

Electrical life = Mechanical life. However, arcing contacts need to be replaced depending upon wear & tear.
? Please consult us.

4-9
Technical Data Sheet - HE Range

Rating (A) 1250 2000 3200 5000

Type Designation HE HE HE HE

Rated current (A) at 50°C In 800 1250 2000 3200

Rated operational voltage (V), 50/60Hz Ue* 415 415 415 415

Rated insulation voltage (V), 50/60Hz Ui 1000 1000 1000 1000

No. of poles 3/4 3/4 3/4 3/4

Rated ultimate short circuit breaking 380/415/500V 50 60 75 95


Icu
capacity 50/60Hz (kA rms) ?
690V 35 40 65

Rated service short circuit breaking 380/415/500V 50 60 75 95


Ics
capacity 50/60Hz (kA rms) ?
690V 35 40 65

0.5 sec 50 60 75 95
Rated short time
**
withstand capacity Icw 1 sec 50 60 75 95
50/60Hz (kA rms)
3 sec - - - ?

380/415/500V 105 132 165 209


Rated making capacity Icm
50/60Hz (kA peak) 690V - 84 143 ?

Rated impulse withstand voltage Uimp 12 12 12 12


of main circuit (kV)
Rated impulse withstand voltage Uimp 4 4 4 4
of aux. circuit (kV)

Typical opening time (ms) 40 40 40 40

Typical closing time (ms) 60 60 60 60

Utilization category B B B B

Suitability for isolation ? ? ? ?

Fixed ? ? x x

Draw out ? ? ? ?

Manual ? ? ? ?

Electrical ? ? ? ?

Electrical & Mechanical life (operating cycles) 20000 20000 10000 5000

Electrical life without maintenance 7000 5000 5000 2500

Dimensions (in mm) Fixed H 394 394 - -

3 Pole 326 4
8
2 - -
W
4 Pole 414 6
2
8 - -

D 431 4
3
1 - -

Draw out H 468 468 468 583

3 Pole 399 555 701 913


W
4 Pole 487 701 909 1182

D 587 587 607 691

* Please consult us for application at dc voltages & higher operational voltage upto 690V AC.
** Icw values are indicated based on thermal considerations. While selecting a breaker please ensure that Icw requirement for the application is not more than
Ics / Icu at the point of installation.

Electrical life = Mechanical life. However, arcing contacts need to be replaced depending upon wear & tear.
? Please consult us.
4-10
Technical Data Sheet - G Range

Rating (A) 400 630 800 1000 1250 1600 2000

Type Designation G G G G G G G

Rated current (A) at 50°C In 400 630 800 1000 1250 1600 2000

Rated operational voltage (V), 50/60Hz Ue 415 415 415 415 415 415 415

Rated insulation voltage (V), 50/60Hz Ui 1000 1000 1000 1000 1000 1000 1000

No. of poles 3 3 3 3 3 3 3

Rated ultimate short circuit breaking Icu 415V 50 50 50 50 50 50 50


capacity 50/60Hz (kA rms)

Rated service short circuit breaking Ics 50


415V 50 50 50 50 50 50
capacity 50/60Hz (kA rms)

Rated short time


withstand capacity 1 sec 50 50 50 50 50 50 50
50/60Hz (kA rms) Icw**

Rated making capacity


50/60Hz (kA peak) Icm 415V 105 105 105 105 105 105 105

Rated impulse withstand voltage Uimp 12


12 12 12 12 12 12
of main circuit (kV)
Rated impulse withstand voltage Uimp 4 4 4 4 4 4 4
of aux. circuit (kV)

Typical opening time (ms) 40 40 40 40 40 40 40

Typical closing time (ms) 60 60 60 60 60 60 60

Utilization category B B B B B B B

Suitability for isolation ???????

Fixed ???????

Manual ???????

Electrical & Mechanical life (operating cycles) 20000 20000 20000 20000 20000 20000 20000

Electrical life without maintenance 8000 8000 8000 8000 7000 6000 4500

Fixed H 394 394 394 394 394 394 394


Dimensions (in mm) 326 326
W 3 Pole 326 326 326 326 326

D 443 443 443 443 443 431 431

** Icw values are indicated based on thermal considerations. While selecting a breaker please ensure that Icw requirement for the application is not more than
Ics / Icu at the point of installation.

Electrical life = Mechanical life. However, arcing contacts need to be replaced depending upon wear & tear.

4-11
Range

Breaking capacities:
Icu = Ics = Icw
Rated Current 400A 630A 800A 1000A 1250A 1600A 2000A 2500A 3200A 4000A 5000A 6300A
CN-CS : E 50kA 50kA 50kA 50kA 50kA 50kA 50kA
Frame-1

CN-CS : G 50kA 50kA 50kA 50kA 50kA 50kA 50kA


Frame-1

CN-CS : S1 50kA 50kA 50kA 50kA 50kA 50kA 50kA 60kA 60kA

Frame-1 Frame-2

CN-CS : C 50kA 50kA 50kA 50kA 55kA 60kA 95kA 95kA

CN-CS : H 65kA 65kA 65kA 65kA 75kA 75kA


CN-CS : H2 75kA 75kA

CN-CS : H/H1 100kA 100kA


CN-CS : HE 50kA 60kA 75kA 95kA

Frame-1 Frame-2 Frame-3 Frame-4

4-12
CAUTION
SPRING UNDER TENSION.
PERSONAL INJURY
MAY BE CAUSED

ELECTRICAL HAZARD
BEWARE OF
ELECTRICAL SHOCK,
PERSONAL INJURY OR
SCALDING BURN
MAY BE CAUSED

CAUTION
WEAR PERSONAL
PROTECTIVE EQUIPMENT
WHILE CONNECTING
OR DISCONNECTING

4-13
5. OPERATION
OPERATION
5.1 MANUALLY OPERATED BREAKERS:
5.1.1 OPERATION FOR G/S1/C/H/HE/D - RANGE BREAKER

(Except 5000/6300-4P version)


TRIP / RESET Push Button Speed of closing is independent of the speed
ON - OFF Indicator 1 of handle movement.
ACB closes in single stroke operation of the
handle.
SET

3
5 Operating sequence of manual breakers:-
- RE

Initially breaker is OFF.


P
TR I

2
1. For carrying out any operation, the
breaker-operating handle has to be
pulled out fully by holding its top portion.
Front View Side View
e
2. For extra leverage, the handle can be
Clos
4 telescoped lengthwise (recommended).
RESETTING: 0
Fig. 5-1 3. Rotate the operating handle by 90 in
anti-clockwise direction (till it becomes
horizontal). The breaker will trip at the
beginning of the resetting operation, if it
is in closed condition.
CLOSING : 0
4. Rotate the operating handle by 90 in
clockwise direction (till it becomes
vertical to close the ACB).
OFF 5. After completing the operation ensure
that the handle is placed back in the
cavity on the front facia.
An indicator provided on front facia (refer
Fig. 5-1) shows the position of the main contacts.
- RED / ON : ‘CLOSED’
Fig. 5-2
- GREEN / OFF : ‘OPEN’
0
Operating Handle (refer Fig. 5-2) can occupy either of the two distinct position spaced 90 apart.
- Horizontal Position : ‘OPEN- RESET’
- Vertical Position : ‘CLOSED’ or ’TRIPPED’

The sequence of operation is


RESET ? CLOSE ? OPEN
Caution :
Resetting the ACB in ‘ON’ condition will
cause the ACB to trip.

Precaution :
Ensure presence of supply voltage to
undervoltage release (if fitted) before
ON
closing the ACB.

In case of manual reset type ACB actuation


of TRIP push button / key of lockable trip
push button, resets the tripping
Fig. 5-3 mechanism of ACB.
5-1
TRIP
OPENING THE CIRCUIT BREAKER :

The breaker can be opened by the following


means :

LOCALLY (Manually) :

ON
1. Press the TRIP push button.
OR
2. Press key of lockable trip push button
(when provided).
Fig. 5-4

3. Rotate key of racking interlock for draw


out breakers (if provided) when the
breaker is in any position between
‘Service’ and ‘Test’.
OFF

Indicate with key

Fig. 5-5

4. Operate handle anti-clockwise.

REMOTELY (Electrically) :
OFF

1. Through shunt release.

2. Through under voltage release.


(Refer section 9: Accessories)
Fig. 5-6

Note: For operation of 5000/6300-4P version of manual ACB refer manual charging (clause 5.2 in page 5-4)
and for closing & opening the circuit breaker (page no. 5-5).

5-2
OPERATION
5.1.2 OPERATION FOR E - RANGE BREAKER

TRIP / RESET Push Button

ON - OFF Indicator
Speed of closing is independent of the speed
of handle movement.
ACB closes in single stroke operation of the handle.
SET

3
- RE

Initially breaker is OFF.


P
TR I

The sequence of operation is


RESET ? CLOSE ? OPEN
Front View
e
Clos
4

Fig. 5-7

0
Operating Handle (refer Fig. 5-7) can occupy either of the two distinct position spaced 90 apart.
- Horizontal Position : ‘OPEN - RESET’
- Vertical Position : ‘CLOSED’ or ’TRIPPED’
An indicator provided on control box (refer Fig. 5-7) shows the position of the main contacts.
- RED / ON : ‘CLOSED’
- GREEN / OFF : ‘OPEN’

Operating sequence of manual breakers:-


RESETTING :
0
Rotate the operating handle by 90 in anti-clockwise direction (till it becomes horizontal).
The breaker will trip at the beginning of the resetting operation, if it is in closed condition.

CLOSING :
0
Rotate the operating handle by 90 in clockwise direction (till it becomes vertical to close the ACB).
Presence of supply voltage is essential to close a breaker fitted with under voltage release.

OPENING :
The breaker can be tripped by the following means:
Local : a) By pressing the red ‘TRIP’ button (refer Fig. 5-7)
b) Key of lockable trip push button (when provided)

Remote : Through Voltmetric release (refer Section 9: Accessories)


The tripping push button also serves to reset the over-current and short circuit release if the breaker
is fitted with local resetting feature. Resetting of the manual breaker by handle will not reset O/L-S/C
release in such case.

Caution :
Resetting the ACB in ‘ON’ condition will cause the ACB to trip.

5-3
5.2 ELECTRICALLY OPERATED CIRCUIT BREAKER :
OPERATION FOR C/S1/H/HE/D - RANGE BREAKER
Initially breaker is OFF and spring is
‘TRIP / RESET’ Push Button
‘CLOSING’ Push Button
discharged.
Spring condition is indicated by a
mechanical indicator visible through a
transparent window on the front facia.

Indicator display Spring condition


YELLOW CHARGED
25 0 ON - OFF Indicator
Side View BLACK DISCHARGED
Spring Charged / Discharged Indicator
Front View
Charging Handle The spring in the circuit breaker operating
mechanism must be charged to store the
energy required to close the main contacts.
Fig. 5-8
The spring may be charged manually using
the charging handle or automatically by the
motor.

Electrical Charging :
The spring is automatically charged &
automatically recharged after each closing
operation. (Provided there is a continuous
supply to the motor)

ON

Manual Charging :
In case of power failure, charge the main
spring through multiple strokes of charging
handle. The handle has to pulled outward by
gripping its top portion.
Fig. 5-9

0
Charge by giving small strokes (25 ) as shown in Fig. 5-8 in the clockwise direction till indicator display
shows a spring charged condition (yellow colour).

Now the breaker is OFF and spring is charged.

5-4
CLOSING THE CIRCUIT BREAKER :

(Ensure precautions before closing same as


manual ACBs.)

Breaker is OFF and spring is charged.


ON
LOCALLY (Manually):
Press ON push button.

Fig. 5-10
REMOTELY (Electrically):
The closing electromagnet, when actuated,
discharges the spring and closes the
breaker.

OPENING :

The methods of opening are the same as those for manually operated breakers (except method ‘4’ of
local opening).

5.3 OPERATIONAL FEATURES

5.3.1 ANTI-PUMPING :

After a close - open cycle, it is not possible to reclose the breaker (for electrically operated breakers) if
the closing command is maintained. This feature known as anti-pumping, is assured mechanically,
both in local and remote control operation. This feature prevents auto reclosure of breaker on fault. For
reclosing the breaker, the permanent closing command should be momentarily interrupted. For Electrical
anti-pumping refer page no.8-19.

5.3.2 TRIP FREE MECHANICAL SWITCHING :

(Both for manually and electrically operated breakers)


The moving contacts of the breaker return and remain in open position, when the opening operation is
initiated after initiation of closing command. In this case the closing command is overruled by the
tripping command.

5-5
6. RACKING
Circuit breaker positions
The indicator on the front, shows the position of the circuit breaker in the cradle.
Service position : In service position both power and control circuits are connected.

Panel door

ON
SERVICE

Fig. 6-1
Panel door facia have to be aligned

Test position : In test position power circuit is open ensuring full safety, while control circuit is
connected for checking accessories as well as breaker operation.

Panel door

OFF

TEST

Fig. 6-2

Isolated position : In isolated position both power and control circuits are disconnected from
supply to ensure complete isolation.

Panel door

OFF
ISOLATED

Fig. 6-3
6-1
PROCEDURE :
Racking OUT / IN
1. Racking operation must be done with the
aid of racking handle, provided in racking
SERVICE handle storage location.

2. Insert the racking handle in the racking


1
slot.

2 3. Rotate the racking handle in clockwise


direction to rack in and in anti clockwise
direction to rack out.

Fig. 6-4 (i)


4. Ensure the breaker is in SERVICE position
and remove the racking handle from the
racking slot.

5. After completion of racking operation


ensure that the racking handle is kept in
Rack in
its correct storage location.

Caution :
Fig. 6-4 (ii) Open the circuit breaker before racking
3 Rack out
IN / OUT.

Note :
SERVICE
I. If the panel door is open, keep the door
interlock pin pressed during racking.
5 II. If racking interlock is provided press the
key inwards and turn it clockwise before
racking.
4

Fig. 6-4 (iii)

Note: If the breaker is inserted or withdrawn with it’s main contacts in closed position, then a device
automatically trips the breaker before separation of the main isolating contacts(during withdrawal)
or before they come into contact (during insertion). The same device prevents the closing of the
breaker at one particular location between the position ’Test’ and ‘Service’.

When racking interlock provided, the key of the lock has to be pressed and turned anti-clockwise (this
will trips the breaker if it is in closed condition at any location between the positions ‘Test’ and ‘Service’)
before initiation of the racking operation, otherwise it will not be possible to rack the breaker in or out.
If the cradle is provided with door interlock, ensure that either the door is closed or interlock is defeated
while attempting racking. 6-2
7. INSTALLATION
7.1 INSTALLATION AMBIENT
Install the ACB in dry, dust free, non-corrosive ambience without subjecting it to abnormal shocks / vibrations.
If the above is not possible, provide adequate degree of protection.
For Atmospheres having Harsh Environments (Sulphur Rich), it is recommended to use C-Power “HE”
range of Air Circuit Breakers.
Refer to Section 12 for the following information.
- Overall dimensions
- Mounting details
- Panel door cut-out and bezel fixing
- Terminal connections
- Fixing of door interlock components on the panel door (provided in a polyethylene bag). For fixing door
interlock components on the cradle (provided in another polyethylene bag),please refer to Section 9.
7.2 INSTALLING A FIXED BREAKER
7.2.1 MOUNTING
• Mount the breaker on the side brackets with the aid of 4 bolts of M8 or M10 (Refer to item No. 1 in
Fig. 7-1). For further details refer the section 12.
Metallic components (if exist) Metallic components (if exist)

Insulating Screen Insulating Screen


200

200
min

min
100

100
min

min

100 100
max max
First fixed Support First fixed Support
1
200

200
min

min

Panel Structure

G/S1/C/H/HE/D-Range breaker E-Range breaker


NOTE: Dimensions are in mm

Fig. 7-1 FIXED ACB - METHOD OF MOUNTING

• Insert spacers, if necessary, to prevent deformation during tightening.


• To facilitate normal maintenance, following clearances are required to be maintained
- 140 mm above the breaker to replace arc chutes.
- 200 mm above the breaker to replace arcing contacts.
- 200 mm below the breaker to replace voltmetric releases.
- 50 mm on either side of the breaker (150 mm on left side in case of breaker with mechanical
interlock).
Clearance distance - a safety requirement :
- It is essential to maintain a minimum clearance of 100 mm above the breaker for permitting
expansion/dispersion of the gases emanating from the arc chutes.
- The metallic components, if exist, should be placed at a minimum distance of 200 mm above the
arc chutes.
- If there are metallic components between 100 mm and 200 mm, then an insulating screen should
be placed at a distance of 100 mm minimum above the arc chutes.
7-1
7.2.2 CONNECTIONS
7.2.2.1 MAIN CIRCUIT
• Clean the terminals and links by using cheese cloth. Do not damage plating.
• Use links as per the recommendations given in IS/IEC: 60947 (Part 1).
• Support these links to guard against electrodynamic forces during short circuit.
• Ensure that the first set of fixed supports (fixing the conductor rigidly through an insulating support to
panel structure) is fixed at a distance 100 mm (as shown in fig. 7-1) so that stresses induced during
short circuit do not exceed elastic limit of the link material.
• Ensure that the links are terminated with right size of bolts, tightened to appropriate torque by using
proper plain and spring washers.
Refer clause 12.4 for additional information on good termination practices.

Torque (kgf-m)
Bolt size Bolt dia (mm)
Standard High-tensile
M8 8 0.85 2.5
M10 10 1.88 4.7
M12 12 3.2 7.8

7.2.2.2 AUXILIARY CIRCUIT


• Auxiliary terminals for control circuit connections are located on the rear top cross-piece of the breaker.
• Max. 24 nos.
• Rated for 16A at 500 V.
• Accommodates flexible cable upto 2.5 mm2.
• Unless otherwise specified by the customer, connections are to be made with PVC insulated 1.5 mm2
copper wire conforming to IS: 694.
• Refer to Sec. 13 for internal wiring.
• The fuse ratings to be provided for the protection of accessories (voltmetric releases, charging motor
and the closing electromagnet) must be based on their power consumption (indicated in Sec. 9 -
Accessories).

7.2.2.3 EARTHING
• The earthing location is in the rear bottom corner of the right side plate of the breaker marked with
symbol. (Please refer drawing in section 12)
• Clean and degrease the unpainted surface of the earthing connection.
• Use M6 screw for connecting earth bar.

7.2.3 ARRANGEMENT OF CUBICLE DOOR


• Provide a cut-out in the cubicle door for breaker front facia projection
• Refer to Sec. 12 for location of the door cut-out with respect to door hinges (right or left) and fixing the
bezel on the door.

7-2
7.3 INSTALLING A DRAWOUT BREAKER
7.3.1 MOUNTING
• Holes are provided on horizontal surface for mounting the cradle (for mounting refer the clause 12.2.1
& 12.2.2 in Section 12).
• Insert spacers, if necessary, to prevent deformation of the cradle during tightening. To ensure proper
dust proofing, maintain the distance of 8.9 mm between the inner side of the cubicle door and the
outer surface of the interlock support .
• No extra space is required to be provided in the cubicle for maintenance. The breaker can be
maintained fully by drawing it out to a ‘Maintenance’ position (telescopic rails fully stretched)
• In case of breaker with mechanical interlocking leave minimum of 150 mm space on the left side of
the ACB for clutch cable routing.
• Clearance distance - a safety requirement :
Follow the same instructions as mentioned for ‘Installing a fixed breaker’ (clause 7.2.1)

7.3.2 CONNECTIONS
7.3.2.1 MAIN CIRCUIT
• Remove the nut plates fixed to the terminals.
• Use the nut plates for making connection to the terminals.
• Follow the same instructions as mentioned for ‘Installing a fixed breaker’.

7.3.2.2 AUXILIARY CIRCUIT


• Secondary Isolating contacts (SICs) meant for control circuit connections are located on cradle &
breaker (Refer to Sec. 4 - Identification)
• Maximum 24 SICs are available for Electrical D/O and 18 SICs for Manual D/O (standard ACBs).
• Each SIC terminal can accommodate two lugs suitable for crimping with 1.5 mm2 flexible cable.
• Rated for 16A at 500 V.
• Unless otherwise specified by the customer, internal connections are made with PVC insulated
1.5 mm2 copper wire conforming to IS: 694.
• The SIC terminals on the breaker and the cradle are arranged in a precise order (refer. to wiring
diagrams in Sec. 13) to facilitate interchangeability between breaker of same specification.
• Different electrical connection for ‘Test’ & ‘Service’ position of the breakers are possible by adopting
the procedure mentioned as follows.

Procedure for having different electrical connections in ‘Test’ and ‘Service’ positions.

Terminal

• Remove fixed SIC block by removing fixing


screws
•Decrimp the terminal which needs to be
removed
•Break at neck of the terminal
Connection

7-3
The standard secondary isolating contact block comprising totally 6 sets of terminals, has two ‘through’
terminals. These ‘through’ terminals are necessary for electrical breakers to give electric supply to the
charging motor in ‘Test’ and ‘Service’ positions (terminals C and D on wiring diagram in Section 13).

Please do not forget to wire the microswitch C6 in ‘Service’ position (refer to Section 13) for electrical
breakers.
• The microswitches in ‘Service’, ‘Test’ or ‘Isolated’ position are designed to take wires with snap on
cable lugs.
• Two covers are provided on the cradle at SIC outgoing side. These covers protect the auxiliary
circuit wire from accidental trapping with the moving part while the breaker is being racked in or
racked out.

• The wiring of the position microswitches should pass between


the rear-end of telescopic rail and the cradle terminal mounting
plate of the cradle before joining the bunch of wires leaving the
secondary isolating contact blocks (as shown in fig. 7-2).

Fig. 7-2

The rating of the fuses to be used for the protection of the accessories (voltmetric releases ,charging
motor and the closing electromagnet) should be based on their power consumption (indicated in
Section 9 - Accessories).

7.3.2.3 EARTHING
•The earthing location is on rear bottom right side of the cradle marked with symbol .
•Clean and degrease the unpainted surface for the earthing connection.
•Connect earthbar of the switchboard / panel to the M10 earthing screw on the cradle.

7-4
8. PROTECTION
8.1 THERMOMAGNETIC RELEASE TYPE DN1
8.1.1 FEATURE
Air circuit breakers are available with multi-tap CT fed over current release system type DN1.
For 4P ACBs with DN1 release and without earth-fault release, multi-tap CT is not provided for Neutral
phase.
The rated secondary current of the CT is 8.75A.

Mechanism of protection is as under :


(I)Three electro-magnets provide protection against short-circuit current. Each electromagnet is
provided with two taps M1 and M2 for selecting operating threshold.
(II)Three bimetallic strips give protection against overloads. These are individually adjustable from
0.75 In to 1.0 In by means of a pointer (2) on the front face of the release (refer to Fig. 8-1).

The release operates through its striker on the main trip latch of the mechanism and is reset by the main
shaft of the circuit breaker at the end of the opening operation for auto reset version.

1 Mechanical Trip Actuator.

2 Point for Adjustment of


Overload Current Setting.

2
Fig. 8-1

In case of breakers with local reset feature, tripping through release leaves the latch of the mechanism
open & hence resetting with the help of the local ‘TRIP/RESET’ or ‘TRIP/LOCK/RESET’ push button is
necessary prior to subsequent closing operation.

The release is provided with a Strip (refer to item no. 1 in Fig. 8-1) for manual tripping. Pressing the strip
downwards will release the mechanical latch of the release and trip the breaker.

The DN1 release incorporates a definite minimum impulsion time of 25 ms on magnetic trip. Trip time is
independent of the magnitude of short circuit current and is achieved by the aid of a fly wheel. This
release has inverse thermal time-current characteristics on overload.

The magnetic threshold of the release depends on the tap of the current transformer chosen. A label is
pasted on the top of the release to indicate the magnetic threshold of the protection system at various
CT taps.

8-1
8.1.2 TIME-CURRENT CHARACTERISTICES OF DN1 RELEASE

10000

1.05
OPERATING LIMITS THERMAL
1.2
1000

100

ZONE OF SHORT CIRCUIT OPERATION (M1/M2)


10
Trip time in seconds

0.4
0.3
M1
0.2
M2
0.1

DN 1

25 ms
TOTAL OPERATING TIME
MIN. IMPULSION TIME
0.01

0.7 1 2 3 4 5 6 7 8 9 10 20 30 40 50 100 400 1000

Multiples of Current

Fig. 8-2

8-2
8.1.3 RELEASE SETTING FOR CN-CS E/G/S1/C/H/D ACBs

TYPE CT CT Setting of Magnetic Thermal Current


DESIGNATION Tap release Setting
(A) (A) (A)

320 1800 * 240 to 300


CN-CS 400 S1/G/E 400
400 2300 * 300 to 400
400 2500 * 300 to 400
CN-CS 630 S1/G/E 630 500 3000 3700 375 to 500
630 3600 4500 472 to 630
400 2700 * 300 to 400
500
500 3200 3900 375 to 500
CN-CS 800 C/H/S1/G/E
640 3900 4900 480 to 640
800
800 4700 6000 600 to 800
800 4700 6000 600 to 800
CN-CS 1000 C/H/S1/G/E 1000
1000 5700 7200 750 to 1000
1000 5700 7200 750 to 1000
CN-CS 1250 C/H/S1/G/E 1250
1200 7000 8900 940 to 1250
1250 7000 8900 940 to 1250
CN-CS 1600 C/H/S1/G/E 1600
1600 8800 11500 1200 to 1600
800 4700 6000 600 to 800
1000 5700 7200 750 to 1000
CN-CS 1600D 1600
1250 7000 8900 940 to 1250
1600 8800 11500 1200 to 1600
1000 5700 7200 750 to 1000
1250
1250 7000 8900 940 to 1250
CN-CS 2000 C/H/S1/G/E
1600 8800 11500 1200 to 1600
2000
2000 11000 14000 1500 to 2000
2000 11000 14000 1500 to 2000
CN-CS 2500 C/H/S1 2500
2500 13500 17000 1875 to 2500
2500 14000 17500 1875 to 2500
CN-CS 3200 H1/H2/S1 3200
3200 17500 22000 2400 to 3200
1600 8500 11500 1200 to 1600
2000
2000 11500 16000 1500 to 2000
CN-CS 3200D 2000 12500 16500 1500 to 2000
3200 2500 14000 18000 1875 to 2500
3200 17000 23000 2400 to 3200
2000 12500 16500 1500 to 2000
2500 14000 18000 1875 to 2500
CN-CS 4000 C/H/H2 4000
3200 17000 23000 2400 to 3200
4000 22000 29000 3000 to 4000
Operating Limits 0.8 to 1.2 of setting 1.05 to 1.2 of setting
* Not recommended.
NOTE : Only one CT per pole can be fitted on the breaker. Request you to choose correct CT
to be mounted in breaker, in case more than one CTs are available for a particular rating. 8-3
8.1.4 TYPES OF PROTECTIONS
Following types of protections can be provided using DN1 release:
• Only overcurrent protection
• Only magnetic protection
• Overcurrent and magnetic protection

8.1.4.1 ONLY OVERCURRENT PROTECTION


T1 M1 T2 M2 T1 M1 T2 M2 T1 M1 T2 M2 S

R Y B CTs

C
Fig. 8-3

When wired as per Fig. 8-3 with points A & C shorted only overcurrent protection (this includes
protection against both over load & short circuit conditions) is provided.

8.1.4.2 PROCEDURE FOR INCORPORATING ONLY MAGNETIC PROTECTION


Connect the current transformer between terminal M1 or M2 and star point S (refer to Fig. 8-4).
The system provides only magnetic protection.

T1 M1 T2 M2 T1 M1 T2 M2 T1 M1 T2 M2 S

C
R Y B
A

Fig. 8-4

8-4
8.2 MICROPROCESSOR BASED RELEASE TYPE SR18 / SR18G
The release SR18/SR18G is a micro-processor based over-current and earth-fault release designed
specifically for breakers. It has three zones of protection in a single unit. The release monitors
and operates on the secondary currents of the current transformer (CT) mounted on the breaker. The
suitable knobs on the facia enable the release to provide a wide range of protection for various applications.

8.2.1 FEATURES
Current Transformer
The release is fed by three single tap current transformers of same
rating as that of the circuit breaker. This current is referred to as
the nominal current (In) throughout this manual. The CT rating on
the secondary side is 750 mA.
The complete list of abbreviations used is given below.

In : Nominal current STD : Short Time delay


Ir : Rated current GFD : Ground Fault delay
LTP : Long Time pick-up LT : Long Time Trip Indicator
GFP : Ground Fault pick-up ST : Short Time Trip Indicator
LTD : Long Time delay GF : Ground Fault Trip Indicator
1 2 3 45 6 7 8 9

1 Current Setting BCD switches. 6 Button to clear previous fault indication.


2 Power ON LED. 7 Connector for External Testing through
SRT-2 Kit.
3 ON/OFF Switch for Thermal Memory.
(Instantaneous ON/OFF, 6&12 In) 8 Query button - for indicating the last
fault.
4 Button to test the SR18G release.
9 LEDS for fault Indication.
5 Time Delay Setting BCD switches.

Type of SETTING RANGE OF SR18/SR18G


Protection PICK-UP CURRENT TIME DELAY

Ir-0.5 to 1.00 times In


Steps : 0.50, 0.60, 0.65, 0.70, 2.5 Sec at 6 times Ir
Long Time
0.75, 0.80, 0.85, 0.90, 0.95, 1.00 Tolerance: ± 10% of current.
Operating Limit: 1.05 to 1.2 times Ir
20 ms to 600 ms.
2 to 10 times In Steps : 20, 60,100,160, 200,
Short Time Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 260, 300, 400, 500, 600 ms.
Tolerance: ± 10% or 20 ms. (whichever is higher)

100 to 400 ms.


Ground 0.2 to 0.6 times In
Steps : 100, 200, 300, 400 ms & OFF
Fault* Steps: 0.2, 0.3, 0.4, 0.5, 0.6
Tolerance: ± 10% or 20 ms. (whichever is higher)

6 and 12 In
Instantaneous
Tolerance: ± 15% of fault current

*Available in SR18G release only. 8-5


Rotary BCD switches are used to adjust setting. Red knob for pick-up currents and blue knobs for
time delays.
Factory Settings are as follows:
LTP =1.0, LTD-2.5s., STP=6, STD=60ms., IP=12, GFP=0.3, GFD=100ms., Thermal Memory = OFF

Short time pick-up, Ground fault pick-up and Ground fault delay have nine, five and five position of
settings respectively. BCD switch arrow placed in between two setting is invalid.

1000
1000

100
100
Trip Time in Sec

10
10
TRIP TIME

11

0.1
0.1
1 1.2 1.5 2 3 4 5 6 7 8 9 10 20
1 Multiples of Rated Current 10
CURRENT MULTIPLE

OVERLOAD CHARACTERISTICS SR18 / 18G


Fig. 8-5
Note : Please change release setting as per your system protection requirement to ensure
effective protection. 8-6
8.2.2 CHARACTERISTIC CURVE
A Typical four zone time-current curve provided by the release is shown in Fig. 8-6

1. Long Time protection zone


Trip time
2. Short Time protection zone
3. Instantaneous protection zone
4 2 4. Ground Fault protection zone
5. Asymptote for Long Time protection

Current

Fig. 8-6

1 1

0.6

0.5

0.4

0.3
0.26

0.2

0.16 )s
(
E
TRIP TIME

IM
T 0.1
0.1
0.1
IP
TRIP TIME

R
T

0.06

0.02

0.01

0.01
0.01 0.1 1 10 100
1 2 3 4 5 6 7 8 9 10 20 100
1 10 100 CURRENT
CURRENTMULTIPLE
MULTIPLES
CURRENT MULTIPLE

SHORT CIRCUIT CHARACTERISTICS SR18 / 18G GROUND FAULT CHARACTERISTICS SR18 / 18G

8-7
8.2.3 CHANGING OF SETTINGS
The settings can be done by changing the knob positions using a suitable screwdriver. Red knobs are used
for setting the pick-up currents, whereas blue knobs are meant for time-delay setting. Settings are on line
changeable but if any of the fault is active than new setting will not be accepted. The position of the knobs
is indicated by the arrow as shown in the figure below. The following examples further clarify this.

EXAMPLE 1 :
Changing long time pick-up (LTP) from 0.95 to 0.5 times In

0.50 0.50
1.00 0.60 1.00 0.60
0.95 0.65 0.95 0.65
Set at 0.95 X In Set at 0.5 X In
0.90 0.70 0.90 0.70
0.85 0.75 0.85 0.75
0.80 0.80

8.2.4 THERMAL MEMORY


When the breaker trips under long-time protection, the cooling time allowed affects the subsequent
trip-time when the breaker is re-energized under fault condition. This feature can be switched off by
the ON/OFF dip switch, provided on the release facia. It is advisable to use a screwdriver to change
the switch position.

8.2.5 TRIP INDICATORS


Three LEDs are used for displaying the type of fault under which the breaker trips. No external
power supply is required for these indicators. The LED corresponding to the fault shows 'red' when
“Query” button is pressed showing the type of fault, which has caused the tripping of the breaker.
This lasts for 72 hrs. max and remains so till it is cleared by 'clear' pushbutton.

Sw1 Sw2 Overload

Short
Sw3 Sw4 Circuit 8.2.6 TEST BUTTON
The test button is used to verify the validation of
Sw5 Sw6 G.F the software internally, checking whether the controller
is healthy or not. When it is pressed the Power-On LED
changes from blinking green (ON state) to steady red.
Inst. However, during the time when the Test button is
pressed all the protections are still alive and none are
Test Clear Query
affected/defeated.

POWER Sw9

8-8
8.3 MICROPROCESSOR BASED RELEASE TYPE SR21i
The release provides the four zones of protection by an electronic circuit with a micro-processor as the
central processing unit.
The four zones of protection are
1) Protection against overload : In Long time zone
2) Protection against short circuit : In Short time zone
3) Protection against short circuit : In Instantaneous zone
4) Protection against earth fault : In Ground fault zone

It trips the breaker through a Flux Shift Device (FSD) which is mounted on the rear bottom side of the
release. The Flux Shift performs the tripping operation through a link connected to the trip rod of the
breaker. The release is reset by the main shaft of the breaker at the end of the opening operation for
auto-reset type ACBs. For ACBs with local reset feature, resetting is done with the help of the local
‘TRIP/RESET’ or ‘TRIP/LOCK/RESET’ Push button.

1 2 3 456 7 8 9

1 Current Setting BCD switches. 6 Button to clear previous fault indication.


2 Power ON LED. 7 Connector for External Testing through
SRT-2 Kit.
3 ON/OFF Switch for Thermal Memory.
8 Query button - for indicating the last
4 Button to test the SR18G release.
fault.
5 Time Delay Setting BCD switches.
9 LEDS for fault Indication.

8.3.1 FEATURES OF THE RELEASE


The release SR21i is a micro-processor based over-current and earth-fault release designed
specifically for C-POWER breakers. It has four zones of protection in a single unit. The release
monitors and operates on the secondary currents of the current transformer (CT) mounted on
the breaker. The setable knobs on the facia enable the release to provide a wide range of
protection for various applications.

Current Transformer
The release is fed by three single tap current transformers of same rating as that of the circuit
breaker. This current is referred to as the nominal current (In) throughout this manual. The CT
rating on the secondary side is 750 mA.
8-9
The complete list of abbreviation used is given below
In : Nominal current STD : Short Time delay
Ir : Rated current GFD : Ground Fault delay
LTP : Long Time Pick-up LT : Long Time Trip
STP : Short Time Pick-up ST : Short Time Trip
Ip : Instantaneous pick-up INS : Instantaneous Trip
GFP : Ground Fault pick-up GF : Ground Fault Trip
LTD : Long Time delay ZSI : Zone Selective Interlocking

Table1 lists the setting range in all four zones of protection. The settings at the time of shipping are
given at the end of the table.

Type of SETTING RANGE OF SR21i


Protection PICK-UP CURRENT TIME DELAY

Ir = 0.5 to 1.00 times In 0.2 to 30 sec. at 6 Ir


Steps: 0.50, 0.60, 0.65, 0.70, 0.75 Steps: 0.2, 0.5, 1, 1.5, 2, 3.5, 6, 12, 17
Long Time
0.80, 0.85, 0.90, 0.95, 1.00 and 30 sec
Operating Limit: 1.05 to 1.2 times Ir Tolerance: ± 10% of current.

20 ms to 600 ms.
2 to 10 times In
Steps: 20, 60, 100, 160, 200, 260, 300,
Short Time Steps: 2, 3, 4, 5, 6, 7, 8, 9 and 10
400, 500 and 600 ms.
Tolerance: ± 10% or 20 ms. (whichever is higher)

Ip = 2 to 16 times In
Steps: 2, 3, 4, 6, 8, 10, 12, 14, 16
Instantaneous
One position as max*
-
Tolerance: ± 15% of fault current

0.2 to 0.6 times In 100 ms to 400 ms.


Ground
Steps: 0.2, 0.3, 0.4, 0.5, 0.6 Steps: 100, 200, 300, 400 ms. & OFF
Fault
Tolerance: ± 10% or 20 ms. (whichever is higher)

* Inst. max. = Inst. OFF . So Positioning the knob to max position will suppress the corresponding
protection.
Setting for all are done by rotary BCD switches having red knob for pick-up currents and blue knobs
for time delays.

Factory Settings:
LTP =1.0, LTD-2s., STP=6, STD=60 ms., Ip=8, GFP=0.3, GFD=100 ms., Thermal Memory = OFF.
Note : Please change release setting as per your system protection requirement to ensure effective
protection.
8-10
8.3.2 CHARACTERISTIC CURVE
A typical four zone time-current curve provided by the release is shown

5
1. Long Time protection zone
2. Short Time protection zone
1
3. Instantaneous protection zone
4. Ground Fault protection zone
Trip time
5. Asymptote for Long Time protection

4 2

Current
Fig. 8-7

The required characteristic curve can be chosen by selecting proper settings. The settings can be
changed as described below.

8.3.3 CHANGING OF SETTINGS


The position of the knobs is indicated by the arrow.

Facia Cut-out cover TRIP Red knobs are used for


has to be removed setting the pick-up currents,
TRIP
to change knob OFF whereas the knobs for
positions. time-delay setting are blue.
OFF

The settings can be made by


changing the knob positions
1
using screw-driver.

0.50 0.50
1.00 0.60 1.00 0.60
0.95 0.65 0.95 0.65
Set at 0.5 x In Set at 0.95 x In
0.90 0.70 0.90 0.70
0.85 0.75 0.85 0.75
0.80 0.80

8-11
8.3.3.1 RANGE OF PROTECTION

LONG TIME PICK-UP : The release rating (Ir) can be selected by the LTP switch from 0.5 times
(50%) to 1.0 times (100%) the rating of the breaker. Table II gives the selected rated current (Ir)
for different positions of the LTP switch for the entire range of breakers.

TABLE II : LONG TIME PICK-UP CURRENT (Ir) FOR VARIOUS SETTINGS (A)

In 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
LTP

0.5 400 500 625 800 1000 1250 1600 2000 2500 3150

0.6 480 600 750 960 1200 1500 1920 2400 3000 3780

0.65 520 650 812 1040 1300 1625 2080 2600 3200 4095

0.7 560 700 875 1120 1400 1750 2240 2800 3500 4410

0.75 600 750 937 1200 1500 1875 2400 3000 3250 4725

0.8 640 800 1000 1280 1600 2000 2560 3200 4000 5040

0.85 680 850 1062 1360 1700 2125 2720 3400 4250 5355

0.9 720 900 1125 1440 1800 2250 2880 3600 4500 5670

0.95 760 950 1187 1520 1900 2375 3040 3800 4750 5985

1 800 1000 1250 1600 2000 2500 3200 4000 5000 6300

10000

8.3.3.2 LONG TIME DELAY


1000
One out of ten possible inverse time-current
characteristics can be selected by choosing
100 the delay at six times the rated current (Ir).
Trip time in sec

10

0.1

0.01
1 1.2 1.5 2 6 10 14 20
Fig. 8-8
Multiples of Set Current 8-12
8.3.3.3 SHORT TIME
The release provides time-delayed protection against short circuit in short protection zone. The
short time pick-up current (STP) can be varied from 2 to 10 times In and the definite delay (STD)
can be set from 20 to 600 ms.

The characteristic curve changes as per Fig. 8-9 given below, as STP & STD are changed.

Trip
time

STD

STP Current

Fig. 8-9

8.3.3.4 INSTANTANEOUS
The release provides instantaneous (with no intentional time delay) protection against short-circuit
in this zone. The instantaneous pick-up current (IP) can be varied from 2 to 16 times In. The
characteristic curve changes with change in IP setting, as shown below in Fig. 8-10. Table III lists
instantaneous pick-up currents for all IP settings for all ratings of breaker.

The Characteristics curve changes with change in IP setting.

In 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Ip

2 1600 2000 2500 3200 4000 5000 6400 8000 10000 12600

3 2400 3000 3750 4800 6000 7500 9600 12000 15000 18900

4 3200 4000 5000 6400 8000 10000 12800 16000 20000 25200

6 4800 6000 7500 9600 12000 15000 19200 24000 30000 37800

8 6400 8000 10000 12800 16000 20000 25600 32000 40000 50400

10 8000 10000 12500 16000 20000 25000 32000 40000 50000 63000

12 9600 12000 15000 19200 24000 30000 38400 48000 60000 75600

14 11200 14000 17500 22400 28000 35000 44800 56000 70000 88200

16 12800 16000 20000 25600 32000 40000 51200 64000 80000 100800

Instantaneous can be switched off by putting the IP switch to the position marked ‘MAX’.

8-13
CHARACTERISTIC CURVE

2
MAX 3

16 4
Trip
time 14 6

12 8
10

Knob setting position for ground fault


IP Current protection switched off

8.3.3.5 GROUND FAULT


In this zone, the release provides time delayed protection against earth fault. The ground fault
pick-up (GFP) can be set from 0.2 to 0.6 time In. The delay (GFD) is settable from 100 to 400 ms
in four equal steps. Table IV lists the ground fault pick-up currents for all ratings of ACB for various
settings of GFP.

In 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
GFP

0.2 160 200 250 320 400 500 640 800 1000 1260

0.3 240 300 375 480 600 750 960 1200 1500 1890

0.4 320 400 500 640 800 1000 1280 1600 2000 2520

0.5 400 500 625 800 1000 1250 1600 2000 2500 3150

0.6 480 600 750 960 1200 1500 1920 2400 3000 3780

The ground fault protection can be switched off by putting the GFD switch to the position marked
‘OFF’.

8-14
The characteristic curve change in GFP & GFD, as shown below in Fig. 8-11

Ground Fault Protection


10
100

OFF 200

1 Trip
time
400 300
Trip time in sec

GRD
Knob setting position for ground
0.1
fault protection switched off
GFP Current

0.01
0.1 0.2 06 X In
Fig. 8-11
Multiples of Rated Current
Ground Fault
8.3.4 THERMAL MEMORY (For SR18/ SR18G/ SR18G with Display/ SR18Gi with Display/ SR21i/ SR71)
Every time electrical power system is overloaded, there are thermal stresses induced in the system. Thermal
stresses caused by repetitive overload faults, can damage the insulation material used in power system, if
the threshold temperature is exceeded (Threshold temperature is the maximum operating temperature). The
thermal memory feature releases record the thermal stresses induced in the system. This thermal
memory ensures reduced tripping time in case of subsequent overload faults. Hot/Cold curves take into
account integrated heating effects to offer closer protection to the system.

Temperature at subsequent
fault (incase of release
without Thermal memory)
1200C
Threshold Temperature at 1st fault
Temperature
of insulation 950C 1050C

Temperature
Temperature

At Subsequent fault
600C (in case of release)
Normal
operating temperature

‘X’ sec <‘X’ sec

Normal 1st Fault 2nd Fault

Intelligent Microprocessor Based Release

Fig. 8-12
8-15
If time delay for overload protection is set at ‘x’ sec, then a release without thermal memory trips the ACB in
‘x’ sec each time an overload fault occurs, even if it is of a repetitive nature. Line for threshold temperature
of insulation depicts such a case, where temperature overshoots threshold temperature, causing damage
to the insulation.

However, protection releases in ACBs are intelligent to detect a repetitive fault. Here, thermal
memory takes into account the stresses caused due to the previous thermal fault resulting in faster
tripping (< ‘x’ sec in this case) of the release, and hence temperature rise is limited to a lower and safer
level.

8.3.5 ZONE SELECTIVE INTERLOCKING (ZSI)


Zone selective interlocking enables faster clearance of faults thereby reducing the thermal and
dynamic stresses produced. This minimizes the damage to the system, thus enhancing the useful
life available to the users.

A 300 ms

*Breaker opening B 200 ms C 200 ms


time additional
Y

D 100 ms E 100 ms

Fig. 8-13

Single line diagram for ZSI

A, B, C, D and E are ACBs with intelligent releases having zone selective interlocking & are connected
in cascade as shown by dotted line. Short time delays are as indicated to achieve time based
discrimination between upstream & downstream breakers.

When a fault occurs in zone ‘Z’, breaker ‘E’ trips after a delay of 100ms*, and breaker ‘C’ and ‘A’ follow
delays of 200ms* and 300ms*, respectively, if required. But in case of a fault at ‘Y’, breaker ‘C’ trips
after a delay of 60ms* (a default value), instead of 200ms*. Thus saving your system of seeing the
fault for another 140ms. Similarly a fault in zone ‘X’ results in breaker ‘A’ tripping after a delay of 60ms*,
thus achieving intelligent discrimination.

8-16
8.3.6 TESTING
Release SR18/SR18G/SR21i can be tested for its functions using test-kit type SRT-2. The release
should be tested with the breaker in isolated or test position. The releases should never be tested
when the breaker is carrying current.

TEST KIT SRT-2 The test-kit simulates setable phase (Long time, short and
Instantaneous) and ground fault conditions which can be
injected to the release through the TEST connector provided
on the front facia of the release. The release can be tested for
its characteristics by applying this input.

Test-Kit can simulate the following fault currents,


For phase fault : 2.5, 4.5, 6.5, 9.5, 11 and 13 times In.
For ground fault : 0.25, 0.35, 0.45, 0.55 times In.

8.3.6.1 PHASE FAULT TEST PROCEDURE

The release can be tested for Long time, Short time and
Instantaneous zone of protection in the following manner,
I. Connect the 9-pin D-sub connecter in the test-kit to
TEST socket on the release.
II. Connect the power supply of the kit to 240 V, 50 Hz
supply. Ignore the reading shown on the LED time
indicator of the test-kit.
III. Select a suitable test-current from the left-side current
setting knob of the test-kit.

EXAMPLE :
If the release is set for LTP = 0.5, STP = 6, IP = 8 then,
test current 2.5 x In will trip the release in Long time.
However for test current of 4.5 or 6.5 x In, the release
will trip in short time, and for all other current it will trip
instantaneously.

IV. Start test by setting the 3-postion TEST switch on the test-kit to PHASE FAULT side. The display on
the kit will reset to zero and start counting till tripping takes place. After tripping the input to the
release is automatically cut-off and display shows the trip time.

V. Test-current can be changed and the release can be re-tested be changing the TEST switch position
to OFF position and then setting it back to PHASE fault.

8-17
8.3.6.2.GROUND FAULT TEST PROCEDURE
The release can be tested for ground fault in a similar way by first selecting the appropriate ground
fault test current and setting the 3-POSITION test switch to GROUND FAULT position.

Power supply unit test need not be conducted if the POWER LED on the release facia keeps on
blinking when the breaker is carrying more than 15-20% of the nominal current.

I. Disconnect the D-Sub connecter from the release TEST socket.


II. Remove the CT connector from the rear side of the release. (MUST BE PUT BACK TIGHTLY
AFTER THE TEST IS OVER)
III. Connect the 9-pin shrouded connecter of the test-kit at the CT connector of the release.
IV. Set the 3-way sliding switch (given at the back-side of the kit) to any of the R, Y, or B phase.
V. Set the Ground Fault pick-up value of the release to 0.4 x In and delay as 400ms.
VI. Pass single phase current by pressing the TEST switch of the kit given at the back. The time
display goes blank when current is passed. The release will reset the status indicators to black
position and will trip in Ground Fault. This test can be repeated for the other phases by changing
the slide-switch position.
VII. Remove the shrouded connector from the release and put the CT connector firmly in its place.

8.3.7 SALIENT POINT


1. The release operates from CT currents only. It uses special CTs which have 750mA secondary
current.
2. In normal operating mode,
a) None of the LEDs will glow, when current is carried by the breaker.
b) The POWER ON LED blinks of the low frequency. When current through the breaker exceeds
the rated current (Ir), the blinking becomes faster indicating overload condition.
c) LED can be reset by pressing the clear push button.
d) POWER ON LED will start blinking only when breaker starts carrying a minimum current of
15% of In.
3. In case of a fault,
a) Respective LED will glow only after pressing the query push button. For example, if the
breaker trips in short time, then that particular short time LED will glow only after pressing
query push button.
b) The breaker gets automatically reset after tripping in case of an ‘Auto Reset’ type of breaker.
For a ‘Local Reset’ type of breaker the Trip/Reset push - button needs to be pressed for
resetting. Respective fault LED will glow.

CAUTION :
No or loose connection will result in CT secondary remaining open, which creates very high
voltage when the breaker carries current, possibly damaging the CT and the release.

8-18
8.4 ELECTRICAL ANTI-PUMPING
When a closing command is given, closing coil of the circuit breaker gets supply through
a normally closed (NC) contact of the anti-pumping contactor. The closing coil is energized
and the breaker closes. The auxiliary contact Q1 of the breaker closes. This energizes the
coil K1 of the anti-pumping contactor and the contactor picks up. This opens its normally
closed (NC) contact in series with the closing coil breaking the persistent closing command.
In order to close the circuit breaker again, the closing coil circuit will have to be reset, which
will happen only after the anti-pumping contactor drops off. The contactor will drop off only
when the closing command is removed. This ensures that once the breaker has closed and
tripped on fault the breaker can close again only after the first closing command is removed
and a fresh closing command is given, thus providing anti-pumping. The anti-pumping
contactor should be selected in accordance with the rating of the closing coil.

C
Closing
Command
K1
(

Service
Spring Charging
C6 Breaker Limit Switch
Q1 Contact K1
Test
F H

A
ECD
(

Spring Charging
Anti-pumping Motor
CC
Closing K1 Contactor
Coil
E
(

ELECTRICAL ANTI-PUMPING

Fig. 8-14

8-19
9. ACCESSORIES
9.1.1 SHUNT RELEASE :

Remote tripping of the circuit breaker can be accomplished by


the aid of shunt release which is offered in two designations viz :

- Type EA for DC application, (65-130% of rated voltage)


-Type EA1 for AC application (10-130% of rated voltage)
Shunt release coil is short time rated and is disconnected from
the circuit by an auxiliary contact (CA-1) when the ACB is in
open condition.

9.1.2 UNDERVOLTAGE RELEASE :

This release permits closing of breaker contacts if the voltage is


above 80% of the nominal voltage and trips the breaker if the
voltage falls below 35% of the nominal voltage.

- Type MV - with no intentional time delay


- Type MVR - with a fixed time delay of 3±1.5 sec.

When U/V release is provided, the ACB can be closed only when
supply is available to the U/V release.
9.1.3 AUXILIARY CONTACT :

Auxiliary contacts are offered in following combinations :

2 NO + 2 NC
6 NO + 6 NC

Note :Number of aux. contacts available to customers may


be less than actual, as some aux. contacts may be
used for internal wiring purpose.

9.1.4 SECONDARY ISOLATING CONTACTS (SIC) :

•Self aligned, spring loaded, fully drawout type


•Required for control circuit connections
•Maximum four blocks, each of six contacts
•The contacts are rated at 16A, 500V AC

Note : Refer clause 9.8.7 for technical data.


Refer clause 13.1for detail wiring diagram.
9-1
9.1.5 SPRING CHARGING MOTOR :

Electrical charging of the main spring can be achieved by using


motor.
- Offered both in AC and DC rating
- Spring charging time: 7 sec (approx.)
- For 415V application, use a 415V/240V transformer rated for
500 VA
- For DC control applications, the circuit must be wired for
double isolation if AC control to DC control conversion is done.

Note : Providing continuous supply to the motor would ensure that the main spring gets charged
after ‘Close’ operation and is ready for the next operation.

9.1.6 CLOSING ELECTROMAGNET :

Closing electromagnet actuates the closing of electrical breaker,


by discharging main spring.

- Offered both in AC and DC rating


- Coil of the closing electromagnet is continuously rated
- In case of DC closing electromagnet, economy resistors* is
used in series with closing electromagnet.

*Refer technical data for resistor details.

9.1.7 AN 1 - ANNUNCIATOR MODULE :


• Individual fault annunciation by LEDs for
- Long time fault
- Short time/Instantaneous fault
- Ground fault
• Can be used with release type SR18/ SR18G/ SR18G with
Display/ SR18Gi with Display & SR21i
• One potential free contact rated 5 A at 230V AC available for
each type of fault
• Flush mounting on panel
• Operating voltage : 240V AC / 110V DC. Other voltages
available on request
• Dimension of A1 module = 96mm x 48mm x 114mm (HxWxD)
• Door cut out dimension = 92mm x 46mm

Note : Refer clause 9.8.7 for technical data


Refer clause 13.1for detail wiring diagram.
9-2
9.1.8 OPERATION COUNTER :

Displays total number of breaker operating cycles and is


mechanically operated.

9.2 FAULT TRIPPING INDICATION ON OVERLOAD & SHORT CIRCUIT :


ACB tripping indication provided with one change-over contact
available for the following :

Common indication for tripping through protection units

• Provided by microswitch C1 fitted in the ACB


• Available for release type DN1/SR18/SR18G/SR18G with
Display/ SR18Gi with display/SR21i/SR71 as an option.

View of the mechanism from front Separate indication for tripping due to overload and short
circuit faults
• Provided for release type DN1 by microswitch C1 fitted inside
the ACB and microswitch C2 fitted inside release

Separate indication for tripping due to overload, short circuit


& earth faults
• Available for releases type SR18/SR18G/SR18G with Display/
SR18Gi with display/SR21i, provided by AN1 annunciator module
to be separately mounted on the panel for remote fault annunciation
• Provided by LEDs in SR71/SR18/SR18G/SR21i releases, for
local annunciation
View of DN1 release without cover
Refer clause 12.2.5 for schematic arrangements of fault indication.

9-3
9.3 FAULT TRIPPING INDICATION ON VOLTMETRIC RELEASES

MICROSWITCH

Indication for shunt release operation

• Provided by microswitch C5 fitted on the shunt release

Indication for undervoltage release operation

• Provided by microswitch C3 fitted on the undervoltage release

Note :
This microswitch can be used for an indication system or any
other transducer viz. electrical interlocks, alarm, etc.

9.4 MICROSWITCHES FOR INDICATING POSITION OF THE BREAKER ON THE CRADLE


C8 C6 C7
C9
• Electrical indication available through microswitches
• Two microswitches with one changeover contact for
I) Test or Isolated position (C8 & C9)
II) Service (C6 & C7)

• In case of an electrical ACB, a service position microswitch


is fitted on the left side as a standard. This can be used to
prevent remote closing of ACB in ‘Test’ & ‘Isolated’ positions
View of cradle from front

9.5 RACKING INTERLOCK

• Before initiation of racking operation, the key of the lock is


to be pressed and turned anticlockwise. Otherwise the
racking operation gets mechanically prevented
• In case the breaker is in closed condition, pressing of the
key trips the breaker between the Service and Test
Door Racking Locking in positions.
Interlock Interlock ‘Isolated’ Position
• The key remains trapped in the lock when not pressed
View of the cradle and this makes it suitable for interlocking.

Note : Refer clause 9.8.7 for technical data.


9-4
9.6 PADLOCKING IN ANY POSITION

To padlock the breaker pull the padlock cover and insert


shackle of the padlock into the cover and lock the breaker
to prevent racking operation.
When the padlock cover pulled to insert shackle of the
lock, the spring-loaded pin attached to padlock cover
interferes with the screw and hence the racking screw
cannot be turned. The breaker cannot be racked.
However, when the padlock removed from cover, the pin
Door Racking Padlocking in is released to its original position and the screw is free to
Interlock Interlock any Position rotate. The breaker can be racked now.
View of the cradle
Maximum 3 nos. of padlocks (Two Ø7mm shank and one Ø5
mm shank) can be used.

This arrangement ensure that the breaker cannot be racked in


any position viz. Service, Test or Isolated.

9.7 DETAILS OF DIFFERENT MICROSWITCHES

LOCATION NO. OF SIC’S FOR


NAME APPLICATION
WIRING

C1 Common indication of tripping due to Inside the 3


O/L, S/C & G/F ACB

C2 Separate indication of tripping Inside the 3


due to O/L, S/C & G/F DN1 release

C3 Indication of U/V release operation On the U/V 2


release

C5 Indication for shunt release operation On the shunt 2


release

C6 Service position-Left In cradle 2

C7 Service position-Right In cradle 2

C8 Test or isolated position-Left In cradle 2

C9 Test or isolated position-Right In cradle 2

9-5
9.7 OPERATION OF MICROSWITCHES

LEFT SIDE

1. Cam on telescopic rail.


1 2 3 2. Microswitch (C8/9) in test or isolated position.
3. Microswitch (C6/7) in service position.

RIGHT SIDE

3 2 1

Fig. Microswitch Mounting For Position Indication.

‘Service’ position : The microswitch operates 3 mm before the ‘service’ position


‘Test’ position : The microswitch operates 3 mm before the ‘test’ position during withdrawal
‘Isolated’ position : The microswitch operates 2 mm before the ‘Isolated’ position

9.8 LOCKING SYSTEM FOR THE BREAKER

Locking system arrangement in Air Circuit Breakers are offered as follows:

For drawout breakers only

}
- Locking in ‘Isolated’ position / ‘Any’ position
- Door Interlock
On cradle.
- Racking interlock
- Rating Error Prevention

For both drawout and fixed breaker


- Lockable trip push button

9.8.1 LOCKING IN ‘ISOLATED’ POSITION / ‘ANY’ POSITION

9.8.1.1 Locking in ‘Isolated’ position

In case number of feeders are fed from two sources e.g. a


main supply source and standby generator and it is
Main Standby
necessary that only one source is connected to the bus Supply Generator

bars i.e. only one of the circuit breakers (X & Y) feeding


supply to the feeders can be switched ‘ON’ at any given X Y
time. To achieve this interlock identical locks are fitted on
the two breakers and only one key is kept in the custody of
A B C D
the attendant.
9-6
Breaker in ‘ISOLATED’ position
• Breaker can be locked & key can be removed
• Breaker cannot be racked in

Fig. 2

Breaker in ‘SERVICE’ or ‘TEST’ position


• Breaker cannot be locked
• Key cannot be removed

Fig. 3

These locks are so designed that when the lock is in released position, i.e. open, key cannot be
removed.

If breaker X is closed and changeover to breaker Y is required, then breaker X has to be


tripped and racked out to ‘Isolated’ position. Locking of the breaker X is possible in its ‘Isolated’
position and the key can be removed to unlock the other breaker Y, Breaker Y can now be racked
into ‘Service’ position and closed. As breaker X is locked in ‘Isolated position and the key is trapped
in the lock of Y, X cannot be put into service position. This serves the purpose of interlocking.

Operation

Withdraw the breaker to ‘Isolated’ position. Turn the key clockwise and remove from the lock.

9.8.1.2 Locking in ‘Any’ position

The operation is similar to that explained but can be locked in any position viz. Service,
Test or Isolated.

9.8.2 DOOR INTERLOCK

9.8.2.1 Door Open and Breaker in ‘Isolated’ position.

When the door is open, the spring-loaded pin interferes with the screw (refer Fig. 4)
and hence the racking screw cannot be turned. However, when the door is closed, the pin is
pressed and the screw is free to rotate. The breaker can be racked now.
9-7
This arrangement ensures that the breaker cannot be racked to the ‘Test’ and ‘Service’ position
unless the door is closed.
PIN SCREW

DOOR OPEN (Screw will intefere with pin)

Fig. 4
Door Interlock

Latch Piece
Pin Latch piece
Breaker
Lever
Lock plats

Lever L

Cradle
Bracket Door Busbar Door
50

Fig. 5 Fig. 6
Breaker in Isolated Position Breaker in ‘Test’/ ‘Service’ Position

When the breaker is in ‘Isolated’ position, make sure that the position of the top end of the lever
results in its movement in anti-clockwise direction. Check that on removal of the pressure, the
lever comes back to its original position due to spring action.

9.8.2.2 Door closed and breaker in ‘Service’ / ‘Test’ position :

When the breaker is racked in, the pin on the left side plate of the breaker presses the lever as
shown in Fig. 5 . The rear portion of the lever rises & comes in front of the latch piece fixed to the
cubical door as shown in Fig. 6. The interference between the latch piece and the lever prevents
the door from opening. However, when the breaker is withdrawn to the ‘Isolated’ position, the door
can be opened since the lever is not pressed by the pin of the breaker side plate and hence there
is no interference between the latch piece and the rear portion of the lever.

The door interlock can be defeated by rotating the screw on the cubicle door in anti-clockwise
direction using a screw driver.
9-8
9.8.3 RACKING INTERLOCK

- Before initiation of racking operation, the key of the lock is to be pressed and turned anti-
clockwise. Otherwise the racking operation gets mechanically prevented
- In case the breaker is in closed condition, pressing of the key trips the breaker between the
positions ‘Test’ and ‘Service’
- The key remains trapped in the lock when not pressed and this makes it suitable for interlocking

9.8.4 RATING ERROR PREVENTION :

The breaker and cradle are fitted with ‘rating error prevention’ feature. Any mismatch of the breaker
and cradle rating will be prevented, as the breaker having any rating other than that of the cradle,
cannot be fitted on the telescopic rail of the cradle.

9.8.5 LOCKABLE TRIP PUSH BUTTON :

This system replaces the normal trip push button by a lockable one and used for the purpose of
locking & interlocking. The push button is suitable for both Manual and Elecrical, Draw-out and
Fixed Breakers of all ratings, which makes interlocking between any version and rating possible.
The system defeats all positive closing signals (manual / electrical) and prevents nuisance closing
of the locked breakers. The key remains trapped on the push button once unlocked which makes it
suitable for interlocking and gives easy access (if one desires) to lock the breaker.

PUSH TO TRIP
TURN ANTI - CLOCKWISE TO LOCK

For S1/C/H/D-Range For E-Range Breakers


Breakers

9.8.6 AUTOMATIC SAFETY SHUTTER FOR DRAWOUT BREAKERS

The shutter automatically covers the cradle terminals (which may be live) once the breaker is
drawn out of ‘Service Position’. This is to avoid accidental contact of the operating personnel with
live parts during maintenance.

9-9
9.8.7 TECHNICAL DATA FOR ACCESSORIES :

ACCESSORIES TECHNICAL DETAILS

Nominal Voltage Power


Operating
Type of Release Consumption at
Use (V) pick up Limits

110 AC 800 VA
240 AC 800 VA 10-130% V
EA1
415 AC 800 VA
SHUNT RELEASE: 24V DC 32 W
48V DC 125 W
EA 65-130% V
110 DC 45 W
220 DC 30 W
Note : Other voltage available on request

240V & 415V 50Hz AC,


Nominal voltage
220V & 415V 60Hz AC, & 24V DC

Pick up (V) 80% Ue


UNDER VOLTAGE
Drop off (V) 35-65% Ue
RELEASE
VA Consumption Pick up - 23 VA
Hold on - 8.5 VA
Watt loss 6W

Rated voltage Rated current


Type for resistive circuit
(V) (A)
125 AC 5.0
C2 250 AC 2.0
MICROSWITCH 30 DC 2.0
125-250 AC 10.0
C1, C3 415 AC 5.0
C5, C6 30 DC 8.0
C7, C8, C9 110 DC 0.5
220 DC 0.2

Continued...
9-10
9.8.7 TECHNICAL DATA FOR ACCESSORIES :

ACCESSORIES TECHNICAL DETAILS

Rated voltage (Us) Power Consumption Range of operation

SPRING CHARGING 240V, 50Hz 300VA


MOTOR 85-110% Us
110V DC
154W
220V DC

Power Consumption Range of


Rated Voltage
(Us) operation
Pick-up Hold-on

CLOSING 110V, 50Hz


240V, 50Hz 320VA 50VA
ELECTROMAGNET
220V, 60Hz
85-110% Us
110V DC, 220V DC 300W 50W
24V,30V,48V DC

Economy
Rated dc Voltage (V)
resistor (ohm)

24V DC 16 (ST24202)
ECONOMY RESISTOR 30V DC 24 (ST17402)
48V DC 62 (ST16890)
110V DC 360 (XK52076)
220V DC 1000 (XK52071)

Electrical Voltage Rated current


Circuit (V) (A)

24 to 415AC 16
Resistive
250V DC 1.2

24 to 415 AC 16
Non-resistive
250V DC 1.0
AUXILIARY CONTACTS
=L/R = 15ms with 2 NO or 2 NC contact in series
Note : Short-circuit protection

Largest permissible cylindrical fuse (as per IEC 60269) 16A

Largest permissible MCB with C-characteristics 16A

9-11
10. MAINTENANCE & TESTING
10.1 MAINTENANCE SCHEDULE:
The frequency of maintenance depends essentially on service condition viz. frequency of operation,
tripping on fault, relative humidity and presence of dust and reactive gases etc.
For Atmospheres having Harsh Environment (Sulphur Rich), it is recommended to use C-Power “ HE” range of
Air Circuit Breakers. The mechanical / electrical life figures of manually or electrically operated CN-CS..E;
CN-CS..G; CN-CS...S1; CN-CS..C, CN-CS..D, CN-CS..HE & CN-CS..H Air Circuit Breakers are as under:
CN-CS 400E to CN-CS 1000E 15,000 operating cycles
CN-CS 1250E to CN-CS 2000E 20,000 operating cycles
CN-CS 400G to CN-CS 2000G 20,000 operating cycles
CN-CS 400S1 to CN-CS 2500S1 20,000 operating cycles
CN-CS 3200S1/C 20,000 operating cycles
CN-CS 800C to CN-CS 2500C 20,000 operating cycles
CN-CS 3200D / 4000C to CN-CS 6300C / 5000HE 5,000 operating cycles
CN-CS 800H to CN-CS 2500H 20,000 operating cycles
CN-CS 1250HE / 2000HE 20,000 operating cycles
CN-CS 3200H1/H2/HE to CN-CS 4000H/H2 10,000 operating cycles
The arc chutes and arcing contacts are suitable for the following kinds of service without maintenance at rated
current and voltage.
CN-CS 400E to CN-CS 1600E 6,000 M-B operating cycles
CN-CS 2000E 4,500 M-B operating cycles
CN-CS 400G to CN-CS 1000G 8,000 M-B operating cycles
CN-CS 1250G 7,000 M-B operating cycles
CN-CS 1600G 6,000 M-B operating cycles
CN-CS 2000G 4,500 M-B operating cycles
CN-CS 400S1 to CN-CS 1000S1 8,000 M-B operating cycles
CN-CS 1250S1 to CN-CS 1600S1 7,000 M-B operating cycles
CN-CS 2000S1/C/H/HE 6,000 M-B operating cycles
CN-CS 2000S1 to CN-CS 3200S1 5,000 M-B operating cycles
CN-CS 800C to CN-CS 1000C 8,000 M-B operating cycles
CN-CS 1250C to CN-CS 1600C 7,000 M-B operating cycles
CN-CS 2500C to CN-CS 3200C / 2500H 5,000 M-B operating cycles
CN-CS 4000C to CN-CS 6300C / 5000HE 2,500 M-B operating cycles
CS-CS 800H to CN-CS 1000H 8,000 M-B operating cycles
CN-CS 1250H to CN-CS 1600H / 1250HE 7,000 M-B operating cycles
CN-CS 3200H1/H2/HE to CN-CS 4000H/H2 5,000 M-B operating cycles
OR
Break operation followed by two make-break operations at rated making / breaking(M-B) capacity (Please refer
IS 13947 (part 2) or IEC 60947-2) OR
25 make-break operations at six times the rated current at nominal voltage.
The main contacts and all the other components of the breaker are designed to last for the entire mechanical /
electrical life of the breaker. It is, however, recommended to carry out inspection as per the schedule mentioned
below:
After every 3000 mechanical operations
OR
After six months of service, if exposed to dust
OR
After an idle period longer than six months
OR
Every year
During the course of inspection, check first the general service conditions of the breaker. Carry out operations
described in Section 5 (these operations can be carried out in ‘Test’ position for draw-out breakers). Subsequently,
check the operating requirements enumerated in Section 5, which may require readjustment in certain cases.

10-1
10.2 DETAILS OF MAINTENANCE, THAT CAN BE CARRIED OUT ON THE BREAKER
ARE AS UNDER :
10.2.1. ARC CHUTE
- Clean the insulating surface and anti-arc strips covering the inside of the arc chutes by the aid
of a dry piece of cloth.
- At the end of its electrical life, it is recommended that arc chutes be reassembled after turning
the anti-arc insulating strips (inside the arc chutes) around. This will expose fresh surface to face
arcing and will double the life of the arc chutes. The arc chutes need to be replaced subsequently.

10.2.2. POLE
- Clean the insulating pieces (hylam piece on both the sides of the contacts).
- Close the breaker and check the arcing contact gap.
It is necessary to readjust the fixed arcing contact if the gap is greater than 1.5 mm.(Refer fig.10-4).
It is not necessary to clean them, even if erosion is observed on the contact buttons. However the
fixed and moving arcing contacts should be replaced when the thickness of the button gets reduced
to 0.5 mm. The anti-arc strips (hylam pieces on both the sides of the contacts) if provided, should
also be replaced simultaneously. Erosion marks on the main contacts if any will not affect the
operation of the breaker. The contact surface can be cleaned with fine emery cloth and wiped
thoroughly (the main contacts cannot be replaced). However in any case if the moving fingers of a
pole appears misaligned, it is not going to affect the performance of breaker.

10.2.3. ASSEMBLY OF THE BREAKERS


The pole assemblies are maintained under pressure by six special screws located on the side
plates of the breakers. The tightening torque need to be checked as per instructions given later in
the chapter. (refer clause 10.3.7).

10.2.4. OVERCURRENT AND VOLTMETRIC RELEASE


The release DN1, SR18, SR18G, SR18G with Display, SR18Gi with Display,SR21i, SR71, MV, EA,
EA 1 etc. do not require any maintenance. Check that tripping and resetting are as per the test
instructions given in clause 10.3.2 to 10.3.6.

10.2.5. GREASING
A breaker normally greased and operating in dust free and non corrosive atmosphere over a period
of two years can undergo its normal cycle of mechanical endurance without greasing. As ideal service
conditions are hardly encountered, it is recommended to re-grease the breaker after a cycle of 500
operations or six months, whichever is earlier. (Please refer to the Fig. 10.1, 10.2 & 10.3 for details of
parts to be greased).
10.2.5.1 Components to be greased
All rubbing surfaces in the mechanism, poles etc. are to be greased except the contacts (copper on
copper) and sintered bearings. Grease sliding surface of fixed and moving secondary isolating
contacts with petroleum jelly.
Prior to greasing, these surface should be thoroughly cleaned. Excess grease must be wiped out.

Note : Please do not use any cleaning agent while cleaning with cloth.

10-2
P

3 P 4

P P

5
P

P 2 P P 1

Molygrease ML
Fig. 10-1 Lithon 2
Section view of manual breaker E-Range

COMPONENTS TO BE GREASED:
P) Pins
1) Roller Assembly
2) Pole Latch Spring Retainer
3) Stainless Steel Profile
4) Slotted Guide
5) Pole Latch Nylon Rollers
GREASE TO BE USED:
1) Lithon 2 of Hindustan Petroleum (for components shown in circle).
2) Molygrease ML of Balmer Lawrie & Co. Ltd (for components shown in square).
SCHEDULE FOR GREASING:
Every 500 operations or 6 Months
Note : Please do not use any other grease than the recommended ones.

10-3
P

3 P 4

P P

5
P

P 2 P P 1
Molygrease ML

Fig. 10-2 Lithon 2

Section view of manual breaker G/S1/C/H/HE/D-Range

COMPONENTS TO BE GREASED:
P) Pins
1) Roller Assembly
2) Pole Latch Spring Retainer
3) Stainless Steel Profile
4) Slotted Guide
5) Pole Latch Nylon Rollers
GREASE TO BE USED:
1) Lithon 2 of Hindustan Petroleum (for components shown in circle).
2) Molygrease ML of Balmer Lawrie & Co. Ltd (for components shown in square).
SCHEDULE FOR GREASING:
Every 500 operations or 6 Months
SECONDARY ISOLATING CONTACTS:
Sliding Surface of fixed and moving contact with petroleum jelly.

Note : Please do not use any other grease than the recommended ones.

10-4
P

3
P 4 6

P 7

P
5

2
P P P 1
Molygrease ML
Fig 10-3 Lithon 2
Section view of electrical breaker

COMPONENTS TO BE GREASED:
P) Pins
1) Roller Assembly
2) Pole Latch Spring Retainer
3) Stainless Steel Profile
4) Slotted Guide
5) Pole Latch Nylon Rollers
6) Crank
7) Plate
GREASE TO BE USED:
1) Lithon 2 of Hindustan Petroleum (for components shown in circle).
2) Molygrease ML of Balmer Lawrie & Co. Ltd (for components shown in square).
SCHEDULE FOR GREASING:
Every 500 operations or 6 Months
SECONDARY ISOLATING CONTACTS:
Sliding Surface of fixed and moving contact with petroleum jelly.

Note : Please do not use any other grease than the recommended ones.

10-5
10.2.5.2 Components greased for life
The following components are provided with self lubricating sintered rings impregnated with grease
for life.
- Trip rod
- Intermediate shaft of manual control
- Free return charging device for electrical ACBs

10.2.5.4 Components not to be greased


- All releases
- Main contacts in pole and cradle terminals
- Earthing terminal
- Secondary isolating contacts

10.2.5.5 Caution
Before any maintenance operation, following procedure must be followed.
- Mechanism spring must be discharged.
- Drawout breaker must be in isolated/maintenance position.
- Circuit breaker which operate rarely, must be periodically operated.
- Please contact our office/authorised service center in case of a problem arising during usage

10-6
10.3 TEST INSTRUCTIONS
The adjustments and tests listed in the following pages are to be carried out after routine maintenance/
replacement of spares. For carrying out some of them, it may be required to remove the front facia.
Follow the procedure given as per clause 10.3.10 for removing the front facia.
Maintenance of the breakers is to be carried out of as per the recommendations mentioned earlier in
this section. The procedure for the replacement of spares will be as per Section 11.

10.3.1 POLE :
Refer to Fig. 10-4
Adjustment of arcing contacts :
Breaker is in ‘Closed’ condition. Move the fixed arcing contacts to obtain the dimension 0.9 ± 0.1 mm
between the fixed and moving arcing contacts.
Tightening couple of the screw (12) : 0.8 kg-m

Note :
8 12
0.9 ± 0.1
9 10
Check the positioning of the arcing contacts again at the end of
the inspection schedule. Gap between the arcing contacts (fixed
and moving) 0.9 ± 0.1 mm. Maximum difference in this dimension
for the arcing contacts of the same pole should not be more
than 0.1 mm.

Limit of wear = 1.5 mm

Tightening couple of the screws (9) and (10) : 0.25 kg-m


(moving arcing contact)

7
Fig. 10-4

10.3.2 OVERLOAD AND SHORT CIRCUIT RELEASE TYPE DN1


10.3.2.1 TRIPPING

In ‘Open’ condition of the breaker, resetting adjustment screw (18)


to be unscrewed nearly completely (see Fig. 10-5).
The release being reset, adjust the connecting piece (19) to get the
dimension 1 ± 0.5 mm between the tripping striker (20) and the lug
(21) of latch (22) in the position of rest (Fig. 10-6).
Red Varnish 1.5

18

Fig. 10-5
10-7
Red Varnish 10.3.2.2 Inspection
0.5

In ‘Closed’ condition of the breaker, check that there is a minimum


play of 0.5 mm between tripping striker (20) and the lug (21) of
latch (22) in the position of rest (See Fig. 10-6).
22 21 20 19
Limit of wear 0.1 mm.
Hold the crank (23) of the release and press the release strip (24).
Fig. 10-6 Release the crank (23) slowly while keeping the strip (24) pressed
and see that the breaker trips (See Fig. 10-7).

24

Important
In order not to block the resetting of the release which takes place
when the breaker trips open, carry out the releasing operation of
Hook
the crank (23) with a hook (See Fig. 10-7).
23

Fig. 10-7

10.3.2.3 RESETTING
10.3.2.3.1 AUTO RESETTING
In ‘Open’ condition of the breaker keep the DN1 release tripped.
Adjust the screw (18) to effect latching-on of the release. Screw 3/4
turn more to ensure a margin of safety for resetting (See Fig. 10-8).
Red Varnish 1.5

18 Note : A very distinct click sound indicates latching-on of the release.


Fig. 10-8

Inspection :
In ‘Open’ condition of the breaker, check for a resetting margin of safety of 1.5 mm by turning the main
shaft in the direction of closing.
Limit of wear : no latching.

10-8
1 ± 0.5
10.3.2.3.2 LOCAL RESETTING
Breaker in ‘Open’ condition
26 The release being in tripped condition and the crank (26) resting
against the stop (27), adjust the connecting piece (44) to get the
27
dimension 1 ± 0.5 mm (See Fig. 10-9). Press the tripping push
44
button (28) and adjust the screw (29) to effect resetting of the
Fig. 10-9
release. Unscrew one turn to ensure a margin of safety in
resetting. (Refer to Fig. 10-10)
30

28
29 Note : A distinct click sound indicates latching-on of the release.
0.2

Latched 0.5
22 21

Fig. 10-10

Inspection
Breaker in ‘Open’ condition :
Press the push button, check for the safety margin of latching-on of 0.5 mm - the crank of the release
returns by this distance before finally latching-on.
With push button (28) pressed check for a minimum play of 0.2 mm between the lug (21) of the latch
(22) and the bottom of the slot.

EXTREME POSITION
OF RESET
10.3.3 MICRO-PROCESSOR BASED RELEASE TYPE SR18/
SR18G/ SR18G with Display/ SR18Gi with Display/ SR21i/
SR71
SR21i 10.3.3.1 TRIPPING
In ‘Open’ condition of the breaker, the resetting adjustment
16
RED VARNISH screw (16) to be unscrewed nearly completely.(See Fig. 10-11).
Fig. 10-11

10-9
SR21i The release being reset, adjust the connecting piece (10) to get the
.5
1±0

dimension of 1±0.5mm between the tripping striker (11) and the lug
(12) of the latch (13) in the position of rest (see Fig. 10-12).
RED VARNISH
13 12 11 10 Inspection
In ‘closed’ condition of the breaker, check that there is a minimum play
Fig. 10-12
of 0.5 mm between the tripping striker (11) and the lug (12) of the latch
(13) in the position of rest (see Fig. 10-12).
Limit of wear : 0.1mm
14
Hold the bracket (14) of the release and given an intentional trip
SR21i command using the test kit for the release. Release the bracket (14)
slowly and see the breaker trips (see Fig. 10-13).
HOOK

Fig. 10-13

PUSH BUTTON The breaker can be tripped by applying 18V DC across the points
SR21i (show in Fig. 10-14) on the D-subconnector of the release. The DC
18V DC source should be capable of delivering 6A continuously. It is to be
noted that one has to use a suitable connector for applying the voltage.
Care should be taken that the push button is not kept pressed for
D - SUB CONNECTOR
more than 1 second. In case the test kit is not available, this method
can be adopted to give the trip signal to see the slow tripping of the
Fig. 10-14 breaker as mentioned in the previous paragraph.

Important
In order not to block the resetting of the release when the breaker trips open, carry out the releasing
operation of the bracket with the hook (see Fig. 10-13).

10-10
10.3.3.2 RESETTING:
EXTREME POSITION
OF RESET 10.3.3.2 .1 AUTO RESETTING
In ‘Open’ condition of the breaker and the release being in tripped
condition, adjust the screw (16) to effect latching-on of the release.
Screw 3-4 turns more to ensure the margin of safety for resetting
SR21i
(See Fig. 10-15).

RED VARNISH
16 Note : A very distinct click sound indicates latching-on of the release.
Limit of wire: no latching
Fig. 10-15

10.3.3.2 .2 LOCAL RESETTING


1 ± 0.5
SR21i Breaker in ‘Open’ condition
The release being in tripped condition and the crank (19) resting
against the stop (20), adjust the connecting piece (21) to get the
dimension of 1 + 0.5 mm (see Fig. 10-16). Press the tripping push
button (23) and adjust the pin (24) to effect resetting of the release.
Unscrew one turn to ensure a margin of safety in resetting (See Fig.
21 20 19
10-17).
Fig. 10-16
Note: A distinct click sound indicates latching-on of the release.

23
25
Inspection
In ‘Open’ condition of the breaker:
Press the push button, check the safety margin of latching-on of 0.5
24 mm the crank of the release returns by this distance before finally
latching-on. With push button (23) pressed, check for a minimum play
of 0.2 mm between the lug (12) of the latch (13) and the bottom of the
slot (see Fig.10-17).
Note: The instruction given in Clause 10.3.3 above are also valid for
0.2

13 12 SR18, SR18G, SR18G with Display, SR18Gi with Display, SR21i and
SR71 releases.
Fig. 10-17

10-11
10.3.4 THE BREAKER NOT FITTED WITH OVERCURRENT
RELEASE
20 In ‘Open’ condition of the breaker, make sure of the following:
0.5 Minimum

A minimum play of 0.5 mm between the tripping striker (20) and the
lug (21) of the latch (22) at rest. A minimum play of 2 mm between,
the resetting screw (18) and the tripping striker (20).
2 Minimum

22 21 18 Note: Trip rod should be locked to mechanism plate by using


Fig. 10-18
(M4x25 CSK Screw).

Hook
1 ± 0.5
10.3.5 VOLTMETRIC RELEASES
32
10.3.5.1 TRIPPING
Refer to Fig.10-19

In ‘Open’ condition of the breaker, unscrew the resetting adjustment


screw (31) nearly completely. The release being latched on, adjust
the connecting piece (32) to get the dimension 1±0.5 mm between
34 22 21 33 31 the lever (33) and the lug (21) of the latch (22) at rest.

Fig. 10-19

Inspection
1
In ‘Open’ condition of the breaker:
Check for a minimum play of 0.5 mm between the lever (33) and the lug (21) of the latch (22) at rest.
Limit of wear: 0.1 mm
Hold the striking pin (34) as shown in the Fig. 10-19, free the latch of the release. Release the striking
pin slowly and see that the breaker trips.

Important
In order not to block the resetting of the release when the breaker trips open, carry out the slow releasing
of the striking pin with the help of a hook.

2-minimum

10.3.5.2 RESETTING
Refer to Fig. 10-20.
In ‘Open’ condition of the breaker, adjust the screw (31) to bring the
striking pin (34) against the stop. Unscrew half a turn.

Varnish
34 31

Fig. 10-20 10-12


Inspection
In ‘Open’ condition of the breaker, check if there exists a minimum margin of safety in latching-on of 2 mm.
Limit of wear : no latching.

10.3.6 BREAKERS NOT FITTED WITH VOLTMETRIC RELEASE:


21 33 35
22
Refer to Fig. 10-21.
2 minimum
In ‘Open’ condition of the breaker:
Check if there exists a minimum play of 2 mm between the lever (33)
and the lug (21) of the latch (22) at rest. Check if there exists a
2-minimum
31
minimum play of 2 mm between the screw (33) and the crank (35).
Fig. 10-21

A A=B±1 B 10.3.7 TIGHTENING OF THE POLE ASSEMBLIES:


Breaker in ‘Open’ condition with special screws (1) loose
(See Fig. 10-22 and Fig. 10-23)
Close the breaker
1
A. For CN-CS 400A - CN-CS 2000A E/G & CN-CS 400A to CN-CS
3200A S1 & CN-CS 800A - CN-CS 3200A C & CN-CS 2000A HE &
CN-CS 1600A D 3P/4P breakers:
(Refer to Fig. 10-22) Tighten the special screws (1) so that the
difference in gaps between the external plates and the poles at the
two ends is not more than 1 mm (A= B±1 mm).
RED VARNISH
Fig. 10-22 Tightening torque = 0.4 kg-m
B. For CN-CS 3200D/4000C & 5000HE & 5000/6300C 3P/4P
1 2 72
RED VARNISH
breakers:
(Refer to Fig. 10-23) Tighten the special screws (1) such that the
fixed screws (2) of the inter-mediate plates (72) can be fixed and
rotated freely.
Tightening torque = 1.5 kg-m
C. For CN-CS 800A to CN-CS 2500A H, CN-CS 1250A HE & CN-CS
2
3200HE & CN-CS 3200H1/H2 & 4000H/H2 3P/4P breakers:
Fig. 10-23
(Refer to Fig. 10-23) Tighten the special screws (1) such that the
10
fixed screws (2) of the inter-mediate plates (72) can be fixed and
rotated freely.
Tightening torque = 0.4 kg meter.

10.3.8 MICROSWITCH FOR POSITION INDICATION (ON CRADLE)


Refer to Fig. 10-24
10.3.8.1 Microswitch in ‘service’ position
Adjust the screw (10) to ensure operation of the microswitch 3±0.5
mm before ‘Service’ position (eliminate the play on the telescopic
12 11 rails by pulling them).
Fig. 10-24
10-13
10.3.8.2 Microswitch in ‘Test’ position
Adjust the test support (11) and the screws (12) to ensure the operation of the microswitch 3±0.5 mm
before the ‘Test’ position in the direction of the withdrawal (eliminate the play by pushing the rails).

10.3.8.3 Microswitch in ‘Isolated’ position


Adjust the support (11) and the screws (12) to ensure operation of the microswitch 2±0.5 mm before the
‘Isolated’ position (eliminate the play by pushing the rails).

10.3.9 MICROSWITCH ON TRIP ROD


(Refer to Fig. 10-25)
36
Signal indication of tripping on overload and
1±0
1 short circuit.
Breaker in ‘Closed’ condition (overcurrent and
37
short circuit release type DN1/ SR18G/ SR18G
with Display/ SR18Gi with Display/ SR21i &
FRONT SIDE SR71 latched-on). Orientation of microswitch
is as shown in sketch. For DN1 Release keep
37 the microswitch closed and adjust by deforming
FOR DN 1 RELEASE the strip (36) in such a manner as to obtain a
FOR SR RELEASE
dimension of 1mm between the strip (36) and
36 the spring pin (37).
Fig. 10-25
For DN1/SR release, operation of the
microswitch must be checked by tripping the
breaker through release.

1 10.3.10 PROCEDURE TO BE FOLLOWED


FOR REMOVING THE FRONT FACIA OF A
BREAKER
For removing the front facia, follow the steps
mentioned below :
Plug 1. Remove the plug of the operating handle
using a screw driver.
Fig.10-26b
(see Fig. 10-26a)
2. Get screw (1) fully unscrewed.
(see Fig. 10-26b)
3. Remove the operating handle.
4. Get the screws at the four corners of the
front facia unscrewed.
(see Fig. 10-26c)
Fig.10-26a Fig.10-26c 5. Remove the front facia from the breaker.

10-14
10.3.11 PROCEDURE FOR RACK-IN/RACK-OUT
FITTING A BREAKER ON ITS CRADLE:
• Before fitting the breaker on its cradle, ensure that the breaker is in ‘OFF’ position.
• Ensure that the closing spring in case of electrically operated breakers is discharged. If it is in
charged condition, press the ‘CLOSE’ push button to discharge it and then press the “TRIP” push
button to bring the breaker in ‘OFF’ position.
• Rack the telescopic rails out to ‘isolated’ position if necessary & further pull them out to
‘Maintenance’ position.
• The breaker and cradle are fitted with ‘rating error prevention’ feature. This prevents the mismatch
of breaker & cradle, as a breaker having rating other than that of the cradle cannot be fitted on the
telescopic rails of the cradle.
• Place the breaker onto the rails and engage with M8 nuts, spring washers and the plain washers
on the telescopic rail studs.
• Ensure that the breaker is not sitting on the collars of the studs.
• Push the breaker in fully and then tighten the nuts on the two accessible studs.
• Pull out the breaker so as to tighten the inner two nuts.

RACK-IN OPERATION:
• Push the breaker in, until lug engages with spring loaded catches. This corresponds to ‘Isolated’
position.
• Take the racking handle out from its storage location and insert it into the racking screw location.
• Before racking ensure that
- Key of the racking interlock (if provided) is pressed and turned anti-clockwise.
- Key of position lock (if provided) is turned clockwise.
- Pin of door interlock is pressed.
• Rotate the racking handle in clockwise direction until position indicator shows ‘SERVICE’ position.

Note: Alignment of breaker facia with cradle facia indicates breaker is in ‘SERVICE’ position.

RACK- OUT OPERATION:

• Take the racking handle out from its storage location and insert it into the racking screw location.
• Before racking out ensure that
- Key of the racking interlock (if provided) is pressed and turned anti-clockwise.
- Key of position lock (if provided) is turned clockwise.
- Pin of door interlock is pressed.
• Rotate the racking handle anti-clockwise until position indicator shows ‘ISOLATED’ position.

10-15
11. SPARE PARTS
11.1 GENERAL
Replacement of the recommended spares is to be carried out satisfactorily in accordance with
the given instructions.

Description Cat Nos.

CTs for SR18/SR18G/SR18G with Display/SR18Gi with display/SR21i


400 S1/G SL01523OOOO
630 S1/G ST37495OOOO
800 C/H/S1/G SL01857OOOO
1000 C/H/S1/G SL01858OOOO
1250 C/H/S1/G SL90571OOOO
1600 C/H/S1/G SL90572OOOO
2000 C/H SL90565OOOO
2000 S1/G SL93210OOOO
2500 C/H/S1 SL90566OOOO
3200 D SL90567OOOO
3200 S1 SL90575OOOO
3200 H0/H1/H2 SL01740OOOO
4000 C SL90568OOOO
4000 H0/H/H2 SL01739OOOO
5000 C SL00990OOOO
6300 C SL00991OOOO
CTs FOR DN1
400 S1/G SL01521OOOO
630 S1/G (Fixed) * SL01522OOOO *
800 C/H/S1/G (400/500 Tap) SL00786OOOO
800 C/S1 (640/800 Tap) SL00787OOOO
800/1000 H& 1000 C/S1/G (800/1000 Tap) SL00788OOOO
1250 C/H/S1/G SL00789OOOO
1600 C/H/S1/G SL00790OOOO
2000 C/H (1000/1250 Tap) SL00791OOOO
2000 S1/G SL00993OOOO
2000 C/H (1600/2000 Tap) SL00792OOOO
2500 C/H/S1 (1600/2000 Tap) SL00793OOOO
3200 D (2000/2500/3200 Tap) ST21261OOOO
3200 S1 SL00794OOOO
3200 H0/H1/H2 SL01707OOOO
4000 H0/H/H2 SL01706OOOO
4000 C SL90560OOOO
* For 630 S1 D/O breaker : SL00374OOOO

11-1
Description Cat Nos.

Arc-chute (440V)
Arc Chute 400-1250 G/S1 SL91934OOOO
Arc Chute 1600-2000 G, 800-1600 C/H, 1600/2000S1 SL90855OOOO
Arc Chute 2000 C/H, 2500 C/H/S1 SL90857OOOO
Arc Chute 3200 C/S1 SL91834OOOO
Arc Chute 3200 H0/H1/H2, 400O H0/H/H2 SL90855OOOO
Arc Chute 5000/6300 C SL91977OOOO
Arc Chute 3200 D/ 4000 C SL92044OOOO
Arc Chute Fixing Kit SL94648OOOO
Arc-chute (690V)
Arc Chute 690V 800-1600 C/H SL91181OOOO
Arc Chute 690V 2000/2500 C/H SL91183OOOO
Arc Chute 3200 H0/H1/H2, 400O H0/H/H2 SL91181OOOO
Arc Chute 690V 3200 D& 4000 C SL92314OOOO
Arc Chute Fixing Kit SL94648OOOO
Fixed Arcing Contact
400-1250 G/S1 SL93890OOOO
800-1600 C, 1600-2000 G/S1 SL93891OOOO
800-1600 H, 2000 S1 SL93040OOOO
2000 C/2500 S1 SL90631OOOO
2500 C/H, 3200 S1 SL90631OOOO
3200 H0/H1/H2, 400O H0/H/H2 SL93040OOOO
3200 D, 4000 C SL90652OOOO
5000-6300 C SL90652OOOO
Moving Arcing Contact
400-1250 G/S1 SL93892OOOO
800-1250 C, 1600 G/S1/C, 2000 G/S1 SL93892OOOO
800-1600 C/H, 25000 S1 SL93892OOOO
2000 C SL90629OOOO
2000 H, 2500 C/H SL90629OOOO
3200 S1 SL93892OOOO
3200 H0/H1/H2, 400O H0/H/H2 SL93892OOOO
3200 D, 4000 C SL90742OOOO
5000-6300 C SL90742OOOO

Arc-chute Moving Arcing Contact Fixed Arcing Contact 11-2


Description Cat Nos.

Cradle Terminal Assembly


800/1000 C& 400-1250 S1 SL91822OOOO
800-1600 H& 1250/1600 C& 1600/2000 S1 SL91823OOOO
2000 C SL91825OOOO
2000 H& 2500 C/H SL91826OOOO
3200 D SL92448OOOO
2500 S1 SL95212OOOO
3200 S1 SL91828OOOO
4000 C SL92668OOOO
3200 H0/H1/H2, 400O H0/H/H2 SL91947OOOO
5000/6300 C SL91971OOOO
Cradle Terminal support
800/1000 C& 400-1250 S1 SL50086OOOO
800-1600 H, 1250/1600 C, 1600/2000 S1 SL50178OOOO
2000 C SL50085OOOO
2500/3200 S1, 2000 H& 2500 C/H SL50128OOOO
3200 H0/H1/H2, 400O H0/H/H2 SL50178OOOO
3200 D& 4000 C SL50093OOOO
5000/6300 C SL61677OOOO
Safety Shutter
Shutter Assy. 800-1600 C/H, 400-2000 S1 SL91833OOOO
Shutter Assy. 2000-3200 C/H, 2500/3200 S1 SL92811OOOO
Shutter Assy. 3200 H0/H1/H2, 400O H0/H/H2 SL91833OOOO
Shutter Assy. 3000 D& 4000 C SL92985OOOO
Shutter Assy. 5000/6300 C SL91972OOOO

Cradle Terminal Assy. Cradle Terminal support

Safety Shutter
11-3
Description Cat Nos.

Jaw Contacts Assembly


Jaw contact Assy. 400/630 S1, 800 S1/C, 1000 S1/C & 1250 S1 SL92860OOOO
Jaw contact Assy. 800/1000 H, 1250 C/H & 1600 S1/C/H SL91816OOOO
Jaw contact Assy. 2000 S1 SL91816OOOO
Jaw contact Assy. 2000 C & 2500 S1 SL90881OOOO
Jaw contact Assy. 2000 H, 2500 C/H & 3200 S1/C SL91116OOOO
Jaw contact Assy. 3200 H0/H1/H2, 400O H0/H/H2 SL93200OOOO
Jaw contact Assy. 3200 D SL90883OOOO
Jaw contact Assy. 4000 C SL91118OOOO
Jaw contact Assy. 5000/6300 C SL91976OOOO
Vertical Terminals
Vertical Terminals 800/1000 C& 400-1250 S1 SL93281OOOO
Vertical Terminals 800-1600 H, 1250/1600 C & 1600/2000
SL93282OOOO
S1
Vertical Terminals 2000 C SL93284OOOO
Vertical Terminals 2000 H, 2500 C/H SL93285OOOO
Vertical Terminals 2500 S1 SL93289OOOO
Vertical Terminals 3200 S1/C SL93286OOOO
Vertical Terminals 3200 H0/H1/H2, 400O H0/H/H2 SL93288OOOO
Horizontal Terminals
Horizontal Terminal 800-1000C ST30113OOOO
Horizontal Terminal 1250-1600C, 800-1600H ST30114OOOO
Horizontal Terminal 2000C ST30115OOOO
Horizontal Terminal 2500C, 2000/2500H ST30116OOOO
Horizontal Terminal 3200 H0/H1/H2, 4000H0/H/H2 ST35744OOOO

Vertical Terminals

Jaw Contacts Assembly

11-4
Description Cat Nos.

Pole Assembly Fix Breaker


Pole Assy. 400-1250 G/S1 SL95601OOOO
Pole Assy. 800/1000 C, 1600 G SL93881OOOO
Pole Assy. 1250/1600 C, 1600 S1, 2000G SL93882OOOO
Pole Assy. 2000 C SL93883OOOO
Pole Assy. 2500 C SL93884OOOO
Pole Assy. 2000/2500 H ST30070OOOO
Pole Assembly Draw-out Breaker
Pole Assy. 400-1250 S1 SL94674OOOO
Pole Assy. 800/1000 C SL90797OOOO
Pole Assy. 800-1600 H SL93192OOOO
Pole Assy. 1250/1600 C& 1600 S1 SL93886OOOO
Pole Assy. 2000 S1 SL94660OOOO
Pole Assy. 2000 C& 2500 S1 SL90800OOOO
Pole Assy. 2500 C SL92730OOOO
Pole Assy. 2000/2500 H ST30071OOOO
Pole Assy. 3200 S1 SL95213OOOO
Pole Assy. 3200 HO/H1, 4000 H0/H SL93470OOOO
Pole Assy. 3200 H2, 400O H2 SL91225OOOO
Pole Assy. 5000/6300 C SL91961OOOO
Pole Assy. 3200 D SL92638OOOO
Poe Assy. 4000 C SL91176OOOO
Pole Connector
Pole connector : 400-2000G,400-3200S1, 800-3200C, 800-
SL00345OOOO
2500H
Pole connector : 3200 H0/H1/H2, 400O H0/H/H2 SL00345OOOO
Pole connector : 3200D, 4000C, 5000/6300 C SL00150OOOO

Pole Assembly
11-5
Description Cat No
Auxiliary Contact Block
2NO+2NC 400-2000 G,400-3200 S1, 800-2500 C/H &
SL92765OOOO
3200 H0/H1/H2, 400O H0/H/H2
2NO+2NC 3200D, 4000-6300 C SL92766OOOO
6NO+6NC 400 -3200 S1, 800 -2500 C/H &3200 H0/H1/H2, 400O H0/H/H2 SL92767OOOO
6NO+6NC 3200D, 4000-6300 C SL92768OOOO
Shunt-Release
Shunt Release EA 24V DC SL92718O4OO
Shunt Release EA 110V DC SL92718O1OO
Shunt Release EA 220V DC SL92718O2OO
Shunt Release EA1 110V SL92718OAOO
Shunt Release EA1 240V AC SL92718OBOO
Shunt Release EA1 415V AC SL92718ODOO
Under-voltage Release
Under-voltage Release 24V DC ST36877OOOO
Under-voltage Release 240V AC SL92720BOOO
Under-voltage Release 415V AC SL92720DOOO
Closing Coil
Closing Coil 24V DC ST15954OOOO
Closing Coil 30V DC ST17210OOOO
Closing Coil 110V AC/DC SL91079OOOO
Closing Coil 240V AC/ 220V DC SL91080OOOO
Closing Coil Kit
Closing Coil Kit 24V DC SL94645OOOO
Closing Coil Kit 30V DC SL94646OOOO
Closing Coil Kit 110V DC SL94643OOOO
Closing Coil Kit 220V DC SL94644OOOO
Resister Kit
Resistor-Kit 24VDC ST24202OOOO Shunt Release
Resistor-Kit 30VDC ST17402OOOO
Resistor-Kit 110VDC XE52076OOOO
Resistor-Kit 220VDC XE52071OOOO
Closing Preventer
Closing Preventer 240V AC SL91956OOOO
Closing Preventer 415V AC SL91955OOOO
Earth fault release for DN1
Type EF1 (10%, 20% In ) SL91340OOOO
Type EF2 (30%, 40%, 50% In) SL91341OOOO

Under-voltage Release

Closing Coil Earth-Fault Release Closing Coil Kit Closing Preventor

11-6
Description Cat No

Insulating-Tube
Insulating-Tube Big 3-Pole
800-1600 C/H & 400-2000 S1, 400-2000 G SL10057OOOO
2000/2500 C/H & 2500/3200 S1, 3200C SL10059OOOO
3200 H0/H1/H2, 400O H0/H/H2 SL10061OOOO
3200 D, 4000 C SL10071OOOO
5000/6300 C SL11503OOOO
Insulating-Tube Big 4-Pole
800-1600 C/H & 400-2000 S1 SL10058OOOO
2000/2500 C/H & 2500/3200 S1, 3200C SL10061OOOO
3200 H0/H1/H2, 400O H0/H/H2 SL11503OOOO
3200 D, 4000 C SL11503OOOO
5000/6300 C SL11506OOOO
Insulating-Tube Small 3-Pole
800-1600 C/H & 400-2000 S1, 400-2000 G SL10062OOOO
2000/2500 C/H & 2500/3200 S1, 3200C SL10064OOOO
3200 H0/H1/H2, 400O H0/H/H2 SL10066OOOO
Insulating-Tube Small 4-Pole
800-1600 C/H & 400-2000 S1 SL10063OOOO
2000/2500 C/H & 2500/3200 S1, 3200C SL10066OOOO
3200 H0/H1/H2, 400O H0/H/H2 SL10509OOOO
Insulating-Hylum Tube Pillar (CT TUBES)
800-1600 C/H & 400-2000 S1, 400-2000 G (3P) SL10067OOOO
800-1600 C/H & 400-2000 S1 (4P) SL10067OOOO
2000/2500 C/H & 2500/3200 S1 (3P) SL10070OOOO
2000/2500 C/H & 2500/3200 S1 (4P) SL10070OOOO
3200 H0/H1/H2, 400O H0/H/H2 (3P) SL10067OOOO
3200 H0/H1/H2, 400O H0/H/H2 (4P) SL10067OOOO
Front Facia Top Cover
800-1600 C/H , 400-2000 S1 & 400-2000 G (3P) SL50202OOOO
800-1600 C/H & 400-2000 S1 (4P) SL50203OOOO
2000/2500 C/H & 2500/3200 S1 (3P) SL50204OOOO
2000/2500 C/H, 2500/3200 S1 (4P) &
SL50206OOOO
3200 H0/H1/H2, 400O H0/H/H2 (3P),
3200 D, 4000 C (3P) SL50215OOOO
3200 D, 4000 C (4P) & 5000/6300C (3P) & 3200HO/H1/H2, 4000HO/H/H2 (4P) SL50247OOOO
5000/6300 C (4P) SL50262OOOO

11-7
Description Cat No
Front Facia Side Cover
800-1600 C/H & 400-2000 S1 (4P) SL50197OOOO
2000/2500 C/H & 2500/3200 S1 (3P) SL50198OOOO
2000/2500 C/H & 2500/3200 S1 (4P) &
SL50200OOOO
3200HO/H1/H2, 4000HO/H/H2 (3P)
3200 D, 4000 C (3P) SL50201OOOO
3200 D, 4000 C (4P) & 5000/6300C (3P) & 3200HO/H1/H2, 4000HO/H/H2 (4P) SL50248OOOO
5000/6300 C (4P) SL50263OOOO
Facia assembly
Front Facia Fixing Kit SL94649OOOO
Front Facia - for Manual ACB SL93201OOOO
Front Facia- for Electrical ACB SL93202OOOO
Cradle Facia SL95260OOOO
Motor
Motor 240V AC SL00315OOOO
Motor 110V DC SL00346OOOO
Motor 220V DC SL00347OOOO
Motor Limit Switch SL92795OOOO
Hardware it for Motor SL93076OOOO
Main Spring
MAIN SPRING 800-1600 C (3P),1600 S1 (3P) (Green) SL90686OOOO
MAIN SPRING 400-1250 S1 (3P) (Black) SL90028OOOO
MAIN SPRING 800-1600 C (4P), 2000-2500 C (3P), 800-1600
SL90687OOOO
H,2000-3200 S1 (3P), 630-1600 S1 (4P) (Blue)
MAIN SPRING 2000/2500 H (4P), 3200 D& 4000 C (3P) (Yellow) SL92735OOOO
MAIN SPRING 5000/6300 C (3P), 3200 D& 4000 C (4P) (Grey) SL93953OOOO
MAIN SPRING 2000/2500 H (3P), 2000-3200 C (4P), 2000-3200 S1
SL91938OOOO
(4P), 800-1600 H (4P) (White)
MAIN SPRING 3200HO/H1/H2 (3P), 4000HO/H/H2 (3P) (Violet) SL93797OOOO
MAIN SPRING 3200HO/H1/H2 (4P), 4000HO/H/H2 (4P) (Light Green) SL93266OOOO
MAIN SPRING 5000/6300 C (4P) (Orange) SL93100OOOO
FRCD
FRCD 400-3200S1 (3P & 4P), 800-3200C (3P & 4P), 800-2500H (3P
SL90825OOOO
& 4P), 3200HO/H1/H2 (3P), 4000HO/H/H2 (3P)
FRCD 3200HO/H1/H2 (4P), 4000HO/H/H2 (4P), 4000-6300C (3P & 4P) SL92642OOOO

Main Spring Motor FRCD


11-8
Description Cat No
Mechanical operation counter
Mechanical operation counter XM80837OOO
Mounting kit for counter assembly SL95882OOOO
MDO to EDO Conversion kit
MDO to EDO 400-3200 S1, 800-2500C/H (3P &4P), 3200 HO/H1/H2,
ST31583OOOA
4000 HO/H/H2 (3P)
MDO to EDO 3200 HO/H1/H2 , 4000HO/H/H2 (4P) ST31583OOOB
MDO to EDO 3200D, 4000/5000/6300 C (3P & 4P) ST31583OOOC
Twisted Link Kit - MF/MDO SL94642OOOO
FRCD Roller Kit SL94647OOOO
Lockable Trip-push Button
Lockable Trip-push Button Type-AA SL93148OOOA
Lockable Trip-push Button Type-BB SL93148OOOB
Lockable Trip-push Button Type-CC SL93148OOOC
Lockable Trip-push Button Type-DD SL93148OOOD
Locking-in Isolated Position (LIP) Type-A SL93146OOOA
Locking-in Isolated Position (LIP) Type-B SL93146OOOB
Locking-in Isolated Position (LIP) Type-C SL93146OOOC
Locking-in Isolated Position (LIP) Type-D SL93146OOOD
Locking-in Any Position (LAP) Type-A SL93147OOOA
Locking-in Any Position (LAP) Type-B SL93147OOOB
Locking-in Any Position (LAP) Type-C SL93147OOOC
Locking-in Any Position (LAP) Type-D SL93147OOOD
Racking-interlock Type- AA SL93149OOOA
Racking-interlock Type-BB SL93149OOOB
Racking-interlock Type-CC SL93149OOOC
Racking-interlock Type-DD SL93149OOOD
Door Interlock SL93150OOOO
LTPB 3 I/C +2 B/C SL91936OOOO
LTPB 5 I/C +4 B/C ST30051OOOO
LTPB 4 I/C +3 B/C ST30052OOOO
LTPB 3 I/C +2 B/C (Type-L) SL01526OOOO
LTPB 3 I/C +2 B/C (TYPE-M) SL01527OOOO
LTPB 3 I/C +2 B/C (TYPE-N) SL01528OOOO
LTPB 3 I/C +2 B/C (TYPE-LM) SL01529OOOO
LTPB 3 I/C +2 B/C (TYPE-MN) SL01530OOOO

11-9
Description Cat No
Spring Kit
Roller Assy. SL90739OOOO
Hardware Kit SL91093OOOO
CONV. KIT AUTO-MANUAL - C2 SL92716OOOO
PUSH BUTTON-RED SL92635OOOO
PUSH BUTTON-GREEN SL92636OOOO
Racking Handle (upto 2500 H & 3200 C/S1) SL93151OOOO
Racking handle (3200 H2 & Above) SL93251OOOO
Operating Handle SL91623OOOO
Control Box (DVB) SL71256OOOO
R.O.H. MANUAL 800-2500A (DVB) SL60631OOOO
R.O.H. MANUAL 400A (DVB) SL60632OOOO
GRIP FOR Operating Handle SL50055OOOO
6 way Secondary isolating contact SL92701OOOO
Microswitch for voltmetric releases each SL92703OOOO
Microswitch for common indication of O/L & S/C (3) each SL92704OOOO
Microswitch for separate indication of O/L & S/C (3) each SL92705OOOO
Service position microswitch - Right SL93142OOOO
Service position microswitch - Left SL93143OOOO
Test or isolated position microswitch - Right SL93144OOOO
Test or isolated position microswitch - Left SL93145OOOO
Telescopic Rail (L) SL90773OOOO
Telescopic Rail (R) SL90774OOOO
6 WAY SIC BLK. SL92701OOOO
Trip-rod Assy. EA / MV SL92626OOOO
Trip-latch SL90715OOOO
Bezel FIXED BREAKER SL91601OOOO
Bezel DRAWOUT BREAKER SL91602OOOO
Main shaft assembly, 5000/6300 C4- Pole SL93252OOOO
Spring Charging Indication SL96000OOOO

Push Button Racking Handle

11-10
HE BREAKERS SPARE PARTS

Description Cat no.

Pole Assembly Fix Breaker


Pole Assembly 1250HE SL93039OOS5
Pole Assembly 2000HE SL91524OOS5
Pole Assembly Draw-out Breaker
Pole Assembly 1250HE SL93192OOS5
Pole Assembly 2000HE SL92730OOS5
Pole Assembly 3200HE (2 PER PACK) SL91225OOS5
Pole Assembly 5000HE SL91961OOS5
Cradle Terminal Assembly
Cradle Terminal Assembly 1250HE SL91823OOS5
Cradle Terminal Assembly 2000HE SL91826OOS5
Cradle Terminal Assembly 3200HE SL91947OOS5
Cradle Terminal Assembly 5000HE SL91971OOS5
Vertical Terminal Assembly
Vertical Terminals 1250HE SL93282OOS5
Vertical Terminals 2000HE SL93285OOS5
Vertical Terminals 3200HE SL93288OOS5
Jaw Contact Assembly
Jaw Contact Assembly 1250HE SL91816OOS5
Jaw Contact Assembly 2000HE SL92726OOS5
Jaw Contact Assembly 3200HE (2 PER PACK) SL95982OOS5
Jaw Contact Assembly 5000HE SL91976OOS5
CT for SR18G with Display
1250HE SL95964OOS5
2000HE SL95965OOS5
3200HE SL95966OOS5
5000HE SL95967OOS5

11-11
REPLACEMENT OF SPARES

11.2 REPLACEMENT OF SPARES COMMON FOR ALL ACBs


NOTE: Refer to section 10 for adjustment and inspection.

5 11.2.1. THERMOMAGNETIC TYPE: DN1


1
Remove the front facia (refer clause 10.3.10).
7 6
Refer to Fig. 11-1. In ‘Open’ condition of the breaker,
disconnect the wires from terminals (1) & (5) – as applicable –
and disconnect connecting piece (6) from Trip rod (3) by
removing pin (7). Remove screws (8). Remove the release and
disconnect connecting piece (6) from it. To refit, proceed in
3 8 reverse order. Grease the connecting pins. Make the connections
Fig. 11-1 as per the wiring diagram given on the cover of the
release (as shown in Fig. 11-1).

3 BRACKET

11.2.2 MICRO PROCESSOR BASED OVERCURRENT


1
2 RELEASE TYPE : SR Release
Remove the front facia (refer clause 10.3.10).
Remove the top cover. Refer the Fig. 11-2. Disconnect
the 9-pin female connector(s) (1) by pressing the top and bottom
flanges (2) and pulling the connector(s) (1) away from the release.
Remove screw (3) (fixing the bracket to the release). Remove three
nos. of screw (4). Remove the release. To refit, proceed in reverse
Fig. 11-2 4 order (as shown in Fig. 11-2).

11.2.3 VOLTMETRIC RELEASES


16
11 17 15 Refer to Fig 11-3.
In ‘Open’ condition of the breaker. Disconnect the wires from
terminals (11). Disconnect the rod (15) from trip rod (13) by
removing pin (16). Unscrew nuts (12). Remove the support and
release assembly, loosen the screws (17), remove the release from
its support and disconnecting rod (15) (as shown in Fig. 11-3).
12 14 13
To refit proceed in reverse order. Grease the connecting pins.
Fig. 11-3

11-12
11.2.4 AUXILIARY CONTACT BLOCK
(For both 2N/O + 2N/C & 6N/O + 6N/C)
Disconnect the connections.
Loosen the screws and remove the auxiliary contact block.
To refit, proceed in reverse order, make sure rotary switch
link is placed properly.
Make the connections as per the wiring diagram shown in
Section 13 and the ferrules attached (as shown in Fig. 11-4) .

Fig. 11-4

11.2.5 MOVING SECONDARY ISOLATING CONTACT BLOCK:


Disconnect the wires.
Remove the fixing screw of the SIC block
To refit proceed in reverse order.
Make the connections as per the wiring diagram shown in Section 13.
(as shown in Fig. 11-5).

Fig. 11-5
11.2.6 FIXED SECONDARY ISOLATING CONTACT BLOCK
Remove wire cover by unscrewing screws (1).
Disconnect the wires.
To refit, proceed in reverse order.
1
Make the connections as per the wiring diagram shown in Section 13.
(as shown in Fig. 11-6).

2 11.3 REPLACEMENT OF SPARES FOR 400-2000E, 400-2000G,


Fig. 11-6 400- 3200S1, 800-3200C, 1600D, 1250HE, 2000HE, 3200HE
800-2500H, 3200H0/H1/H2 & 4000 H0/H/H2
NOTE: Spare kits accompany detailed instructions on HOW TO
1
CONNECT & TEST a particular accessory.

11.3.1 ARC CHUTE


Press latching lever (1) and rotate it.
Remove the arc chute by pulling it upwards.
To refit, place the arc chute over the arcing horns (2) and rotate the latch
2 for locking. (as shown in Fig. 11-7)

Fig. 11-7

11-13
E 11.3.2 ARCING CONTACTS
2
11.3.2.1 FIXED ARCING CONTACTS

1
Replacement of fixed arcing contacts is to be done in ‘Open’
condition of the breaker.
Loosen the screws (1) and slide the arcing contacts forward.
To refit, proceed in reverse order. (as shown in Fig. 11-8)

11.3.2.1 MOVING ARCING CONTACTS :


Replacement of moving arcing contacts is to be done in
‘Closed’ condition of the breaker.
Fig. 11-8 Loosen the screws (2) by about 1.5 mm to disengage locating
boss (E) and then pull upwards.
To refit, proceed in reverse order (as shown in Fig. 11-8) .

Note: Spare kits accompany detailed instructions on how to connect & test a particular accessory.

11.4 REPLACEMENT OF SPARES FOR C3 & C4 D/O ACB’s


11.4.1 JAW CONTACTS
Ensure orientation of steps while mounting jaw contacts on
upper and lower terminals of breaker as shown in Fig. 9-9

Plain Surface
Small Step

Small Step
Big step

3200D 4000C/5000C/5000HE/6300C

For Upper Terminals

Small Step
Big step

Plain Surface
Small Step

3200D 4000C/5000C/5000HE/6300C

For Lower Terminals

Fig. 9-9 11-14


12. OVERALL DIMENSIONS
12.1 DIMENSIONAL DETAILS FOR FIXED BREAKERS
12.1.1 For CN-CS...E 400A-2000A 3P

340 min
Insulator

40 min +1.0 40 min


316 20 min

100 min
56 102 102 56 30
Z

X
385
325

285

4 HOLES X
Ø12
227

20 20 216
32

22 137.5 298
402 21
179.5

Terminal Connections
2 Holes-ø13
Rating Type X Y Z
30 15

400A -1250A 5 150 35.5

1600A 10 145 23.5 25 12.5


50

2000A 15 140 23.5 400A - 2000 A

Note : All Dimensions are in mm.


Consider door to front facia Gasket thickness of 2.5mm thick.

12-1
12.1 DIMENSIONAL DETAILS FOR FIXED BREAKERS
12.1.2 For CN-CS...G 400A-2000A 3P

for Metallic Components

To Remove
340 min Arc Chute
for Insulating Sheet

200 min
7
36 min 326 36 min

140 min
Door

100 min
20 min Bezel
26 58 264 26

27
9
394

309

4 Hole-Ø12

385

256
for Mounting 33
(21)

104

22

68.8
15 15
27
216
Earthing Terminal 30 35
20 301 54
2 Holes-Ø6.3 2.6 min
405 86 10

56 102 102 56

35.5

23.5 23.5
5 10 15

5 10 15
227
227
227

140
145
150

Terminal for 400/630/800G Terminal for 1600G Terminal for 2000G


1000/1250G

Terminal Connections
2 Holes-ø13

30 15

25 12.5
50

400A - 2000 A

Note : All Dimensions are in mm. 12-2


12.1 DIMENSIONAL DETAILS FOR FIXED BREAKERS
*
12.1.3 For 400A to 1600A 3P/4P S1, 800 to 1600A 3P/4P C/H, 2000A to 2500A 3P C/H, 3200A 3P C,
1250HE 3P/4P, 2000HE 3P
for Metallic Components

To Remove
340 min Arc Chute
for Insulating Sheet

200 min
7
36 min A 36 min

140 min
Door

100 min
20 min Bezel
26 58 264 26

27
9
394

16
309

16 4 Hole-Ø12

385

256
for Mounting 33
(21)

104

22

68.8
16 16
27
216
Earthing Terminal 30 35
230
20 301 54
D E F E D 2 Holes-Ø6.3 2.6 min
405 86 10

#
35.5 35.5 23.5 23.5

5 8 10 15

5 8 10 15
227

227
227

227
150

145

140
147

Terminal for Terminal for Terminal for 800 C, Terminal for 1600 S1
400/630 S1 800/1000 S1 1000 C &1250 S1 800/1000 H, 1250/1600 C/H/,
#
35.5 : For 1250S1 2000/2500 C/H/HE & 3200C
1250HE

Terminal Connections
Ratings Dimensions(mm) 2 Holes-ø13
CN-CS
A D E F 30 15

400/630/800/1000/1250/1600A S1 3P
800/1000/1250/1600A C/H 3P 326 57 102 -
12.5
1250A HE 3P 25
400/630/800/1000/1250/1600A S1 4P 50

800/1000/1250/1600A C/H 4P 414 56 98 98 400/630 S1 & 800/1000/1250/1600 C/H/S1,1250HE


1250A HE 4P
2000/2500A 3 Holes-ø13
C/H 3P
2000A HE 3P 482 83 154 - 30
15
3200A* C 3P

Note : All Dimensions are in mm.


25 25 25 25
* Special Version (3200C x 3P/4P)
made for Export Only 100

2000-2500 C/H & 3200 C/2000HE

12-3
DIMENSIONAL DETAILS FOR FIXED BREAKERS
12.1.4 For 2000A to 2500A 4P C/H & 3200A 4P C, 2000A HE 4P
for Metallic Components

to Remove
340 min Arc Chute
for Insulating Sheet

200 min
7
36 min A 36 min

140 min
Door

100 min
20 min Bezel
26 58 264 26 9
27

4 Holes-Ø10

385
for Mounting

256
33
394

16
309

16

22
(21)

27
104

68.8
230
Earthing Terminal 30 35
20 301 54
2 Holes-Ø6.3 2.6 min
D E F E D 405 10
86

23.5
15

15
227
140

Terminal for 2000-2500 C/H/HE & 3200 C, 2000HE

Terminal Connections

3 Holes-ø13
Ratings Dimensions(mm)
CN-CS 30
A D E F 15
2000/2500A C/H 4P

2000A HE 4P 628 82 150 156


3200A * C 4P
25 25 25 25
Note : All Dimensions are in mm.
* Special Version (3200C x 3P/4P)
made for Export Only 100

2000-2500 C/H/ & 3200 C,2000HE

12-4
DIMENSIONAL DETAILS FOR FIXED BREAKERS
for Metallic Components
12.1.5 For 3200D/4000C 3P/4P
to Remove
356min Arc Chute
16min for Insulating Sheet

200min
B

140min
7

100min
26 58 264 Door
Bezel

27
71

503
509

25
394

256
309

22

27

68.8
33
21

Earthing Terminal 230 2.6min


16 2 Holes-ø6.3 20 54
27 140
444 85 10
36 min 36 min

4 A 4
Terminal Connections
D E E F D 71
26 26 15 6 Holes-Ø14

30
15

70
15
287

30 50 50
173.5

160

For 3200D/4000C
Terminal for 3200D / 4000C
102

Dimensions (mm)
Ratings
CN-CS A B D E F
16 16
4 Holes-ø12 for Mounting
3200D/4000A C 3P 628 636 112 202 -
Rear View

3200D/4000A C 4P 830 838 112 202 202

Bezel Fixing Plan for all Fixed Breakers


Hinge 305
Hinge 12 Holes-Ø4 101 332
112
325

363
112
A

112

5.5

11 min 59 294 15 min


Door Cutout Bezel
Door Drilling for
Note : A = 89 for 4000C/3200D
A = 91 for other fixed ACBs
Bezel Fixing Plan

Note : All Dimensions are in mm. 12-5


12.2 DIMENSIONAL DETAILS FOR DRAW-OUT BREAKERS
12.2.1 For 800A to 2500A C/H, 3200C, 3200A H1/H2, 4000A H/H2, 400A to 3200A S1 3P/4P
1250A HE, 2000A HE, 3200A HE3P/4P for Metallic Components
75 Isolated Position
A
380 min
51 Test Position

200 min
122 for Insulating Sheet
40 max 7

100 min
94.5 264 Service Position Door
64.5 Bezel

26

256
468

397.5
404

160
M 10
46 28
4 74

68.8
6 54
(10)
17.5 min.
20
199.5 6 18.9 max.
538 18 245
8.9 min.
Earthing Terminal
D E F E D
64.5 40 40 65 60
5 5 25 15
10 15 15
308.5
308.5

308.5
308.5

221.5

221.5

221.5
221.5

Terminal for 400S1 Terminal for Terminal for Terminal for


630/800/1000/1250 S1 1250/1600/2500C/H/ 3200 S1/C 3200H1/H2, 3200HE
& 800/1000C, 2000C, & 800/1000/2000H/ & 4000H/H2
2500S1 1600/2000S1, 1250HE, 2000HE

Ratings Dimensions (mm) Dimensions (mm)


Ratings
CN - CS A D E F HE-Range A D E F
400/630/800/1000/1250/1600/2000A S1 3P 1250HE 3P 399 97.5 102 -
399 97.5 102 -
800/1000/1250/1600A C/H 3P 1250HE 4P 487 96.5 98 98
400/630/800/1000/1250/1600/2000A S1 4P 2000HE 3P 555 123.5 154 -
487 96.5 98 98
800/1000/1250/1600A C/H 4P 2000HE 4P 701 122.5 150 156
2500/3200A S1 3P 3200HE 3P 701 148.5 202 -
2000/2500/3200A* C 3P 555 123.5 154 - 3200HE 4P 909 151.5 202 202
2000/2500A H 3P
2500/3200A S1 4P
2000/2500/3200A* C 4P 701 122.5 150 156
2000/2500A H 4P Note : All Dimensions are in mm.
3200A H1/H2 3P * Special Version (3200C x 3P/4P)
701 148.5 202 - made for Export Only
4000A H/H2 3P
3200A H1/H2 4P
909 151.5 202 202
4000A H/H2 4P continued.... 12-6
DIMENSIONAL DETAILS FOR DRAW-OUT BREAKERS
Flat Terminal Connections
100 63
50
25 30 30 25

20 19
12.5 10.2 10.2 10.2

4 Slots 6 Slots 4 Slots


58.4

58.4

58.4
38

8.5 x 9.5

38

38
8.5 x 9.5 8.5 x 9.5

8.5 8.5 8.5

800 - 1000C & 400-1250S1 2000C 800-1000H,1250HE, 1250/1600C/H


& 1600-2000S1

106 106

33 33 33 33

20 20

12
12

6 Holes-Ø14
67
43

62
38

6 Holes-Ø14
2000H/HE & 2500C/H 2500S1

106 160
25 25 25 25 25
33 33 6 Holes-Ø14
17.5
20
12

6 Holes-Ø14
70
43

25
67

50

12.5

3200C/S1 3200H1/H2/HE & 4000H/H2

12-7
DIMENSIONAL DETAILS FOR DRAW-OUT BREAKERS
12.2.2 For 3200D/4000C 3P/4P, 5000HE/5000C/6300C 3P/4P
A
124
for Metallic Components
96.5 264

400min
75 Isolated Position

for Insulating Sheet 51 Test Position

200min
40max Service Position

100min
102
404

Terminal for 3200D


28
5

26
6

199.5
467
368

FRONT VIEW M 10
256

160
(74)
D E E E D

28
5
10

20
5 17.5min
1 18.9max
615 8.9min

18 245
583

SIDE VIEW

42 54 67

15 15
64.5 Earthing Terminal

REAR VIEW
368

368

8 Holes-Ø14
256

256

217
160

25 25 25 25 25
6 Holes -Ø 14
17.5
63

28
Terminal for Terminal for
17.5 4000 C 5000C/HE & 6300C
25
50

40 50 40 43.5
12.5

7
Door
Bezel
Terminal Connections
Terminal Connections 4000C 5000C/HE & 6300C 160

60 60

Dimensions (mm) 20
256

Ratings 12
CN-CS A D E
6 Holes-Ø14
46

70

3200D/4000C 3P 711 155.5 200


68.8

3200D/4000C 4P 913 156.5 200


10 54
5000HE/C/6300C 3P 913 187.5 269
Terminal Connections 3200D
5000HE/C/6300C 4P 1182 187.5 269
Note : All Dimensions are in mm. 12-8
DIMENSIONAL DETAILS FOR DRAW-OUT BREAKERS
12.2.3 Mounting Details :- For Horizontal Mounting of all Draw-out Breakers

For 3P/4P 630A to 2500C/H//S1,1250HE, 2000HE, 3200C/S1/H1/H2/HE, 4000H/H2


107.5 367.5 40 10 Holes-Ø11 for Mounting G
Ratings Type
24 (mm)
800A - 1600A 3P C/H/HE 280.3
400A - 2000A 3P S1 280.3
800A - 1600A 4P C/H/HE 368.3
400A - 2000A 4P S1 368.3
2000 / 2500A 3P C/H/HE 436.3
*G

Front 2000 / 2500A 4P C/H/HE 582.3


2500 / 3200A 3P S1 436.3
2500 / 3200A 4P S1 582.3
3200A 3P H1/H2/HE 582.3
24 4P H1/H2/HE 790.3
3200A
64.1

4000A 3P H / H2 582.3
4000A 4P H / H2 790.3
20 481 37

For 3200D/4000C/5000C/HE/6300C 3P/4P


592
10 Holes-Ø11 for Mounting
552
25

Ratings Dimensions
CN-CS
A
3200D/4000C 3P 711
3200D/4000C 4P 913
A

Front
5000C/HE, 6300C 3P 913
5000C/HE, 6300C 4P 1182

25

50
108.5
184.5

12.2.4 Bezel Fixing Plan for all Draw-out Breakers


6 Holes-Ø4 305 332
Hinge Hinge
224
412

450
199

5.5
1
Base of
Cradle

20.5 min A 294 5 min Door Drilling Bezel


for Bezel Fixing Plan
Door Cutout

Note :For 3200A D 3P/4P, 4000A C 3P/4P, 5000HE/C/6300C 3P/4P ACB, A=81.5
For other Drawout Breakers A=79.5 Note : All Dimensions are in mm 12-9
DIMENSIONAL DETAILS FOR DRAW-OUT BREAKERS

12.2.6 Door Interlock fixing for Plan for all Draw-out Breakers

DOOR

HOLES Ø8.5
HOLES Ø12.5
15
111.4

10.5 CRADLE
BRACKET TO BE WELDED TO THE
DOOR FROM INSIDE AFTER ALIGNING
THE Ø12.5 HOLE OF THE
BRACKET TO THAT OF THE DOOR.

12.2.7 OTHER TERMINAL ORIENTATIONS FOR DRAW-OUT ACBs

12.2.7.1 Horizontal Terminals


Rear Side
85 85 85 97 110
10

10
15

15

15
308.5

221.5

800 - 1000C 1250 - 1600C/H 2000C 2500C/H 3200 H0/H1/H2


& 800/1000H & 2000H & 4000 H0/H/H2
2 Holes-Ø14 3 Holes-Ø14 4 Holes-Ø14 6 Holes -Ø 14
6 Holes -Ø14
12.5

20
12.5

16.5

25 25 25 25 25
15

25 25 25

33 33
106
100

160
50

63
25

16.5

12.5 25 12.5 30
60 12.5 25 12 43
60
17.5

60 72 12.5 25
85

Note : All Dimensions are in mm 12-10


12.2.7 OTHER TERMINAL ORIENTATIONS FOR DRAW-OUT ACBs

12.2.7.2 Vertical Terminals

V S W

U 40

4 Holes-ØT Q P Top

R
N
M
387.5
X

308.5
221.5

Side View Rear View

Ratings M N P Q R S T U V W X
400-1250 S1 & 800-1000 C 10.2 38 20 25 29.2 5 9 65 95 10 58.4
1600-2000 S1 & 1250 HE,1250-1600 C/H
20 40 20 25 29.2 5 9 65 95 10 80
800-1000 H
2000 C 20 40 20 40 29.2 22.5 14 80 110 15 80
2000 HE, 2500 S1/C/H
20 40 20 40 33.5 7.5 14 80 110 15 80
2000 H
3200 S1 30 60 20 40 33.5 7.5 14 80 110 15 120

12.2.7.3 Vertical Terminals 3200 H1/H2/HE, 4000 H/H2


V
U S W
6 HOLES- ØT
Q P 60

Top
M NN

R
387.5
X

308.5
221.5

Side View Rear View

Ratings M N P Q R S T U V W X
3200 H1/H2/HE, 4000 H/H2 30 50 45 40 22.5 95 14 105 135 15 160

Note : 1) All Dimensions are in mm. 2) Consult us for other Terminal Orientations.
12-11
12.3 REPRESENTATIVE TERMINATION ARRANGEMENT

12.3.1 For 3-Pole breaker

Fixed Support

First Fixed Support


100 mm Min

12-12
REPRESENTATIVE TERMINATION ARRANGEMENT
12.3.2 For 4-Pole breaker

Fixed Support

First Fixed Support


100 mm Min

Note : In 4-Pole ACBs, neutral pole is fully rated.


Hence the poles at either extreme can be used
as the neutral.

Note : Factory gives NRYB configuration when


viewed from the front of the ACB as standard.

12-13
12.4 External Neutral CT

For earth fault protection and protection of neutral against overload, neutral CT is required.
For 4- pole breakers, the CT is provided inside the breaker, whereas for 3 pole breakers,
external CT is required to be provided.

It important that with C-POWER breaker, special neutral Cts supplied by L&T are used.

H1

H2

W1 D1
W2

CT Dimensions
Breaker rating Window (min) External (max)
W1 H1 W2 H2 D1
400/630 S1/E/G 52 11 94 94 40
800 C/S1/H/E/G 52 16 94 99 40
1000 C/S1/H/E/G 52 16 94 99 40
1250 C/S1/H/HE/E/G 52 16 94 99 40
1600 C/S1/H/E/G 52 16 94 99 40
2000 S1/E/G 52 16 94 99 40
2000 C/H/HE 102 16 146 99 40
2500 C/S1/H 102 16 146 99 40
3200 C/S1 102 16 146 99 40
3200 H1/H2/HE 150 16 190 99 40
4000 H/H2 150 16 190 99 40
3200 D, 4000 C 144 25 192 110 40
5000 C/HE 220 25 259 110 45
6300 C 220 25 259 110 45

Note : All Dimensions are in mm


12-14
12.5 GOOD TERMINATION PRACTICES

The following points will help make a good electrical joint having low contact resistance and hence lower
temperature rise :

1. Inspection of links:
? Bending of the links, if any, and position of the termination holes should be such that the mating surfaces
shall meet in a plane.
? Bending radius should be at least equal to 2 times the thickness of the busbar.
2. Preparing the link:
? Ensure that the holes are free from burrs.
? Aluminium to aluminium joint-
? Clean the contact surfaces (just prior to the joining) with a wire brush to obtain a bright finish.
? Remove metal particles from surfaces and edges with a clean cloth.
? Apply a thin film of contact grease (neutral petroleum jelly) immediately to avoid oxidation.
? Aluminium to copper joint-
This is applicable to joint between ACB terminals and links.
? Clean the ACB terminals with cloth only.
? If silver plated aluminium is used then clean the area of the joint with cloth only.
? If bare aluminium is used then clean the contact surfaces (just prior to the joining) with a wire brush to
obtain a bright finish. Remove metal particles from surfaces and edges with a clean cloth and apply a
thin film of contact grease (neutral petroleum jelly) immediately to avoid oxidation
3. Sleeve or tape should not be sandwiched in the intended area of contact.
4. When joining busbars, the overlap of the busbars should be equal to the width of the busbar.
5. Use right size (correct length and diameter) of bolts with plain and conical spring (Belleville) washers.
If aluminium hardware is used then only plain washers can be used.
6. Recommended tightening torque for aluminium joints is as follows,

Torque (kgf-m)
Bolt Size Standard High-tensile
M8 0.85 2.5
M10 1.88 4.7
M12 3.2 7.8
M16 7.3 18.0

Tightening should be done using a torque wrench or equivalent tool. Do not over-tighten the joint.
7. After termination a minimum gap equal to the thickness the busbars is to be maintained during the
subsequent run.
8. Supports:
? Should provide minimum 2 supports in order to prevent the weight of links on ACB terminals:
st
? 1 support < 100mm
? Other supports should be provided at regular intervals so that stresses induced during short circuit do
not exceed the elastic limit of the link material.
9. Corrosive atmosphere:
? Corrosive atmosphere has a profound effect on connections. Nonconductive layers are formed on the
connecting surface which heats up the joint and deteriorates the performance. Frequent maintenance of
the joints / connections is required in such cases. Monitoring the joint temperatures with non-contact
thermometers is also useful.
For Atmosphere having Harsh Environment, it is recommended to use C-Power “HE” Range of ACBs.12-15
13. WIRING DIAGRAMS
13.1 WIRING DIAGRAM FOR C-POWER ACBs
N R Y B

(+24V DC)
1 3 5 AS+ 7 9 11 13 15 E C 81 42 41 J 50 73 70 E

(
(

(
(

(
(

(
R
CA-1

Only for DC
x x x x
C11

(
4
Internal Wiring

SR18G+D
(

Electrical
DN1/SR18

Internal Wiring
SR18G/SR18G+D
anti-pumping
CC NCT MV CP
SR21i/SR71
F H
EA/
EA1

ECD
(

81
(

82
(

C6

(
(

(
(

(
(
(

(
(

(
(

(
(
(-24V DC)
@
Load 2 40 6 AS- 8 10 12 14 16 A B D 82 41 42 K 52 55 74 75 71 72 B

Main Protection & Aux Shunt Aux Power Aux Aux Aux Aux Electric U/V Closing Spring Common Separate Shunt Under
Supply
Aux Closing Neutral Electrical
Circuit Control Unit NC Release NC for SR18G NO NC NO NC NO Coil Charging C.T. Release Preventer Charging fault fault trip voltage anti-pumping
with Display Device Indication Indication Indication Indication Indication
Ref no. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

As per order/requirement

FCA Limit switch(Shown in breaker reset condition)


The above drawing is for EDO breakers.
R Economy Resistor
1) For MDO/MF versions
C11 Limit switch operates when closing electromagnet is held on
Ref no. 3, 11, 12 are not applicable
C6 ‘Service’ position microswitch for withdrawable circuit breakers (shown in ‘test’ position)
E, B, C, D, A, 15 are applicable only in electrical breakers.

2) For EF versions For SR 21i release (P&C unit)


The ref. no. 13, 14, 15, 16, 17, 18, 19, 20, 21 are provided SI, SO I discrimination Short ckt i/p & o/p
as per customer requirement. GI, GO I discrimination Ground fault i/p & o/p
G Ground

# Available for manual ACBs as well .


13 12
* CA1,N.O. Contacts 3 & 4 not available for auxiliary use,
CA4 CA3
14 11 if shunt release type EA/EA1 is used.

@ SIC-A
15 10

CA4 CA3
16 9
TEST SERVICE
17 8
BREAKER AUXILIARY CONTACTS

CA5 CA2 Programmed to complete the circuit only in ‘Test’


18 7
position. This enables carrying out operations of
breakers by bypassing the electrical interlocks
19 6 which are active in ‘Service’ position.
CA5 CA2 NOTE : 1. Max 24 SICs available on ACB (For control, accessories and auxiliary circuits)
20 5
2. For Electrical ACBs
A,B,C,D & E are used for internal breaker wiring.
21 4 Applicable only for AC control supply

CA6 *
CA1 3. For 4P breakers 81,82 are not available.
22 3
# 4. When using An1 Annunciator Module with SR18G/18Gi (with display releases)
23 2 A) AS+ & AS- always appear after 5,6 nos. of the SIC.
B) If 1,2,3,4,5,6 nos. of SICs are not there, AS+ & AS- will appear first.
CA6 CA1 C) SIC 13 and 14 Nos. are not offered in 3P EDO and 3P MDO standard breakers.
24 1
5. Wiring diagrams of Earth fault trip indication is similar Shunt /Undervoltage trip indication.

13-1
13.2 SIGNALLING

13.2.1 SPRING CHARGE INDICATION 13.2.2 SIGNALLING FOR VOLTMETRIC RELEASES


(FOR ELECTRICAL ACBs)
13.2.2.1 SHUNT RELEASE
BPED
L8 L5

L9

70 65
B7 B8 73
H
74
FCA G
M
D
13.2.2.2 UNDER VOLTAGE RELEASE
BPED
L4

13.2.3 BREAKER ON-OFF INDICATION


L10

L11 72
B5 70
63

CAI
71

13.2.4 POSITION INDICATION INDICATING LAMPS


13.2.4.1 ISOLATED / TEST POSITION
L4-for Under Voltage Trip
L6/12 C8 OR C9
L5-for ‘Shunt’ Trip
L6-for ‘Isolated’ and/or ‘Test Position’
L7-for ‘Service Position’
L8-for ‘Spring Discharged’
L9-for ‘Spring Charged’
13.2.4.2 SERVICE POSITION L10-for ’Breaker On’
L11-for ‘Breaker Off’
L7 C6 OR C7
L12-for ‘Test’ Position
B5, B6, B7, B8 - Contactors Electromagnets
BPED - ‘Signal Cancelling’ Push Button

SIGNALING SWITCHES
13.2.4.3 SERVICE, TEST, ISOLATED POSITION
L7
C3-for ‘Under Voltage’ Trip
C5-for ‘Shunt’ Trip
L12
C6-for ‘Service’ Position (Left)
L6 C7-for ‘Service’ Position (Right)
C6 OR C7
C8 OR C9 C8-for ‘Isolated/Test’ Position (Left)
C9-for ‘Isolated/Test’ Position (Right)
C12-for ‘Earth fault’ Trip
Note : Wiring shown inside dotted lines is internally wired in ACB
13-2
13.2.5 SIGNALLING FOR OVERLOAD AND SHORT - CIRCUIT TRIPPING

13.2.5.1 Manual Reset 13.2.5.2 Auto Reset


The cancelling of the fault signal is effected Cancelling of fault signalling is provided by
by pressing the local trip button, which also push button BPED. The presence of the fault
resets the overcurrent release. signal does not prevent closing of the circuit
breaker.

Common Signalling
Common Signalling
B2

L1 L1
52 C1
52
50 C1 50

51 51
BPED

Separate Signalling Separate Signalling


BPED L2

L3
L2
55
B3
C2

L3
54
B4
55 52
B1
52
C1 50
C2 C1
54 51
51

Signalling Switches

C1-for ‘Overload and Short Circuit’ Trip


C2-for ‘Short Circuit’ Trip

INDICATING LAMPS

L1-Common for ‘Overload and short Circuit’ Trip


L2-for ‘Overload’ Trip
L3-for ‘Short Circuit’ Trip
B1, B2, B3, B4 - Contactors
BPED - ‘Signal Cancelling’ Push button
–( O–– SIC terminals

Note : Wiring shown inside dotted lines is internally wired in ACB

13-3
13.3 WIRING DIAGRAM: 3Ø, 4 WIRE SCHEME (FIXED BREAKERS)

13.3.1 For Earth Fault Protection with DN & EF Release

N R Y B
81

82
DN RELEASE

T1 M1 T2 M2 T1 M1 T2 M2 T1 M1 T2 M2 S

Star Point
TR Phase1 Phase2 Phase3
Red TY Yellow TB Blue S

N R Y B
S C1
A1
A2 EF
RELEASE
A A3

13.3.2 For Earth Fault Protection with SR21i /SR18G/SR18G with Display/SR18Gi with Display Release

N R Y B
81

S1 S1 S1 S1
SR21i CT CONNECTOR

S2 S2 S2
1 2
S2
82
3 4

5 6

7 8

9 10
N R Y B

Note: 1) Wiring Diagram shown is for 3Pole


B±1 ACBs.
2) For 4 Pole ACBs, Neutral CT may
be mounted on Neutral Pole inside
the Breaker and therefore Terminal
A±1

No. 81 (& 82 for SR21i/SR18Gi Release)


may not be required in such cases.

13-4
13.4 WIRING DIAGRAM: 3Ø, 4 WIRE SCHEME (DRAWOUT BREAKERS)
4mm² - Copper Wire

N R Y B
S1 S1

S2 S2

DNRELEASE

T1 M1 T2 M2 T1 M1 T2 M2 T1 M1 T2 M2 S

Star Point
TR Phase1 Phase2 Phase3
Red TY Yellow TB Blue S

N R Y B
S C1
A1
A2 EF
RELEASE
A A3

For Earth Fault Protection with DN & EF Release

13-5
14. SPECIAL APPLICATIONS
14.1. 690V Application of C-POWER ACBs

C-Power breakers are also suitable for operation at 690V with following changes / precautions.
A) Arc chute suitable for 690V to be used.
b) Characteristics such as rated service Short circuit breaking capacity and rated ultimate short
circuit breaking capacity are as specified on label.
c) Only top terminals (marked line) of breaker are to be connected to the incoming side of supply.
The label indicating suitability of the breaker at 690V with special arc chutes is put on the facia of the
breaker.

The label indicating characteristics is put just below the nameplate on the side of the breaker.
The label identifying 'Line' terminal is put above the top terminal on the rear side of the breaker in fixed
ACBs and on the rear side of the cradle in draw out ACBs.

14.2. HE Range of C-Power ACBs.

C-Power breakers with corrosion protection are designed for use in sulphur -rich environments. These include
petroleum refineries, paper mills and water treatment, chemical and synthetic fibre plants- all of which produce
large quantities of sulphur dioxide (SO2) or hydrogen sulphate (H2S).

Conventional circuit breakers used in such an environment require frequent maintenance. The L&T C-Power
breaker with corrosion protection features a special surface treatment on all the parts that are exposed to gases
in a corrosive environment.

These products do not require special maintenance and can operate reliably in the following environmental
conditions:
3C4 for SO2 (concentrations from 4.8 to 14.8 x 10-6)
3C4 for H2S (concentrations from 9.9 to 49.7 x 10-6)

HE Range of C-Power breakers complies with the following IEC standards:


IEC 60721-3-3 - Classification of environmental condition.
IEC 60068-2-42 - Sulphur dioxide test for contacts and connections.
IEC 60068-2-43 - Hydrogen sulfide test for contacts and connection.
IEC 60068-2-30 - Damp heat, cyclic ( 12+ 12- hour cycle).
IEC 60068-2-52 - Salt mist, cyclic.

14-1
Electrical Standard Products (ESP) Branch Offices:

REGISTERED OFFICE AND L&T House, Group MIG - 5 No: 73, Karpaga Nagar, 8th Street
HEAD OFFICE Padmanabhpur K. Pudur
L&T House, Ballard Estate Durg 491 001 Madurai 625007
P. O. Box 278 Tel: 0788-2213833 / 14 / 28 / 29 Tel: 0452-2537404, 2521068
Mumbai 400 001 Fax: 0788-2213820 Fax: 0452-2537552
Tel: 022-6752 5656 e-mail: esp-mdu@LNTEBG.com
Fax: 022-6752 5858 A1/11, Astronauts Avenue
Website: www.Larsentoubro.com Bidhan Nagar EBG North Wing Office - Level 2
Durgapur 713 212 Gate 7, Powai Campus
Tel: 0343-2536891 / 8952 / 7844 Mumbai 400 072
ELECTRICAL STANDARD PRODUCTS (ESP) Fax: 0343-2536493 Tel: 022-67052874 / 2737 / 1156
501, Sakar Complex I e-mail: esp-dgp@LNTEBG.com Fax: 022-67051112
Opp. Gandhigram Rly. Station e-mail: esp-bom@LNTEBG.com
Ashram Road Milanpur Road, Bamuni Maidan
Ahmedabad 380 009 Guwahati 781 021 #12, Shivaji Nagar
Tel: 079-66304007-11 Tel: 0361-2651297 North Ambazari Road
Fax: 079-26580491 / 66304025 Fax: 0361-2551308 Nagpur 440 010
e-mail: esp-ahm@LNTEBG.com e-mail: esp-gau@LNTEBG.com Tel: 0712-2260012 / 3
Fax: 0712-2260020 / 30
38, Cubbon Road, Post Box 5098 II Floor, Vasantha Chambers e-mail: esp-nag@LNTEBG.com
Bangalore 560 001 5-10- 173, Fateh Maidan Road
Tel: 080-25020100 Hyderabad 500004 32, Shivaji Marg
Fax: 080-25580525 Tel: 040-66720250 P. O. Box 6223
e-mail: esp-blr@LNTEBG.com Fax: 040-23296468 New Delhi 110 015
e-mail: esp-hyd@LNTEBG.com Tel: 011-41419514 / 5 / 6
Fax: 011-41419600
131/1, Zone II
e-mail: esp-del@LNTEBG.com
Maharana Pratap Nagar D-24, Prithvi Raj Road, C-Scheme
Bhopal 462 011 Jaipur 302 001
L&T House
Tel: 0755-4098706 / 7 / 8 / 9 Tel: 0141-2385916 / 8
P. O. Box 119
Fax: 0755-2769264 Fax: 0141-2373280 191/1, Dhole Patil Road
e-mail: esp-bho@LNTEBG.com e-mail: esp-jai@LNTEBG.com Pune 411 001
Tel: 020-26135048
Plot No. 559, Annapurna Complex Akashdeep Plaza, 2nd Floor Fax: 020-26124910, 26135048
Lewis Road P. O. Golmuri e-mail: esp-pnq@LNTEBG.com
Bhubaneswar 751 014 Jamshedpur 831 003
Tel: 0674-6451342, 2436696 Jharkhand 3rd Floor
Fax: 0674-2537309 Tel: 0657-2340864 / 387 Vishwakarma Chambers
e-mail: esp-bbi@LNTEBG.com Fax: 0657-2341250 Majura Gate, Ring Road
e-mail: esp-jam@LNTEBG.com Surat 395 002
SCO 32, Sector 26-D Tel: 0261-2473726
Madhya Marg, P. O. Box 14 Skybright Bldg. M. G. Road Fax: 0261-2477078
Chandigarh 160 026 Ravipuram Junction, Ernakulam e-mail: esp-sur@LNTEBG.com
Tel: 0172-4646841 to 7 Kochi 682 016
Fax: 0172-4646802 Tel: 0484-4409420 / 4 / 5 / 7 Radhadaya Complex
e-mail: esp-chd@LNTEBG.com Fax: 0484-4409426 Old Padra Road
e-mail: esp-cok@LNTEBG.com Near Charotar Society
10, Club House Road Vadodara 390 015
Chennai 600 002 3-B, Shakespeare Sarani Tel: 0265-2311744 / 6613610 / 1 / 2
Tel: 044-28462072 / 4 / 5 / 2109 Kolkata 700 071 Fax: 0265-2336184
Fax: 044-28462102 / 3 Tel: 033-44002572 / 3 / 4 e-mail: esp-bar@LNTEBG.com
e-mail: esp-maa@LNTEBG.com Fax: 033-22822589
e-mail: esp-ccu@LNTEBG.com 48-8-16, Dwarakanagar
67, Appuswamy Road Visakhapatnam 530 016
Post Bag 7156 A28,Indira Nagar, Faizabad Road Tel: 0891-6620411-2 / 3
Opp. Nirmala College Uttar Pradesh, Fax: 0891-6620416
Coimbatore 641 045 Lucknow 226 016 e-mail: esp-viz@LNTEBG.com
Tel: 0422-2588120 / 1 / 5 Tel: 0522-2312904 / 5 / 6
Fax: 0422-2588148 Fax: 0522-2311671
e-mail: esp-cbe@LNTEBG.com e-mail: esp-Lko@LNTEBG.com

Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.

Electrical Standard Products


Larsen & Toubro Limited
Powai Campus, Mumbai 400 072
Customer Interaction Center (CIC)
BSNL / MTNL (toll free) : 1800 233 5858
Reliance (toll free) : 1800 200 5858
Tel : 022 6774 5858
Fax : 022 6774 5859
E-mail : cic@LNTEBG.com
Website : www.LNTEBG.com

CD00494

You might also like