You are on page 1of 6

Advanced Synchronous Reference Frame Controller for three-Phase UPS

Powering Unbalanced and Nonlinear Loads

Kyung-Hwan Kim Nam-Joo Park, Dong-Seok Hyun


Ehwa Technologies and Information Company Hanyang University
Department of Power System Department of Electrical Engineering
272-20 Taejun, Kwangjoo, KyungKi-Do, KOREA 17 Haengdang-dong, Seongdong-Gu, Seoul KOREA
Email: hellokim@eti21.com Email: pnano@ihanyang.ac.kr

information of the filter components. Also a heightened


Abstract— This paper describes a high performance voltage sampling frequency is needed to reduce the residue tracking
controller for 3-phase 4 wire UPS (Uninterruptible Power errors. In UPS control system, the phase of the reference
Supply) system, and proposes a new scheme of synchronous voltages are changed continuously for synchronization with a
reference frame controller in order to compensate for the
voltage source of the utility or the other UPS in parallel
voltage distortions due to unbalanced and nonlinear loads.
Proposed scheme in this paper is able to completely eliminate the
operation. This situation will produce a bad effect on the
negative sequence voltage distortion due to unbalanced loads performance of repetitive-based controller.
and also reduce the harmonic voltage distortion due to As another approach, the selected harmonic compensation
non-linear loads, even if the bandwidth of voltage control loop is method using discrete Fourier transformation (DFT) [5] and
a very narrow. Therefore, the proposed scheme is especially the synchronous reference frame controller (SRFC) [6] have
appropriate for a fully digital controlled UPS or a high power been proposed. However, the DFT method requires too much
UPS with limited voltage control bandwidth. In order to computation, and the method by SRFC requires the
compensate for the effects of unbalanced loads, the synchronous knowledge of the leading angle which compensates for the
reference frame controller with the positive and negative
system delay.
sequence computation block is proposed, and the synchronous
frame controller with a bandpass filter is proposed to
Unfortunately, the aforementioned approaches do not
compensate for the selected harmonic frequency of output compensate the voltage distortion due to unbalanced loads.
voltage. The effectiveness of the proposed scheme has been Also the majority of them require a wide bandwidth of the
investigated and verified through computer simulations and voltage control loop, likewise a fast sampling frequency. In
experiments by a 30kVA UPS. [7], synchronous reference frame controller has been
proposed in order to compensate the negative sequence
component voltage distortion due to unbalanced loads.
I. INTRODUCTION However, with respect that PI controllers in the scheme do not
With the ever-increasing use of electronic equipments in operate in pure DC domain, the heightened voltage control
the market, the majority of loads fed by UPS (Uninterruptible bandwidth with over hundreds of Hz is needed for the zero
Power Supply) are nonlinear and/or unbalanced loads. These steady state error, and its performance depend on the delay in
unbalanced and nonlinear loads create the voltage distortions measuring the output voltages.
which lead to load failures as well as a reduction of inverter One important point to be duly considered in designing a
MTBF on the output of UPS [1]. Therefore, the limitation of voltage controller for UPS is the voltage control bandwidth.
the voltage distortions has become the main aim in designing Considering a full digitalized UPS in the market,
a high quality UPS. Since the origin of these voltage microprocessor or DSP (Digital Signal Processor) actually
distortions is due to the distorted voltage drop on the output must do so many things to increase the value of the product,
impedance of inverter output filter by the distorted load such as the serial communication for networking, the
currents, several approaches directly proposed a strategically man-machine interface, the displaying of currents, voltages
selected output filter with a low-impedance [1], [2]. and some of parameters, the tracing some waveforms, and the
Different approaches have been proposed in order to managing of fault history, etc. They limit the switching
reduce the voltage distortion in UPS or a 3-phae inverter. frequency; likewise limit the voltage control bandwidth to less
High performance feedback control scheme using a dead-beat than several hundred rad/sec. Generally, the commercialized
control and an observer has been proposed in [3]. Although 3-phase 4-wire UPS have about from 5 KHz to 10 KHz of
this technique is able to ensure a fast and robust control of switching or sampling frequency, and it has an output LC
output voltage, the scheme requires the current controller in filter whose natural frequency is about from 300Hz to 500Hz.
the minor loop with a fast sampling frequency and the Under these conditions, if the integral controller is used to
knowledge of the filter components. meet about 1% of steady state errors, the bandwidth of voltage
In [4], repetitive learning controller is designed to control loop will be limited to more and less 100Hz. This
eliminate the periodic tracking error by nonlinear load situation is especially true for a high power UPS because of its
disturbances. Although this scheme is able to compensate the limited switching frequency.
parameter uncertainties of the output filter, it requires still the This paper proposes advanced synchronous reference
frame controller (SRFC) based on [6] and [7]. The proposed

0-7803-9033-4/05/$20.00 ©2005 IEEE. 1699


scheme can be able to compensate the voltage distortion due II. REVIEW SYNCHRONOUS FRAME CONTROLLER
to non-linear or unbalanced loads even though the voltage In a balanced and linear 3-phase system, synchronous
control bandwidth is very narrow of less than several hundred reference frame transforms both the reference values and the
rad/sec. The scheme is able to provide not only the zero feedback values into DC quantities, and SRFC shown in
steady state error but also fast transient response without any figure 1 is able to provide the zero steady state error even
knowledge of the leading angle and the value of parameters. though the bandwidth of its voltage control loop is narrow.
The effectiveness of the proposed control scheme is verified Also, in respect that it has the simple structure, and it has an
by computer simulations and an experimental UPS system inherent feature of PLL (Phase Locked Loops) through the
that has a 30kVA load power capacity. adjustment of its reference values, SRFC can be considered as
one of best control scheme for UPS. Unfortunately, the
vcd
* *
uca *
, ucb , ucc* integral terms of PI controller in synchronous reference frame
*
do not provide the effectiveness for unbalanced or non-linear
vcq
loads.
(ωt ) vPd Reference [6] and [7] has showed a feasibility of SRFC that
vPq
vca , vcb, vcc is able to eliminate the effects of both non-linear and
(ωt ) unbalanced loads if each strategy is combined. Figure 2 show
the concept of SRFC for unbalanced load compensation
Fig. 1: Conventional SRFC
which is proposed in [7]. The negative sequence controller in
the scheme compensates the negative voltage distortion due to
unbalanced load with the synchronous reference frame
rotating at the fundamental frequency in the opposite
vcd
* direction against the positive sequence. In this scheme, the
uca* , ucb* , ucc*
negative sequence components of feedback voltage vNd, vNq is
vcq
*
pulsating with the two times fundamental frequency under the
(ωt ) vcd unbalanced load and PI controllers does not operate in pure
vca, vcb, vcc
vcq DC domain. Therefore, in order to ensure the zero tracking
error in this scheme, the voltage control bandwidth over than
(ωt ) 120Hz at least and no delay in measuring the output voltages
vNd = Vm cos 2ωt
*
are required.
vNq = −Vm sin 2ωt
*
Figure 3 shows the concept of SRFC for the selected
(−ωt ) harmonic voltage compensation, which is introduced in [6].
vNd
vNq
This method proposes a synchronous reference frame rotating
at the selected harmonic frequency to be compensated in
(−ωt ) positive and negative sequence. This scheme also requires the
more heightened voltage control bandwidth in order to
Fig.2 Negative sequence voltage compensator compensate the harmonic voltage because that PI controllers
operate with a pulsating feedback value. Another drawback in
the scheme for UPS is that it requires the knowledge of the
leading angle ϕ n which compensates for the system delay. It is
*
not easy to calculate the leading angle considering the phase
vcd uca* , ucb* , ucc*
of reference voltages are changed continuously for
vcq
*
synchronization with a voltage source of the utility or the
(ωt ) vcd other UPS in parallel operation.
vcq
III. PROPOSED SYNCHRONOUS FRAME CONTROLLER
(ωt )
*
c ,c ,c
ha
*
hb
*
hc
Figure 4 shows the proposed scheme in this paper. The
negative-sequence voltage controller (NVC) compensates the
negative voltage distortion due to unbalanced loads, and

* * *
vca , vcb , vcc
harmonic voltage compensator (HVC) compensates the
vca, vcb, vcc ( n ωt ) (nωt + ϕn ) harmonic voltage distortion due to non-linear loads. Compare
∫ to SRFC shown in [6] [7], the positive and the negative
(−nωt + ϕn )
sequence computation block are introduced for unbalanced
(− nωt )
load compensation, and bandpass filter is introduced for
non-linear load compensation. The main feature of the
scheme is that NVC and HVC is able to provide the
Fig.3 Harmonic voltage compensator zero-steady state error even if the bandwidth of voltage
control loop is not wide enough.

1700
A. Negative-sequence Voltage Compensator (NVC) s 2 − bs + c
Y ( s) = X ( s) (3)
Any unbalance output voltage can be expressed as three s 2 + bs + c
symmetrical components of positive, negative and zero
sequence components as follows, In this scheme, the negative sequence computation block
(NSC) shown in equation (3) is accomplished as figure 5. The
Vc = Vc ( + ) +V c ( − )+Vc ( 0 ) (1) positive sequence computation block can be similarly
where accomplished. Note that the NSC and PSC transform the
unbalanced output voltage into the symmetrical balanced sets,
[
Vc = [vca , vcb , vcc ]T , Vc ( + ) = vca ( + ) , vcb( + ) , vcc ( + ) T , ] then, these balanced sets are transformed into perfect DC
[
Vc ( − ) = vca ( − ) , vcb ( − ) , vcc ( − ) ]
T
, Vc (0) = [vca (0) , vcb (0) , vcc (0) ]T quantities by the Park-transformation as

Then the positive and negative component are obtained as ⎡v ⎤


⎡v ⎤ ⎡ cos θ cos(θ − 2π / 3) cos(θ − 2π / 3)
ca
2 ⎤⎢ ⎥ (4)
cd

⎢ ⎥= ⎢ − sin(θ − 2π / 3) ⎦⎥ ⎢
v

⎣ − sin θ − sin(θ − 2π / 3)
cb
⎣v ⎦ 3
⎡vca ( + ) ⎤ ⎡1 ⎤ ⎡vca ⎤ ⎡ 0 1 -1⎤ ⎡vca ⎤ ⎢⎣ v ⎥⎦
cq
-1 -1
2 2 cc

⎢ ⎥ 1 ⎢ -1 ⎥ ⎢v ⎥ - ⎢-1 0 1 ⎥ ⎢v ⎥ (2) where


⎢vcb ( + ) ⎥ = 3 ⎢ 2 1 -1 1
2
⎥ ⎢ cb ⎥ j2 3 ⎢ ⎥ ⎢ cb ⎥ vcd is d-axis voltage on synchronous reference frame.
⎢⎣ vcc ( + ) ⎦⎥ ⎢⎣ -1 2 -1
2 1 ⎥⎦ ⎢⎣ vcc ⎥⎦ ⎢⎣ 1 -1 0 ⎥⎦ ⎢⎣ vcc ⎥⎦
vcq is q-axis voltage on synchronous reference frame.

⎡vca ( − ) ⎤ ⎡ 1 −1 −1
⎤ ⎡vca ⎤ ⎡0 1 −1⎤ ⎡ vca ⎤
⎢ v ⎥ = 1 ⎢ −1
2 2
Therefore, PI controllers in NVC is operated with pure DC
1 −1 ⎥ ⎢v ⎥ + 1 ⎢ −1 0
⎢ ⎥ (3)
1 ⎥ vcb
⎢ cb ( − ) ⎥ 3 ⎢ 2 2
⎥ ⎢ cb ⎥ j2 3
⎢ ⎥⎢ ⎥ control variables, its output contribute the zero steady state
⎢⎣ vcc ( − ) ⎥⎦ ⎢⎣ −1 2 −1
2 1 ⎥⎦ ⎢⎣ vcc ⎥⎦ ⎢⎣ 1 −1 0⎥
⎦ ⎢⎣ vcc ⎥⎦ error for the compensation of a negative sequence component
voltage distortion regardless of the voltage control bandwidth
where
or phase lag due to system delay including the LC filter. The
j is 90 °phase shift. zero-sequence voltage distortion is compensated by the
The 90 ° phase shift is accomplished by all-pass filter as output transformer with Delta-Wye winding.

*
vcd
vca , vcb , vcc

*
vcq
*
vcd = 0
(ωt )
(ωt )
(± nωt )

vcd
vcq
vca (+)
vcb (+)
(ωt ) vcc (+)
* * *
cna , cnb , cnc

vca (−)
* * *
vcb (−)
cha , chb , chc (−ωt ) (−ωt ) vcc (−)

* * *
vca , vcb , vcc

(−5ωt ) (−5ωt )

(7ωt ) (7ωt )

Fig.4 Proposed control scheme for unbalanced and nonlinear load compensation

1701
13 controllers in the conventional SRFC without any
16 compensation have the pulsating signals.
16 Figure 7 shows the simulation results under the condition
1
(vca − vcb ) that the UPS system feeds the balanced 100% of non-linear
1 j2 3
vca vca( − ) loads. It can be seen from figure 7(b) that the 5th and 7th
2 3
Allpass Filter 90° Shift vcb(− ) harmonic components of the output voltage were
1 completely eliminated. Likewise the proposed scheme is
vcb vcc( − )
2 3 1 able to provide the improved THD (Total Harmonic
Allpass Filter 90° Shift (vcb − vcc )
j2 3 Distortion) in the output voltage. Through these simulation
vcc results, the feasibility of the proposed control scheme can be
Allpass Filter 90° Shift verified.
13
16 V. EXPERIMENTAL RESULT
16 The prototype for the fully digital controlled three-phase
inverter using two DSP (TMS320C33 and
Fig.5 Block diagram of negative sequence computation TMS320LF2407A) was built to investigate the operation
performance and to prove the feasibility of the proposed
B. Harmonic Voltage Compensator (HVC) control scheme. The major parameters of the UPS system
HVC in the proposed scheme is designed to compensate the used in the experiments are given as follows
selected harmonic voltage distortion due to nonlinear loads.
The scheme shows an example of 5th and 7th harmonic z Power rating: 30kVA
compensation. The symmetrical balanced harmonic z Fundamental frequency : 60Hz
component of the output voltage can be obtained by the z Nominal line-to-line output voltage : 208V
dedicated bandpass filter whose characteristic frequency is z DC bus : 405V
corresponding to the selected harmonic frequency that is to be z Inverter and converter switching frequency : 6kHz
compensated. The bandpass filters in the scheme output the z Voltage control bandwidth: about 120Hz
symmetrical balanced sets of the 5th and 7th harmonic z Output transformer turns ratio : 1.22:1
components, and these symmetrical balanced sets of harmonic z Output transformer parameters: %X=5%, %R=3.5%
components can be transformed into DC quantities by the z Selected frequencies for harmonic compensation: 5th, 7th
Park-transformation. Likewise PI controllers in HVC are
operated with pure DC control variables, and can provide the Figure 8 shows the q-axis voltage reference which is
zero steady state errors for selected harmonic frequency. pulsating with about 120Hz and the q-axis output voltage of
HVC in the scheme do not require the knowledge of the the test equipment. It can be seen from this figure that the
system parameter, the leading angle which compensate the voltage control bandwidth of the prototype is about 120Hz.
system delay including the LC filter, and a fast switching Figure 9 shows 3-phase UPS output voltage waveform under
frequency. the unbalanced load. Note that the imbalance of the output
In conclusion NVC and HVC operates as the feed-forward voltage has been perfectly improved to 0.19, while imbalance
controller for the compensation of voltage distortion. of 3.57 is obtained from the conventional SRFC without any
compensation shown in figure 1. The negative sequence
IV. SIMULATION RESULT component of the output voltage is also perfectly eliminated
Simulation has been performed to verify the validity of the to 0.4V from 6 V.
proposed control scheme shown in figure 4. Unbalanced In order to compensate the harmonic voltage distortion due
load condition, where 100% load is connected between nonlinear load, the 5th and 7th harmonic compensating strategy
A-phase and neutral point and the other phase are left open proposed in this paper has been implemented on the prototype
circuit, is used in the computer simulation. Figure 6 shows of UPS. Figure 10 shows the output voltage and current
3-phase output voltage waveforms, RMS values, negative waveforms under the condition, where uncontrolled 3-phase
sequence components, and the control inputs (PI controller rectifier load is connected. Figure 11 shows Fourier spectra of
output) respectively under the condition where the the voltage and current waveforms which are shown in figure
unbalanced load is applied at 100msec from the no-load state. 10. The upper waveform is for the current and the other is for
Note that only peak portion of the output voltage waveforms the output voltage. The voltage and current distortions before
are shown in this figure. and after the compensation are shown in Table I. Note that the
It can be seen from the simulation results that the proposed 5th and 7th harmonic components of output voltage are
SRFC is able to completely eliminate the negative sequence perfectly eliminated to near zero.
component of the output voltage within one period of the These experimental result shows that proposed scheme is
output voltage, and the PI controllers in the proposed able to provide the zero steady state errors for the unbalanced
scheme are operated with pure DC quantities while the PI and nonlinear load compensation even though the bandwidth
of the voltage control loop is limited.

1702
output voltages without compensation output voltages with compensation

RMS of output voltage without compensation RMS of output voltage with compensation

negative sequence components of output negative sequence components of output


voltage without compensation voltage with compensation

output of PI controllers in SFC output of PI controllers in SFC


without compensation with compensation

(a) SRFC Without any compensation (b) Proposed SRFC

Fig.6 Simulation Results: Unbalanced load compensation

output voltage and current THD of voltage and current FFT of output voltage

a) Conventional SRFC without any compensation

output voltage and current THD of voltage and current FFT of output voltage

b) Proposed Synchronous Frame Controller

Fig.7 Simulation Results: Non-linear load compensation

1703
TABLE I SYSTEM PARAMETERS VI. CONCLUSION
This paper has proposed the advanced synchronous
Harmonic With Compensation Without Compensation
order
reference frame control scheme for the unbalanced and
Voltage Curren Voltage Current
(%) t(%) (%) (%) nonlinear load compensation in UPS. SRFC proposed in this
5th 0.1 28.3 2.6 26.0 paper is able to perfectly compensate for the negative voltage
7th 0.1 11.8 1.8 10.5 distortion and the selected harmonic voltage distortion
11th 1.1 7.9 2.4 5.5
created by unbalanced load and non-linear load respectively
13th 2.6 4.4 2.9 5.7
THD(%) 2.9 5.9 even if the bandwidth of voltage control loop is limited to less
than 100Hz. PI controllers in the proposed scheme operate
with pure DC values under the unbalanced and nonlinear load
144 condition, in the same as SRFC under balanced system, which
142
140 is able to provide the zero steady state error.
138
136
The proposed scheme is particularly suitable for a full
134
132
digital controlled high power UPS with limited voltage loop
130 bandwidth.
1 11 21 31 41 51 61 71 81 91 101 111 121 131 141 151 161 171 181 191

×166.7 µ sec
Fig.8 q-axis voltage reference and feedback APPENDIX
The voltage imbalance is calculated by equation shown
below

Maximum value of RMS/ Average value of RMS

REFERENCES
[1] MICHAEL A. BOOST And PHOIVOS D. ZIOGAS, “Towards a
zero-output impedance UPS system” IEEE Trans. Industry
a) conventional SRFC b) proposed SRFC Applications, vol. 25, no.3, pp. 408–418, MAY/JUNE 1989.
Fig.9 3-phase voltage waveforms of proposed scheme [2] Peng Li, Bai Dan, Kang Yong, and Chen Jian, “Research on
during unbalanced load (10V/div, 5ms/div); three-phase inverter with inbalanced load,” Conference Records on
a)vab=203.5,Vbc=210.9,Vca=207.0 APEC 2004, CD ROM, Feb. 2004.
b)vab=206.8, Vbc=207.2,Vca=207.2 [3] Youichi Ito and Shoichi Kawauchi, “Microprocessor-Based Robust
Digital Control for UPS with Three-phase PWM Inverter,” IEEE Trans.
on power Electronics, vol.10, no.2, , pp.196-204, March 1995.
[4] Keliang Zhou and Danwei Wang, “Digital Repetitive Learning
Controller for Three-Phase CVCF PWM Inverter,” IEEE Trans. on
Industrial Electronics, vol.48, No.4, 1996, pp.121-125.
[5] A.Von Jounne, P.N. Engeti and D.J. Lucas, “DSP Control of High
power UPS Systems Feeding Nonlinear Loads,” IEEE Trans. on
Industrial Electronics, vol.43, No.1, 1996, pp.121-125.
[6] P.Mattavelli, and S.Fasolo, “Implementation of Synchronous Frame
Control for High Performance AC Power Supplies,” Proceedings of the
2000 IEEE Industry Applications Conference, vol.3, pp.1988-1995.
a) Conventional SRFC b) Proposed SRFC [7] P.Hsu and M. Behnke, “A Three-phase Synchronous Frame Controller
Fig.10 Voltage and load current waveforms during non-linear for Unbalanced Load,” Proceedings of the 1988 IEEE Power
load(voltage-100V/div, current-50A/div, time- 5ms/div) Electronics Specialists Conference, vol.2, pp.1369-1374.

current

voltage

1st 3rd 5th 11th 13th 1st 3rd 5th 11th 13th
a) Conventional SFC b) Proposed SFC

Fig.11 Fourier spectra of voltage and load current during


nonlinear load
(voltage-4V/div, current-4A/div, frequency- 100Hz/div)

1704

You might also like