stranded aluminium conductor - conductor screen of semiconducting compound -
insulation of cross-linked polyethylen (XLPE) - screen of semiconducting
compound - semiconducting bedding - screen of copper wires and copper tape -
swelling powder or tape - aluminium tape tightly bonded to the PE sheath - PE
sheath
Application
in ground, outdoors, in water, indoors and in cable ducts
Standards
International IEC 60502-2
National DIN VDE 0276 part 620
Characteristics
Construction characteristics
Conductor shape Circular stranded (RM)
Lead free Yes
Halogen free Yes
Insulation XLPE (chemical)
Screen Copper wire + copper tape
Protection Aluminium tape
Outer sheath PE
Radial waterproof Yes
Longitudinally watertight Yes
Usage characteristics
Packaging Drum
Minimum operating temperature -40 °C
Minimum installation temperature -20 °C
Max. conductor temperature in service 90 °C
Lead free Halogen Radial Longitudinally Minimum operating Minimum Max.conductor Bending factor
Yes free waterproof watertight temperature installation temp.in service when laying
Yes Yes Yes -40 °C temperature 90 °C 15 (xD)
-20 °C
NA2XS(FL)2Y RM 18/30 kV
Usage characteristics
Short-circuit max. conductor temperature 250 °C
Bending factor when laying 15 (xD)
Selling information
Note: On request we are delivering three single core laid up cables on one drum
Lead free Halogen Radial Longitudinally Minimum operating Minimum Max.conductor Bending factor
Yes free waterproof watertight temperature installation temp.in service when laying
Yes Yes Yes -40 °C temperature 90 °C 15 (xD)
-20 °C