You are on page 1of 2

Technical Data Bulletin

ISO-X 30198

ISO-X
Fault Isolator Module

GENERAL INFORMATION
The Chemetron Fire Systems ISO-X Fault Isolator
Module is used with the Micro 200-I, 300-I, & 400-I
Control Panels to protect the system against wire-
to-wire short circuits on the SLC loops.

FEATURES
P Powered directly by an SLC loop, no external
power required.
P Mounts in standard 4 inch square (2-1/8" deep) ISO-X Fault Isolator Module
junction box.
P Integral LED blinks to indicate normal condition.
Illuminates steadily when short circuit condition
is detected.
P High noise immunity (EMF/RFI).
P Wide viewing angle of LED.
P SEMS screws with clamping plates for ease of
wiring.
P Opens SLC loop automatically on detection of
short, preventing the short from causing failure
of the entire loop.
P Automatically resets on correction of short.
P Supports Style 4, 6, or 7 wiring.

APPLICATIONS Face Plate

The Fault Isolator Modules should be spaced be-


tween groups of sensors in a loop to protect the CONSTRUCTION
rest of the loop. Use to isolate short circuit
problems within a section of a loop so that other The face plate is made of LEXAN with an off-
sections can continue to operate normally. The white color. It includes a yellow LED indicator that
ISO-X supports a maximum of 25 devices in be- pulses under normal conditions and illuminates
tween isolators. steadily when a short is detected.

OPERATION Automatically opens circuit when the line voltage

1998 Chemetron Fire Systems All rights reserved (3/98). MANUFACTURED BY NOTIFIER
4801 Southwick Drive Matteson, IL 60443 708/748-1503 FAX 708/748-2847
Technical Data Bulletin
ISO-X 30198

drops below 4 volts. Fault Isolator Modules should be


spaced between groups of sensors (maximum 25) in
a loop to protect the rest of the loop. If a short
SPECIFICATIONS
should occur between any two isolators, then both
Operating Voltage: 15 28 volts DC (Peak)
isolators immediately switch to an open circuit state
Current Range: 5 mA for LED latched in alarm
and isolate the groups of sensors between them. The
remaining units on the loop continue to fully operate. Standby Current: 400 FA maximum, plus super-
visory current
In Style 4 loops, the ISO-X is generally used at each Pulsing Current: 30 mA for 15 mS.
T-tap branch to limit the effect of short circuits on a Temperature Range: 32E to 120EF (0E to 49EC)
branch to the devices on that branch. The LED Humidity Range: 10% 95% Relative
indicator is on continuously during a short circuit Weight: 5.0 oz. (150 g)
condition.

The ISO-X Fault Isolator Module automatically re-


stores the shorted portion of the communications
ARCHITECTURAL/ENGINEERING
loop to normal condition when the short circuit SPECIFICATIONS
condition is removed.
Fault Isolator Modules shall be provided to automati-
INSTALLATION cally isolate wire-to-wire short circuits on an SLC loop.
The Fault Isolator Module shall limit the number of
Mount on a standard 4 inch square junction box that modules or detectors that may be rendered
is at least 2-1/8" deep. Terminal screws are provided inoperative by a short circuit fault on the SLC loop. If
for in and out wiring. Installation instructions are a wire-to-wire short occurs, the Fault Isolator Module
provided with each module. shall automatically open-circuit (disconnect) the SLC
loop. When the short circuit condition is corrected, the
Surface mount backbox is available as an option. Fault Isolator Module shall automatically reconnect the
isolated section of the SLC loop. The Fault Isolator
Module shall not require any address-setting, and its
PRODUCT LINE INFORMATION operations shall be totally automatic. It shall not be
necessary to replace or reset a Fault Isolator Module
ISO-X . . . . . Isolator Module. after its normal operation. The Fault Isolator Module
70100740 . . Surface Mount Backbox shall mount in a standard 4 inch deep electrical box, in
a surface mounted backbox, or in the Fire Alarm Con-
trol Panel. It shall provide a single LED that shall flash
to indicate that the Isolator is operational and shall
illuminate steadily to indicate that a short circuit
condition has been detected and isolated.

Ordering Information

Shipping Weight
Stock Number Description lbs (kg)
70100727 ISO-X Fault Isolator Module .6 (.27)
70100740 Surface Mount Backbox .6 (.27)

1998 Chemetron Fire Systems All rights reserved (3/98). MANUFACTURED BY NOTIFIER
4801 Southwick Drive Matteson, IL 60443 708/748-1503 FAX 708/748-2847