You are on page 1of 60

MiCOM P740

Numerical Busbar Protection

RELAY MENU DATABASE

P740/EN GC/C11

08/03
Relay Menu Database P740/EN GC/C11

MiCOM P740

RELAY MENU DATABASE


P740/EN GC/C11 Relay Menu Database

MiCOM P740

A Menu Database (COURIER)

B Digital Data Bus (DDB)

C Default Programmable Scheme Logic (PSL)

This version of P740/EN GC/C11 is specific to the following models

Model number
P741-------01-B
P742-------01-B
P743-------01-B

For other models / software versions, please contact ALSTOM T&D Protection and
Control for the relevant information.
Relay Menu Database P740/EN GC/C11

MiCOM P740

Relay Menu Database

This Chapter is split into several sections, these are as follows:


Menu Database for Courier, User Interface
Digital Data Bus (Internal Digital Signal)
Default Programmable Logic

1. MENU DATABASE
This database defines the structure of the relay menu for the Courier interface and
the front panel user interface. This includes all the relay settings and measurements.
Indexed strings for Courier and the user interface are cross referenced to the Menu
Datatype Definition section (using a G Number). For all settable cells the setting limits
and default value are also defined within this database.

2. INTERNAL DIGITAL SIGNALS (DDB)


This table defines all of the relay internal digital signals (opto inputs, output contacts
and protection inputs and outputs). A relay may have up to 512 internal signals each
reference by a numeric index as shown in this table. This numeric index is used to
select a signal for the commissioning monitor port. It is also used to explicitly define
protection events produced by the relay.

3. DEFAULT PROGRAMMABLE LOGIC


This section documents the default programmable logic for the various models of the
relay is supply with the MiCOM S1 Scheme Logic Editor PC support software.

References
Introduction Chapter: User Interface operation and connections to relay
Courier User Guide R6512
P740/EN GC/C11 Relay Menu Database

MiCOM P740
Relay Menu Database P740/EN GC/C11

MiCOM P740

A - MENU DATABASE
P740/EN GC/C11 Relay Menu Database

MiCOM P740
Relay Menu Database
abcd P740/EN GC/C11

Page A-1
MiCOM P740

A - Menu database for Courier, User Interface (MiCOM P741 only)


Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level
00 00 SYSTEM DATA

1 Language Indexed String G19 English Setting 0 3 1 2

2 Password ASCII Password(4 bytes) G20 AAAA Setting 65 90 1 0

4 Description ASCII Text(16 bytes) MiCOM P741 Setting 32 163 1 2

5 Plant Reference ASCII Text(16 bytes) ALSTOM Setting 32 163 1 2

6 Model Number ASCII Text(32 bytes) Model Number Data Cortec Code 18 characters

8 Serial Number ASCII Text(7 bytes) Serial Number Data

9 Frequency Unsigned Integer(1 byte) 50 Setting 50 60 10 2

0A Comms Level Unsigned Integer(2 bytes) 2 Data

0B Relay Address Unsigned Integer(2 bytes) 1 Setting 1 6 1 2 Rear Courier Address available via LCD
Address=255 with default settings
0C Plant Status Binary Flags(16 bits) Data

0D Control Status Binary Flags(16 or 32 bits) Data

0E Active Group Unsigned Integer(2 bytes) G1 Data

11 Software Ref. 1 ASCII Text(16 characters) Data

20 Opto I/P Status Binary Flag(32 bits) Data


Indexed String
21 Relay O/P Status Binary Flag(32 bits) Data
Indexed String
22 Alarm Status Binary Flag(32 bits) Data
Indexed String
D0 Access Level Unsigned Integer(2 bytes) G1 Data

D1 Password Control Unsigned Integer(2 bytes) G22 2 Setting 0 2 1 2

D2 Password Level 1 ASCII Password(4 characters) G20 AAAA Setting 65 90 1 1

D3 Password Level 2 ASCII Password(4 characters) G20 AAAA Setting 65 90 1 2

01 00 VIEW RECORDS

1 Last Record Unsigned Integer(2) 0 Setting 0 249 1 0 Max value is oldest record

2 Menu Cell Ref Cell Reference N/A (From Record) Data Indicates type of event
See Event sheet
3 Time & Date IEC870 Time & Date (From Record) Data
Relay Menu Database
abcd P740/EN GC/C11

Page A-2
MiCOM P740

A - Menu database for Courier, User Interface (MiCOM P741 only)


Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level
4 Record Text Ascii String(32) Data See Event sheet

5 Record Value Binary Flag(32)/UINT32 Data Note DTL depends on event type
See Event sheet of Spreadsheet
6 Select Fault Unsigned Integer 0 Setting 0 4 1 0 Allows Fault Record to be selected

7 Active Group Unsigned Integer 0 Data

8 Faulted Phase Binary Flags (8 Bits) N/A GXX Data Started phases + tripped phases

9 Start Elements Binary Flags (32 Bits) N/A GXX Data Started elements

0A Trip Elements Binary Flags (32 Bits) N/A GXX Data Tripped elements 1

0C Time Stamp IEC870 Time & Date G12 Data

0D Fault Alarms Binary Flags (32 Bits) G87 Data Faullt Alarms/Warnings

0E System Frequency Courier Number (frequency) Data

0F Fault Duration Courier Number (time) Data

11 IA diff Courier Number (current) G24 Data

12 IB diff Courier Number (current) G24 Data

13 IC diff Courier Number (current) G24 Data

14 IN diff Courier Number (current) G24 Data

15 IA bias Courier Number (current) G24 Data

16 IB bias Courier Number (current) G24 Data

17 IC bias Courier Number (current) G24 Data

18 IN bias Courier Number (current) G24 Data

19 IA CZ diff Courier Number (current) G24 Data

1A IB CZ diff Courier Number (current) G24 Data

1B IC CZ diff Courier Number (current) G24 Data

1C IN CZ diff Courier Number (current) G24 Data

1D Faulted Zone Binary Flags (16 Bits) G212 Data

F0 Select Report Unsigned Integer Manual override to Setting 0 4 1 2 Allows Self Test Report to be selected
select a fault record.
Relay Menu Database
abcd P740/EN GC/C11

Page A-3
MiCOM P740

A - Menu database for Courier, User Interface (MiCOM P741 only)


Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level
F1 Report Text Ascii String(32) Data

F2 Type UINT32 Data

F3 Data UINT32 Data

FF Reset Indication Indexed String G11 No Command 0 1 1 1

02 00 MEASUREMENTS 1

1 IA Diff CZ Courier Number (current) G24 Data

2 IB Diff CZ Courier Number (current) G24 Data

3 IC Diff CZ Courier Number (current) G24 Data

4 IN Diff CZ Courier Number (current) G24 Data

03 00 MEASUREMENTS 2 Visibility depend of the number of the zone configured

1 Zx1: IA diff Courier Number (current) G24 Data

2 Zx1: IB diff Courier Number (current) G24 Data

3 Zx1: IC diff Courier Number (current) G24 Data

4 Zx1: IN diff Courier Number (current) G24 Data

5 Zx1: IA bias Courier Number (current) G24 Data

6 Zx1: IB bias Courier Number (current) G24 Data

7 Zx1: IC bias Courier Number (current) G24 Data

8 Zx1: IN bias Courier Number (current) G24 Data

,,,

79 Zx16: IA diff Courier Number (current) G24 Data Ligne = 8*Numzone - 7

7A Zx16: IB diff Courier Number (current) G24 Data

7B Zx16: IC diff Courier Number (current) G24 Data

7C Zx16: IN diff Courier Number (current) G24 Data

7D Zx16: IA bias Courier Number (current) G24 Data

7E Zx16: IB bias Courier Number (current) G24 Data


Relay Menu Database
abcd P740/EN GC/C11

Page A-4
MiCOM P740

A - Menu database for Courier, User Interface (MiCOM P741 only)


Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

7F Zx16: IC bias Courier Number (current) G24 Data

80 Zx16: IN bias Courier Number (current) G24 Data

04 00 TOPOLOGY 1

01 Current Node 01 Binary Flag (16 bits) G212 Data Visible if <> 0

02 Current Node 02 Binary Flag (16 bits) G212 Data Visible if <> 0

03 Current Node 03 Binary Flag (16 bits) G212 Data Visible if <> 0

04 Current Node 04 Binary Flag (16 bits) G212 Data Visible if <> 0

05 Current Node 05 Binary Flag (16 bits) G212 Data Visible if <> 0

06 Current Node 06 Binary Flag (16 bits) G212 Data Visible if <> 0

07 Current Node 07 Binary Flag (16 bits) G212 Data Visible if <> 0

08 Current Node 08 Binary Flag (16 bits) G212 Data Visible if <> 0

09 Current Node 09 Binary Flag (16 bits) G212 Data Visible if <> 0

0A Current Node 10 Binary Flag (16 bits) G212 Data Visible if <> 0

0B Current Node 11 Binary Flag (16 bits) G212 Data Visible if <> 0

0C Current Node 12 Binary Flag (16 bits) G212 Data Visible if <> 0

0D Current Node 13 Binary Flag (16 bits) G212 Data Visible if <> 0

0E Current Node 14 Binary Flag (16 bits) G212 Data Visible if <> 0

0F Current Node 15 Binary Flag (16 bits) G212 Data Visible if <> 0

10 Current Node 16 Binary Flag (16 bits) G212 Data Visible if <> 0

05 00 TOPOLOGY 2

01 Current Node 01 Binary Flag (32 bits) G217 Data Visible if <> 0

02 Current Node 02 Binary Flag (32 bits) G217 Data Visible if <> 0

03 Current Node 03 Binary Flag (32 bits) G217 Data Visible if <> 0

04 Current Node 04 Binary Flag (32 bits) G217 Data Visible if <> 0

05 Current Node 05 Binary Flag (32 bits) G217 Data Visible if <> 0
Relay Menu Database
abcd P740/EN GC/C11

Page A-5
MiCOM P740

A - Menu database for Courier, User Interface (MiCOM P741 only)


Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

06 Current Node 06 Binary Flag (32 bits) G217 Data Visible if <> 0

07 Current Node 07 Binary Flag (32 bits) G217 Data Visible if <> 0

08 Current Node 08 Binary Flag (32 bits) G217 Data Visible if <> 0

09 Current Node 09 Binary Flag (32 bits) G217 Data Visible if <> 0

0A Current Node 10 Binary Flag (32 bits) G217 Data Visible if <> 0

0B Current Node 11 Binary Flag (32 bits) G217 Data Visible if <> 0

0C Current Node 12 Binary Flag (32 bits) G217 Data Visible if <> 0

0D Current Node 13 Binary Flag (32 bits) G217 Data Visible if <> 0

0E Current Node 14 Binary Flag (32 bits) G217 Data Visible if <> 0

0F Current Node 15 Binary Flag (32 bits) G217 Data Visible if <> 0

10 Current Node 16 Binary Flag (32 bits) G217 Data Visible if <> 0

06 00 PU CONF & STATUS

01 PU in service Binary Flags (32 Bits) G213 0 Setting 0 0xFFFFFFFF 1 1 PU declared in service

02 PU connected Binary Flags (32 Bits) G213 Data PU synchronised

03 PU topo valid Binary Flags (32 Bits) G213 Data PU with topology parameters valid

04 Reset Circt Flt Indexed String G11 No Command 0 1 1 2 Reset command after circuitry fault

05 CircuitryFfault Binary Flags (16 Bits) G212 Data Circuitry Fault by zone

06 Circ Fault Phase Binary Flags (4 Bits) GXX Data Circuitry Fault by phase

08 00 DATE AND TIME

1 Date/Time IEC870 Time & Date N/A G12 Setting 0

N/A Date Front Panel Menu only


36892 ADU if 1/1/2001 possible
N/A Time Front Panel Menu only
0.5
4 IRIG-B Sync Indexed String G37 Disabled Setting 0 1 1 2 Master CU : visibe if IRIG-B Fitted
Slave CU : 0804=0 (invisible)
5 IRIG-B Status ASCII String G17 Data Master CU : visible if 0804=1
Slave CU : 0805=0 (invisible)
6 Battery Status Indexed String G59 Data
Relay Menu Database
abcd P740/EN GC/C11

Page A-6
MiCOM P740

A - Menu database for Courier, User Interface (MiCOM P741 only)


Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

7 Battery Alarm Indexed String G37 Enabled Setting 0 1 1 2

09 00 CONFIGURATION

1 Restore Defaults Indexed String G53 No Operation Command 0 5 1 2

2 Setting Group Indexed String G61 Select via Menu Setting 0 1 1 2

3 Active Settings Indexed String G90 Group 1 Setting 0 3 1 1

4 Save Changes Indexed String G62 No Operation Command 0 2 1 2

5 Copy From Indexed String G90 Group 1 Setting 0 3 1 2

6 Copy to Indexed String G98 No Operation Command 0 3 1 2

7 Setting Group 1 Indexed String G37 Enabled Setting 0 1 1 2

8 Setting Group 2 Indexed String G37 Disabled Setting 0 1 1 2

9 Setting Group 3 Indexed String G37 Disabled Setting 0 1 1 2

0A Setting Group 4 Indexed String G37 Disabled Setting 0 1 1 2

10 Diff Busbar Prot Indexed String G37 Enabled Setting 0 1 1 2

11 Optos Setup Indexed String G80 Visible Setting 0 1 1 2

25 Input Labels Indexed String G80 Visible Setting 0 1 1 1

26 Output Labels Indexed String G80 Visible Setting 0 1 1 1

29 Recorder Control Indexed String G80 Visible Setting 0 1 1 1

2A Disturb Recorder Indexed String G80 Visible Setting 0 1 1 1

2B Measure't Setup Indexed String G80 Visible Setting 0 1 1 1

2C Comms Settings Indexed String G80 Invisible Setting 0 1 1 1

2D Commission Tests Indexed String G80 Visible Setting 0 1 1 1

2E Setting Values Indexed String G54 Secondary Setting 0 1 1 1

0B 00 RECORD CONTROL

1 Clear Events Indexed String G11 No Command 0 1 1 1

2 Clear Faults Indexed String G11 No Command 0 1 1 1


Relay Menu Database
abcd P740/EN GC/C11

Page A-7
MiCOM P740

A - Menu database for Courier, User Interface (MiCOM P741 only)


Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

3 Clear Maint Indexed String G11 No Command 0 1 1 1

0C 00 DISTURB RECORDER

1 Duration Courier Number (time) G2 1.2 Setting 1.2 1.2 0 2 FIXED VALUE: 1.2s
Cell not modifiable
2 Trigger Position Courier Number (%) G2 50 Setting 0 50 1 2 Ffixed step: 200ms

3 Trigger Mode Indexed String G34 Single Setting 0 1 1 2 Function not available => cell not modifiable

4 Analog Channel 1 Indexed String G214 IA diff Setting 0 8 1 2 Function not available => cell not modifiable

5 Analog Channel 2 Indexed String G214 IB diff Setting 0 8 1 2 Function not available => cell not modifiable

6 Analog Channel 3 Indexed String G214 IC diff Setting 0 8 1 2 Function not available => cell not modifiable

7 Analog Channel 4 Indexed String G214 IN diff Setting 0 8 1 2 Function not available => cell not modifiable

8 Analog Channel 5 Indexed String G214 IA bias Setting 0 8 1 2 Function not available => cell not modifiable

9 Analog Channel 6 Indexed String G214 IB bias Setting 0 8 1 2 Function not available => cell not modifiable

0A Analog Channel 7 Indexed String G214 IC bias Setting 0 8 1 2 Function not available => cell not modifiable

0B Analog Channel 8 Indexed String G214 IN bias Setting 0 8 1 2 Function not available => cell not modifiable

0C Digital Input 1 Indexed String G32 Unused Setting 0 DDB Size 1 2

0D Digital Input 2 Indexed String G32 Unused Setting 0 DDB Size 1 2

0E Digital Input 3 Indexed String G32 Unused Setting 0 DDB Size 1 2

0F Digital Input 4 Indexed String G32 Unused Setting 0 DDB Size 1 2

10 Digital Input 5 Indexed String G32 Unused Setting 0 DDB Size 1 2

11 Digital Input 6 Indexed String G32 Unused Setting 0 DDB Size 1 2

12 Digital Input 7 Indexed String G32 Unused Setting 0 DDB Size 1 2

13 Digital Input 8 Indexed String G32 Unused Setting 0 DDB Size 1 2

14 Digital Input 9 Indexed String G32 Unused Setting 0 DDB Size 1 2

15 Digital Input 10 Indexed String G32 Unused Setting 0 DDB Size 1 2

16 Digital Input 11 Indexed String G32 Unused Setting 0 DDB Size 1 2

17 Digital Input 12 Indexed String G32 Unused Setting 0 DDB Size 1 2


Relay Menu Database
abcd P740/EN GC/C11

Page A-8
MiCOM P740

A - Menu database for Courier, User Interface (MiCOM P741 only)


Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

18 Digital Input 13 Indexed String G32 Unused Setting 0 DDB Size 1 2

19 Digital Input 14 Indexed String G32 Unused Setting 0 DDB Size 1 2

1A Digital Input 15 Indexed String G32 Unused Setting 0 DDB Size 1 2

1B Digital Input 16 Indexed String G32 Unused Setting 0 DDB Size 1 2

1C Digital Input 17 Indexed String G32 Unused Setting 0 DDB Size 1 2

1D Digital Input 18 Indexed String G32 Unused Setting 0 DDB Size 1 2

1E Digital Input 19 Indexed String G32 Unused Setting 0 DDB Size 1 2

1F Digital Input 20 Indexed String G32 Unused Setting 0 DDB Size 1 2

20 Digital Input 21 Indexed String G32 Unused Setting 0 DDB Size 1 2

21 Digital Input 22 Indexed String G32 Unused Setting 0 DDB Size 1 2

22 Digital Input 23 Indexed String G32 Unused Setting 0 DDB Size 1 2

23 Digital Input 24 Indexed String G32 Unused Setting 0 DDB Size 1 2

24 Digital Input 25 Indexed String G32 Unused Setting 0 DDB Size 1 2

25 Digital Input 26 Indexed String G32 Unused Setting 0 DDB Size 1 2

26 Digital Input 27 Indexed String G32 Unused Setting 0 DDB Size 1 2

27 Digital Input 28 Indexed String G32 Unused Setting 0 DDB Size 1 2

28 Digital Input 29 Indexed String G32 Unused Setting 0 DDB Size 1 2

29 Digital Input 30 Indexed String G32 Unused Setting 0 DDB Size 1 2

2A Digital Input 31 Indexed String G32 Unused Setting 0 DDB Size 1 2

2B Digital Input 32 Indexed String G32 Unused Setting 0 DDB Size 1 2

2C Manual Trigger Indexed String G11 No Command 0 1 1 1

2D Zone To Record Binary Flags (16 Bits) G212 0 Setting 0 0x8000 1 2

0D 00 MEASURE'T SETUP

01 Default Display Indexed String G52 0 Setting 0 4 1 2 Aff; Total Zone

2 Local Values Indexed String G54 Secondary Setting 0 1 1 2 Local Measurement Values
Relay Menu Database
abcd P740/EN GC/C11

Page A-9
MiCOM P740

A - Menu database for Courier, User Interface (MiCOM P741 only)


Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

3 Remote Values Indexed String G54 Primary Setting 0 1 1 2 Remote Measurement Values

04 Ibp Base Cur Pri Courier Number (Current) G1 1000 Setting 1 10000 1 2

0F 00 COMMISSION TESTS

1 Opto I/P Status Binary Flag(16 bits) Data


Indexed String
2 Relay O/P Status Binary Flag(32 bits) Data
Indexed String
3 Test Port Status Binary Flags(8 bits) Data
Indexed String
4 LED Status Binary Flags(8 bits) 0-7 Data

5 Monitor Bit 1 Unsigned Integer Relay 1 Setting 0 511 1 1

6 Monitor Bit 2 Unsigned Integer Relay 2 Setting 0 511 1 1

7 Monitor Bit 3 Unsigned Integer Relay 3 Setting 0 511 1 1

8 Monitor Bit 4 Unsigned Integer Relay 4 Setting 0 511 1 1

9 Monitor Bit 5 Unsigned Integer Relay 5 Setting 0 511 1 1

0A Monitor Bit 6 Unsigned Integer Relay 6 Setting 0 511 1 1

0B Monitor Bit 7 Unsigned Integer Relay 7 Setting 0 511 1 1

0C Monitor Bit 8 Unsigned Integer Relay 8 Setting 0 511 1 1

0D Test Mode Indexed String G215 Disabled Setting 0 1 1 2

0E Test Pattern Binary Flags (21bits) G9 0 Setting 0 20 1 2


Indexed String
0F Contact Test Indexed String G93 No Operation Command 0 2 1 2

10 Test LEDs Binary Flags (8bits) G94 No Operation Command 0 1 1 2


Indexed String
12 87BB monitoring Binary Flags (16bits) G212 0xFFFF Setting 0 0xFFFF 1 2

13 87BB&50BF disabl Binary Flags (16bits) G212 0xFFFF Setting 0 0xFFFF 1 2

14 87BBTrip Pattern Binary Flags (16bits) G212 0 Setting 0 0xFFFF 1 2

15 87BB Trip Order Indexed String G94 No Operation Command 0 1 1 2

20 DDB 0-31 Binary Flag (32 bits) N/A Data Relay


Visible by Courier
Relay Menu Database
abcd P740/EN GC/C11

Page A-10
MiCOM P740

A - Menu database for Courier, User Interface (MiCOM P741 only)


Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level
21 DDB 32-63 Binary Flag (32 bits) N/A Data Opto
Visible by Courier
22 DDB 64-95 Binary Flag (32 bits) N/A Data
Visible by Courier
23 DDB 96-127 Binary Flag (32 bits) N/A Data
Visible by Courier
24 DDB 128-159 Binary Flag (32 bits) N/A Data
Visible by Courier
25 DDB 160-191 Binary Flag (32 bits) N/A Data
Visible by Courier
26 DDB 192-223 Binary Flag (32 bits) N/A Data
Visible by Courier
27 DDB 224-255 Binary Flag (32 bits) N/A Data
Visible by Courier
28 DDB 256-287 Binary Flag (32 bits) N/A Data
Visible by Courier
29 DDB 288-319 Binary Flag (32 bits) N/A Data
Visible by Courier
2A DDB 320-351 Binary Flag (32 bits) N/A Data
Visible by Courier
2B DDB 352-383 Binary Flag (32 bits) N/A Data
Visible by Courier
2C DDB 384-415 Binary Flag (32 bits) N/A Data
Visible by Courier
2D DDB 415-447 Binary Flag (32 bits) N/A Data
Visible by Courier
2E DDB 448-479 Binary Flag (32 bits) N/A Data
Visible by Courier
2F DDB 480-511 Binary Flag (32 bits) N/A Data

11 00 OPTOS SETUP

1 Global Nominal V Indexed String G200 2 Setting 0 5 1 2

02 Opto Input 1 Indexed String G201 2 Setting 0 4 1 2

03 Opto Input 2 Indexed String G201 2 Setting 0 4 1 2

04 Opto Input 3 Indexed String G201 2 Setting 0 4 1 2

05 Opto Input 4 Indexed String G201 2 Setting 0 4 1 2

06 Opto Input 5 Indexed String G201 2 Setting 0 4 1 2

07 Opto Input 6 Indexed String G201 2 Setting 0 4 1 2

08 Opto Input 7 Indexed String G201 2 Setting 0 4 1 2

09 Opto Input 8 Indexed String G201 2 Setting 0 4 1 2


Relay Menu Database
abcd P740/EN GC/C11

Page A-11
MiCOM P740

A - Menu database for Courier, User Interface (MiCOM P741 only)


Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

GROUP 1
PROTECTION SETTINGS
30 00 GROUP 1
DIFF BUSBAR PROT
01 Diff Phase Fault (Sub-Heading)

02 Current Is Courier Number (Current) G2 0,1*Ibp Setting 0,02*Ibp 1*Ibp 0,01*Ibp 2

03 Phase Slope k Courier Number (%) G2 40 Setting 20 90 1 2

04 ID>2 Current Courier Number (Current) G2 1,2*Ibp Setting 0,1*Ibp 4*Ibp 0,01*Ibp 2

05 ID>1 Current Courier Number (Current) G2 0,05*Ibp Setting 0,01*Ibp 0,5*Ibp 0,01*Ibp 2

06 ID>1 Alarm Timer Courier Number (Time) G2 5 Setting 0.1 100 0.1 2

07 Diff Earth Fault Indexed String G37 Disabled Setting 0 1 1 2

08 IBiasPh> Cur. Courier Number (Current) G2 2*Ibp Setting 0,2*Ibp 10*Ibp 0,1*Ibp 2

09 Earth Cur. IsN Courier Number (Current) G2 0,1*Ibp Setting 0,02*Ibp 1*Ibp 0,01*Ibp 2

0A Earth Slope kN Courier Number (%) G2 20 Setting 20 90 1 2

0B IDN>2 Current Courier Number (Current) G2 0,1*Ibp Setting 0,05*Ibp 2*Ibp 0,05*Ibp 2

0C IDN>1 Current Courier Number (Current) G2 0,05*Ibp Setting 0,01*Ibp 0,5*Ibp 0,01*Ibp 2

0D IDN>1 Alarm Tim. Courier Number (Time) G2 5 Setting 0.1 100 0.1 2

DIFF BUSBAR PROT


4A 00 GROUP 1
INPUT LABELS
1 Opto Input 1 ASCII Text (16 chars) Opto Label 01 Setting 32 39 1 2

2 Opto Input 2 ASCII Text (16 chars) Opto Label 02 Setting 32 39 1 2

3 Opto Input 3 ASCII Text (16 chars) Opto Label 03 Setting 32 39 1 2

4 Opto Input 4 ASCII Text (16 chars) Opto Label 04 Setting 32 39 1 2

5 Opto Input 5 ASCII Text (16 chars) Opto Label 05 Setting 32 39 1 2

6 Opto Input 6 ASCII Text (16 chars) Opto Label 06 Setting 32 39 1 2

7 Opto Input 7 ASCII Text (16 chars) Opto Label 07 Setting 32 39 1 2

8 Opto Input 8 ASCII Text (16 chars) Opto Label 08 Setting 32 39 1 2


Relay Menu Database
abcd P740/EN GC/C11

Page A-12
MiCOM P740

A - Menu database for Courier, User Interface (MiCOM P741 only)


Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

4B 00 GROUP 1
OUTPUT LABELS
1 Relay 1 ASCII Text (16 chars) Relay Label 01 Setting 0 7 1 2

2 Relay 2 ASCII Text (16 chars) Relay Label 02 Setting 0 7 1 2

3 Relay 3 ASCII Text (16 chars) Relay Label 03 Setting 0 7 1 2

4 Relay 4 ASCII Text (16 chars) Relay Label 04 Setting 0 7 1 2

5 Relay 5 ASCII Text (16 chars) Relay Label 05 Setting 0 7 1 2

6 Relay 6 ASCII Text (16 chars) Relay Label 06 Setting 0 7 1 2

7 Relay 7 ASCII Text (16 chars) Relay Label 07 Setting 0 7 1 2

8 Relay 8 ASCII Text (16 chars) Relay Label 08 Setting 0 7 1 2

GROUP 2
PROTECTION SETTINGS
50 00 Repeat of Group 1 columns/rows

GROUP 3
PROTECTION SETTINGS
70 00 Repeat of Group 1 columns/rows

GROUP 4
PROTECTION SETTINGS
90 00 Repeat of Group 1 columns/rows

C0 00 TOPO SETTINGS

01 Topology Size Unsigned integer Data

02 Topology Element 1 Binary Flag (32bits) Data

03 Topology Element 2 Binary Flag (32bits) Data

04 Topology Element 3 Binary Flag (32bits) Data


Relay Menu Database
abcd P740/EN GC/C11

Page A-13
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level
00 00 SYSTEM DATA

1 Language Indexed String G19 English Setting 0 3 1 2

2 Password ASCII Password(4 bytes) G20 AAAA Setting 65 90 1 0

4 Description ASCII Text(16 bytes) MiCOM P742/P743 Setting 32 163 1 2

5 Plant Reference ASCII Text(16 bytes) ALSTOM Setting 32 163 1 2

6 Model Number ASCII Text(32 bytes) Model Number Data Cortec / 18 characters

8 Serial Number ASCII Text(7 bytes) Serial Number Data

9 Frequency Unsigned Integer(1 byte) 50 Setting 50 60 10 2

0A Comms Level Unsigned Integer(2 bytes) 2 Data

0B Relay Address Unsigned Integer(2 bytes) 7 Setting 7 102 1 2 Rear Courier Address available via LCD
1 Address=255 with default settings
0C Plant Status Binary Flags(16 bits) Data

0D Control Status Binary Flags(16 or 32 bits) Data

0E Active Group Unsigned Integer(2 bytes) G1 Data

10 CB Trip/Close Indexed String(2) G55 No Operation Command 0 2 1 2 Visible to Rear Port


(command Bks & isolators)
11 Software Ref. 1 ASCII Text(16 characters) Data

20 Opto I/P Status Binary Flag(32 bits) Data ADU extension 24 ou 32 bits
Indexed String
21 Relay O/P Status Binary Flag(32 bits) Data
Indexed String
22 Alarm Status Binary Flag(32 bits) G96 Data
Indexed String
D0 Access Level Unsigned Integer(2 bytes) G1 Data

D1 Password Control Unsigned Integer(2 bytes) G22 2 Setting 0 2 1 2

D2 Password Level 1 ASCII Password(4 characters) G20 AAAA Setting 65 90 1 1

D3 Password Level 2 ASCII Password(4 characters) G20 AAAA Setting 65 90 1 2

01 00 VIEW RECORDS

1 Last Record Unsigned Integer(2) G1 0 Setting 0 249 1 0 Max value is oldest record

2 Menu Cell Ref Cell Reference N/A G13 (From Record) Data Indicates type of event
Relay Menu Database
abcd P740/EN GC/C11

Page A-14
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level
See Event sheet
3 Time & Date IEC870 Time & Date G12 (From Record) Data

4 Record Text Ascii String(32) Data See Event sheet

5 Record Value Binary Flag(32)/UINT32 G27 Data Note DTL depends on event type
See Event sheet of Spreadsheet
6 Select Fault Unsigned Integer G1 0 Setting 0 4 1 0 Allows Fault Record to be selected

7 Active Group Unsigned Integer G1 0 Data

8 Faulted Phase Binary Flags (8 Bits) N/A G16 Data Started phases + tripped phases

9 Start Elements Binary Flags (32 Bits) N/A GXX Data Started elements

0A Trip Elements Binary Flags (32 Bits) N/A GXX Data Tripped elements 1

0C Time Stamp IEC870 Time & Date G12 Data

0D Fault Alarms Binary Flags (32 Bits) G87 Data Faullt Alarms/Warnings

0E System Frequency Courier Number (frequency) G25 Data

10 Relay Trip Time Courier Number (time) G24 Data

11 IA Courier Number (current) G24 Data

12 IB Courier Number (current) G24 Data

13 IC Courier Number (current) G24 Data

14 IN Courier Number (current) G24 Data

15 VA Courier Number(voltage) G24 Data Build = Option Transfo Tension

16 VB Courier Number(voltage) G24 Data Build = Option Transfo Tension

17 VC Courier Number(voltage) G24 Data Build = Option Transfo Tension

18 VN Courier Number(voltage) G24 Data Build = Option Transfo Tension

F0 Select Report Unsigned Integer G27 Manual override to Setting 0 4 1 2 Allows Self Test Report to be selected
select a fault record.
F1 Report Text Ascii String(32) Data

F2 Type UINT32 G27 Data

F3 Data UINT32 G27 Data

FF Reset Indication Indexed String G11 No Command 0 1 1 1


Relay Menu Database
abcd P740/EN GC/C11

Page A-15
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

02 00 MEASUREMENTS 1

1 IA Magnitude Courier Number (current) G24 Data

2 IA Phase Angle Courier Number (angle) G30 Data

3 IB Magnitude Courier Number (current) G24 Data

4 IB Phase Angle Courier Number (angle) G30 Data

5 IC Magnitude Courier Number (current) G24 Data

6 IC Phase Angle Courier Number (angle) G30 Data

7 IN Magnitude Courier Number (current) G24 Data

8 IN Phase Angle Courier Number (angle) G30 Data

9 IN Derived Magn Courier Number (current) G24 Data

0A IN Derived Angle Courier Number (angle) G30 Data

0B I1 Magnitude Courier Number (current) G24 Data

0C I2 Magnitude Courier Number (current) G24 Data

0D I0 Magnitude Courier Number (current) G24 Data

04 00 TOPOLOGY

1 Link CT / zone Binary Flag(32 bits) G212 Data Zones connected to CT


Indexed String Isolator and/or breaker closed
2 Zx1: IA diff Courier Number (Current) G24 Data x1=n of zone connected to isolator 1
IF xx=255, no zone connected
3 Zx1: IB diff Courier Number (Current) G24 Data

4 Zx1: IC diff Courier Number (Current) G24 Data

5 Zx1: IN diff Courier Number (Current) G24 Data

6 Zx1: IA bias Courier Number (Current) G24 Data

7 Zx1: IB bias Courier Number (Current) G24 Data

8 Zx1: IC bias Courier Number (Current) G24 Data

9 Zx1: IN bias Courier Number (Current) G24 Data

0A Zx2: IA diff Courier Number (Current) G24 Data x2=n of zone connected to isolator 2
Relay Menu Database
abcd P740/EN GC/C11

Page A-16
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level
IF xx=255, no zone connected
0B Zx2: IB diff Courier Number (Current) G24 Data

0C Zx2: IC diff Courier Number (Current) G24 Data

0D Zx2: IN diff Courier Number (Current) G24 Data

0E Zx2: IA bias Courier Number (Current) G24 Data

0F Zx2: IB bias Courier Number (Current) G24 Data

10 Zx2: IC bias Courier Number (Current) G24 Data

11 Zx2: IN bias Courier Number (Current) G24 Data

12 Zx3: IA diff Courier Number (Current) G24 Data x3=n of zone connected to isolator 3
IF xx=255, no zone connected
13 Zx3: IB diff Courier Number (Current) G24 Data

14 Zx3: IC diff Courier Number (Current) G24 Data

15 Zx3: IN diff Courier Number (Current) G24 Data

16 Zx3: IA bias Courier Number (Current) G24 Data

17 Zx3: IB bias Courier Number (Current) G24 Data

18 Zx3: IC bias Courier Number (Current) G24 Data

19 Zx3: IN bias Courier Number (Current) G24 Data

1A Zx4: IA diff Courier Number (Current) G24 Data x4=n of zone connected to isolator 4
IF xx=255, no zone connected
1B Zx4: IB diff Courier Number (Current) G24 Data

1C Zx4: IC diff Courier Number (Current) G24 Data

1D Zx4: IN diff Courier Number (Current) G24 Data

1E Zx4: IA bias Courier Number (Current) G24 Data

1F Zx4: IB bias Courier Number (Current) G24 Data

20 Zx4: IC bias Courier Number (Current) G24 Data

21 Zx4: IN bias Courier Number (Current) G24 Data

07 00 CB CONTROL
Relay Menu Database
abcd P740/EN GC/C11

Page A-17
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level
1 Prot Trip Pulse Courier Number (Time) G2 0.2 Setting 0.05 2 0.01 2 Protection trip pulse time

2 Trip Latched Indexed String G37 Disabled Setting 0 1 1 2 To hold relay closed after trip

3 Reset Trip Latch Indexed String G11 No Command 0 1 1 2 Cde to reset upholding

4 CB Control by Indexed String G99 Disabled Setting 0 7 1 2

5 Man Close Pulse Courier Number (Time) G2 0.5 Setting 0.1 5 0.1 2

6 Man Trip Pulse Courier Number (Time) G2 0.5 Setting 0.1 5 0.1 2

7 Man Close Delay Courier Number (Time) G2 10 Setting 0 60 1 2

08 00 DATE and TIME

1 Date/Time IEC870 Time & Date N/A G12 Setting 0

N/A Date Front Panel Menu only


35807
N/A Time Front Panel Menu only
0.5
6 Battery Status Indexed String G59 Data

7 Battery Alarm Indexed String G37 Enabled Setting 0 1 1 2

09 00 CONFIGURATION

1 Restore Defaults Indexed String G53 No Operation Command 0 5 1 2

2 Setting Group Indexed String G61 Select via Menu Setting 0 1 1 2

3 Active Settings Indexed String G90 Group 1 Setting 0 3 1 2

4 Save Changes Indexed String G62 No Operation Command 0 2 1 2

5 Copy From Indexed String G90 Group 1 Setting 0 3 1 2

6 Copy to Indexed String G98 No Operation Command 0 3 1 2

7 Setting Group 1 Indexed String G37 Enabled Setting 0 1 1 2

8 Setting Group 2 Indexed String G37 Disabled Setting 0 1 1 2

9 Setting Group 3 Indexed String G37 Disabled Setting 0 1 1 2

0A Setting Group 4 Indexed String G37 Disabled Setting 0 1 1 2


Relay Menu Database
abcd P740/EN GC/C11

Page A-18
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level
10 BB Trip Confirm Indexed String G37 Enabled Setting 0 1 1 2

11 Optos Setup Indexed String G80 Visible Setting 0 1 1 2

12 Overcurrent Prot Indexed String G37 Disabled Setting 0 1 1 2

13 Earth Fault Prot Indexed String G37 Disabled Setting 0 1 1 2

14 CB Fail & I< Indexed String G37 Disabled Setting 0 1 1 2

25 Input Labels Indexed String G80 Visible Setting 0 1 1 1

26 Output Labels Indexed String G80 Visible Setting 0 1 1 1

28 CT & VT Ratios Indexed String G80 Visible Setting 0 1 1 1

29 Recorder Control Indexed String G80 Visible Setting 0 1 1 1

2A Disturb Recorder Indexed String G80 Visible Setting 0 1 1 1

2B Measure't Setup Indexed String G80 Visible Setting 0 1 1 1

2D Commission Tests Indexed String G80 Visible Setting 0 1 1 2

2E Setting Values Indexed String G54 Secondary Setting 0 1 1 1

0A 00 CT AND VT RATIOS

07 Phase CT Primary Courier Number (Current) G35 1000 Setting 1 30000 1 2 I1=Phase CT secondary rating

08 Phase CT Sec'y Courier Number (Current) G2 1 Setting 1 5 4 2


Label M4=0A07/0A08
20 CT Class Indexed String G205 X Setting 0 3 1 2 Label M17=(0A07/0A08)^2

21 RBPh / RBN Unsigned Integer G1 1 Setting 0.5 10 0.1 2

23 Power Parameters (Sub-Heading)

24 Standard Input Indexed String G206 British Setting 0 1 1 2 British->0 / IEC->1

25 Knee Voltage Vk Courier Number (Voltage) G2 250 Setting 20 5000 10 2 0A24=0 => British

26 Rated Burden VA Courier Number (VA) G1 25 Setting 5 200 5 0A24=1 => IEC

27 Rated Burden Ohm Courier Number(Ohms) G35 25 / I1^2 Data 5 / I1^2 200 / I1^2 5 / I1^2 2 0A24=1 => IEC
Calculated not modifiable
28 KSCC Unsigned Integer G1 10 Setting 10 50 5 0A24=1 => IEC

29 RCT Sec'y Courier Number(Ohms) G35 0.5 Setting 0.1 50 0.1 2


Relay Menu Database
abcd P740/EN GC/C11

Page A-19
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

2B Eff. Burden Ohm Courier Number(Ohms) G35 25 / I1^2 Setting 0,1 / I1^2 200 / I1^2 0,01 / I1^2 2

2C Eff. Burden VA Courier Number (VA) G1 25 Data 0.1 200 0.01 Calculaled not modifiable

0B 00 RECORD CONTROL

1 Clear Events Indexed String G11 No Command 0 1 1 1

2 Clear Faults Indexed String G11 No Command 0 1 1 1

3 Clear Maint Indexed String G11 No Command 0 1 1 1

0C 00 DISTURB RECORDER

1 Duration Courier Number (time) 1.5 Setting 0.1 10.5 0.01 2

2 Trigger Position Courier Number (%) 33.3 Setting 0 100 0.1 2

3 Trigger Mode Indexed String G34 Single Setting 0 1 1 2

4 Analog Channel 1 Indexed String G31 IA Setting 0 8 1 2

5 Analog Channel 2 Indexed String G31 IB Setting 0 8 1 2

6 Analog Channel 3 Indexed String G31 IC Setting 0 8 1 2

7 Analog Channel 4 Indexed String G31 IN Setting 0 8 1 2

8 Analog Channel 5 Indexed String G31 Unused Setting 0 8 1 2 Build = Option Transfo Tension

9 Analog Channel 6 Indexed String G31 Unused Setting 0 8 1 2 Build = Option Transfo Tension

0A Analog Channel 7 Indexed String G31 Unused Setting 0 8 1 2 Build = Option Transfo Tension

0B Analog Channel 8 Indexed String G31 Unused Setting 0 8 1 2 Build = Option Transfo Tension

0C Digital Input 1 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

0D Input 1 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

0E Digital Input 2 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

0F Input 2 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

10 Digital Input 3 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

11 Input 3 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

12 Digital Input 4 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model
Relay Menu Database
abcd P740/EN GC/C11

Page A-20
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

13 Input 4 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

14 Digital Input 5 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

15 Input 5 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

16 Digital Input 6 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

17 Input 6 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

18 Digital Input 7 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

19 Input 7 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

1A Digital Input 8 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

1B Input 8 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

1C Digital Input 9 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

1D Input 9 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

1E Digital Input 10 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

1F Input 10 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

20 Digital Input 11 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

21 Input 11 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

22 Digital Input 12 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

23 Input 12 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

24 Digital Input 13 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

25 Input 13 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

26 Digital Input 14 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

27 Input 14 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

28 Digital Input 15 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

29 Input 15 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

2A Digital Input 16 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

2B Input 16 Trigger Indexed String G66 No Trigger Setting 0 2 1 2


Relay Menu Database
abcd P740/EN GC/C11

Page A-21
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level
2C Digital Input 17 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

2D Input 17 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

2E Digital Input 18 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

2F Input 18 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

30 Digital Input 19 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

31 Input 19 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

32 Digital Input 20 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

33 Input 20 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

34 Digital Input 21 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

35 Input 21 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

36 Digital Input 22 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

37 Input 22 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

38 Digital Input 23 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

39 Input 23 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

3A Digital Input 24 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

3B Input 24 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

3C Digital Input 25 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

3D Input 25 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

3E Digital Input 26 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

3F Input 26 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

40 Digital Input 27 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

41 Input 27 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

42 Digital Input 28 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

43 Input 28 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

44 Digital Input 29 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

45 Input 29 Trigger Indexed String G66 No Trigger Setting 0 2 1 2


Relay Menu Database
abcd P740/EN GC/C11

Page A-22
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

46 Digital Input 30 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

47 Input 30 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

48 Digital Input 31 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

49 Input 31 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

4A Digital Input 32 Indexed String G32 Unused Setting 0 DDB Size 1 2 DDB Size different for each model

4B Input 32 Trigger Indexed String G66 No Trigger Setting 0 2 1 2

0D 00 MEASURE'T SETUP

1 Default Display Indexed String G52 0 Setting 0 4 1 2

2 Local Values Indexed String G54 Secondary Setting 0 1 1 2 Local Measurement Values

3 Remote Values Indexed String G54 Primary Setting 0 1 1 2 Remote Measurement Values

0F 00 COMMISSION TESTS

1 Opto I/P Status Binary Flag(16 bits) Data


Indexed String
2 Relay O/P Status Binary Flag(32 bits) Data
Indexed String
3 Test Port Status Binary Flags(8 bits) Data
Indexed String
4 LED Status Binary Flags(8 bits) 0-7 Data

5 Monitor Bit 1 Unsigned Integer Relay 1 Setting 0 511 1 1

6 Monitor Bit 2 Unsigned Integer Relay 2 Setting 0 511 1 1

7 Monitor Bit 3 Unsigned Integer Relay 3 Setting 0 511 1 1

8 Monitor Bit 4 Unsigned Integer Relay 4 Setting 0 511 1 1

9 Monitor Bit 5 Unsigned Integer Relay 5 Setting 0 511 1 1

0A Monitor Bit 6 Unsigned Integer Relay 6 Setting 0 511 1 1

0B Monitor Bit 7 Unsigned Integer Relay 7 Setting 0 511 1 1

0C Monitor Bit 8 Unsigned Integer Relay 8 Setting 0 511 1 1

0D Test Mode Indexed String G215 Disabled Setting 0 1 1 2

0E Test Pattern Binary Flags (21bits) G9 0 Setting 0 20 1 2


Relay Menu Database
abcd P740/EN GC/C11

Page A-23
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level
Indexed String
0F Contact Test Indexed String G94 No Operation Command 0 2 1 2

10 Test LEDs Binary Flags (8bits) G94 No Operation Command 0 1 1 2


Indexed String
12 Position Pattern Binary Flags (7bits) G216 0 Setting 0 79 1 2 Forced Position for Isolators and Circuit Breaker

13 Position Test Indexed String G93 No Operation Command 0 2 1 2

20 DDB 0-31 Binary Flag (32 bits) N/A Data Relay


Visible by Courier and Modbus
21 DDB element 32-63 Binary Flag (32 bits) N/A Data Opto
Visible by Courier and Modbus
22 DDB element 64-95 Binary Flag (32 bits) N/A Data
Visible by Courier and Modbus
23 DDB element 96-127 Binary Flag (32 bits) N/A Data
Visible by Courier and Modbus
24 DDB element 128-159 Binary Flag (32 bits) N/A Data
Visible by Courier and Modbus
25 DDB element 160-191 Binary Flag (32 bits) N/A Data
Visible by Courier and Modbus
26 DDB element 192-223 Binary Flag (32 bits) N/A Data
Visible by Courier and Modbus
27 DDB element 224-255 Binary Flag (32 bits) N/A Data
Visible by Courier and Modbus
28 DDB element 256-287 Binary Flag (32 bits) N/A Data
Visible by Courier and Modbus
29 DDB element 288-319 Binary Flag (32 bits) N/A Data
Visible by Courier and Modbus
2A DDB element 320-351 Binary Flag (32 bits) N/A Data
Visible by Courier and Modbus
2B DDB element 352-383 Binary Flag (32 bits) N/A Data
Visible by Courier and Modbus
2C DDB element 384-415 Binary Flag (32 bits) N/A Data
Visible by Courier and Modbus
2D DDB element 415-447 Binary Flag (32 bits) N/A Data
Visible by Courier and Modbus
2E DDB element 448-479 Binary Flag (32 bits) N/A Data
Visible by Courier and Modbus
2F DDB element 480-511 Binary Flag (32 bits) N/A Data
Visible by Courier and Modbus

11 00 OPTOS SETUP

1 Global Nominal V Indexed String G200 2 Setting 0 5 1 2

02 Opto Input 1 Indexed String G201 2 Setting 0 4 1 2

3 Opto Input 2 Indexed String G201 2 Setting 0 4 1 2


Relay Menu Database
abcd P740/EN GC/C11

Page A-24
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level
4 Opto Input 3 Indexed String G201 2 Setting 0 4 1 2

5 Opto Input 4 Indexed String G201 2 Setting 0 4 1 2

06 Opto Input 5 Indexed String G201 2 Setting 0 4 1 2

7 Opto Input 6 Indexed String G201 2 Setting 0 4 1 2

08 Opto Input 7 Indexed String G201 2 Setting 0 4 1 2

9 Opto Input 8 Indexed String G201 2 Setting 0 4 1 2

0A Opto Input 9 Indexed String G201 2 Setting 0 4 1 2

0B Opto Input 10 Indexed String G201 2 Setting 0 4 1 2

0C Opto Input 11 Indexed String G201 2 Setting 0 4 1 2

0D Opto Input 12 Indexed String G201 2 Setting 0 4 1 2

0E Opto Input 13 Indexed String G201 2 Setting 0 4 1 2

0F Opto Input 14 Indexed String G201 2 Setting 0 4 1 2

10 Opto Input 15 Indexed String G201 2 Setting 0 4 1 2

11 Opto Input 16 Indexed String G201 2 Setting 0 4 1 2

12 Opto Input 17 Indexed String G201 2 Setting 0 4 1 2

13 Opto Input 18 Indexed String G201 2 Setting 0 4 1 2

14 Opto Input 19 Indexed String G201 2 Setting 0 4 1 2

15 Opto Input 20 Indexed String G201 2 Setting 0 4 1 2

16 Opto Input 21 Indexed String G201 2 Setting 0 4 1 2

17 Opto Input 22 Indexed String G201 2 Setting 0 4 1 2

18 Opto Input 23 Indexed String G201 2 Setting 0 4 1 2

19 Opto Input 24 Indexed String G201 2 Setting 0 4 1 2

GROUP 1
BUSBAR ELEMENT
30 00 GROUP 1
BB TRIP CONFIRM
01 I>BB Current Set Courier Number (Current) G2 1,2*I1 Setting 0,05*I1 4*I1 0,01*I1 2
Relay Menu Database
abcd P740/EN GC/C11

Page A-25
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

02 IN>BB Current Courier Number (Current) G2 0,2*I1 Setting 0,05*I1 4*I1 0,01*I1 2

BB TRIP CONFIRM
35 00 GROUP 1
BACKUP OVERCURRENT
01 I>1 Function Indexed String G43 Disabled Setting 0 10 1 2

02 I>1 Current Set Courier Number (Current) G2 3*I1 Setting 0,10*I1 32*I1 0,01*I1 2

03 I>1 Time Delay Courier Number (Time) G2 1 Setting 0 100 0.01 2

04 I>1 TMS Courier Number (Time) G2 1 Setting 0.025 1.2 0.025 2 5 >= 3501 >=2

05 I>1 Time Dial Courier Number (Time) G2 7 Setting 0.5 15 0.1 2

06 I>1 Reset Char Indexed String G60 DT Setting 0 1 1 2

07 I>1 tReset Courier Number (Time) G2 0 Setting 0 100 0.1 2 5 >= 3501 >=1 OR (3506 = 0 AND 3501 >= 6)

08 I>2 Function Indexed String G209 Disabled Setting 0 3 1 2

09 I>2 Current Set Courier Number (Current) G2 20*I1 Setting 0,10*In 32*I1 0,01*I1 2

0A I>2 Time Delay Courier Number (Time) G2 1 Setting 0 100 0.01 2

OVERCURRENT
38 00 GROUP 1
EARTH FAULT
01 IN>1 Function Indexed String G43 Disabled Setting 0 10 1 2

02 IN>1 Current Set Courier Number (Current) G2 0,3*I1 Setting 0,10*I1 32*I1 0,01*I1 2

03 IN>1 Time Delay Courier Number (Time) G2 1 Setting 0 100 0.01 2

04 IN>1 TMS Courier Number (Time) G2 1 Setting 0.025 1.2 0.025 2 5 >= 3801 >=2

05 IN>1 Time Dial Courier Number (Time) G2 7 Setting 0.5 15 0.1 2

06 IN>1 Reset Char Indexed String G60 DT Setting 0 1 1 2

07 IN>1 tReset Courier Number (Time) G2 0 Setting 0 100 0.1 2 5 >= 3801 >=1 OR (3806 = 0 AND 3801 >= 6)

08 IN>2 Function Indexed String G209 Disabled Setting 0 3 1 2

09 IN>2 Current Set Courier Number (Current) G2 20*I1 Setting 0,10*I1 32*I1 0,01*I1 2

0A IN>2 Time Delay Courier Number (Time) G2 1 Setting 0 100 0.01 2


Relay Menu Database
abcd P740/EN GC/C11

Page A-26
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

EARTH FAULT
45 00 GROUP 1
CB FAIL
01 Control by Indexed String G210 I< Setting 0 2 1 2 I<, 52a, I< & 52a

02 I< Current Set Courier Number (Current) G2 0,05*I1 Setting 0,05*I1 1*I1 0,01*I1 2

03 I> Status Indexed String G37 Disabled Setting 2

04 I> Current Set Courier Number (Current) G2 1,2*I1 Setting 0,05*I1 4*I1 0,01*I1 2 4503<>0 and 4501<>1

05 IN> Current Set Courier Number (Current) G2 0,2*I1 Setting 0,05*I1 4*I1 0,01*I1 2 4503<>0 and 4501<>1

06 INTERNAL TRIP (Sub Heading)

07 CB Fail Timer 1 Courier Number (Time) G2 0.05 Setting 0 10 0.01 2

08 CB Fail Timer 2 Courier Number (Time) G2 0.2 Setting 0 10 0.01 2 4508 > 4507

09 EXTERNAL TRIP (Sub Heading)

0A CB Fail Timer 3 Courier Number (Time) G2 0.05 Setting 0 10 0.01 2

0B CB Fail Timer 4 Courier Number (Time) G2 0.2 Setting 0 10 0.01 2 450B > 450A

CB FAIL
46 00 GROUP 1
SUPERVISION
0D I0 SUPERVISION (Sub Heading)

0E Error Factor Kce Courier Number (%) G2 40 Setting 1 100 1 2

0F Alarm Delay Tce Courier Number (Time) G2 5 Setting 0.1 10 0.1 2

SUPERVISION
4A 00 GROUP 1 Product Dependent
INPUT LABELS
1 Opto Input 1 ASCII Text (16 chars) G3 Opto Label 01 Setting 32 55 1 2
1
2 Opto Input 2 ASCII Text (16 chars) G3 Opto Label 02 Setting 32 55 1 2

3 Opto Input 3 ASCII Text (16 chars) G3 Opto Label 03 Setting 32 55 1 2

4 Opto Input 4 ASCII Text (16 chars) G3 etc.. Setting 32 55 1 2

5 Opto Input 5 ASCII Text (16 chars) G3 Setting 32 55 1 2

6 Opto Input 6 ASCII Text (16 chars) G3 Setting 32 55 1 2


Relay Menu Database
abcd P740/EN GC/C11

Page A-27
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

7 Opto Input 7 ASCII Text (16 chars) G3 Setting 32 55 1 2

8 Opto Input 8 ASCII Text (16 chars) G3 Setting 32 55 1 2

9 Opto Input 9 ASCII Text (16 chars) G3 Setting 32 55 1 2

0A Opto Input 10 ASCII Text (16 chars) G3 Setting 32 55 1 2

0B Opto Input 11 ASCII Text (16 chars) G3 Setting 32 55 1 2

0C Opto Input 12 ASCII Text (16 chars) G3 Setting 32 55 1 2

0D Opto Input 13 ASCII Text (16 chars) G3 Setting 32 55 1 2

0E Opto Input 14 ASCII Text (16 chars) G3 Setting 32 55 1 2

0F Opto Input 15 ASCII Text (16 chars) G3 Setting 32 55 1 2

10 Opto Input 16 ASCII Text (16 chars) G3 Setting 32 55 1 2

11 Opto Input 17 ASCII Text (16 chars) G3 Setting 32 55 1 2

12 Opto Input 18 ASCII Text (16 chars) G3 Setting 32 55 1 2

13 Opto Input 19 ASCII Text (16 chars) G3 Setting 32 55 1 2

14 Opto Input 20 ASCII Text (16 chars) G3 Setting 32 55 1 2

15 Opto Input 21 ASCII Text (16 chars) G3 Setting 32 55 1 2

16 Opto Input 22 ASCII Text (16 chars) G3 Setting 32 55 1 2

17 Opto Input 23 ASCII Text (16 chars) G3 Setting 32 55 1 2

18 Opto Input 24 ASCII Text (16 chars) G3 Setting 32 55 1 2

INPUT LABELS
4B 00 GROUP 1 Product Dependent
OUTPUT LABELS
1 Relay 1 ASCII Text (16 chars) G3 Relay Label 01 Setting 0 23 1 2

2 Relay 2 ASCII Text (16 chars) G3 Relay Label 02 Setting 0 23 1 2

3 Relay 3 ASCII Text (16 chars) G3 Relay Label 03 Setting 0 23 1 2

4 Relay 4 ASCII Text (16 chars) G3 etc Setting 0 23 1 2

5 Relay 5 ASCII Text (16 chars) G3 Setting 0 23 1 2


Relay Menu Database
abcd P740/EN GC/C11

Page A-28
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level
6 Relay 6 ASCII Text (16 chars) G3 Setting 0 23 1 2

7 Relay 7 ASCII Text (16 chars) G3 Setting 0 23 1 2

8 Relay 8 ASCII Text (16 chars) G3 Setting 0 23 1 2

9 Relay 9 ASCII Text (16 chars) G3 Setting 0 23 1 2

0A Relay 10 ASCII Text (16 chars) G3 Setting 0 23 1 2

0B Relay 11 ASCII Text (16 chars) G3 Setting 0 23 1 2

0C Relay 12 ASCII Text (16 chars) G3 Setting 0 23 1 2

0D Relay 13 ASCII Text (16 chars) G3 Setting 0 23 1 2

0E Relay 14 ASCII Text (16 chars) G3 Setting 0 23 1 2

0F Relay 15 ASCII Text (16 chars) G3 Setting 0 23 1 2

10 Relay 16 ASCII Text (16 chars) G3 Setting 0 23 1 2

11 Relay 17 ASCII Text (16 chars) G3 Setting 0 23 1 2

12 Relay 18 ASCII Text (16 chars) G3 Setting 0 23 1 2

13 Relay 19 ASCII Text (16 chars) G3 Setting 0 23 1 2

14 Relay 20 ASCII Text (16 chars) G3 Setting 0 23 1 2

15 Relay 21 ASCII Text (16 chars) G3 Setting 0 23 1 2

OUTPUT LABELS
GROUP 2
PROTECTION SETTINGS
50 00 Repeat of Group 1 columns/rows

GROUP 3
PROTECTION SETTINGS
70 00 Repeat of Group 1 columns/rows

GROUP 4
PROTECTION SETTINGS
90 00 Repeat of Group 1 columns/rows

C0 00 TOPO SETTINGS

01 Topology Size Unsigned integer Data

02 Topology Element 1 Binary Flag (32bits) Data


Relay Menu Database
abcd P740/EN GC/C11

Page A-29
MiCOM P740
A - Menu database for Courier, User Interface (MiCOM P742 and P743 only)
Courier Ref
Courier Text Courier Data Type LCD ref Data Default Setting Cell Type Min Max Step Password Comment
Col Row Courier Level

,,,

FB Topology Element 250 Binary Flag (32bits) Data


Relay Menu Database P740/EN GC/C11

MiCOM P740

B - DIGITAL DATA BUS


P740/EN GC/C11 Relay Menu Database

MiCOM P740
Relay Menu Database
abcd P740/EN GC/C11

MiCOM P740 Page B-1

B - Digital Data Bus (For P741 Only)

DDB N Source Description English Text

0 Relay Relay Label 01 Output Label 01


1 Relay Relay Label 02 Output Label 02
2 Relay Relay Label 03 Output Label 03
3 Relay Relay Label 04 Output Label 04
4 Relay Relay Label 05 Output Label 05
5 Relay Relay Label 06 Output Label 06
6 Relay Relay Label 07 Output Label 07
7 Relay Relay Label 08 Output Label 08
32 Opto Opto Label 01 Opto Input 1
33 Opto Opto Label 02 Opto Input 2
34 Opto Opto Label 03 Opto Input 3
35 Opto Opto Label 04 Opto Input 4
36 Opto Opto Label 05 Opto Input 5
37 Opto Opto Label 06 Opto Input 6
38 Opto Opto Label 07 Opto Input 7
39 Opto Opto Label 08 Opto Input 8
64 Led LED 1 Led 1
65 Led LED 2 Led 2
66 Led LED 3 Led 3
67 Led LED 4 Led 4
68 Led LED 5 Led 5
69 Led LED 6 Led 6
70 Led LED 7 Led 7
71 Led LED 8 Led 8
72 PSL (IN) SG Bit LSB LSB Setting Group
73 PSL (IN) SG Bit MSB MSB Setting Group
74 PSL (IN) Reset Circt Flt Reset Circuitry Fault
75 PSL (IN) Ext. Start DR Starting Disturbance Recorder
76 PSL (IN) Ext. CZ confirm. External CZ confirmation (0=confirmed)
77 PSL (IN) Reset Latches Reset Relays and Led latched in PSL
80 Virtual Relay Virtual Relay 01 Virtual Relays 01
81 Virtual Relay Virtual Relay 02 Virtual Relays 02
82 Virtual Relay Virtual Relay 03 Virtual Relays 03
83 Virtual Relay Virtual Relay 04 Virtual Relays 04
84 Virtual Relay Virtual Relay 05 Virtual Relays 05
85 Virtual Relay Virtual Relay 06 Virtual Relays 06
86 Virtual Relay Virtual Relay 07 Virtual Relays 07
87 Virtual Relay Virtual Relay 08 Virtual Relays 08
88 Virtual Relay Virtual Relay 09 Virtual Relays 09
89 Virtual Relay Virtual Relay 10 Virtual Relays 10
90 Virtual Relay Virtual Relay 11 Virtual Relays 11
91 Virtual Relay Virtual Relay 12 Virtual Relays 12
92 Virtual Relay Virtual Relay 13 Virtual Relays 13
93 Virtual Relay Virtual Relay 14 Virtual Relays 14
94 Virtual Relay Virtual Relay 15 Virtual Relays 15
95 Virtual Relay Virtual Relay 16 Virtual Relays 16
103 PSL (OUT) System Minor Syst Error Minor System Error
104 PSL (IN) Alarm User 1 Self Reset User Alarm 1
105 PSL (IN) Alarm User 2 Self Reset User Alarm 2
106 PSL (IN) Alarm User 3 Self Reset User Alarm 3
107 PSL (IN) Alarm User 4 Self Reset User Alarm 4
108 PSL (IN) Alarm User 5 Self Reset User Alarm 5
109 PSL (IN) Alarm User 6 Self Reset User Alarm 6
110 PSL (IN) Alarm User 7 Self Reset User Alarm 7
111 PSL (IN) Alarm User 8 Self Reset User Alarm 8
112 PSL (OUT) 87BB Protection Fault 87BB zone 16 Fault current in zone 16
113 PSL (OUT) 87BB Protection Fault 87BB zone 15 Fault current in zone 15
114 PSL (OUT) 87BB Protection Fault 87BB zone 14 Fault current in zone 14
115 PSL (OUT) 87BB Protection Fault 87BB zone 13 Fault current in zone 13
116 PSL (OUT) 87BB Protection Fault 87BB zone 12 Fault current in zone 12
117 PSL (OUT) 87BB Protection Fault 87BB zone 11 Fault current in zone 11
118 PSL (OUT) 87BB Protection Fault 87BB zone 10 Fault current in zone 10
119 PSL (OUT) 87BB Protection Fault 87BB zone 09 Fault current in zone 9
120 PSL (OUT) 87BB Protection Fault 87BB zone 08 Fault current in zone 8
121 PSL (OUT) 87BB Protection Fault 87BB zone 07 Fault current in zone 7
122 PSL (OUT) 87BB Protection Fault 87BB zone 06 Fault current in zone 6
123 PSL (OUT) 87BB Protection Fault 87BB zone 05 Fault current in zone 5
124 PSL (OUT) 87BB Protection Fault 87BB zone 04 Fault current in zone 4
125 PSL (OUT) 87BB Protection Fault 87BB zone 03 Fault current in zone 3
126 PSL (OUT) 87BB Protection Fault 87BB zone 02 Fault current in zone 2
127 PSL (OUT) 87BB Protection Fault 87BB zone 01 Fault current in zone 1
128 PSL (OUT) 87BB Protection Circt Flt zone 16 Circuitry fault in zone 16
129 PSL (OUT) 87BB Protection Circt Flt zone 15 Circuitry fault in zone 15
130 PSL (OUT) 87BB Protection Circt Flt zone 14 Circuitry fault in zone 14
131 PSL (OUT) 87BB Protection Circt Flt zone 13 Circuitry fault in zone 13
132 PSL (OUT) 87BB Protection Circt Flt zone 12 Circuitry fault in zone 12
133 PSL (OUT) 87BB Protection Circt Flt zone 11 Circuitry fault in zone 11
Relay Menu Database
abcd P740/EN GC/C11

MiCOM P740 Page B-2

B - Digital Data Bus (For P741 Only)

DDB N Source Description English Text

134 PSL (OUT) 87BB Protection Circt Flt zone 10 Circuitry fault in zone 10
135 PSL (OUT) 87BB Protection Circt Flt zone 09 Circuitry fault in zone 9
136 PSL (OUT) 87BB Protection Circt Flt zone 08 Circuitry fault in zone 8
137 PSL (OUT) 87BB Protection Circt Flt zone 07 Circuitry fault in zone 7
138 PSL (OUT) 87BB Protection Circt Flt zone 06 Circuitry fault in zone 6
139 PSL (OUT) 87BB Protection Circt Flt zone 05 Circuitry fault in zone 5
140 PSL (OUT) 87BB Protection Circt Flt zone 04 Circuitry fault in zone 4
141 PSL (OUT) 87BB Protection Circt Flt zone 03 Circuitry fault in zone 3
142 PSL (OUT) 87BB Protection Circt Flt zone 02 Circuitry fault in zone 2
143 PSL (OUT) 87BB Protection Circt Flt zone 01 Circuitry fault in zone 1
144 PSL (OUT) 87BB Protection Trp 87BB zone 16 Busbar trip in zone 16
145 PSL (OUT) 87BB Protection Trp 87BB zone 15 Busbar trip in zone 15
146 PSL (OUT) 87BB Protection Trp 87BB zone 14 Busbar trip in zone 14
147 PSL (OUT) 87BB Protection Trp 87BB zone 13 Busbar trip in zone 13
148 PSL (OUT) 87BB Protection Trp 87BB zone 12 Busbar trip in zone 12
149 PSL (OUT) 87BB Protection Trp 87BB zone 11 Busbar trip in zone 11
150 PSL (OUT) 87BB Protection Trp 87BB zone 10 Busbar trip in zone 10
151 PSL (OUT) 87BB Protection Trp 87BB zone 09 Busbar trip in zone 9
152 PSL (OUT) 87BB Protection Trp 87BB zone 08 Busbar trip in zone 8
153 PSL (OUT) 87BB Protection Trp 87BB zone 07 Busbar trip in zone 7
154 PSL (OUT) 87BB Protection Trp 87BB zone 06 Busbar trip in zone 6
155 PSL (OUT) 87BB Protection Trp 87BB zone 05 Busbar trip in zone 5
156 PSL (OUT) 87BB Protection Trp 87BB zone 04 Busbar trip in zone 4
157 PSL (OUT) 87BB Protection Trp 87BB zone 03 Busbar trip in zone 3
158 PSL (OUT) 87BB Protection Trp 87BB zone 02 Busbar trip in zone 2
159 PSL (OUT) 87BB Protection Trp 87BB zone 01 Busbar trip in zone 1
160 PSL (OUT) 50BF Protection Trp 50BF zone 16 Breaker failure trip (50BF) in zone 16
161 PSL (OUT) 50BF Protection Trp 50BF zone 15 Breaker failure trip (50BF) in zone 15
162 PSL (OUT) 50BF Protection Trp 50BF zone 14 Breaker failure trip (50BF) in zone 14
163 PSL (OUT) 50BF Protection Trp 50BF zone 13 Breaker failure trip (50BF) in zone 13
164 PSL (OUT) 50BF Protection Trp 50BF zone 12 Breaker failure trip (50BF) in zone 12
165 PSL (OUT) 50BF Protection Trp 50BF zone 11 Breaker failure trip (50BF) in zone 11
166 PSL (OUT) 50BF Protection Trp 50BF zone 10 Breaker failure trip (50BF) in zone 10
167 PSL (OUT) 50BF Protection Trp 50BF zone 09 Breaker failure trip (50BF) in zone 9
168 PSL (OUT) 50BF Protection Trp 50BF zone 08 Breaker failure trip (50BF) in zone 8
169 PSL (OUT) 50BF Protection Trp 50BF zone 07 Breaker failure trip (50BF) in zone 7
170 PSL (OUT) 50BF Protection Trp 50BF zone 06 Breaker failure trip (50BF) in zone 6
171 PSL (OUT) 50BF Protection Trp 50BF zone 05 Breaker failure trip (50BF) in zone 5
172 PSL (OUT) 50BF Protection Trp 50BF zone 04 Breaker failure trip (50BF) in zone 4
173 PSL (OUT) 50BF Protection Trp 50BF zone 03 Breaker failure trip (50BF) in zone 3
174 PSL (OUT) 50BF Protection Trp 50BF zone 02 Breaker failure trip (50BF) in zone 2
175 PSL (OUT) 50BF Protection Trp 50BF zone 01 Breaker failure trip (50BF) in zone 1
176 PSL (OUT) Commissioning Test Man.Trip zone 16 Manual trip zone 16
177 PSL (OUT) Commissioning Test Man.Trip zone 15 Manual trip zone 15
178 PSL (OUT) Commissioning Test Man.Trip zone 14 Manual trip zone 14
179 PSL (OUT) Commissioning Test Man.Trip zone 13 Manual trip zone 13
180 PSL (OUT) Commissioning Test Man.Trip zone 12 Manual trip zone 12
181 PSL (OUT) Commissioning Test Man.Trip zone 11 Manual trip zone 11
182 PSL (OUT) Commissioning Test Man.Trip zone 10 Manual trip zone 10
183 PSL (OUT) Commissioning Test Man.Trip zone 09 Manual trip zone 9
184 PSL (OUT) Commissioning Test Man.Trip zone 08 Manual trip zone 8
185 PSL (OUT) Commissioning Test Man.Trip zone 07 Manual trip zone 7
186 PSL (OUT) Commissioning Test Man.Trip zone 06 Manual trip zone 6
187 PSL (OUT) Commissioning Test Man.Trip zone 05 Manual trip zone 5
188 PSL (OUT) Commissioning Test Man.Trip zone 04 Manual trip zone 4
189 PSL (OUT) Commissioning Test Man.Trip zone 03 Manual trip zone 3
190 PSL (OUT) Commissioning Test Man.Trip zone 02 Manual trip zone 2
191 PSL (OUT) Commissioning Test Man.Trip zone 01 Manual trip zone 1
192 PSL (OUT) Commissioning Test Lck Lev.1 zone16 Commissioning mode 87BB monitoring in zone 16
193 PSL (OUT) Commissioning Test Lck Lev.1 zone15 Commissioning mode 87BB monitoring in zone 15
194 PSL (OUT) Commissioning Test Lck Lev.1 zone14 Commissioning mode 87BB monitoring in zone 14
195 PSL (OUT) Commissioning Test Lck Lev.1 zone13 Commissioning mode 87BB monitoring in zone 13
196 PSL (OUT) Commissioning Test Lck Lev.1 zone12 Commissioning mode 87BB monitoring in zone 12
197 PSL (OUT) Commissioning Test Lck Lev.1 zone11 Commissioning mode 87BB monitoring in zone 11
198 PSL (OUT) Commissioning Test Lck Lev.1 zone10 Commissioning mode 87BB monitoring in zone 10
199 PSL (OUT) Commissioning Test Lck Lev.1 zone09 Commissioning mode 87BB monitoring in zone 9
200 PSL (OUT) Commissioning Test Lck Lev.1 zone08 Commissioning mode 87BB monitoring in zone 8
201 PSL (OUT) Commissioning Test Lck Lev.1 zone07 Commissioning mode 87BB monitoring in zone 7
202 PSL (OUT) Commissioning Test Lck Lev.1 zone06 Commissioning mode 87BB monitoring in zone 6
203 PSL (OUT) Commissioning Test Lck Lev.1 zone05 Commissioning mode 87BB monitoring in zone 5
204 PSL (OUT) Commissioning Test Lck Lev.1 zone04 Commissioning mode 87BB monitoring in zone 4
205 PSL (OUT) Commissioning Test Lck Lev.1 zone03 Commissioning mode 87BB monitoring in zone 3
206 PSL (OUT) Commissioning Test Lck Lev.1 zone02 Commissioning mode 87BB monitoring in zone 2
207 PSL (OUT) Commissioning Test Lck Lev.1 zone01 Commissioning mode 87BB monitoring in zone 1
208 PSL (OUT) Commissioning Test Lck Lev.2 zone16 Commissioning mode 87BB & 50BF disabled in zone 16
209 PSL (OUT) Commissioning Test Lck Lev.2 zone15 Commissioning mode 87BB & 50BF disabled in zone 15
210 PSL (OUT) Commissioning Test Lck Lev.2 zone14 Commissioning mode 87BB & 50BF disabled in zone 14
Relay Menu Database
abcd P740/EN GC/C11

MiCOM P740 Page B-3

B - Digital Data Bus (For P741 Only)

DDB N Source Description English Text

211 PSL (OUT) Commissioning Test Lck Lev.2 zone13 Commissioning mode 87BB & 50BF disabled in zone 13
212 PSL (OUT) Commissioning Test Lck Lev.2 zone12 Commissioning mode 87BB & 50BF disabled in zone 12
213 PSL (OUT) Commissioning Test Lck Lev.2 zone11 Commissioning mode 87BB & 50BF disabled in zone 11
214 PSL (OUT) Commissioning Test Lck Lev.2 zone10 Commissioning mode 87BB & 50BF disabled in zone 10
215 PSL (OUT) Commissioning Test Lck Lev.2 zone09 Commissioning mode 87BB & 50BF disabled in zone 9
216 PSL (OUT) Commissioning Test Lck Lev.2 zone08 Commissioning mode 87BB & 50BF disabled in zone 8
217 PSL (OUT) Commissioning Test Lck Lev.2 zone07 Commissioning mode 87BB & 50BF disabled in zone 7
218 PSL (OUT) Commissioning Test Lck Lev.2 zone06 Commissioning mode 87BB & 50BF disabled in zone 6
219 PSL (OUT) Commissioning Test Lck Lev.2 zone05 Commissioning mode 87BB & 50BF disabled in zone 5
220 PSL (OUT) Commissioning Test Lck Lev.2 zone04 Commissioning mode 87BB & 50BF disabled in zone 5
221 PSL (OUT) Commissioning Test Lck Lev.2 zone03 Commissioning mode 87BB & 50BF disabled in zone 3
222 PSL (OUT) Commissioning Test Lck Lev.2 zone02 Commissioning mode 87BB & 50BF disabled in zone 2
223 PSL (OUT) Commissioning Test Lck Lev.2 zone01 Commissioning mode 87BB & 50BF disabled in zone 1
224 PSL (OUT) 87BB Protection Trip 87BB Busbar trip order (87BB)
225 PSL (OUT) 87BB Protection Trip 87BB block Busbar trip order blocked by commissioning mode
226 PSL (OUT) 87BB Protection Trip Manual zone Manual Trip Order
227 PSL (OUT) 50BF Protection Trip 50BF Breaker fail trip order (50BF)
228 PSL (OUT) 50BF Protection Trip 50BF block Breaker fail trip order blocked by commissioning mode
229 PSL (OUT) 87BB Protection Dead Zone Signal Fault in dead zone
230 PSL (OUT) 87BB Protection Fault phase A Fault current in phase A
231 PSL (OUT) 87BB Protection Fault phase B Fault current in phase B
232 PSL (OUT) 87BB Protection Fault phase C Fault current in phase C
233 PSL (OUT) 87BB Protection Earth fault Sensitive earth fault current
234 PSL (OUT) 87BB Protection Circuitry Fault Circuitry fault on 1 or several zones
235 PSL (OUT) Commissioning Test Alm Lck Level 1 Commissioning mode 87BB monitoring
236 PSL (OUT) Commissioning Test Alm Lck Level 2 Commissioning mode 87BB & 50BF disabled
237 PSL (OUT) Config. valid Valid configuration
238 PSL (OUT) Topology valid Topology file valid
240 PSL (OUT) Main System Er. Main system error
241 PSL (OUT) 1st CU main err. CU main error
242 PSL (OUT) 2nd CU main err. Remote CU main error
243 PSL (OUT) 87BB Protection Fault Check Zone Busbar fault detected by both CZ (internal & external)
244 PSL (OUT) 87BB Protection Circt Flt ph A Circuitry fault in phase A
245 PSL (OUT) 87BB Protection Circt Flt ph B Circuitry fault in phase B
246 PSL (OUT) 87BB Protection Circt Flt ph C Circuitry fault in phase C
247 PSL (OUT) 87BB Protection Circt Flt Earth Residual circuitry fault
256 PSL (OUT) System Err Chan A Com 1 PU communication error: com A board 1
257 PSL (OUT) System Err Chan B Com 1 PU communication error: com B board 1
258 PSL (OUT) System Err Chan C Com 1 PU communication error: com C board 1
259 PSL (OUT) System Err Chan D Com 1 PU communication error: com D board 1
260 PSL (OUT) System Err Chan A Com 2 PU communication error: com A board 2
261 PSL (OUT) System Err Chan B Com 2 PU communication error: com B board 2
262 PSL (OUT) System Err Chan C Com 2 PU communication error: com C board 2
263 PSL (OUT) System Err Chan D Com 2 PU communication error: com D board 2
264 PSL (OUT) System Err Chan A Com 3 PU communication error: com A board 3
265 PSL (OUT) System Err Chan B Com 3 PU communication error: com B board 3
266 PSL (OUT) System Err Chan C Com 3 PU communication error: com C board 3
267 PSL (OUT) System Err Chan D Com 3 PU communication error: com D board 3
268 PSL (OUT) System Err Chan A Com 4 PU communication error: com A board 4
269 PSL (OUT) System Err Chan B Com 4 PU communication error: com B board 4
270 PSL (OUT) System Err Chan C Com 4 PU communication error: com C board 4
271 PSL (OUT) System Err Chan D Com 4 PU communication error: com D board 4
272 PSL (OUT) System Err Chan A Com 5 PU communication error: com A board 5
273 PSL (OUT) System Err Chan B Com 5 PU communication error: com B board 5
274 PSL (OUT) System Err Chan C Com 5 PU communication error: com C board 5
275 PSL (OUT) System Err Chan D Com 5 PU communication error: com D board 5
276 PSL (OUT) System Err Chan A Com 6 PU communication error: com A board 6
277 PSL (OUT) System Err Chan B Com 6 PU communication error: com B board 6
278 PSL (OUT) System Err Chan C Com 6 PU communication error: com C board 6
279 PSL (OUT) System Err Chan D Com 6 PU communication error: com D board 6
280 PSL (OUT) System Err Chan A Com 7 PU communication error: com A board 7
281 PSL (OUT) System Err Chan B Com 7 PU communication error: com B board 7
282 PSL (OUT) System Err Chan C Com 7 PU communication error: com C board 7
283 PSL (OUT) System Err Chan D Com 7 PU communication error: com D board 7
284 PSL (OUT) System Err Chan A Com 8 PU communication error: com A board 8
285 PSL (OUT) System Err Chan B Com 8 PU communication error: com B board 8
286 PSL (OUT) System Err Chan C Com 8 PU communication error: com C board 8
287 PSL (OUT) System Err Chan D Com 8 PU communication error: com D board 8
288 PSL (OUT) System PU Adr 38 error Error: several PU adresse 38
289 PSL (OUT) System PU Adr 37 error Error: several PU adresse 37
290 PSL (OUT) System PU Adr 36 error Error: several PU adresse 36
291 PSL (OUT) System PU Adr 35 error Error: several PU adresse 35
292 PSL (OUT) System PU Adr 34 error Error: several PU adresse 34
293 PSL (OUT) System PU Adr 33 error Error: several PU adresse 33
294 PSL (OUT) System PU Adr 32 error Error: several PU adresse 32
295 PSL (OUT) System PU Adr 31 error Error: several PU adresse 31
296 PSL (OUT) System PU Adr 30 error Error: several PU adresse 30
Relay Menu Database
abcd P740/EN GC/C11

MiCOM P740 Page B-4

B - Digital Data Bus (For P741 Only)

DDB N Source Description English Text

297 PSL (OUT) System PU Adr 29 error Error: several PU adresse 29


298 PSL (OUT) System PU Adr 28 error Error: several PU adresse 28
299 PSL (OUT) System PU Adr 27 error Error: several PU adresse 27
300 PSL (OUT) System PU Adr 26 error Error: several PU adresse 26
301 PSL (OUT) System PU Adr 25 error Error: several PU adresse 25
302 PSL (OUT) System PU Adr 24 error Error: several PU adresse 24
303 PSL (OUT) System PU Adr 23 error Error: several PU adresse 23
304 PSL (OUT) System PU Adr 22 error Error: several PU adresse 22
305 PSL (OUT) System PU Adr 21 error Error: several PU adresse 21
306 PSL (OUT) System PU Adr 20 error Error: several PU adresse 20
307 PSL (OUT) System PU Adr 19 error Error: several PU adresse 19
308 PSL (OUT) System PU Adr 18 error Error: several PU adresse 18
309 PSL (OUT) System PU Adr 17 error Error: several PU adresse 17
310 PSL (OUT) System PU Adr 16 error Error: several PU adresse 16
311 PSL (OUT) System PU Adr 15 error Error: several PU adresse 15
312 PSL (OUT) System PU Adr 14 error Error: several PU adresse 14
313 PSL (OUT) System PU Adr 13 error Error: several PU adresse 13
314 PSL (OUT) System PU Adr 12 error Error: several PU adresse 12
315 PSL (OUT) System PU Adr 11 error Error: several PU adresse 11
316 PSL (OUT) System PU Adr 10 error Error: several PU adresse 10
317 PSL (OUT) System PU Adr 09 error Error: several PU adresse 9
318 PSL (OUT) System PU Adr 08 error Error: several PU adresse 8
319 PSL (OUT) System PU Adr 07 error Error: several PU adresse 7
321 PSL (OUT) System 1st CU minor er. CU minor error
322 PSL (OUT) System 2nd CU minor er. Remote CU minor error
323 PSL (OUT) System Minor Err COM1 Minor error in COM 1 board
324 PSL (OUT) System Minor Err COM2 Minor error in COM 2 board
325 PSL (OUT) System Minor Err COM3 Minor error in COM 3 board
326 PSL (OUT) System Minor Err COM4 Minor error in COM 4 board
327 PSL (OUT) System Minor Err COM5 Minor error in COM 5 board
328 PSL (OUT) System Minor Err COM6 Minor error in COM 6 board
329 PSL (OUT) System Minor Err COM7 Minor error in COM 7 board
330 PSL (OUT) System Minor Err COM8 Minor error in COM 8 board
332 PSL (OUT) System Operating Mode 1
333 PSL (OUT) System Operating Mode 2
Expert Only
334 PSL (OUT) Disturbance Recorder Pre-fault
335 PSL (OUT) Disturbance Recorder Post-fault
336 Virtual Opto Virtual Opto 01 Virtual Opto 01
337 Virtual Opto Virtual Opto 02 Virtual Opto 02
338 Virtual Opto Virtual Opto 03 Virtual Opto 03
339 Virtual Opto Virtual Opto 04 Virtual Opto 04
340 Virtual Opto Virtual Opto 05 Virtual Opto 05
341 Virtual Opto Virtual Opto 06 Virtual Opto 06
342 Virtual Opto Virtual Opto 07 Virtual Opto 07
343 Virtual Opto Virtual Opto 08 Virtual Opto 08
344 Virtual Opto Virtual Opto 09 Virtual Opto 09
345 Virtual Opto Virtual Opto 10 Virtual Opto 10
346 Virtual Opto Virtual Opto 11 Virtual Opto 11
347 Virtual Opto Virtual Opto 12 Virtual Opto 12
348 Virtual Opto Virtual Opto 13 Virtual Opto 13
349 Virtual Opto Virtual Opto 14 Virtual Opto 14
350 Virtual Opto Virtual Opto 15 Virtual Opto 15
351 Virtual Opto Virtual Opto 16 Virtual Opto 16
352 PSL (OUT) CommTest Enabled Commissionning Test enable
353 PSL (OUT) 87BB Enabled Busbar protection enable
354 PSL (OUT) 87BBN Enabled Busbar earth enable
355 PSL (OUT) Reset Circt Flt Reset after fault
356 PSL (OUT) Topo/Set Changed Change on topology or configuration
357 PSL (OUT) Manual Start DR Disturbance recorder - Manual start
358 PSL (OUT) PU Topo no valid Topology file error for one or several PU
359 PSL (OUT) Alarm Field Volt Alarm field voltage
360 PSL (OUT) Ext. CZ confirm. External CZ confirmation
367 PSL (OUT) General alarm General alarm
400 PSL Relay 01 Output relay 1 condition
401 PSL Relay 02 Output relay 2 condition
402 PSL Relay 03 Output relay 3 condition
403 PSL Relay 04 Output relay 4 condition
404 PSL Relay 05 Output relay 5 condition
405 PSL Relay 06 Output relay 6 condition
406 PSL Relay 07 Output relay 7 condition
407 PSL Relay 08 Output relay 8 condition
408 PSL Relay 09 Reserved
409 PSL Relay 10 Reserved
410 PSL Relay 11 Reserved
411 PSL Relay 12 Reserved
412 PSL Relay 13 Reserved
413 PSL Relay 14 Reserved
Relay Menu Database
abcd P740/EN GC/C11

MiCOM P740 Page B-5

B - Digital Data Bus (For P741 Only)

DDB N Source Description English Text

414 PSL Relay 15 Reserved


415 PSL Relay 16 Reserved
416 PSL Relay 17 Reserved
417 PSL Relay 18 Reserved
418 PSL Relay 19 Reserved
419 PSL Relay 20 Reserved
420 PSL Relay 21 Reserved
421 PSL Relay 22 Reserved
422 PSL Relay 23 Reserved
423 PSL Relay 24 Reserved
424 PSL Relay 25 Reserved
425 PSL Relay 26 Reserved
426 PSL Relay 27 Reserved
427 PSL Relay 28 Reserved
428 PSL Relay 29 Reserved
429 PSL Relay 30 Reserved
430 PSL Relay 31 Reserved
431 PSL Relay 32 Reserved
432 PSL LED Cond IN 1 Led 1 condition
433 PSL LED Cond IN 2 Led 2 condition
434 PSL LED Cond IN 3 Led 3 condition
435 PSL LED Cond IN 4 Led 4 condition
436 PSL LED Cond IN 5 Led 5 condition
437 PSL LED Cond IN 6 Led 6 condition
438 PSL LED Cond IN 7 Led 7 condition
439 PSL LED Cond IN 8 Led 8 condition
440 Aux Timer Timer IN 1 Input timer 1
441 Aux Timer Timer IN 2 Input timer 2
442 Aux Timer Timer IN 3 Input timer 3
443 Aux Timer Timer IN 4 Input timer 4
444 Aux Timer Timer IN 5 Input timer 5
445 Aux Timer Timer IN 6 Input timer 6
446 Aux Timer Timer IN 7 Input timer 7
447 Aux Timer Timer IN 8 Input timer 8
448 Aux Timer Timer OUT 1 Output timer 1
449 Aux Timer Timer OUT 2 Output timer 2
450 Aux Timer Timer OUT 3 Output timer 3
451 Aux Timer Timer OUT 4 Output timer 4
452 Aux Timer Timer OUT 5 Output timer 5
453 Aux Timer Timer OUT 6 Output timer 6
454 Aux Timer Timer OUT 7 Output timer 7
455 Aux Timer Timer OUT 8 Output timer 8
456 FRT Fault_REC_TRIG Fault Recorder Trigger
Relay Menu Database
abcd P740/EN GC/B11

Page B-6
MiCOM P740

B - Digital Data Bus (For P742 and P743 Only)

DDB No Source Description English Text

0 Relay Relay Label 01 Relay 1 - Trip Phase A / Relay 2 - Phase B / Relay 3 - Phase C
1 Relay Relay Label 02 87BB, 50BF(CU), I> and IN> trip are directly connected even they don't
2 Relay Relay Label 03 appear in PSL
3 Relay Relay Label 04 Relay 4
4 Relay Relay Label 05 Relay 5
5 Relay Relay Label 06 Relay 6
6 Relay Relay Label 07 Relay 7
7 Relay Relay Label 08 Relay 8 - Setting P742
8 Relay Relay Label 09 Relay 9
9 Relay Relay Label 10 Relay 10
10 Relay Relay Label 11 Relay 11
11 Relay Relay Label 12 Relay 12
12 Relay Relay Label 13 Relay 13
13 Relay Relay Label 14 Relay 14
14 Relay Relay Label 15 Relay 15
15 Relay Relay Label 16 Relay 16
16 Relay Relay Label 17 Relay 17
17 Relay Relay Label 18 Relay 18
18 Relay Relay Label 19 Relay 19
19 Relay Relay Label 20 Relay 20
20 Relay Relay Label 21 Relay 21 - Setting P743
32 Opto Opto Label 01 Opto Input 1
33 Opto Opto Label 02 Opto Input 2
34 Opto Opto Label 03 Opto Input 3
35 Opto Opto Label 04 Opto Input 4
36 Opto Opto Label 05 Opto Input 5
37 Opto Opto Label 06 Opto Input 6
38 Opto Opto Label 07 Opto Input 7
39 Opto Opto Label 08 Opto Input 8
40 Opto Opto Label 09 Opto Input 9
41 Opto Opto Label 10 Opto Input 10
42 Opto Opto Label 11 Opto Input 11
43 Opto Opto Label 12 Opto Input 12
44 Opto Opto Label 13 Opto Input 13
45 Opto Opto Label 14 Opto Input 14
46 Opto Opto Label 15 Opto Input 15
47 Opto Opto Label 16 Opto Input 16 - Setting P742
48 Opto Opto Label 17 Opto Input 17
49 Opto Opto Label 18 Opto Input 18
50 Opto Opto Label 19 Opto Input 19
51 Opto Opto Label 20 Opto Input 20
52 Opto Opto Label 21 Opto Input 21
53 Opto Opto Label 22 Opto Input 22
54 Opto Opto Label 23 Opto Input 23
55 Opto Opto Label 24 Opto Input 24 - Setting P743
64 Led LED 1 Led 1
65 Led LED 2 Led 2
66 Led LED 3 Led 3
67 Led LED 4 Led 4
68 Led LED 5 Led 5
69 Led LED 6 Led 6
70 Led LED 7 Led 7
71 Led LED 8 Led 8
72 PSL (IN) Isolator Position Q1 Open Isolator 1 - Auxiliary contact open
73 PSL (IN) Isolator Position Q1 Closed Isolator 1 - Auxiliary contact closed
74 PSL (IN) Isolator Position Q2 Open Isolator 2 - Auxiliary contact open
75 PSL (IN) Isolator Position Q2 Closed Isolator 2 - Auxiliary contact closed
76 PSL (IN) Isolator Position Q3 Open Isolator 3 - Auxiliary contact open
77 PSL (IN) Isolator Position Q3 Closed Isolator 3 - Auxiliary contact closed
78 PSL (IN) Isolator Position Q4 Open Isolator 4 - Auxiliary contact open
79 PSL (IN) Isolator Position Q4 Closed Isolator 4 - Auxiliary contact closed
80 PSL (IN) Isolator Position Q5 Open Isolator 5 - Auxiliary contact open
81 PSL (IN) Isolator Position Q5 Closed Isolator 5 - Auxiliary contact closed
82 PSL (IN) Isolator Position Q6 Open Isolator 6 - Auxiliary contact open
83 PSL (IN) Isolator Position Q6 Closed Isolator 6 - Auxiliary contact closed
84 PSL (IN) CB Fail Ext. 3 ph Trip Integrated breaker failure logic - 3 phase initialisation
85 PSL (IN) CB Fail External Trip A Integrated breaker failure logic - Initialisation Phase A
86 PSL (IN) CB Fail External Trip B Integrated breaker failure logic - Initialisation Phase B
87 PSL (IN) CB Fail External Trip C Integrated breaker failure logic - Initialisation Phase C
88 PSL (IN) CB Control Man.CB Close Cmd CB Closing order (used in topology processing)
89 PSL (IN) CB Control CB not available CB auxiliary Contact not available
90 PSL (IN) CB Control Ext. CB Fail External breaker failure logique, input to send backtrip order to CU
91 PSL (IN) CB Control CB Aux. 3ph(52a) CB Auxiliary contact open 3ph (52a)
92 PSL (IN) CB Control CB Aux. 3ph(52b) CB Auxiliary contact closed 3ph (52b)
93 PSL (IN) CB Control CB Aux. A (52a) CB Auxiliary contact open Phase A (52a)
94 PSL (IN) CB Control CB Aux. A (52b) CB Auxiliary contact closed Phase A (52b)
95 PSL (IN) CB Control CB Aux. B (52a) CB Auxiliary contact open Phase B (52a)
Relay Menu Database
abcd P740/EN GC/B11

Page B-7
MiCOM P740

B - Digital Data Bus (For P742 and P743 Only)

DDB No Source Description English Text

96 PSL (IN) CB Control CB Aux. B (52b) CB Auxiliary contact closed Phase B (52b)
97 PSL (IN) CB Control CB Aux. C (52a) CB Auxiliary contact open Phase C (52a)
98 PSL (IN) CB Control CB Aux. C (52b) CB Auxiliary contact closed Phase C (52b)
99 PSL (IN) Reset Lockout Reset trip relays 1, 2, 3
100 PSL (IN) SG Bit LSB LSB Setting Group
101 PSL (IN) SG Bit MSB MSB Setting Group
102 PSL (IN) Reset All values
103 PSL (IN) Reset Latches Reset relays and leds latched in PSL
104 PSL (IN) User Alarm 1 Self Reset User Alam 1
105 PSL (IN) User Alarm 2 Self Reset User Alam 2
106 PSL (IN) User Alarm 3 Self Reset User Alam 3
107 PSL (IN) User Alarm 4 Self Reset User Alam 4
108 PSL (IN) User Alarm 5 Self Reset User Alam 5
109 PSL (IN) User Alarm 6 Self Reset User Alam 6
110 PSL (IN) User Alarm 7 Self Reset User Alam 7
111 PSL (IN) Aux Volt Superv Auxiliary voltage supervision
112 Virtual relay Virtual Relay 01 Virtual Relay 1
113 Virtual relay Virtual Relay 02 Virtual Relay 2
114 Virtual relay Virtual Relay 03 Virtual Relay 3
115 Virtual relay Virtual Relay 04 Virtual Relay 4
116 Virtual relay Virtual Relay 05 Virtual Relay 5
117 Virtual relay Virtual Relay 06 Virtual Relay 6
118 Virtual relay Virtual Relay 07 Virtual Relay 7
119 Virtual relay Virtual Relay 08 Virtual Relay 8
120 Virtual relay Virtual Relay 09 Virtual Relay 9
121 Virtual relay Virtual Relay 10 Virtual Relay 10
122 Virtual relay Virtual Relay 11 Virtual Relay 11
123 Virtual relay Virtual Relay 12 Virtual Relay 12
124 Virtual relay Virtual Relay 13 Virtual Relay 13
125 Virtual relay Virtual Relay 14 Virtual Relay 14
126 Virtual relay Virtual Relay 15 Virtual Relay 15
127 Virtual relay Virtual Relay 16 Virtual Relay 16
128 PSL (IN) Isolator Position Man.Close Q1 Cmd Isolator 1 - Closing order (used in topology processing)
129 PSL (IN) Isolator Position Man.Close Q2 Cmd Isolator 2 - Closing order(used in topology processing)
130 PSL (IN) Isolator Position Man.Close Q3 Cmd Isolator 3 - Closing order (used in topology processing)
131 PSL (IN) Isolator Position Man.Close Q4 Cmd Isolator 4 - Closing order (used in topology processing)
132 PSL (IN) Isolator Position Man.Close Q5 Cmd Isolator 5 - Closing order (used in topology processing)
133 PSL (IN) Isolator Position Man.Close Q6 Cmd Isolator 6 - Closing order (used in topology processing)
134 PSL (IN) CB Control Man. Close CB CB Control : manual closing order
135 PSL (IN) CB Control Man. Trip CB CB Control : manual opening order
136 PSL (OUT) CB Fail Ext. Retrip Ph A CBF Phase A external retrip (TBF3)
137 PSL (OUT) CB Fail Ext. Retrip Ph B CBF Phase B external retrip (TBF3)
138 PSL (OUT) CB Fail Ext. Retrip Ph C CBF Phase C external retrip (TBF3)
139 PSL (OUT) CB Fail Int retrip 3 ph CBF 3Ph internal retrip (TBF1)
140 PSL (OUT) CB Fail CBF Int Backtrip CBF backtrip - internal (TBF2)
141 PSL (OUT) CB Fail CBF ext Backtrip CBF backtrip - external (TBF4)
142 PSL (OUT) CB Fail CB Fail Alarm CB Fail Alarm (TBF1 + TBF2 + TBF3 + TBF4)
144 PSL (OUT) Phase Overcurrent I>1 Start A Overcurrent Start I>1 phase A
145 PSL (OUT) Phase Overcurrent I>1 Start B Overcurrent Start I>1 phase B
146 PSL (OUT) Phase Overcurrent I>1 Start C Overcurrent Start I>1 phase C
147 PSL (OUT) Earth Fault IN>1 Start Overcurrent Start I>1 phase N
148 PSL (OUT) Phase Overcurrent I>1 Trip Overcurrent Phase Trip 3Ph I>1
149 PSL (OUT) Earth Fault IN>1 Trip Overcurrent Earth Trip 3Ph I>1
150 PSL (OUT) Phase Overcurrent I>2 Start A Overcurrent Start I>2 phase A
151 PSL (OUT) Phase Overcurrent I>2 Start B Overcurrent Start I>2 phase B
152 PSL (OUT) Phase Overcurrent I>2 Start C Overcurrent Start I>2 phase C
153 PSL (OUT) Earth Fault IN>2 Start Overcurrent Start I>2 phase N
154 PSL (OUT) Phase Overcurrent I>2 Trip Overcurrent Phase Trip 3Ph I>2
155 PSL (OUT) Earth Fault IN>2 Trip Overcurrent Earth Trip 3Ph I>2
160 PSL (OUT) 87BB Protection Zone 16 Off Zone 16 in commissioning mode or circuitry fault
161 PSL (OUT) 87BB Protection Zone 15 Off Zone 15 in commissioning mode or circuitry fault
162 PSL (OUT) 87BB Protection Zone 14 Off Zone 14 in commissioning mode or circuitry fault
163 PSL (OUT) 87BB Protection Zone 13 Off Zone 13 in commissioning mode or circuitry fault
164 PSL (OUT) 87BB Protection Zone 12 Off Zone 12 in commissioning mode or circuitry fault
165 PSL (OUT) 87BB Protection Zone 11 Off Zone 11 in commissioning mode or circuitry fault
166 PSL (OUT) 87BB Protection Zone 10 Off Zone 10 in commissioning mode or circuitry fault
167 PSL (OUT) 87BB Protection Zone 09 Off Zone 9 in commissioning mode or circuitry fault
168 PSL (OUT) 87BB Protection Zone 08 Off Zone 8 in commissioning mode or circuitry fault
169 PSL (OUT) 87BB Protection Zone 07 Off Zone 7 in commissioning mode or circuitry fault
170 PSL (OUT) 87BB Protection Zone 06 Off Zone 6 in commissioning mode or circuitry fault
171 PSL (OUT) 87BB Protection Zone 05 Off Zone 5 in commissioning mode or circuitry fault
172 PSL (OUT) 87BB Protection Zone 04 Off Zone 4 in commissioning mode or circuitry fault
173 PSL (OUT) 87BB Protection Zone 03 Off Zone 3 in commissioning mode or circuitry fault
174 PSL (OUT) 87BB Protection Zone 02 Off Zone 2 in commissioning mode or circuitry fault
175 PSL (OUT) 87BB Protection Zone 01 Off Zone 1 in commissioning mode or circuitry fault
176 PSL (OUT) 87BB Protection Trip Zone 16 Trip zone 16 from 87BB, 50BF or manual trip zone
177 PSL (OUT) 87BB Protection Trip Zone 15 Trip zone 15 from 87BB, 50BF or manual trip zone
Relay Menu Database
abcd P740/EN GC/B11

Page B-8
MiCOM P740

B - Digital Data Bus (For P742 and P743 Only)

DDB No Source Description English Text

178 PSL (OUT) 87BB Protection Trip Zone 14 Trip zone 14 from 87BB, 50BF or manual trip zone
179 PSL (OUT) 87BB Protection Trip Zone 13 Trip zone 13 from 87BB, 50BF or manual trip zone
180 PSL (OUT) 87BB Protection Trip Zone 12 Trip zone 12 from 87BB, 50BF or manual trip zone
181 PSL (OUT) 87BB Protection Trip Zone 11 Trip zone 11 from 87BB, 50BF or manual trip zone
182 PSL (OUT) 87BB Protection Trip Zone 10 Trip zone 10 from 87BB, 50BF or manual trip zone
183 PSL (OUT) 87BB Protection Trip Zone 09 Trip zone 9 from 87BB, 50BF or manual trip zone
184 PSL (OUT) 87BB Protection Trip Zone 08 Trip zone 8 from 87BB, 50BF or manual trip zone
185 PSL (OUT) 87BB Protection Trip Zone 07 Trip zone 7 from 87BB, 50BF or manual trip zone
186 PSL (OUT) 87BB Protection Trip Zone 06 Trip zone 6 from 87BB, 50BF or manual trip zone
187 PSL (OUT) 87BB Protection Trip Zone 05 Trip zone 5 from 87BB, 50BF or manual trip zone
188 PSL (OUT) 87BB Protection Trip Zone 04 Trip zone 4 from 87BB, 50BF or manual trip zone
189 PSL (OUT) 87BB Protection Trip Zone 03 Trip zone 3 from 87BB, 50BF or manual trip zone
190 PSL (OUT) 87BB Protection Trip Zone 02 Trip zone 2 from 87BB, 50BF or manual trip zone
191 PSL (OUT) 87BB Protection Trip Zone 01 Trip zone 1 from 87BB, 50BF or manual trip zone
192 PSL (OUT) 87BB Protection I>BB Start A Overcurrent Ia>BB - Busbar Trip Confirmation
193 PSL (OUT) 87BB Protection I>BB Start B Overcurrent Ib>BB - Busbar Trip Confirmation
194 PSL (OUT) 87BB Protection I>BB Start C Overcurrent Ic>BB - Busbar Trip Confirmation
195 PSL (OUT) 87BB Protection IN>BB Start Overcurrent In>BB - Busbar Confirmation
196 PSL (OUT) 87BB Protection I>BB Block Ph A Overcurrent Ia>BB - Blocking Busbar on external fault
197 PSL (OUT) 87BB Protection I>BB Block Ph B Overcurrent Ib>BB - Blocking Busbar on external fault
198 PSL (OUT) 87BB Protection I>BB Block Ph C Overcurrent Ic>BB - Blocking Busbar on external fault
199 PSL (OUT) 87BB Protection IN>BB Block Overcurrent In>BB - Blocking Busbar on external fault
200 PSL (OUT) CT Saturation Saturation ph A Saturation Phase A
201 PSL (OUT) CT Saturation Saturation ph B Saturation Phase B
202 PSL (OUT) CT Saturation Saturation ph C Saturation Phase C
203 PSL (OUT) Monitoring Current Overflow Optical fibre current format > Max
204 PSL (OUT) CT Saturation Max Flux ph A Max flux presomption Phase A
205 PSL (OUT) CT Saturation Max Flux ph B Max flux presomption Phase B
206 PSL (OUT) CT Saturation Max Flux ph C Max flux presomption Phase C
207 PSL (OUT) Monitoring Alarm OffsetABCN Offset Analog board Phase A, B, C or N
208 PSL (OUT) CT Saturation Predict err ph A Variation error Phase A (from derived current)
209 PSL (OUT) CT Saturation Predict err ph B Variation error Phase B (from derived current)
210 PSL (OUT) CT Saturation Predict err ph C Variation error Phase C (from derived current)
212 PSL (OUT) Monitoring Sat ADC ph A ADC saturation Phase A
213 PSL (OUT) Monitoring Sat ADC ph B ADC saturation Phase B
214 PSL (OUT) Monitoring Sat ADC ph C ADC saturation Phase C
215 PSL (OUT) Monitoring Sat ADC Neutral ADC saturation Phase N
216 PSL (OUT) Monitoring Delta IA Variation Phase A
217 PSL (OUT) Monitoring Delta IB Variation Phase B
218 PSL (OUT) Monitoring Delta IC Variation Phase C
219 PSL (OUT) Monitoring Delta IN Variation Phase N
220 PSL (OUT) System Fibre Com Error PU/CU communication error
221 PSL (OUT) System PU Main Error PU main error
222 PSL (OUT) Monitoring Acq Error 3Io Sample acquisition error - 3*Io=In
223 PSL (OUT) Monitoring CT Fail Alarm 3*Io=In error with Tce timer
Trip 3ph from 87BB, 50BF(CU), I>, IN> or manual zone trip (CU). Trip
224 PSL (OUT) All Protection Internal Trip
command directly apply to relay 1, 2, 3 without PSL
225 PSL (OUT) 87BB Protection Trip 87BB Busbar trip in one zone, not especially on this PU
226 PSL (OUT) 87BB Protection Trip 87BB Block Busbar trip blocked by commissioning mode
227 PSL (OUT) 50BF Protection Trip 50BF (CU) 50BF backtrip from CU in one zone, not especially on this PU
228 PSL (OUT) Commissioning Test Man.Trip zone Manual trip in one zone, not especially on this PU
229 PSL (OUT) 50BF Protection Dead Zone Fault Dead zone alarm
230 PSL (OUT) 50BF Protection Circuitry Fault Circuitry fault on dead zone
232 PSL (OUT) System Operating mode 1
233 PSL (OUT) System Operating mode 2 for expert only
234 PSL (OUT) System Operating mode 3
235 PSL (OUT) System Config. valid Valid configuration
236 PSL (OUT) System Topology valid Topology file valid
237 PSL (OUT) System Topo/Set valid Configuration & Topology valid
256 PSL (OUT) Overcurrent Protection I> Any Trip Overcurrent Trip (phase or earth fault)
257 PSL (OUT) CB Control CBAvailabToTrip Circuit Breaker available to trip
258 PSL (OUT) 50BF Protection BF Trip Request Internal or external 50BF (backtrip order to CU)
264 PSL (OUT) Overcurrent Protection I> No Trip Overcurent trip - complement
265 PSL (OUT) CB Control CBNotAvailToTrip CB available to trip - complement
266 PSL (OUT) 50BF Protection BFTripNoRequest Internal or external 50BF - complement
273 PSL (OUT) CB Control Ctrl CB Trip Manual trip for local Circuit Breaker
274 PSL (OUT) CB Control Ctrl CB Close Manual closing for local Circuit Breaker
275 PSL (OUT) Commissioning Test PU OutOfService Commissioning Mode - PU out of service
276 PSL (OUT) Commissioning Test PU I/O Disabled Commissioning Mode - I/O disabled
279 PSL (OUT) CT Saturation Reset Flux for expert only
280 PSL (OUT) CT Saturation Restart Flux for expert only
281 PSL (OUT) Comm Test Enable Activation Commissionning Test
282 PSL (OUT) I>BB Enabled Activation OC Busbar Confirmation
283 PSL (OUT) Trip Rel Latched Activation latched trip relay
284 PSL (OUT) I>2 Block BB ON Activation OC Busbar Blocking Phase
285 PSL (OUT) IN>2 Block BB ON Activation OC Busbar Blocking Residual
286 PSL (OUT) Reset Trip Relay Reset latched trip relay 1,2 and 3
287 PSL (OUT) Topo/Set Changed Setting or topology change
Relay Menu Database
abcd P740/EN GC/B11

Page B-9
MiCOM P740

B - Digital Data Bus (For P742 and P743 Only)

DDB No Source Description English Text

288 PSL (OUT) Isolator Position Q1 Closed Isolator 1 closed (used for topology processing)
290 PSL (OUT) Isolator Position Q2 Closed Isolator 2 closed (used for topology processing)
292 PSL (OUT) Isolator Position Q3 Closed Isolator 3 closed (used for topology processing)
294 PSL (OUT) Isolator Position Q4 Closed Isolator 4 closed (used for topology processing)
296 PSL (OUT) Isolator Position Q5 Closed Isolator 5 closed (used for topology processing)
298 PSL (OUT) Isolator Position Q6 Closed Isolator 6 closed (used for topology processing)
300 PSL (OUT) CB Position CB Closed Cicuit breaer closed (used for topology processing)
301 PSL (OUT) CB Control CB Healthy Circuit Breaker 1 available (used for topology processing)
304 PSL (OUT) Isolator Position Q1 Status Forced Isolator 1 - Forced position
305 PSL (OUT) Isolator Position Q2 Status Forced Isolator 2 - Forced position
306 PSL (OUT) Isolator Position Q3 Status Forced Isolator 3 - Forced position
307 PSL (OUT) Isolator Position Q4 Status Forced Isolator 4 - Forced position
308 PSL (OUT) Isolator Position Q5 Status Forced Isolator 5 - Forced position
309 PSL (OUT) Isolator Position Q6 Status Forced Isolator 6 - Forced position
310 PSL (OUT) CB Position CB Status Forced Circuit Breaker 1 - Forced position
311 PSL (OUT) Commissioning Test Forced Mode ON Forced position enable
312 PSL (OUT) CB Control CB Aux. 52a Circuit Breaker open
313 PSL (OUT) CB Control CB Aux. 52b Circuit Breaker closed
314 PSL (OUT) CB Control CB Trip 3 ph Circuit Breaker trip 3 phases
315 PSL (OUT) CB Control CB Trip phase A Circuit Breaker trip phase A
316 PSL (OUT) CB Control CB Trip phase B Circuit Breaker trip phase B
317 PSL (OUT) CB Control CB Trip phase C Circuit Breaker trip phase C
318 PSL (OUT) Alarm Field Volt Alarm field voltage
319 PSL (OUT) General Alarm General alarm
320 PSL (OUT) CB Control CB Status Alarm CB status alarm - CB auxiliary contact supevision
321 PSL (OUT) CB Control Man CB Trip Fail CB control alarm - trip error
322 PSL (OUT) CB Control Man CB Cls Fail CB control alarm - closed error
323 PSL (OUT) CB Control Ctrl Cls in Prog Circuit Breaker closed in progress
324 PSL (OUT) CB Control Control Close Circuit Breaker closed control
325 PSL (OUT) CB Control Control Trip Circuit Breaker open control
326 PSL (OUT) All Protection Any Trip OR between DDB 136, 137, 138, 139, 224
352 PSL Relay 01 Output relay 1 condition
353 PSL Relay 02 Output relay 2 condition
354 PSL Relay 03 Output relay 3 condition
355 PSL Relay 04 Output relay 4 condition
356 PSL Relay 05 Output relay 5 condition
357 PSL Relay 06 Output relay 6 condition
358 PSL Relay 07 Output relay 7 condition
359 PSL Relay 08 Output relay 8 condition
360 PSL Relay 09 Output relay 9 condition
361 PSL Relay 10 Output relay 10 condition
362 PSL Relay 11 Output relay 11 condition
363 PSL Relay 12 Output relay 12 condition
364 PSL Relay 13 Output relay 13 condition
365 PSL Relay 14 Output relay 14 condition
366 PSL Relay 15 Output relay 15 condition
367 PSL Relay 16 Output relay 16 condition
368 PSL Relay 17 Output relay 17 condition
369 PSL Relay 18 Output relay 18 condition
370 PSL Relay 19 Output relay 19 condition
371 PSL Relay 20 Output relay 20 condition
372 PSL Relay 21 Output relay 21 condition
373 PSL Relay 22 Reserved
374 PSL Relay 23 Reserved
375 PSL Relay 24 Reserved
376 PSL Relay 25 Reserved
377 PSL Relay 26 Reserved
378 PSL Relay 27 Reserved
379 PSL Relay 28 Reserved
380 PSL Relay 29 Reserved
381 PSL Relay 30 Reserved
382 PSL Relay 31 Reserved
383 PSL Relay 32 Reserved
384 PSL LED Cond IN 1 Led 1 condition
385 PSL LED Cond IN 2 Led 2 condition
386 PSL LED Cond IN 3 Led 3 condition
387 PSL LED Cond IN 4 Led 4 condition
388 PSL LED Cond IN 5 Led 5 condition
389 PSL LED Cond IN 6 Led 6 condition
390 PSL LED Cond IN 7 Led 7 condition
391 PSL LED Cond IN 8 Led 8 condition
392 Aux Timer Timer IN 1 Input timer 1
393 Aux Timer Timer IN 2 Input timer 2
394 Aux Timer Timer IN 3 Input timer 3
395 Aux Timer Timer IN 4 Input timer 4
396 Aux Timer Timer IN 5 Input timer 5
397 Aux Timer Timer IN 6 Input timer 6
Relay Menu Database
abcd P740/EN GC/B11

Page B-10
MiCOM P740

B - Digital Data Bus (For P742 and P743 Only)

DDB No Source Description English Text

398 Aux Timer Timer IN 7 Input timer 7


399 Aux Timer Timer IN 8 Input timer 8
400 Aux Timer Timer OUT 1 Output timer 1
401 Aux Timer Timer OUT 2 Output timer 2
402 Aux Timer Timer OUT 3 Output timer 3
403 Aux Timer Timer OUT 4 Output timer 4
404 Aux Timer Timer OUT 5 Output timer 5
405 Aux Timer Timer OUT 6 Output timer 6
406 Aux Timer Timer OUT 7 Output timer 7
407 Aux Timer Timer OUT 8 Output timer 8
408 FRT Fault_REC_TRIG Fault recorder trigger
Relay Menu Database P740/EN GC/C11

MiCOM P740

C - DEFAULT PROGRAMMABLE
SCHEME LOGIC (PSL)
P740/EN GC/C11 Relay Menu Database

MiCOM P740
Relay Menu Database P740/EN GC/C11

MiCOM P740 Page C-1

MiCOM P741
PROGRAMMABLE SCHEME LOGIC (01) FOR CENTRAL UNIT

Input-Opto Couplers

Opto Label 01 Reset Latches


DDB #032 DDB #077

Opto Label 02 Ext. Start DR


DDB #033 DDB #075

Opto Label 03 Reset Circt Flt


DDB #034 DDB #074

Opto Label 04 Ext. CZ confirm


DDB #035 DDB #076

TRIP 87BB
DDB #224

20
TRIP 50BF FAULT_REC_TRIG
DDB #227 Dwell DDB #456
0

Dead Zone signal


DDB #229
P740/EN GC/C11 Relay Menu Database

Page C-2 MiCOM P740

MiCOM P741
PROGRAMMABLE SCHEME LOGIC (01) FOR CENTRAL UNIT

Output Contact

0
Fault phase A Relay Label 01
DDB #230 Pick-Up DDB #000
0

0
Fault phase B Relay Label 02
DDB #231 Pick-Up DDB #001
0

0
Fault phase C Relay Label 03
DDB #232 Pick-Up DDB #002
0

Trp 87BB Zone 01


DDB #159
0
Trp 50BF Zone 01 Relay Label 04
DDB #175 Pick-Up DDB #003
0
Man. Trip Zone 01
DDB #191

Trp 87BB Zone 02


DDB #158
0
Trp 50BF Zone 02 Relay Label 05
DDB #174 Pick-Up DDB #004
0
Man. Trip Zone 02
DDB #190

0
Circuitry Fault Relay Label 06
DDB #234 Pick-Up DDB #005
0

Crct Flt Zone 01


DDB #143
0
Lck Lev.1 Zone01 Relay Label 07
DDB #207 Pick-Up DDB #006
0
Lck Lev.2 Zone01
DDB #223

Crct Flt Zone 02


DDB #142
0
Lck Lev.1 Zone02 Relay Label 08
DDB #206 Pick-Up DDB #007
0
Lck Lev.2 Zone02
DDB #222
Relay Menu Database P740/EN GC/C11

MiCOM P740 Page C-3

MiCOM P741
PROGRAMMABLE SCHEME LOGIC (01) FOR CENTRAL UNIT

Leds Front Panel

Fault phase A Output_led_01


DDB #230 Latching DDB #064 Phase A

Fault phase B Output_led_02


DDB #231 Latching DDB #065 Phase B

Fault phase C
DDB #232 Latching Output_led_03
DDB #066 Phase C

Trip 87BB
DDB #224 Latching Output_led_04
DDB #067 Busbar Trip

Trip 50BF
DDB #227 Latching Output_led_05
DDB #068
Breaker Fail

Circuitry Fault Output_led_06


DDB #234 Latching DDB #069 Circuitry Fault
P740/EN GC/C11 Relay Menu Database

Page C-4 MiCOM P740

MiCOM P742 & P743


PROGRAMMABLE SCHEME LOGIC (01) FOR PERIPHERAL UNITS

Input-Opto Couplers

Opto Label 01 Reset Latches


DDB #032 DDB #103

Opto Label 02 Reset Lockout


DDB #033 DDB #099

Opto Label 03 Q1 Closed


DDB #034 DDB #073

Opto Label 04 Q1 Open


DDB #035 DDB #072

Opto Label 05 Q2 Closed


DDB #036 DDB #075

Opto Label 06 Q2 Open


DDB #037 DDB #074

Opto Label 07 CB Aux. 3ph (52a)


DDB #038 DDB #091

Opto Label 08 CB Aux. 3ph (52b)


DDB #039 DDB #092

Opto Label 09 Q3 Closed


DDB #040 DDB #077

Opto Label 10 Q3 Open


DDB #041 DDB #076

Opto Label 12 Ext. 3 ph Trip


DDB #043 DDB #084

Opto Label 13 CB not available


DDB #044 DDB #089

Opto Label 14 Ext. CB Fail


DDB #045 DDB #090

Opto Label 15 Man.CB Close Cmd


DDB #046 DDB #088

Dead Zone Fault


DDB #229
20
Fault_REC_TRIG
Dwell DDB #408
0
Any Trip
DDB #326

P3721ENa
Relay Menu Database P740/EN GC/C11

MiCOM P740 Page C-5

MiCOM P742 & P743


PROGRAMMABLE SCHEME LOGIC (01) FOR PERIPHERAL UNITS

Output Contact

Ext. Retrip Ph A
DDB #136

Ext. Retrip Ph B
DDB #137 0
Relay Label 06
Pick-Up DDB #005
Ext. Retrip Ph C 0
DDB #138

Int retrip 3 ph
DDB #139

0
CB Fail Alarm Relay Label 04
DDB #142 Pick-Up DDB #003
0

0
Relay Label 05
Opto Label 13
Pick-Up DDB #004
DDB #044 0

Internal Trip
DDB #224 0
Relay Label 07
Pick-Up DDB #006
Dead Zone Fault 0
DDB #229

CB Status Alarm 0
DDB #320 Relay Label 08
Pick-Up DDB #007
Opto Label 03 0
DDB #034

Opto Label 04
DDB #035
& 5000
Dwell
Opto Label 03
0
DDB #034

Opto Label 04
DDB #035

Opto Label 05
DDB #036

Opto Label 06
DDB #037
& 5000
Dwell User Alarm 1
Opto Label 05 DDB #104
0
DDB #036

Opto Label 06
DDB #037

Opto Label 09
DDB #040

Opto Label 10
DDB #041
& 5000
Dwell
Opto Label 09
DDB #040
0

Opto Label 10
DDB #041
P740/EN GC/C11 Relay Menu Database

Page C-6 MiCOM P740

MiCOM P742 & P743


PROGRAMMABLE SCHEME LOGIC (01) FOR PERIPHERAL UNITS

Leds Front Panel

Q1 Closed Output_led_01
DDB #288 Latching DDB #064 Isolator 1

Q2 Closed Output_led_02
DDB #290 Latching DDB #065 Isolator 2

Q3 Closed
DDB #292 Latching Output_led_03
DDB #066 Isolator 3

CB Fail Alarm
DDB #142
Output_led_05
Latching DDB #068 Breaker Fail
Opto Label 13
DDB #044

Internal Trip
DDB #224
Busbar Trip
Trip 87BB
& Latching Output_led_06
DDB #069
DDB #225

Dead Zone Fault Output_led_07


DDB #229 Latching DDB #070 Dead Zone
Publication : P740/EN GC/C11