You are on page 1of 4

TECHNICAL DATA

Specification: FOR FIRE RESISTANT, OVERALL SCREENED,


ARMOURED CABLE GENERALLY TO BS 5308-1 & IEC 60331-23 ISO 9001:2008
Certificate N°
2006/7034b

Project Name: 200,000 MTA Polystyrene Plant


Location: ALEXANDRIA - EGYPT
Client: ENPPI - ESTYRENICS
P.O. No.: 7781-925-196-12
Manufacturer's Appelation/Type : S FXSRU 1*…*...//EN-EG
RATED VOLTAGE 300/500 V
DESCRIPTION: CU/MICA/XLPE/OSCR/LSZH/GSWA/LSZH
CONDUCTOR STRANDED ANNEALED COPPER Class 2 acc. to BS 6360
INSULATION MICA/GLASS FIRE RESISTANT TAPE + XLPE
OVERALL SCREEN POLYESTER TAPE + TINNED COPPER DRAIN WIRE + METALLIZED POLYESTER TAPE
BEDDING LOW SMOKE ZERO HALOGEN COMPOUND ( LSZH )
ARMOUR GALVANIZED STEEL WIRES
OVERSHEATH LOW SMOKE ZERO HALOGEN COMPOUND ( LSZH )

DIMENSIONAL CHARACTERISTICS
C. REF : 1.1 1.2 1.3
CABLE SIZE mm² 1*2*1.5 1*2*2.5 1*3*1.5
CONDUCTOR Size mm² 1.5 2.5 1.5
Fire resistant tape Mica/Glass Mica/Glass Mica/Glass
INSULATION Nom. thickness of XLPE mm 0.6 0.6 0.6
Identification By colors & / Or Numbers
TWISTING Pair Pair Triad
Nom. size. of tinned drain wire mm² 0.5 0.5 0.5
OVERALL SCREEN
Total thick.of metallized tape mm 0.036 0.036 0.036
BEDDING Nom. thickness mm 0.8 0.8 0.8
ARMOUR Nom.diam. of each wire mm 0.9 0.9 0.9
Nom. thickness mm 1.4 1.4 1.4
OVERSHEATH
Color RED RED RED
MARKING By yellow or black ink jet printing on one line over the outer jacket
OVERALL DIAM. Nom. Diameter (-3% +7%) mm 14.5 15.5 13.5
CABLE WEIGHT Approx. kg/km 364 421 338

ELECTRICAL & MECHANICAL CHARACTERISTICS


Max. DC conductor resistance at 20°C. ohm/Km 12.34 7.56 12.34
Voltage test for 1 minute
- Between conductors VAC 1000 1000 1000
- Between conductors & screen VAC 1000 1000 1000

• Operating conditions: Fire resistance according to IEC 60331-23


Max. Continuous operating Temp. : 90°C ( 750°C for 90 mins )

Prepared by: A.CH Customer Ref. N°:. Our Ref.: 11057 Approved by:

11057-1T. SFXSRU
TECHNICAL DATA
Specification: FOR FIRE RESISTANT, INDIVIDUALLY &
OVERALL SCREENED, ARMOURED CABLE GENERALLY ISO 9001:2008
Certificate N°
TO BS 5308-1 & IEC 60331-23 2006/7034b

Project Name: 200,000 MTA Polystyrene Plant


Location: ALEXANDRIA - EGYPT
Client: ENPPI - ESTYRENICS
P.O. No.: 7781-925-196-12
Manufacturer's Appelation/Type : S FXSSRU 6*…*...//EN-EG
RATED VOLTAGE 300/500 V
DESCRIPTION: CU/MICA/XLPE/ISCR/OSCR/LSZH/GSWA/LSZH
CONDUCTOR STRANDED ANNEALED COPPER Class 2 acc. to BS 6360
INSULATION MICA/GLASS FIRE RESISTANT TAPE + XLPE
INDIVIDUAL SCREEN POLYESTER TAPE + TINNED COPPER DRAIN WIRE + METALLIZED POLYESTER TAPE
OVERALL SCREEN POLYESTER TAPE + TINNED COPPER DRAIN WIRE + METALLIZED POLYESTER TAPE
BEDDING LOW SMOKE ZERO HALOGEN COMPOUND ( LSZH)
ARMOUR GALVANIZED STEEL WIRES
OVERSHEATH LOW SMOKE ZERO HALOGEN COMPOUND ( LSZH)

DIMENSIONAL CHARACTERISTICS
C. REF : 1.4 1.5 1.6
CABLE SIZE mm² 6*2*1.5 6*2*2.5 6*3*1.5
CONDUCTOR Size mm² 1.5 2.5 1.5
Fire resistant tape Mica/Glass
INSULATION Nom. thickness of XLPE mm 0.6 0.6 0.6
Identification By colors &/OR Numbers
TWISTING Pairs Pairs Triads
Nom. size. of tinned drain wire mm² 0.5 0.5 0.5
INDIVIDUAL SCREEN
Total thick.of metallized tape mm 0.036 0.036 0.036
ASSEMBLING Concentric layers
Nom. size. of tinned drain wire mm² 0.5 0.5 0.5
OVERALL SCREEN
Total thick.of metallized tape mm 0.036 0.036 0.036
BEDDING Nom. thickness mm 1.3 1.3 1.3
ARMOUR Nom.diam. of each wire mm 1.6 1.6 1.6
Nom. thickness mm 1.7 1.7 1.7
OVERSHEATH
Color RED RED RED
MARKING By yellow or black ink jet printing on one line over the outer jacket
OVERALL DIAM. Nom. Diameter (-3% +7%) mm 28 30 30
CABLE WEIGHT Approx. kg/km 1290 1500 1520

ELECTRICAL & MECHANICAL CHARACTERISTICS


Max. DC conductor resistance at 20°C. ohm/Km 12.34 7.56 12.34
Voltage test for 1 minute
- Between conductors VAC 1000 1000 1000
- Between conductors & screen VAC 1000 1000 1000

• Operating conditions: Fire resistance according to IEC 60331-23


Max. Continuous operating Temp. : 90°C ( 750°C for 90 mins )

Prepared by: A.CH Customer Ref. N°:. Our Ref.: 11057 Approved by:

11057-1T. SFXSSRU
TECHNICAL DATA
Specification: FOR FIRE RESISTANT, INDIVIDUALLY &
OVERALL SCREENED, ARMOURED CABLE GENERALLY ISO 9001:2008
Certificate N°
TO BS 5308-1 & IEC 60331-23 2006/7034b

Project Name: 200,000 MTA Polystyrene Plant


Location: ALEXANDRIA - EGYPT
Client: ENPPI - ESTYRENICS
P.O. No.: 7781-925-196-12
Manufacturer's Appelation/Type : S FXSSRU 12*…*...//EN-EG
RATED VOLTAGE 300/500 V
DESCRIPTION: CU/MICA/XLPE/ISCR/OSCR/LSZH/GSWA/LSZH
CONDUCTOR STRANDED ANNEALED COPPER Class 2 acc. to BS 6360
INSULATION MICA/GLASS FIRE RESISTANT TAPE + XLPE
INDIVIDUAL SCREEN POLYESTER TAPE + TINNED COPPER DRAIN WIRE + METALLIZED POLYESTER TAPE
OVERALL SCREEN POLYESTER TAPE + TINNED COPPER DRAIN WIRE + METALLIZED POLYESTER TAPE
BEDDING LOW SMOKE ZERO HALOGEN COMPOUND ( LSZH)
ARMOUR GALVANIZED STEEL WIRES
OVERSHEATH LOW SMOKE ZERO HALOGEN COMPOUND ( LSZH)

DIMENSIONAL CHARACTERISTICS
C. REF : 1.7 1.8 1.9
CABLE SIZE mm² 12*2*1.5 12*2*2.5 12*3*1.5
CONDUCTOR Size mm² 1.5 2.5 1.5
Fire resistant tape Mica/Glass
INSULATION Nom. thickness of XLPE mm 0.6 0.6 0.6
Identification By colors &/OR Numbers
TWISTING Pairs Pairs Triads
Nom. size. of tinned drain wire mm² 0.5 0.5 0.5
INDIVIDUAL SCREEN
Total thick.of metallized tape mm 0.036 0.036 0.036
ASSEMBLING Concentric layers
Nom. size. of tinned drain wire mm² 0.5 0.5 0.5
OVERALL SCREEN
Total thick.of metallized tape mm 0.036 0.036 0.036
BEDDING Nom. thickness mm 1.5 1.5 1.7
ARMOUR Nom.diam. of each wire mm 1.6 1.6 2.0
Nom. thickness mm 1.9 1.9 2.0
OVERSHEATH
Color RED RED RED
MARKING By yellow or black ink jet printing on one line over the outer jacket
OVERALL DIAM. Nom. Diameter (-3% +7%) mm 35 38 40
CABLE WEIGHT Approx. kg/km 1980 2350 2680

ELECTRICAL & MECHANICAL CHARACTERISTICS


Max. DC conductor resistance at 20°C. ohm/Km 12.34 7.56 12.34
Voltage test for 1 minute
- Between conductors VAC 1000 1000 1000
- Between conductors & screen VAC 1000 1000 1000

• Operating conditions: Fire resistance according to IEC 60331-23


Max. Continuous operating Temp. : 90°C ( 750°C for 90 mins )

Prepared by: A.CH Customer Ref. N°:. Our Ref.: 11057 Approved by:

11057-1T. SFXSSRU (2)


TECHNICAL DATA
Specification: FOR FIRE RESISTANT, SCREENED,
ARMOURED CABLE GENERALLY TO BS 5308-1 & IEC ISO 9001:2008
Certificate N°
60331-23 2006/7034b

Project Name: 200,000 MTA Polystyrene Plant


Location: ALEXANDRIA - EGYPT
Client: ENPPI - ESTYRENICS
P.O. No.: 7781-925-196-12
Manufacturer's Appelation/Type : S FXSRU 1*…*...//EN-EG S FXSSRU ...*…*...//EN-EG
C. REF : 1.1 - 1.2 & 1.3 1.4 TO 1.9

TEST AT WORKS

Routine Tests
- Max. DC conductors resistance at 20°C acc. to BS 5308 Parag. 17
- Voltage test acc. to BS 5308 parag. 15

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided

Sample tests
Check of the build - up and color coding of the cable
Check of dimensions
Insulation : according to BS 5308-1 Parag. 6
Bedding : according to BS 5308-1 Parag. 13.4
Armour : according to BS 5308-1 Parag. 13.3.4
Oversheath : according to BS 5308-1 Parag. 13.5

These tests will be carried out on one length of each size during each inspection .
Tests certificates will be provided by Liban Cables

Type tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation
at break) in accordance with BS 5308
Max. 4 pairs/triads chosen randomly shall be tested for fire resistance acc. to IEC 60331-23.
Fire resistance test according to IEC 60331-23 (750۫°C for 90 mins) :
- 190V between conductors
- 110V between cond. and screen
These tests will be carried out on one length of the order .
Tests certificates will be provided by Liban Cables

Prepared by: A.CH Customer Ref. N° Our Ref: 11057 Approved by:

11057-1T. test (SFXS-SRU)